Sei sulla pagina 1di 3

XYZ

Page 1 of 3

QC~PLAN.
Project No. & Name: Name of Client/ Consultant: SL ACTIVITY CONTROLLING DOCUMENT Drawing Contract Specs. Drawing Contract Specs. Drawing Contract Specs. NATURE & EXTENT OF INSP./TEST Visual , 100% ACCEPTANCE CRITERIA - As per drawing / spec.

Potable Water Line


Doc. No. M & E QC~Plan- 061c/ REV. 0 PERSON RESP. AT LOCATION Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer RECORD Potable Water Line M & E QC~Form- 061c-01/ REV. 0 Potable Water Line M & E QC~Form- 061c-01/ REV. 0 Potable Water Line M & E QC~Form- 061c-01/ REV. 0

No. 1 Route line marking and trenching 2 a) Bedding b) Pipe laying

Visual , 100%

- Pipeline laid on appropriate cushioning material - Proper sleeves and packing to be provided - Adequate pipe supports and hangers to be provided - Protected against ingress of deleterious matter by plug or cap on open ended pipe or sleeve Wrapping - One layer of 'Denso' anti-corrosive tape - One layer of 'Denso' PVC backed tape Screwed Joints - To be made with the PTFE tape upto 40 mm. dia - Hemp and jointing compound for 50 mm and above size Flanged Joints - Appropriate material, full-faced, corrugated and metal joint rings of copper alloy to BS5292

Visual , 100%

c) Protection of copper pipe work

Drawing Contract Specs.

Visual , 100%

Engineer/ Foremen/ Quality Engineer

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

d) Jointing material

Drawing Contract Specs.

Visual , 100%

Engineer/ Foremen/ Quality Engineer

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

225432311.xls.ms_office

Date: January 26, 2001

XYZ

Page 2 of 3

QC~PLAN.
Project No. & Name: Name of Client/ Consultant: SL ACTIVITY CONTROLLING DOCUMENT Drawing Contract Specs. NATURE & EXTENT OF INSP./TEST Visual , 100% ACCEPTANCE CRITERIA - Fit at not more than 20 m. intervals and near equipment connection - Easy to facilitate installation and maintenance - To drain the water without accumulation of air - Provide open vent (or) automatic air vent at high points in water mains - Vent discharge located at visible place - Avoid excessive stress - Same pipe material type used for expansion loop - Stainless steel bellows type used for expansion joints - Provision for expansion checked by Customer - As per drawing - Provide blocks (if specified) at changes of directions, branches and take-off places

Potable Water Line


Doc. No. M & E QC~Plan- 061c/ REV. 0 PERSON RESP. AT LOCATION Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer RECORD Potable Water Line M & E QC~Form- 061c-01/ REV. 0

No. e) Flanges and unions

f) Check the provision of drainage and venting

Drawing Contract Specs.

Visual , 100%

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

g) Expansion loops (or) joints

Drawing Contract Specs. Mfr's. data sheet

Visual , 100%

Engineer/ Foremen/ Quality Engineer

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

h) Thrust blocks

Drawing Contract Specs.

Visual , 100%

Engineer/ Foremen/ Quality Engineer

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

3 Testing & Inspection a) Pipe work

Drawing Contract Specs.

Hydrotest, 100%

- Tested at 7 bar (or) 2 times working Engineer/ pressure whichever is greater Foremen/ - Test duration: Minimum one hour Quality Engineer - Flushed after testing - Use calibrated pressure gauge

Hydrotest Report M & E QC~Form- 061-02/ REV. 0

225432311.xls.ms_office

Date: January 26, 2001

XYZ

Page 3 of 3

QC~PLAN.
Project No. & Name: Name of Client/ Consultant: SL ACTIVITY CONTROLLING DOCUMENT Drawing Contract Specs. NATURE & EXTENT OF INSP./TEST Visual, 100% ACCEPTANCE CRITERIA - Domestic waterline sterilized

Potable Water Line


Doc. No. M & E QC~Plan- 061c/ REV. 0 PERSON RESP. AT LOCATION Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer RECORD Potable Water Line M & E QC~Form- 061c-01/ REV. 0

No. b) The connection to existing main, if any

c) The post bedding

Drawing Contract Specs.

Visual, 100%

d) Backfilling activities

Drawing Contract Specs.

Visual, 100%

Final Inspection

Drawing Contract Specs.

Visual, 100%

- Min. 100 mm. cover of well compacted layer of fill on pipe work. - Joints covered properly with sand after testing - Lightly compacted loose fill material. - No sharp edge stones - Fill material as per specs. - Ensure the works in accordance with contractual requirements - Thrust blocks provided (if specified) at changes of direction, branches, take offs etc. - Route markers placed at 50 m interval and at each turning point (if specified)

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

Potable Water Line M & E QC~Form- 061c-01/ REV. 0

Work Location: Remarks:

Quality Engineer: Date:

Engineer / Foremen: Date:

225432311.xls.ms_office

Date: January 26, 2001