Topic:

Technology and Solutions


Protection and Substation Automation

REB500 / REB500sys
BBP, DR & SYSTEM

Configuration & Settings in HMI500

ABB Switzerland Ltd. - 1

HMI500_BBP / 2003-04-01 / RW

!!

Settings / configuration in HMI500


Objectives r CT configuration r In- and Output configuration r BBP In- and Outputs r Signal / event configuration r Disturbance Recorder configuration r System settings - blocking behavior
ABB Switzerland Ltd. - 2

r BBP settings
HMI500_BBP / 2003-04-01 / RW

r Event settings

!!

CT configuration
Current transformer primary CT nominal current R, S, T

Detail

primary CT nominal current ratio N


ABB Switzerland Ltd. - 3
HMI500_BBP / 2003-04-01 / RW

secondary CT nominal current R, S, T, N (only for information selection made by cabling)

!!

In- & Output configuration - DOUBLE BB


single line diagram

overview binary module outputs inputs

ABB Switzerland Ltd. - 4

HMI500_BBP / 2003-04-01 / RW

!!

BBP In- & Output configuration - FEEDER


inputs

Double BB: image Q1 & Q2 (open & close) outputs

ABB Switzerland Ltd. - 5

HMI500_BBP / 2003-04-01 / RW

21110_TRIP = tripping command from intertripping system to CR 11 - 16 (RST main 1 & main2)

!!

BBP In- & Output configuration - COUPLER


inputs

outputs

Double BB: image Q0 (open & close) and Q0 closing command !!!

ABB Switzerland Ltd. - 6

HMI500_BBP / 2003-04-01 / RW

21110_TRIP = tripping command from intertripping system to CR 11 - 16 (RST main 1 & main2)

!!

Input configuration - IMAGES (CB / isolator)

images must have 2 aux. contacts closed indication

open indication

event recording

ABB Switzerland Ltd. - 7

HMI500_BBP / 2003-04-01 / RW

event send to IBB 1 / 2

event send to the eventlist CU / BU

!!

Output configuration - TRIPPING


latched

blocking !!!

event recording
ABB Switzerland Ltd. - 8
HMI500_BBP / 2003-04-01 / RW

at leading edge send to BU & CU

!!

Input configuration - SYSTEM

ABB Switzerland Ltd. - 9

HMI500_BBP / 2003-04-01 / RW

typical system input signals

!!

Output configuration - SYSTEM

IMPORTANT: all possible alarms have to be configured !!!


ABB Switzerland Ltd. - 10
HMI500_BBP / 2003-04-01 / RW

!!

Input configuration - SYSTEM INPUT COMMANDS

1 aux. contacts OC input

no prolongation

event recording

ABB Switzerland Ltd. - 11

HMI500_BBP / 2003-04-01 / RW

event send to IBB 1 / 2

event send to the eventlist CU

!!

Output configuration - SYSTEM ALARM

reset delay 0 ms

non blocking !!!

event recording

ABB Switzerland Ltd. - 12

HMI500_BBP / 2003-04-01 / RW

at leading and lagging edge send to CU

!!

Disturbance Recorder configuration - SETTINGS


enable DR station #

sampling frequency

# of records Pre-fault and Postfault time


HMI500_BBP / 2003-04-01 / RW

ABB Switzerland Ltd. - 13

memory behaviour

!!

Disturbance Recorder configuration - SIGNALS


signals to be recorded - must be configured as in- or outputs in the binary modules !!!

text in the disturbance record


ABB Switzerland Ltd. - 14

HMI500_BBP / 2003-04-01 / RW

trigger condition

!!

System settings
condition for differential current alarm: no blocking blocking of BBP selective blocking BBP (zone blocking)

isolator running time

remote tripping pulse length


ABB Switzerland Ltd. - 15

HMI500_BBP / 2003-04-01 / RW

condition for isolator image alarm: no blocking blocking of BBP & intertripping selective blocking BBP & intertripping (zone blocking)

!!

BBP settings
Minimum short current (IKmin) Stability factor K

ABB Switzerland Ltd. - 16

HMI500_BBP / 2003-04-01 / RW

time delay for differential current alarm

pick up value of differential current supervision

!!

ABB Switzerland Ltd. - 17


HMI500_BBP / 2003-04-01 / RW

Event Recorder Memory settings

memory behaviour

!!

ABB Switzerland Ltd. - 18


HMI500_BBP / 2003-04-01 / RW

!!