AL-TOUKHI COMPANY FOR INDUSTRY, TRADING &CONTRACTING

Description:

Contract No.:
DISTANCE AND DEF MICOM P442

Customer:
SAUDI ELECTRICITY COMPANY [COA]
Site:
S/S { 8128 }
AL-AZIZIA

Tested By: JAL INTL


Name
-------------------------------------- MURUGAN-.A-------------------------------------------Date & Signature:
23 / 02 / 2009

10731041 / 00
Customer Ref.:
Panel / Designation / Location No.
R03A

Sheet:
1 of 12
Cont.:
Project No.:

Witnessed By: SEC - COA


Name
-----------------------------HANIMOSTAFA------------------------------------------------Date & Signature:
/ / 2009 --------------------------------------------------------------------------------------------------------------

--------------------------------------------------------------------------------------------------------------

MICOM P 442

AL-TOUKHI COMPANY FOR INDUSTRY, TRADING &CONTRACTING


Description:

Contract No.:
DISTANCE AND DEF MICOM P442

Customer:
SAUDI ELECTRICITY COMPANY [COA]
Site:
S/S { 8128 }
AL-AZIZIA
1. RELAY DATA:
CIRCUIT
:
MODEL NO.
:
SERIAL NO.
:
Make
:
Desgn.
:
DRAWING/SH :

UGF + OHL 9013


P44231AB6M0350J
3253471/09/08
AREVA
67N (DEF PROT.)
CD 066119 / SH.231

Sheet:
2 of 12
Cont.:

10731041 / 00
Customer Ref.:
Panel / Designation / Location No.
R03A
RATED VOLTAGE (Vn)
RATED CURRENT (In)
RATED AUX. VOLTAGE (Vx)
FREQUENCY
OPTO I/P VOLTS
SOFTWARE VER.

:
:
:
:
:
:

Project No.:

100 120 VAC


1A
110 250 VDC
60 HZ
110/125 V DC
C4.1

2. RELAY CHECKS (With Relay De-energized):


Sr.
No.

Relay Checks

Result

Inspection for physical damage / defects.

OK

Case Earthing

OK

CT Shorting contacts facility

OK

Verify connections as per approved drawings

OK

Watchdog contacts (J11-J12 closed, J13-J14 open)

OK

3. RELAY CHECKS (With Relay Energized):


Sr.
No.
1
2
3
4
5
6

Relay Checks

Result

Watchdog contacts (J11-J12 opened, J13-J14 closed)

OK

Date & Time - Set clock to local time


- Time maintained when Aux. Supply removed
Alarm (yellow) LED to check make Test Mode enable under
Commissioning Test menu.
Out of service (yellow) LED to check make Test Mode enable under
Commissioning Test menu.
Trip (red) LED apply any fault to produce any trip condition
All 8 programmable LEDs apply Test LEDs under Commissioning test
menu.

OK
OK
OK
OK
OK
52.75 V
52.75 V

4. Operating DC supply current:


Tested By: JAL INTL
Name
-------------------------------------- MURUGAN-.A-------------------------------------------Date & Signature:
23 / 02 / 2009

Witnessed By: SEC - COA


Name
-----------------------------HANIMOSTAFA------------------------------------------------Date & Signature:
/ / 2009 --------------------------------------------------------------------------------------------------------------

--------------------------------------------------------------------------------------------------------------

MICOM P 442

AL-TOUKHI COMPANY FOR INDUSTRY, TRADING &CONTRACTING


Description:

Contract No.:
DISTANCE AND DEF MICOM P442

Customer:
SAUDI ELECTRICITY COMPANY [COA]
Site:
S/S { 8128 }
AL-AZIZIA

Tested By: JAL INTL


Name
-------------------------------------- MURUGAN-.A-------------------------------------------Date & Signature:
23 / 02 / 2009

10731041 / 00
Customer Ref.:
Panel / Designation / Location No.
R03A

Sheet:
3 of 12
Cont.:
Project No.:

Witnessed By: SEC - COA


Name
-----------------------------HANIMOSTAFA------------------------------------------------Date & Signature:
/ / 2009 --------------------------------------------------------------------------------------------------------------

--------------------------------------------------------------------------------------------------------------

MICOM P 442