En esta simulacin se considerado el tap del conmutador en la posicin -7 (flujo prefalla) de manera que se genere un error de relacin respecto al ajuste.
De los resultados de las simulaciones de cortocircuito solo se considera las
contribuciones sombreadas de amarillo.
----------------------------------------------------------------------------------------------------------------------------------| MOABITO220
220.00
32.60 36.25
|
| Cub_6 /Tr3
T83_261
HV-Side
333.511
0.875 -52.55
|
| Cub_4 /Lne
L-2234
Terminal j
152.806
0.401 123.67
|
| Cub_7 /Lne
L-2267
Terminal i
181.318
0.476 130.64
|
|
|
----------------------------------------------------------------------------------------------------------------------------------| MOABITO60
60.00
0.00 0.00
|
| Cub_2 /Lne
L-6046
Terminal i
0.000
0.000 0.00
|
| Cub_3 /Tr2
T2-SEPO1
HV-Side
0.000
0.000 0.00
|
| Cub_4 /Tr2
T2-SEPO2
HV-Side
0.000
0.000 0.00
|
| Cub_6 /Coup Breaker
Terminal j
310.133
2.984 127.45
|
----------------------------------------------------------------------------------------------------------------------------------| MOABITO10
10.00
0.71 -111.36
|
| Cub_4 /Tr3
T83_261
LV-Side
0.000
0.000 0.00
|
-----------------------------------------------------------------------------------------------------------------------------------
(Fase R)
(Fase R)
(Fase R)
(Fase R)
(Fase R)
(Fase R)
Nomber of Windings:
W1
100
Rated(MVA)
220
Nom. (kV)
WYE
Connection
YES
Grounding
0
Angle WRT
300
CT primary
5
CT sec. tap
Inom. Prim.
262.4
Inom.Sec.
4.374
ABC
Rotations
3
W2
W3
100
60
60
10
WYE DELTA
YES
NO
0
30
1000
4000
5
5
962.3 3464.1
4.811
4.330
W4
0
0.48
WYE
YES
0
3000
5
0.0
0.000
Angle
W6
Magnitude
Angle
W6
0
0.48
WYE
YES
0
3000
5
0.0
0.000
TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5
Magnitude
W5
IA
IB
IC
14.58
-52.6
14.58
-172.6
14.58
67.5
0
69
WYE
YES
0
1000
5
0.0
0.000
auto
ACTUAL VALUES
Operating Characteristic
I diff, pu
12
11
10
9
14.92
127.5
14.92
7.5
14.92
247.5
0.00
-53.9
0.00
-166.0
0.00
61.4
0.00
-180.0
0.00
-300.0
0.00
-60.0
0.00
0.00
0.00
-180.0
-300.0
-60.0
0.00
0.0
DIFFERENTIAL CURRENTS
Iad
Ibd
0.22
Magnitude 0.22
-23.9
-143.2
Angle
Icd
0.23
-263.2
RESTRAINT CURRENTS
Iar
Ibr
3.21
Magnitude 3.21
Icr
3.21
8
7
6
5
4
0.00
0.0
3
2
1
DIFF. OPERATION
0
0
2
3
4
Slope characteristics
Iad
7
Ibd
Icd
10
11
12
I restr, pu
0.00
0.0
NO TRIP
Ia
No trip
Ib
No trip
Ic
No trip
W1
ConnectType
0 deg
Angle
ZS Current Subtr
0 (0 deg)
60
262
W3
220
W2
12.5
IDL1
IDL2
IDL3
PDIF 87T
Limite
IdUnre
10
962
ON
15
3464
OFF
10
IdMin
EndSection1
EndSection2
SlopeSection2
SlopeSection3
IdUnre
NegSecDiffEn
IminNegSec
NegSecROA
0.30
1.25
3.00
40.00
80.00
8.00
IB
IB
IB
%
%
IB
0.04
60
IB
Deg
Section2
7.5
Operate
Conditionally
Section1
ON
FUNCTION STATUS
A (W1)
pu
IDNS
0.00
0.00
IDL1
61.18
0.23
IDL2
61.18
0.23
IDL3
61.18
0.23
IBIAS
875.00
3.33
DIFF OPERATION
NO TRIP
PHASE A
PHASE B
PHASE C
NO TRIP
NO TRIP
NO TRIP
Operate
Unconditionaly
Section3
TransformerDiff2Wind(PDIF,87T)
2.5
Restrain
0
0
2.5
7.5
10
PRIMARY VALUES
REFERENCE WINDING
W1
I BASE
I_W1 (A)
I_W2 (A)
()
()
FASE R
875.00
-52.55
2984.00
127.45
FASE S
875.00
-172.55
2984.00
7.45
FASE T
875.00
67.45
2984.00
247.45
12.5
I_W1
I_W3 (A)
()
0.00
-53.92
0.00
-166.01
0.00
61.42
15
W1
Transformer Side
Y ( Wye)
Winding Connection
Vector Group Numeral
Rated Primary Voltage (kV)
Rated Aparent Power (MVA)
0 deg
0 (0 deg)
60
100
15
W3
Fault
Characteristic
D (Delta)
Y (Wye)
220
Earthed
Start Point is
W2
100
Earthed
10
60
Isolated
10
Tripping
Differential Protection
Pickup V. of Diff Current
Slope 1 of Tripping
Base Point for Slope 1
Slope 2 of Tripping
Base Point for Slope 2
Pickup V. of High Set Trip
Pickup for Add-on Stab.
Duration of Add-on Stab.
0.30
0.30
0.00
0.60
2.50
12.00
8.00
15.00
Tripping Characteristics
A (W1)
Diff L1 _ IDiff/INOBJ
61.18
Diff L2 _ IDiff/INOBJ
61.18
Diff L3 _ IDiff/INOBJ
61.18
Stab L1 _ IRest/INOBJ
1688.82
Stab L2 _ IRest/INOBJ
1688.82
Stab L3 _ IRest/INOBJ
1688.82
Blocking
I/InO
I/InO
I/InO
I/InO
I/InO
Cycle
Add-on Stabilization
IDL1
IDL3
Fault Charact
Add-on
pu
0.23
0.23
0.23
6.44
6.44
6.44
10
15
INYECCION DE CORRIENTE
DEVANADO DE REFERENCIA
W1
I BASE
I_W1 (A)
I_W2 (A)
()
()
FASE R
875
-52.55
2984
127.45
FASE S
875
-172.55
2984
7.45
FASE T
875
67.45
2984
247.45
IDL2
PDIF 87T
High Set Trip
20
I_W1
I_W3 (A)
()
0.00
-53.92
0.00
-166.01
0.00
61.42
DIFF OPERATION
NO TRIP
PHASE A PHASE B PHASE C
NO TRIP NO TRIP NO TRIP
-----------------------------------------------------------------------------------------------------------------------------------
25
ABC
3
W2
W3
100
60
60
10
WYE DELTA
YES
NO
0
30
1000
4000
5
5
962.3 3464.1
4.811
4.330
Angle
W6
Magnitude
Angle
W5
0
0.48
WYE
YES
0
3000
5
0.0
0.000
0
0.48
WYE
YES
0
3000
5
0.0
0.000
TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5
Magnitude
IA
IB
IC
5.53
-5.4
3.28
-145.9
3.17
128.3
1.19
77.1
2.63
45.9
3.03
-86.3
0.59
-53.9
0.73
-166.0
0.74
61.4
0.00
-180.0
0.00
-300.0
0.00
-60.0
W6
0
69
WYE
YES
0
1000
5
0.0
0.000
RESTRAINT GRAPH
0.30 Slope1
35.0
2.00
4.00 Slope2
80.0
ACTUAL VALUES
auto
Operating Characteristic
I diff, pu
12
11
10
9
0.00
0.00
0.00
-300.0
-60.0
0.00
0.0
0.00
0.0
0.00
0.0
DIFFERENTIAL CURRENTS
Iad
Ibd
0.01
Magnitude 0.91
-358.7
-103.8
Angle
Icd
0.91
-179.1
RESTRAINT CURRENTS
Iar
Ibr
0.60
Magnitude 1.06
Icr
1.02
8
7
6
5
4
-180.0
3
2
1
DIFF. OPERATION
0
0
Slope characteristics
Iad
Ibd
Icd
10
11
12
I restr, pu
TRIP
Ia
Trip
Ib
No trip
Ic
Trip
W2
ConnectType
0 deg
Angle
0 (0 deg)
60
262
12.5
IDL1
IDL2
IDL3
PDIF 87T
Limite
IdUnre
10
962
ON
ZS Current Subtr
15
W3
220
W1
3464
ON
OFF
10
IdMin
EndSection1
EndSection2
SlopeSection2
SlopeSection3
IdUnre
0.30
1.25
3.00
40.00
80.00
8.00
IB
IB
IB
%
%
IB
0.04
60
IB
Deg
Section2
7.5
Operate
Conditionally
Section1
ON
NegSecDiffEn
IminNegSec
NegSecROA
Operate
Unconditionaly
Section3
TransformerDiff2Wind(PDIF,87T)
2.5
Restrain
FUNCTION STATUS
A (W1)
pu
IDNS
142.52
0.54
IDL1
286.77
1.09
IDL2
143.80
0.55
IDL3
142.99
0.54
IBIAS
315.81
1.20
DIFF OPERATION
TRIP
PHASE A
PHASE B
PHASE C
TRIP
TRIP
TRIP
0
0
2.5
7.5
10
PRIMARY VALUES
REFERENCE WINDING
W1
I BASE
I_W1 (A)
I_W2 (A)
()
()
FASE R
332.00
-5.37
238.00
77.10
FASE S
197.00
-145.90
525.00
45.91
FASE T
190.00
128.34
605.00
-86.25
12.5
15
I_W1
I_W3 (A)
()
473.00
-53.92
580.00
-166.01
595.00
61.42
W1
Transformer Side
Y (Wye)
W inding Connection
Vector Group Numeral
Rated Primary Voltage (kV)
Rated Aparent Power (MVA)
0 deg
220
15
W3
Fault
Characteristic
D (Delta)
Y (Wye)
0 (0 deg)
60
100
Earthed
Start Point is
W2
100
Earthed
10
60
Isolated
10
Tripping
Differential Protection
Pickup V. of Diff Current
Slope 1 of Tripping
Base Point for Slope 1
Slope 2 of Tripping
Base Point for Slope 2
Pickup V. of High Set Trip
Pickup for Add-on Stab.
Duration of Add-on Stab.
0.30
0.30
0.00
0.60
2.50
12.00
8.00
15.00
Tripping Characteristics
A (W1)
Diff L1 _ IDiff/INOBJ
286.78
Diff L2 _ IDiff/INOBJ
143.79
Diff L3 _ IDiff/INOBJ
142.98
Stab L1 _ IRest/INOBJ
407.96
Stab L2 _ IRest/INOBJ
352.81
Stab L3 _ IRest/INOBJ
395.04
Blocking
I/InO
I/InO
I/InO
I/InO
I/InO
Cycle
Add-on Stabilization
IDL1
IDL3
Fault Charact
Add-on
pu
1.09
0.55
0.54
1.55
1.34
1.51
10
15
INYECCION DE CORRIENTE
DEVANADO DE REFERENCIA
W1
I BASE
I_W1 (A)
I_W2 (A)
()
()
FASE R
332
-5.37
238
77.1
FASE S
197
-145.9
525
45.91
FASE T
190
128.34
605
-86.25
DIFF OPERATION
TRIP
PHASE B PHASE C
TRIP
TRIP
PHASE A
TRIP
IDL2
PDIF 87T
High Set Trip
20
I_W1
I_W3 (A)
()
473.00
-53.92
580.00
-166.01
595.00
61.42
25