Sei sulla pagina 1di 10

1

9 8 2

8 3 8

8 3 8

12

R R

TYPICAL LAYOUT
One-and-Half Scheme

C
1250 1250

A
1250 1250 1250 1250

7000

7000

3500

3500

7000

7000

7000

7000

13000

28000

28000

B
1250 1250

CB11

CB12

CB13

CB14

CB21

CB22

CB23

CB31

CB32

CB33

CB34

CB41

CB42

CB43

CB44

3500

7000

7000

28000

3500

TR1

TR2

TR3

TR4

TR5

TR6

A_A
APPROX9800 1250 4210 4570 4570 3300 1000

B_B
APPROX9800 1250 4210 4570 4570 3300 1000

C_C

9140

T U

14600

14600

550kV HGIS

550kV HGIS for Fu Jian Shui Kou Power Station, China; 2001

The 550kV HGIS is designed based on the technology of 550kV GIS, and its basic components are the same as that of 550kV GIS such as CB, DS, ES, FES, CT and BSG, which can be combined with the VT, LA and overhead buses of open-type combined apparatus as a new switchyard for control, protection, measurement and maintenance of power system. It is characterized by small size, reliable operation, strong anti-pollution and competitive price.

Parts of GIS

CB for GIS DS for GIS ES for GIS FES for GIS CT for GIS BSG for GIS

VT for AIS LA for AIS Overhead bus

New GIS Switchyard

FEATURES 1 High reliability


Owing to the special main wiring and some features combined with that of open-type combined apparatus, 550kV HGIS has the following features: high operating reliability, good applicability to environment and anti-earthquake characteristics, small size, reliable breaking property and operating mechanism, high insulating reliability, minimum work at site, lower SF6 leakage.

2 Good applicability
550kV HGIS takes use of the standard constructive modules of 550kV GIS in its design so that the HGIS has a compact construction and building-block arrangement, meeting the requirements of various main wirings.

3 Excellent economy
The price of 550kV HGIS is about 80% that of 550kV GIS, and the assembling area is 45% that of conventional open-type switchyard only, so it has an excellent economy.

RATINGS
The main technical data of 550kV HGIS are the same as that of 550kV GIS. Rated voltage: 550kV; Rated current: 3150A, 4000A; Rated frequency: 50Hz/60Hz; Rated lightning impulse withstand voltage: To earth/Across breaks: 1550/1550+450kV; Rated switching impulse withstand voltage: To earth/Across breaks: 1175/1175+450kV; Rated power frequency withstand voltage: To earth/Across breaks: 680/680+318kV; Rated short-time withstand current: 50kA, 63kA; Rated peak withstand current: 125kA, 160kA; Rated short-circuit duration: 3s; Operating mechanism: Spring mechanism for CB; motor and spring mechanism for DS,ES,FES;

=V NM

MODE OF ARRANGEMENT
Typical arrangememt of 550kV HGIS basically has following three types

1 Arrangement of 1 1/2 wiring


BSG FES DS CT ES CB BSG FES DS CT DS ES DS CT BSG FES ES DS CT DS ES DS CT CB CT ES DS BSG FES

ES

ES CB

ES

2 Arrangement of 1-CB wiring


BSG FES DS CT ES CB DS CT ES BSG FES

3 Arrangement of 2-CB wiring


BSG FES DS CT ES CB BSG FES DS CT DS ES CT BSG FES CB DS CT ES

ES

ES

DS

NN NO

363kV/300kV GIS

1. Factory assembly of a 363kV GIS 2. 300kV GIS for Jalan Gallowag S/S, Malaysia;1997 3. 300kV GIS for Pudu ULu S/S Malaysia; 1996 4. 363kV GIS for An Kang Hydraulic Power Station,China;1990 5. 363kV GIS for Wei Nan Power Station of ShanxiProuince, China;1990 2

FEATURES
1 High breaking reliability
The circuit breakers become more reliable as the number of breaks is reduced to a single break.

2 High insulating reliability


The insulating spacers, tubes ,levers and insulating desks etc for GIS are made with casting machines from Germany and under the chemical directions and production processing from Mitsubishi. The power frequency withstand test and partial discharge test have been done on those parts, and the values of the partial discharge are lower than the requirements by IEC.

3 Good applicability
It is characterized by a compact construction and small occupation of space since equipped with the circuit breaker of single break, the expenses for the foundation or the building are reduced.

4 Minimum work at assembling site


The advanced processing devices and all-round quality control system have been adopted in manufacture of the GIS. The GIS is assembled and tested against the conditions of assembling site, packed in transport unit after tested, for easy and convenient transport and minimizing work at site.

5 Lower leakage of SF6 gas


The mode of separated monitoring is used in the SF6 gas system of GIS,doing away with SF6 valves and SF6 piping system. New self-sealed adapters and SF6 gas densimeters are used to get rid of the possibility of SF6 leakage outside the GIS, lowering the SF6 gas leakage.

Double-busbar arrangement of 300~363kV GIS (Vertical type circuit breaker) Double-busbar arrangement of 300~363kV GIS (Horizontal type circuit breaker)

NP NQ

MODE OF ARRANGEMENT

Double-busbar arrangement of 300~363kV GIS

RATINGS
Main Technical Data for 300~363kV GIS ( Based on IEC )
Ratings Item Installaton Ambient temperature Humidity (per month) Applied ambient Height above sea level conditions Wind velocity Earthquake intensity Creepage distance Rated voltage Rated current Rated short-time withstand current (3s) General data Peak withstand current Lighting impulse withstand voltage(peak) Power frequency withstand voltage(r.m.s) Rated SF6 gas pressure(exclusive of CB) Annual leakage rate of SF6 gas % m m/s g cm/kV kV A kA kA kV kV MPa % 1050 460 0.5 1 Unit 300kV 363kV Remarks Indoor or outdoor -30~40 90 1000~3000 35 Horizontal acceleration: 0.15, 0.3 Vertical acceleration: 0.0075, 0.15 1.7, 2.1, 2.5 300 363 Accelerated simultaneously Calculated to rated voltage At 25

2000/2500/3150/4000 40/50 100/125 1175 510 1 min 20