Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
You are here: Home > Products > Uninterruptible Pow er Supply (UPS) > Smart-UPS On-Line
Technical Specifications
Documentation
Options
Output
Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Note Output Voltage Distortion Output Frequency (sync to mains) Other Output Voltages Crest Factor Topology Waveform Type Output Connections 2100 Watts / 3000 VA 2100 Watts / 3000 VA 230V Configurable for 220 : 230 or 240 nominal output voltage Less than 3% 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 220, 240 3:1 Double Conversion Online Sine wave (8) IEC 320 C13 (2) IEC 320 C19 (2) IEC Jumpers Bypass Internal Bypass (Automatic and Manual)
www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SURTD3000XLI&tab=models&page_type=print
1/5
7/3/13
Input
Nominal Input Voltage Input Frequency Input Connections 230V 50/60 Hz +/- 5 Hz (auto sensing) British BS1363A IEC-320 C20 Schuko CEE 7/EU1-16P Cord Length Input voltage range for main operations Input voltage adjustable range for mains operation Other Input Voltages 2.44 meters 160 - 280V 100 - 280V 220, 240
Curve A B C D E
Part Number(s) SURTD3000XLI SURTD3000XLI + (1)SURT192XLBP SURTD3000XLI + (2)SURT192XLBP SURTD3000XLI + (3)SURT192XLBP SURTD3000XLI + (4)SURT192XLBP
www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SURTD3000XLI&tab=models&page_type=print
2/5
7/3/13
Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output.
Energy Use/Efficiency
www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SURTD3000XLI&tab=models&page_type=print
3/5
7/3/13
Hover over the line on the graph above to view the efficiency at any desired load Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output.
Physical
Maximum Height Maximum Width Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height 432.00 mm 130.00 mm 660.00 mm 3U 54.55 KG 63.64 KG 347.00 mm
4/5
www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SURTD3000XLI&tab=models&page_type=print
7/3/13
Environmental
Operating Environment Operating Relative Humidity Operating Elevation Storage Temperature Storage Relative Humidity Storage Elevation Audible noise at 1 meter from surface of unit Online Thermal Dissipation 0 - 40 C 0 - 95% 0-3000 meters -15 - 45 C 0 - 95% 0-15000 meters 55.00 dBA 609.00 BTU/hr
Conformance
Regulatory Approvals Standard Warranty BSMI, C-tick, CE, CSA, EN 50091-1, EN 50091-2, EN 55022 Class A, EN 60950, EN 61000-3-2, GOST, JEON, UL 1778, VCCI, VDE 2 years repair or replace
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
www.apc.com/products/resource/include/techspec_index.cfm?base_sku=SURTD3000XLI&tab=models&page_type=print
5/5