Proper detection and treatment of power swing to reduce the risk of Blackouts
Gustav Steynberg
Siemens AG 2008 Energy Sector
Basics
P=
VG VM sin( ) XG + X L + XM
I*XG
I*XL
I*XM P Pmax
VA VG
VB VM
0 90 180
Siemens AG 2008 Energy Sector
Page 2
Nov-09
Jrg Blumschein
VG
=180 0 90 180
VA=0
Page 3
Nov-09
Jrg Blumschein
= 60 normal load condition = 120 dangerous for distance protection = 180 unstable power swing out of step tripping R
Z( = 180 ) Z( = 120 )
Z( = 60 )
Page 4
Nov-09
Jrg Blumschein
Required characteristics for power swing detection No settings are required, thus no complex calculation is needed. Detection of power swing with frequencies up to 7Hz. Detection of power swings that occur during single-pole open condition and during faults. Immediate unblocking of distance protection on all kind of faults occurring during power swing. Quick detection of reappeared power swing after fault clearance. Out-of-step tripping in case of unstable power swing
Page 5
Nov-09
Jrg Blumschein
Continuous calculation and monitoring of Impedances First impedance in power swing area: algorithm starts to analyze the impedance trajectory
Zone
Page 6
Nov-09
Jrg Blumschein
Page 7
Nov-09
Jrg Blumschein
monotony criterion
X X1 X2 X1 X2 1 R2 R2 R2 R1 R R1
power swing if R1 and R2 or 2 and X1 and X2 2 have same directions direction no power swing if R1 and R2 and X1 and X2 have different directions
X2
Page 8
Nov-09
Jrg Blumschein
continuity criterion
X X
power swing if R or X exceed a threshold no power swing if R and X are below the threshold R R
Page 9
Nov-09
Jrg Blumschein
smoothness criterion
X X1 X1 R2 R2 R1 X2 R1
Page 10
Nov-09
Jrg Blumschein
10
Impedance trajectory will not follow a perfect elliptical path difficult to manage with blinders easy to detect with criteria monotony, continuity and smoothness
Page 11
Nov-09
Jrg Blumschein
11
Page 12
Nov-09
Jrg Blumschein
12
Page 13
Nov-09
Jrg Blumschein
13
Trip
Trip
D2
Busbar 1
Transmission network
Busbar 2
D3
Trip
Trip
D4
3-phase fault
Distribution network
Relay 5
Power swing blocking function prevents the distance relays D1 .. D4 from unselective tripping
Page 14
Nov-09
Jrg Blumschein
14
power swing is initiated by the reverse fault: The impedance moves on a circular trajectory The power swing blocking function prevents an unselective trip, before the impedance vector enters the tripping zone Z1
ZFault
Zone Zone Z3
15