Sei sulla pagina 1di 5

Inspection Procedure

12-SAIP-50 Use of Metal Studs in Buildings Document Responsibility: Inspection Engineering Standards Committee 18 April 2009

Saudi Aramco DeskTop Standards


Table of Contents 1 2 3 4 5 6 Scope............................................................ Purpose......................................................... References.................................................... Definitions...................................................... Fabrication and Assembly............................. Erection and Installation................................ 2 2 2 2 3 3

Previous Issue: 31 July 2004 Next Planned Update: 18 April 2014 Page 1 of 5 Primary contact: Kakpovbia, Anthony E. on 966-3-8747226
CopyrightSaudi Aramco 2009. All rights reserved.

Document Responsibility: Inspection Engineering Standards Committee Issue Date: 18 April 2009 Next Planned Update: 18 April 2014

12-SAIP-50 Use of Metal Studs in Buildings

Scope 1.1 1.2 This procedure addresses inspection requirements for use of metal studs in buildings. This SAIP is intended to establish a standardized methodology by Saudi Aramco inspection personnel in the implementation of inspection programs within Saudi Aramco facilities. The SAIP shall not be included in purchase order or contract documents issued to outside agencies.

Purpose 2.1 The intent of this procedure is to provide typical inspection guidelines for the installation of metal stud framing. This guideline is to supplement relevant purchase orders, contracts, specifications, design drawings, scope of work and other Saudi Aramco Inspection Procedures and Manufacturer's Recommended Practices. Prudent construction practices must be followed, and any exceptions to the following guidelines shall be brought to the attention of the appropriate construction agency. These guidelines provide inspection requirements only.

2.2 3

References ANSI/ASTM C645 Recommended Practice ANSI/ASTM C754 AWS D1.3 Gypsum Construction Handbook

Definitions 4.1 Furring Member - Rigid furring channels and studs that serve as a base for screw attachment of gypsum board used either as direct furring (attached directly to the building structure) or as cross furring (attached at right angles to main members). Runner - refers to floor or ceiling track. Channels - refers to the material to which furring members are attached. Cross Furring - refers to a member installed perpendicular to main beams that serves as a base for screw attachment of gypsum board.
Page 2 of 5

4.2 4.3 4.4

Document Responsibility: Inspection Engineering Standards Committee Issue Date: 18 April 2009 Next Planned Update: 18 April 2014

12-SAIP-50 Use of Metal Studs in Buildings

Fabrication and Assembly 5.1 Metal framing members shall be of the proper size and design for the intended use, and shall be installed in accordance with specifications ASTM C754 and ASTM C645. Axially loaded studs shall be installed to bear directly upon the inside of the runner web. Only approved fastening methods as stated in scope of work or manufacturer's recommended practices shall be used in stud wall framing. Prefabricated panels and sub assemblies shall be square and braced against racking during erection. Bent, buckled or distorted members shall not be used. Material shall be identifiable in accordance with ANSI/ASTM C754.

5.2 5.3 5.4 5.5 5.6 6

Erection and Installation 6.1 RUNNER/TRACK Installation 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 6.2 Runners shall be aligned at floor and ceiling. Runners shall be anchored 2 inches (5 cm) from the end and maximum 24 inches (61 cm) on center. Runner butt joints shall be anchored to a common structural element or spliced or welded. Uniform, level bearing support shall be provided for the bottom runner. Runners shall not be mitered at intersection.

Stud Installation 6.2.1 6.2.2 6.2.3 6.2.4 Studs shall be vertical and engage both top and bottom runners with open side facing in the same direction and with punch outs properly aligned. Stud spacing shall not exceed 24 inches (61 cm) on center. Studs shall be securely fastened to the flanges of both top and bottom runners. Studs shall be aligned directly below other overhead framing members.
Page 3 of 5

Document Responsibility: Inspection Engineering Standards Committee Issue Date: 18 April 2009 Next Planned Update: 18 April 2014

12-SAIP-50 Use of Metal Studs in Buildings

6.2.5 6.2.6

If paragraph 6.2.4 above is not possible, lintels shall be provided. No splicing is permitted in (a) runner over lintels, (b)diaphragm sheathing or (c) diagonal bracing. Splices are not permitted in load bearing studs.

6.2.8

When splices are permitted, in non load bearing studs, the lap shall be a minimum of 8 inches (20 cm.). To splice two studs, place one into the other forming a box section. Jack studs shall be installed below window sills, above window and door headers at free standing stair rails and elsewhere to furnish support and shall be securely attached to supporting members. Blocking as required for cabinet and mounted fixtures is to be installed.

6.2.9

6.2.10 Wall stud bridging shall resist bending and rotation and not exceed 4 ft 3 inches (130 cm.) on center. 6.2.11 Web cutouts shall not impair minimum sectional properties and be calculated as stated in table 1 of ASTM C645. 6.2.12 Flange cutouts are not permitted in studs. 6.2.13 Cutouts in runners and furring channels shall not impair essential structural properties. 6.2.14 A stud shall be installed no more than 2 inches (5 cm) from intersecting construction. 6.2.15 A stud shall be installed and anchored to all door frame/jambs. 6.2.16 Welded connections not referenced in ASTM C754 nor ASTM C645 shall be made in accordance with AWS D1.3. 6.2.17 Welds on galvanized material shall be coated in accordance with applicable SAES-H-series. 6.3 Chase Wall Framing 6.3.1 6.3.2 Install studs and runners as described in Sections 5 and 6 and the studs must be opposite one another. Cross braces horizontally to opposite studs shall be installed not to exceed 4 ft (122 cm) on center.

Page 4 of 5

Document Responsibility: Inspection Engineering Standards Committee Issue Date: 18 April 2009 Next Planned Update: 18 April 2014

12-SAIP-50 Use of Metal Studs in Buildings

6.3.3

Cross braces shall be either minimum 12 inches (30 cm) wide gypsum board with 3 fasteners in each stud, or stud or runner with 2 fasteners in each connection to supporting stud.

18 April 2009

Revision Summary Editorial revision to change the primary contact. Revised the Next Planned Update.

Page 5 of 5

Potrebbero piacerti anche