Polymeric Surge Arrester up to 550 kV


Catalogue 2008

Content Installations Introduction Application Benefits Design Concept I. Single Modules for series parallel surge arresters A. Construction B. Housing material II. The Module Series Parallel Design A. Voltage distribution and stress grading B. Thermal ageing and partial discharge C. Comparison between Series Parallel and single column design D. Electrical tests for Series Parallel surge arrester E. Advantages of the Series Parallel design Appropriate Surge Arrester Selection I. Electrical performance and housings II. Surge Arresters for System Voltages 123 kV and 170 kV III. Surge Arresters for System Voltages 245 kV and 362 kV IV. Surge Arresters for System Voltages 420 kV and 550 kV V. Accessories 16 VI.Transmission Line Surge Arresters for Overhead Poles and Overhead Lines up to 150 kV Additional Equipment Surge Counter Tyco Electronicss total commitment to quality Tyco Electronics presents the complete solution 22 23 24 7 8 10 12 4 4 4 5 5 5 6 6 6 2 3 3 3

20

Installations

110 kV Surge Arresters - Estonia

66 kV Surge Arresters - Statkraft, Norway

132 kV Surge Arresters - Statkraft - Norway

300 kV Surge Arresters - Statnet

400 kV Surge Arresters - Damhead Creek UK

400 kV Surge Arresters - Statnet

500 kV Surge Arresters - Indonesia

Introduction Tyco Electronics has been manufacturing surge arresters for over 60 years. Our knowledge and experience we use to develop our surge arrester range today. Tyco Electronics is well known for their insulation and protection products worldwide. The range of HV surge arresters up to 550 kV and line discharge classes from 2 up to 5 operates in 130 countries in diverse climates from the artic circle to the tropics. Since 1988 Tyco Electronics have designed the patented series parallel metal oxide surge arrester which unique in construction and provides many advantages over conventional single column and multiple columns porcelain and polymeric housed arresters. They were designed and tested to meet defined abnormal service conditions as detailed in Annex A of IEC 60099-4 (1991). The unique construction of this series parallel surge arrester provides electrical and mechanical properties that cannot be obtained with single or multiple column types. In particular the geometry and unitary construction provides inherent voltage grading that does not require additional grading rings or further correction of the maximum continous operating voltage (Uc) required for arresters of conventional construction. Application This range of Silicone Rubber housed surge arresters is applicable for substation equipment and transmission lines. Because of their high cantilever strength, they n b used to replace the able support insulators n HV terminations. This results in simplified installation for HV terminations at reduced cost which is aesthetically m acceptabIe to the general pubIic. It should b noted that this type of installation n not b achieved with other surge arresters of lower strength construction.

Benefits Low residual voltages Superior protection margins Superior TOV performance Inbuilt stress grading along the full length More effective grading per unit length than a single column type Similar stress distribution like single column type, but without stress grading ring Resistant against Radial stress based on the gap free Bowthorpe patented construction Safe non-shattering short circuit behavior to higher current levels High-energy handling Direct molded housing to prevent moisture ingress Hydrophobic and tracking and erosion resistant silicone housing Superior pollution performance Excellent cantilever and tensile performance Excellent mechanical, vibration and impact withstand capability Extremely strong mechanical strength Low thermal ageing of varistor insulation Smaller footprint than equivalent single column SA with grading ring Modular design for quick installation and commission Light weight Capable to withstand seismic condition Uniform current sharing Maintenance free Tested in accordance with IEC60099-4 at independent accredited laboratories Certified to GOST requirements and has accreditation in Russian Federal network and Ukraine Power Ministry Quality design and manufacturing, ISO 9001 and 14001 compliant

Design Concept

1-column porcelain housed and nonintegrated polymeric housed type surge arresters have a lot of weaknesses. A few of them are the control of uniform stress grading and the radial field strength which are the most important issues in these surge arrester design types. The high radial field would lead to discharge in the surge arrester enclosure between the porcelain inside and the metal oxide varistors.

B. Housing material Housing material is service proven formulation of Silicone Rubber. The silicone housing was developed using the knowledge accumulated over 35 years of internal Tyco Electronics materials science expertise and experience, resulting in an optimum shed profile and a material with excellent tracking and erosion resistance. This range of Silicone Rubber housed surge arresters has b n fully tested to meet the very severe pressure-relief tests.

I. Single Modules for Series Parallel Surge Arrester A. Construction The Tyco Electronics Bowthorpe patented surge arrester construction overcame this weakness by eliminating this air gap by direct moulding of the silicone rubber housing onto the wrapped ZnO varistor elements and the terminal assembly. The applied ZnO varistors ensure a very good electrical behaviour. The polymeric housing and the shed form (figure 1a) shows a good performance in salt-fog tests. Excellent hydrophobicity

Stainless Steel Terminal Block

Aluminium End Block

Corona Ring

Safe non-shattering failure mode


Silicone Rubber Housing Intermediate metal work

Heat Sink

ZnO Varistor Element

Die Cast Aluminium Sealing End

Insualted base

Figure 1a: Tyco Electronics Bowthorpe surge arrester core and series parallel arrester

Track and erosion resistant

Voltage across this surge arrester section

Thermal ageing of the varistor would be caused by the lack of self limiting under the combination of high stress and low source impedance. The series parallel surge arrester design has eliminated both, thermal and partial discharge ageing to the metal oxide arrester. The Series Parallel surge arrester has no internal air gaps and therefore requires no grading ring to avoid internal ionisation.

Figure 2a shows the coaxial circuit approximation model l and figure 2b shows typical results obtained and confirmed the near uniform longitudinal voltage stress distribution. Unlike other designs the Series Parallel surge arrester does not require external means such as grading rings, to aid the voltage distribution.

3,275m radius

0.1

(R

0.14 (r) 0.46 (d)

Earth Plane

II. The Module Series Parallel Design A. Voltage distribution and stress grading The voltage distribution is largely governed by the surge arrester geometry and intermediate plates. The intermediate connection plates of the series parallel surge arresters provide additional natural grading capacitance. The intermediate connection plates have stray capacitances which cascade and shunt to earth. Furthermore, the resistance and capacitance of the non-linear varistors also provide voltage grading. The equivalent cascade capacitance network (Fig. 1b) gives more uniform electric field distribution when compared it with a single column porcelain or nonporcelain house surge arrester with or without grading ring. Intermediate connecting plates assist the reduction in radial stress at the highest voltage sections. The overall geometry of the modular surge arrester is such that both radial and longitudinal voltage stress was at an acceptable value at the highest system operating voltage.
Plinth

6.60 m

Figure 1b: Equivalent electric circuit network and the additional capacitance introduced by the series parallel surge

(not to scale)

Figure 2a: Field plot of series surge arrester using a coaxial circuit approximation model

3.275m

A 26.02% 19.38% 14.44% 10.83% 8.18%

B 18.92% 18.78% 16.25% 12.34% 9.35% 7.19% 5.67% 4.65%

C 12.42% 12.40% 12.37% 12.36% 12.30% 11.11% 8.94% 7.33%

Earth Plane

6.28% 4.93% 4.04%

5.94%

6.85%

10.77%

Plinth

Figure 2b: Filed plot result of series parallel surge arrester A Varistor non-conduct B Varistor partially conduct C Varistor fully conduct

B. Thermal ageing and partial discharge An exponential longitudinal voltage grading of a surge arrester is undesirable phenomenon for varistor disks especially for those which are in top of the Surge Arrester. Low energy ionisation of the parallel air gap due to the high electrical stress would lead to ageing and failure of the varistor insulation. It has been established that partial discharge activity in close proximity to metal oxide varistors will lead to rapid ageing and premature failure. Therefore, the conventional single column arrester requires a grading ring for the additional reasons other than uneven field or thermal considerations. Equivalent circuit network (Fig. 2a) can only handle the varistor element in its linear model either before or after the threshold turn on point. For the former, varistors have high resistance and its capacitance that dictates the surge arrester voltage grading. Beyond the turn on point the varistors have low resistance and this dominates the voltage grading. Further more for the former case, although the varistor or varistors are seeing high stress, the equivalent network as shown in figure 3, has high source impedance (Z). Under these conditions the voltage across the varistor will collapse as soon as any significant current commences to flow. The high equivalent source impedance effectively limited the voltage and current that can be applied to the varistor elements located in top surge arrestor section high stress region. It is in this context that further consideration must be given to actual ageing mechanism.

C. Comparison between series parallel and single column design There are differences and similarities between the field plot to a single column porcelain house surge arrester and the Series Parallel design. They are summarized as follows: The Series Parallel arrester has more effective grading per unit length than the single column type Specially a Series Parallel 4P type exhibits similar stress distribution to the IEC example calculations, but without use the oversize diameter voltage grading rings Radial stress is an issue for porcelain housed design due to the inbuilt air gap between the varistor and the housing inner wall but not for the gap free (integrated housing) Tyco Electronics patented construction

CURRENT (2.0 kA/div) CH 1 CH 2 CH 3 0 TIME (s)

10 kA

In addition, a proprietary internal procedure was introduced to check the current sharing of parallel columns within a series parallel surge arrester. A proprietary process ensures that between parallel columns the lowest practical differences in characteristics can be employed in one complete series parallel surge arrester. Therefore, residual voltages, energy absorption and heat dissipation are shared among the parallel units. E. Installation and maintenance advantages of the series parallel design Good stress grading without the need of oversize grading ring Light weight no heavy lifting equipment is required for installation Light weight no heavy duty foundation is required for the surge arrester Modular design - quick installation and commission Lattice structure - exceptional strong mechanical strength Non shatter of the surge arrester housing transportation easiness Non shatter of the surge arrester housing - no damage to personal and nearby expensive equipments Good pollution performancemaintenance free Environmental acceptable materialmaintenance free The series parallel design is capable to withstand seismic condition set in the current international standards which guarantees reliable maintenance in all regions.

D. Series Parallel surge arrester electrical tests The following standard IEC routine testing for every series parallel surge arrester units: - Reference voltage measurement - Partial discharge measurement - Leakage current measurement - Residual voltage measurement

Voltage across this surge arrester section

High series impedance

Surge Arrester Section

Open circuit Voltage Source

I. Surge Arrester Selection

Electrical Performance
System Voltage Rated Voltage Line Discharge Class Long Duration Current Nominal Discharge Current (4/10s) Rated Short Energy Circuit Capability at Current Ur acc. To IEC 60099-4 kA 40 40 63 63 40 40 63 63 40 40 63 63 40 63 63 63 63 63 63 63 63 kJ/kV 4,5 7,0 10,8 12,5 4,5 7,0 10,8 12,5 4,5 7,0 10,8 12,5 7,0 10,8 12,5 9,4 10,8 12,5 16,4 12,5 16,4 Type Page

kB 123

kB kB kB A 84-126 2 450 10 96-126 3 750 10 96-120 4 1100 20 108-120 5 1500 20 Neutral Ground 75 2 450 10 170 132-150 3 750 10 132-150 4 1100 20 132 5 1500 20 Neutral Ground 96 2 450 10 Neutral Ground 96 3 750 10 245 180-214 4 1100 20 180-214 5 1500 20 Neutral Ground 168 3 750 10 362 240-290 4 1100 20 260-290 5 1500 20 Neutral Ground 180 3 750 20 420 336-360 4 1100 20 330-393 5 1500 20 336-360 5 1800 20 550 396-444 5 1500 20 420-468 5 1800 20 High current inpulse (4/10s) - 100 kA (for all Surge Arrester types)

HSR 2PH 3P 4P HSR 2PH 3P 4P HSR 2PH 3P 4P 2PH 3P 4P 3P 3P 4P 5P 4P 5P

8 8 8 8 8 8 8 8 8 8 10 10 10 10 10 10 12 12 12 12 12

HSR

2PH

3P

4P

II. Surge Arrester for System Voltages 110 kV and 170 kV Protective Characteristics

System Voltage

Ur*

Uc**

Line Discharge Class

Max. U res tested with current wave Switching surge Lightning Current (30/60 s) (8/20 s) 250 A kV 500 A kV 183 192 197 208 208 213 224 232 235 237 259 272 203 203 210 218 226 226 234 242 249 257 265 198 206 213 213 221 244 222 245 162 280 291 291 301 312 274 285 295 305 276 208 203 5 kA kV 209 219 225 237 237 243 256 265 268 271 296 311 227 227 235 244 253 253 262 270 279 288 296 219 228 236 236 245 270 240 265 185 314 325 325 337 349 304 315 326 338 298 237 227 10 kA kV 225 235 242 255 255 261 275 285 288 291 318 334 241 241 250 260 269 269 278 287 297 306 315 232 241 250 250 259 285 253 280 199 334 346 346 358 371 321 333 345 357 314 255 241 20 kA kV 248 259 266 281 281 288 303 314 317 321 350 369 261 261 271 281 291 291 301 311 321 331 341 249 258 268 268 278 306 271 299 219 361 374 374 388 401 345 357 370 383 337 281 261

Steep Current (1/20 s)

kV 123

kV 84 87 91 95 96 98 102 106 108 110 120 126 95 96 98 103 106 108 110 114 120 121 126 96 98 103 105 108 120 108 120

kV 67,0 70,0 73,0 76,0 76,8 79,0 82,0 85,0 86,4 88,0 96,0 101 76,0 76,8 79,0 82,4 84,8 86,4 88,0 81,2 96,0 96,8 101 76,8 79,0 82,4 84,0 86,4 96,0 86,4 96,0 60,0 106 110 112 115 120 106 110 115 120 106 76,8 76,8 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 5 5 2 3 3 3 3 3 3 4 4 4 5 2 3

10 kA kV 242 252 259 274 274 281 295 306 309 313 341 359 257 257 267 276 286 286 296 306 316 326 336 247 257 266 266 276 304 268 296 213 355 369 369 382 395 342 355 368 380 333 274 257

171 178 183 193 193 198 208 216 218 221 241 253 191 191 198 205 213 213 220 227 235 242 249 188 195 202 202 209 231 211 233 151 264 274 274 284 293 260 270 279 289 262 193 191

Neutral Ground 75 170 132 138 140 144 150 132 138 144 150 132 Neutral Ground 96 Neutral Ground 96 * ** *** ****

Ur - Rated Voltage Uc - Cont. Operating voltage "TOV" curves are given in Technical data for selected Surge Arrester (on request) Accessories selection see on the pages 14 - 19

Surge Arrester with other characteristics are available on request

Temporary Creepage Overvoltage length capability for 1 sec***

Overall height

Rec. Min. distance between phase centers

Rec. Min. Max. Cantilever Weight load distance between phase to earth mm 455 475 495 516 521 536 556 577 586 597 651 684 516 521 536 559 575 586 597 619 651 657 684 521 536 559 570 586 651 586 651 407 716 749 760 782 814 716 749 782 814 716 521 521 N 600 600 600 600 600 600 600 600 600 600 600 600 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 2000 2000 2000 2000 2000 2000 2875 2875 900 500 500 500 500 500 1875 1875 1875 1875 2750 600 1000 kg 17 17 17 17 17 17 17 17 17 17 17 17 35 35 35 35 35 35 35 35 35 35 35 65 65 65 65 65 65 64 64 11 46 46 46 46 46 84 84 84 84 86 17 35

Product code****

kV 97,7 102 106 111 112 115 120 124 127 128 140 147 109 110 113 118 121 124 126 131 138 139 145 115 117 122 124 128 141 119 132 87,5 152 159 160 166 173 155 162 169 176 145 113 110

mm 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 3975 5300 5300 5300 5300 5300 5300 5300 5300 5300 5300 3975 3975

mm 1428 1428 1428 1428 1428 1428 1428 1428 1428 1428 1428 1428 1454 1454 1454 1454 1454 1454 1454 1454 1454 1454 1454 1500 1500 1500 1500 1500 1500 1838 1838 950 1936 1936 1936 1936 1936 2000 2000 2000 2000 1951 1428 1454

mm 841 1133 1168 1203 1212 1238 1274 1309 1325 1344 1438 1494 1337 1346 1373 1412 1440 1459 1478 1516 1572 1581 1628 1612 1639 1678 1697 1725 1838 1725 1838 759 1685 1741 1760 1798 1854 1951 2007 2064 2120 1951 1212 1346

3HSRC(P)84L1E1M0(5) 3HSRC(P)87L1E1M0(5) 3HSRC(P)91L1E1M0(5) 3HSRC(P)95L1E1M0(5) 3HSRC(P)96L1E1M0(5) 3HSRC(P)98L1E1M0(5) 3HSRC(P)102L1E1M0(5) 3HSRC(P)106L1E1M0(5) 3HSRC(P)108L1E1M0(5) 3HSRC(P)110L1E1M0(5) 3HSRC(P)120L1E1M0(5) 3HSRC(P)126L1E1M0(5) 2P3HSRC95L2E2M4 2P3HSRC96L2E2M4 2P3HSRC98L2E2M4 2P3HSRC103L2E2M4 2P3HSRC106L2E2M4 2P3HSRC108L2E2M4 2P3HSRC110L2E2M4 2P3HSRC114L2E2M4 2P3HSRC120L2E2M4 2P3HSRC121L2E2M4 2P3HSRC126L2E2M4 3P3SR96L2E2M7-4 3P3SR98L2E2M7-4 3P3SR103L2E2M7-4 3P3SR105L2E2M7-4 3P3SR108L2E2M7-4 3P3SR120L2E2M7-4 4P3SR108L2E2M7-5 4P3SR120L2E2M7-5 2HSRC(P)75L1E1M0(5) 2P4HSRC132L2E2M4 2P4HSRC138L2E2M4 2P4HSRC140L2E2M4 2P4HSRC144L2E2M4 2P4HSRC150L2E2M4 3P4SR132L2E2M7 3P4SR138L2E2M7 3P4SR144L2E2M7 3P4SR150L2E2M7 4P4SR132L2E2L7-5 3HSRC(P)96L1E1M0(5) 2P3HSRC96L2E2M4

III. Surge Arrester for System Voltages 245 kV and 362 kV Protective Characteristics

System Voltage

Ur*

Uc**

Line Discharge Class

Max. U res tested with current wave Switching surge Lightning Current (30/60 s) (8/20 s) 250 A kV 500 A kV 368 381 381 394 407 407 419 419 445 370 383 383 396 408 421 421 447 353 498 551 551 551 569 569 587 587 587 605 531 551 551 572 572 572 592 592 592 368 5 kA kV 408 422 422 436 450 450 464 464 492 401 414 414 428 442 456 456 483 395 552 611 611 611 630 630 650 650 650 670 575 597 597 619 619 619 641 641 641 408 10 kA kV 431 446 442 461 475 471 490 490 520 422 437 437 451 466 480 480 510 420 582 645 645 645 666 666 686 686 686 707 606 629 629 652 652 652 675 675 675 431 20 kA kV 463 479 479 495 511 511 527 527 558 452 468 468 483 499 514 514 546 454 625 692 692 692 715 715 737 737 737 760 648 673 673 698 698 698 723 723 723 463

Steep Current (1/20 s)

kV 245

kV 180 183 186 192 194 198 201 205 214 180 183 186 192 198 201 204 214

kV 144 146 149 154 155 158 161 164 171 144 146 149 154 158 161 153 171 134 192 211 214 217 221 223 226 229 230 232 208 211 214 217 221 223 226 230 232 144 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 3 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 3

10 kA kV 459 475 475 491 507 507 523 523 555 447 463 463 478 494 509 509 540 447 621 688 688 688 710 710 732 732 732 754 642 667 667 691 691 691 716 716 716 459

349 361 361 373 385 385 397 397 421 352 364 364 376 389 401 401 425 332 472 522 522 522 539 539 556 556 556 573 505 525 525 544 544 544 563 563 563 349

Neutral Ground 168 362 240 264 268 271 276 279 283 286 288 290 260 264 268 271 276 279 283 288 290 Neutral Ground 180 * ** *** ****

Ur - Rated Voltage Uc - Cont. Operating voltage "TOV" curves are given in Technical data for selected Surge Arrester (on request) Accessories selection see on the pages 14 - 19

Surge Arrester with other characteristics are available on request

10

Temporary Creepage Overvoltage length capability for 1 sec***

Overall height

Rec. Min. distance between phase centers

Rec. Min. Max. Cantilever Weight load distance between phase to earth mm 977 993 1009 1042 1053 1075 1091 1113 1161 977 993 1009 1042 1075 1091 1107 1161 912 1303 1422 1454 1471 1498 1514 1536 1552 1563 1574 1411 1433 1454 1471 1498 1514 1536 1563 1574 977 N 1750 1750 1750 1750 1750 1750 1750 1750 1750 2625 2625 2625 2625 2625 2625 2625 2625 500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2250 2250 2250 2250 2250 2250 2250 2250 2250 1750 kg 103 103 103 103 103 103 103 103 103 108 108 108 108 108 108 108 108 46 141 141 141 141 141 141 141 141 141 141 170 170 170 170 170 170 170 170 170 103

Product code****

kV 210 216 219 225 229 232 237 242 250 198 201 204 211 218 221 224 235 193 283 312 316 320 326 329 334 337 339 342 286 290 295 298 303 307 311 317 319 210

mm 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 6625 5300 9275 9275 9275 9275 9275 9275 9275 9275 9275 9275 10600 10600 10600 10600 10600 10600 10600 10600 10600 6625

mm 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 2500 1936 3500 3500 3500 3500 3500 3500 3500 3500 3500 3500 4000 4000 4000 4000 4000 4000 4000 4000 4000 3500

mm 2402 2430 2458 2515 2534 2571 2599 2637 2722 2402 2430 2458 2515 2571 2599 2628 2722 2023 2966 3192 3229 3257 3304 3333 3370 3398 3417 3436 3154 3192 3229 3257 3304 3333 3370 3417 3436 2402

3P5SR180L2E2M7-4 3P5SR183L2E2M7-4 3P5SR186L2E2M7-4 3P5SR192L2E2M7-4 3P5SR194L2E2M7-4 3P5SR198L2E2M7-4 3P5SR201L2E2M7-4 3P5SR205L2E2M7-4 3P5SR214L2E2M7-4 4P5SR180L2E2M4-5 4P5SR183L2E2M4-5 4P5SR186L2E2M4-5 4P5SR192L2E2M4-5 4P5SR198L2E2M4-5 4P5SR201L2E2M4-5 4P5SR204L2E2M4-5 4P5SR214L2E2M4-5 2P4HSRC168L2E2M4 3P7SR240L2E2M7-4 3P7SR264L2E2M7-4 3P7SR268L2E2M7-4 3P7SR271L2E2M7-4 3P7SR276L2E2M7-4 3P7SR279L2E2M7-4 3P7SR283L2E2M7-4 3P7SR286L2E2M7-4 3P7SR288L2E2M7-4 3P7SR290L2E2M7-4 4P8SR260L2E2M7-5 4P8SR264L2E2M7-5 4P8SR268L2E2M7-5 4P8SR271L2E2M7-5 4P8SR276L2E2M7-5 4P8SR279L2E2M7-5 4P8SR283L2E2M7-5 4P8SR288L2E2M7-5 4P8SR290L2E2M7-5 3P5SR180L2E2M7

11

IV. Surge Arrester for System Voltages 420 kV and 550 kV Protective Characteristics

System Voltage

Ur*

Uc**

Line Discharge Class

Max. U res tested with current wave Switching surge Lightning Current (30/60 s) (8/20 s) 250 A kV 500 A kV 691 686 732 737 674 735 689 740 868 868 868 919 689 735 919 919 919 919 919 927 927 927 927 927 927 955 955 955 1011 950 950 950 950 950 950 1011 1011 1011 1011 955 1011 950 1011 1041 5 kA kV 765 760 810 816 729 796 746 801 939 939 939 994 746 796 994 994 994 994 994 1003 1003 1003 1003 1003 1003 1033 1033 1033 1094 1028 1028 1028 1028 1028 1028 1094 1094 1094 1094 1033 1094 1028 1094 1127 10 kA kV 808 802 856 865 769 839 786 844 990 990 990 1048 786 839 1048 1048 1048 1048 1048 1057 1057 1057 1057 1057 1057 1089 1089 1089 1153 1083 1083 1083 1083 1083 1083 1153 1153 1153 1153 1089 1153 1083 1153 1188 20 kA kV 868 862 919 925 823 898 842 904 1060 1060 1060 1122 842 898 1122 1122 1122 1122 1122 1132 1132 1132 1132 1132 1132 1166 1166 1166 1235 1160 1160 1160 1160 1160 1160 1235 1235 1235 1235 1166 1235 1160 1235 1272

Steep Current (1/20 s)

kV 420

kV 336 336 360 360 330 360 336 360 381 385 389 393 336 360

kV 269 269 288 288 264 288 269 288 305 308 311 314 269 288 317 320 323 326 329 317 320 323 326 329 332 335 336 338 355 324 327 330 333 336 336 342 345 348 355 336 355 336 355 374 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5

10 kA kV 862 856 913 919 815 889 833 895 1049 1049 1049 1111 833 889 1111 1111 1111 1111 1111 1120 1120 1120 1120 1120 1120 1154 1154 1154 1222 1148 1148 1148 1148 1148 1148 1222 1222 1222 1222 1154 1222 1148 1222 1259

655 650 693 698 641 699 656 704 826 826 826 874 656 699 874 874 874 874 874 882 882 882 882 882 882 908 908 908 962 903 903 903 903 903 903 962 962 962 962 908 962 903 962 991

550

396 400 404 408 411 396 400 404 408 411 415 419 420 423 444 405 409 413 416 420 424 428 431 435 444 420 444 420 444 468 * ** *** ****

Ur - Rated Voltage Uc - Cont. Operating voltage "TOV" curves are given in Technical data for selected Surge Arrester (on request) Accessories selection see on the pages 14 - 19

Surge Arrester with other characteristics are available on request

12

Temporary Creepage Overvoltage length capability for 1 sec***

Overall height

Rec. Min. distance between phase centers

Rec. Min. Max. Cantilever Weight load distance between phase to earth mm 1824 2824 1954 1954 1791 1954 1824 1954 2068 2089 2111 2133 1824 1954 2149 2171 2193 2214 2231 2149 2171 2193 2214 2231 2252 2274 2279 2296 2410 2198 2220 2241 2258 2279 2301 2323 2339 2361 2410 2279 2410 2279 2410 2540 N 1375 1250 1250 1125 2250 2125 2000 2000 2000 2000 2000 2000 2400 2400 2000 2000 2000 2000 2000 1875 1875 1875 1875 1875 1875 1875 1875 1875 1875 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 2200 2200 2000 2000 2000 kg 159 178 178 197 170 190 210 210 210 210 210 210 236 236 210 210 210 210 210 230 230 230 230 230 230 230 230 230 230 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250

Product code****

kV 388 397 423 426 364 397 370 397 370 397 419 424 428 432 436 440 444 449 452 436 440 444 449 452 457 461 463 465 488 446 450 454 458 463 466 471 474 479 486 462 488 462 488 512

mm 10600 11925 11925 13250 10600 11925 13250 13250 13250 13250 13250 13250 11925 11925 13250 13250 13250 13250 13250 14575 14575 14575 14575 14575 14575 14575 14575 14575 14575 14575 15900 15900 15900 15900 15900 15900 15900 15900 15900 14575 14575 15900 15900 15900

mm 4000 4500 4500 5000 3812 4575 5075 5075 5075 5075 5075 5075 4575 4575 5075 5075 5075 5075 5075 5575 5575 5575 5575 5575 5575 5575 5575 5575 5575 5575 6075 6075 6075 6075 6075 6075 6075 6075 6075 6075 6075 6075 6075 6075

mm 3868 3868 4094 4094 3812 4094 3868 4094 4291 4329 4367 4404 3868 4094 4432 4470 4508 4545 4573 4432 4470 4508 4545 4573 4611 4649 4658 4686 4884 4517 4555 4592 4620 4658 4696 4733 4761 4799 4884 4658 4884 4658 4884 5109

3P8SR336L2E2M7-4 3P9SR336L2E2M7-4 3P9SR360L2E2M7-4 3P10SR360L2E2M7-4 4P8SR330L2E2M7 4P9SR360L2E2M7 4P10SR336L2E2M7 4P10SR360L2E2M7 4P10SR381L2E2M7 4P10SR385L2E2M7 4P10SR389L2E2M7 4P10SR393L2E2M7 5P9SR336L2E2M7 5P9SR360L2E2M7 4P10SR396L2E2M7 4P10SR400L2E2M7 4P10SR404L2E2M7 4P10SR408L2E2M7 4P10SR411L2E2M7 4P11SR396L2E2M7 4P11SR400L2E2M7 4P11SR404L2E2M7 4P11SR408L2E2M7 4P11SR411L2E2M7 4P11SR415L2E2M7 4P11SR419L2E2M7 4P11SR420L2E2M7 4P11SR423L2E2M7 4P11SR444L2E2M7 4P12SR405L2E2M7 4P12SR409L2E2M7 4P12SR413L2E2M7 4P12SR416L2E2M7 4P12SR420L2E2M7 4P12SR424L2E2M7 4P12SR428L2E2M7 4P12SR431L2E2M7 4P12SR435L2E2M7 4P12SR444L2E2M7 5P11SR420L2E2M7 5P11SR444L2E2M7 5P12SR420L2E2M7 5P12SR444L2E2M7 5P12SR468L2E2M7

13

Modular Single Column Polymeric Surge Arrester Type HSR

Line lead accessories

L1 50 mm stud with washers and nut M16

L2 Line clamp to suit conductors up to 16 mm

L5 Line clamp to suit conductors up to 35 mm

L6 Aluminium stem 30 mm x 80 mm

Arrester Type = Rated Voltage Ur in kV


2HSRC 48.00 72.00 83.75 91.25 2HSRCP 98.75 106.25 110.00 60.00 96.00 75.00 102.50 87.50 108.00 95.00

HSRC HSRCP

Earthing accessories

E1 2 x M10 x 20 Hexagonal headed set screws and spring washers

E2 Earth clamp to conductors up to 16 mm

E5 Earth clamp to conductors up to 35 mm

Mounting accessories

M5 4 Hole Pedestal Base 127-140 PCD (Pitch Circle Dia.)

M3 Set of 4 Polyfibre Insulators supplied with M5

M0 Without fixing accessories

M10 Single polyfibre Insulator

Sample: 3 HSRC 110 L2 E2 M4 Parallel Pathe Arrester Housing Voltage Mounting Earth Terminal Line Terminal

14

Modular Polymeric Surge Arresters Type 2PH

L5 Line clamp to suit conductors up to 35 mm

L3 Line clamp to suit conductors up to 16 mm

Silicone Rubber Housed Arrester Module L6 Aluminium stem 30 mm x 80 mm

Aluminium Conection Strap

E5 Earth clamp to conductors up to 35 mm

E2 Earth clamp to conductors up to 16 mm

M4 Set of 2 Polyfibre Base Insulators

E1 2 x M10 x 20 Hexagonal headed set screws and spring washers

Sample: 2P 3HSRC 110 L2 E2 M4 Parallel Pathe Arrester Housing Voltage Mounting Earth Terminal Line Terminal

15

Modular Polymeric Surge Arresters Type 3P

Corona Ring L5 Line clamp to suit conductors up to 35 mm

Silicone Rubber Housed Arrester Module

L3 Line clamp to suit conductors up to 16 mm

L2 Aluminium stem 30 mm x 80 mm Silicone Aluminium Intersection crossarm

Corona Shield

E5 D < 35

E2 D < 16 1 2 10 H = 20 M7 Set of 3 Polyfibre Base Insulators connected to galvanised steel plate

Sample: 3P 8SR 336 L2 E2 M7 Parallel Pathe Arrester Housing Voltage Mounting Earth Terminal Line Terminal

16

Modular Polymeric Surge Arresters Type 4P

Corona Ring

L5 Line clamp to suit conductors up to 35 mm

Silicone Rubber Housed Arrester Module

L3 Line clamp to suit conductors up to 16 mm

Silicone Aluminium Intersection cross-arm

L2 Aluminium stem 30 mm x 80 mm

Corona Shield

E5 D < 35

E2 D < 16 M7 Set of 4 Polyfibre Base Insulators connected to galvanised steel plate

1 2 10 H = 20

Sample: 4P 8SR 336 L2 E2 M7 Parallel Pathe Arrester Housing Voltage Mounting Earth Terminal Line Terminal

17

Line Accessories L5 2P L2

ALUMINIUM LINE STEM

17 Mounting Hole

Material: Galvanised Steel All fixings M10

L3

HSR L6

ALUMINIUM LINE STEM

Material: back plate galvanised steel Fixing galvanized steel 17 Mounting Hole Clamp plate nickel plated brass

Earthing Accessories E5 3P E5 2P E5

17 Mounting Hole

Material: galvanized steel All fixing M10

2 hols 11

Material: galvanized steel All fixing M10

2 hols 11

Material: galvanized steel All fixing M10

2P E2

3P E2 / HSRP E2

Material: M2 base plate Aluminum Fixing galvanized steel Clamp plate nickel plated brass All fixing M10

2 hols 11

Material: back plate galvanised steel Fixing galvanized steel Clamp plate nickel plated brass All fixing M10

18

Mounting Accessories M0 No mounting

HSR M10

HSR M3

Total creepage 105 mm Polyfibre moulded insulator Insert with M16 hole tapped 20 mm minimum full thread M16 x 40 hex head set screw and spring washer

HSR M5
4 Slots to suit M12 screws equally spaced on 127-140 P.C.D

Total creepage 105 mm Polyfibre moulded insulator Insert with M16 hole tapped 20 mm minimum full thread M16 x 40 hex head set screw and spring washer Net weight: 0.75 kg approx, including screws

17 Mounting Hole

2 Holes Tapped M10

Material:- Silicon Aluminium

4P M7

3P M7
2-OFF 11 HOLES FOR EARTH CONNECTION

24

3 HOLES FOR M16 BOLTS EQUI-SPACED 0N 332 P.C.D.

NAMEPLATE DETAILS

Upper base plate (galvanized steel) Polyfibre moulded insulator (creepage 105 mm) Insert with M16 hole tapped 20 mm minimum full thread M16 x 40 hex head set screw and spring washer

Upper base plate (galvanized steel)


6

Total Creepage 105mm. Polfibre Moulded Insulator Insert with M16 hole tapped 20 mm minimum full thread M16 x 40 hex head set screw and spring washer

19

Transmission Line Surge Arresters - TLA

Lightning is responsible for approximately 65% of all of the non-scheduled outages occurring on transmission lines. Power supply utilities have verified the load losses due to voltage sags in their systems from transitory outages caused by lightning activity and in some regions they have found serious permanent damages on important lines. The effect of transitory disturbances on transmission lines can also be more critical in areas with high ground resistivity when associated with high lightning activity. Although a fault time is shorter than 1 minute, in many cases this is still unacceptable. This loss of supply is critical for all modern industries, electronical equipment and especially production processes. In most cases line arresters (TLA), electrically connected in parallel with the insulating string, have been considered as the most effective method currently applied to improve transmission line performance, especially when associated with improvements of the grounding system and usually presents the best benefit versus cost relationship in reducing flashovers of the insulator string due to excessive voltages. Generic Technical data Earthing Configuration - E2 Specification Classification Voltage Rating High Current Performance Line Discharge Minimum Energy Capability acc. to IEC 60099-4 at Ur Disconnect Device tested in accordance with Insulation Material Silicone Vibration Tested Report No. IEC600099-4 10 kA 10 to 192 kV 100 kA Class 2
TLA Surge Arrester Supension Clamp Disconnect Device Earth Connection Strain Relief Shackel and Swivel Joint Grading Ring for voltages above 150 kV

4,5 kJ/kV IEC 60099-4 Rubber BOE002000

Strain Relief Wire Connection

Earthing Configuration - E1
Silicone Rubber Insulation TLA Surge Arrester

Features & Benefits HV arrester suspended from a transmission line giving enhanced transmission line performance Increasing system line voltage on standard insulated transmission lines Minimising circuit beaker operation with possible system outage resulting from back flashover on the transmission line Switching overvoltages are absorbed over the length of the line reducing the severity of surge at the substation Transmission systems can be operated even where sub-soil gives poor tower footing resistance Eliminating interrupted power supply for sensitive industrial processes Installing TLA on a standard 3 phase voltage system along the line, at calculated intervals, allows for optimum performance of the TLA, to give an increased system line voltage. Therefore eliminating the need to increase the standard insulation level required on conventional system upgrade.

Disconnect Device

Disconnect Device Earth Cable with Strain Relief

Earth Connection

Supension Clamp Assembly


Galvanic Steel Clamp Straps & Podings Aluminium Line Clamp

Copper Shoring Braid/Cable

Galvanised Steel Line Palm

M12 Connection For Shoring Braid.Cable

M16 x 35 Min. Full Thread

TLA Surge Arrester

Clamp Conductor Range Diameter

Dimensions in mm A B C D

U Bolt

Weight kg

L2 L3 L4 L5

9.5 - 19 18 - 30 30 - 45 45 - 65

180 217 267 320

80 90 100 120

90 110 120 140

40 50 64 86

45 45 75 75

1.8 3.0 4.3 6.0

20

Transmission Line Surge Arresters - TLA Dimensions

TLA 4: 150-192 kV

TLA 3: 108-144 kV

TLA 2: 40-96 kV
A

TLA 1: 15-45 kV
A

Protective Charateristics
Ur* Uc** Line Discharge Class Max. U res tested with current wave Swithcing Surge (30/60 s) 250 A KV KV KV 1000 A KV Lightning Current (8/20 s) 5 kA KV 10 kA KV 20 kA KV Steep Temporary Creepage Current Over-voltage length capability for (1/20s) 1s *** 10 A KV KV MM MM Overall height Product code ***

15 18 21 24 27 30 36 39 42 45 48 60 72 75 84 96 108 120 138 144 150 168 180 192 * ** *** ****

12,0 14,0 17,0 19,0 22,0 24,0 29,0 31,0 34,0 36,0 38,4 48,0 57,6 60,0 67,2 76,8 86,4 96,0 110,0 115,0 120,0 134,0 144,0 154,0

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

29,3 36,6 41,5 48,8 53,7 58,6 70,8 78,2 83,0 87,9 95,2 117,0 142,0 147,0 166,0 188,0 212,0 234,0 274,0 283,0 293,0 330,0 354,0 376,0

30,1 37,6 42,7 50,2 55,2 60,2 72,8 80,3 85,3 90,3 97,8 120,0 146,0 151,0 171,0 193,0 218,0 241,0 281,0 291,0 301,0 339,0 364,0 386,0

37,0 46,2 52,4 61,6 67,8 73,9 89,3 98,6 105,0 111,0 120,0 148,0 179,0 185,0 209,0 237,0 268,0 296,0 345,0 357,0 370,0 416,0 447,0 474,0

39,7 49,7 56,3 66,2 72,8 79,4 96,0 106,0 113,0 119,0 129,0 159,0 192,0 199,0 225,0 255,0 288,0 318,0 371,0 384,0 397,0 447,0 480,0 510,0

43,8 54,7 62,0 73,0 80,3 87,6 106,0 117,0 124,0 131,0 142,0 175,0 241,0 219,0 248,0 281,0 317,0 350,0 409,0 423,0 438,0 493,0 529,0 562,0

42,6 53,3 60,4 71,1 78,2 85,3 103,0 114,0 121,0 128,0 139,0 171,0 206,0 213,0 242,0 274,0 309,0 341,0 398,0 412,0 426,0 480,0 515,0 547,0

17,7 21,2 24,8 28,3 31,9 35,4 42,5 46,0 49,6 53,1 56,6 70,8 85,0 88,5 99,1 113,0 127,0 142,0 163,0 170,0 177,0 198,0 212,0 227,0

930 930 930 930 930 1325 1325 1325 2000 2000 2650 2650 2650 2650 4000 4000 3975 3975 6000 6000 5300 8000 8000 8000

321 321 321 321 321 476 476 476 476 476 952 952 952 952 952 952 1428 1428 1428 1428 1906 1906 1906 1906

TLA1B15L1E1M2 TLA1B18L1E1M0 TLA1B21L1E1M0 TLA1B24L1E1M0 TLA1B27L1E1M0 TLA1C30L1E1M0 TLA1C36L1E1M0 TLA1C39L1E1M0 TLA1E42L1E1M0 TLA1E45L1E1M0 TLA2C48L1E1M0 TLA2C60L1E1M0 TLA2C72L1E1M0 TLA2C75L1E1M0 TLA2E84L1E1M0 TLA2E96L1E1M0 TLA3C108L1E1M0 TLA3C120L1E1M0 TLA3E138L1E1M0 TLA3E144L1E1M0 TLA4C150L1E1M0 TLA4E168L1E1M0 TLA4E180L1E1M0 TLA4E192L1E1M0

Ur - Rated Voltage Uc - Cont. Operating voltage "TOV" curves are given in Technical data for selected Surge Arrester (on request) Accessories selection see on the pages 14 - 19

Surge Arrester with other characteristics are available on request

21

Surge Counters Type SC 12 & SC 13


The Tyco Electronics Bowthorpe EMP range of Surge Arrester monitoring instruments are fully tested for use with any manufacturers surge arrester. The SC 12 is a Surge Counter only, whilst the SC 13 provides the additional measurement of total leakage current. The analogue instrument provides a means of monitoring the current through the arrester and the leakage current over the surface of the arrester housing. Significant changes after installation may indicate a deterioration in the arrester or a build up of surface contamination. These instruments, which require no auxiliary supply, are designed for installation in the earth connections of a single surge arrester or alternatively the SC 12 may be used with the common earth of a three phase set. Fully weatherproofed and sealed for life they are housed in a one piece gravity die cast aluminium case coated to enhance its already high degree of resistance to surface corrosion. The glass viewing window is sealed in place, using a silicon rubber adhesive, and a desiccator is enclosed to ensure any residual moisture trapped during sealing is absorbed for the service life of the counter. Mounting is effected by means of an integrally cast lug at the rear of the case providing a single clearance hole for the galvanized steel M 12 bolt supplied. The SC 12 and SC 13 are service proven and require no special maintenance or servicing apart from general cleaning of the glass viewing window and the moulded epoxy resin line bushing.
Line termination M12 nickel plated brass fitted with 2 nickel plated brass locknuts Moulded resin insulator Hermetically sealed glass display panel

M12 x 35 galvanized steel with full nut and springwasher

Ground terminal M12 nickel plated brass fitted with 2 nickel plated brass locknuts

Meter: 6 digit cyclometer at least 5 counts/ second Minimum count current: 200 A 8/20 microsecond wave Maximum High Current Withstand 100 kA 4/10 microsecond wave Nominal Residual Voltage withstand at 100 kA with 4/10 s Wave 5 kV peak Meter scale (bilinear scale) Ref SC 13: SC 13 leakage (bilinear scale) Ref SC 13L

0-30 A

0-50 A

Both counters can be supplied with an auxiliary contact rated 1,0 A 250V for connection to remote signaling equipment. If required put suffix e.g. SC 12/AC

22

Tyco Electronics total commitment to quality

Even the best technology must be backed up by a thorough and consistentquality assurance program. At Tyco Electronics, we subject every product to an extensive quality control regimen which includes the following procedures: At every production stage, beginning with the raw materials and continuingthrough to the packaged product, the QC lab tests all physical and electricalcharacteristics which can influence quality. By means of lot numbers the Quality Assurance Program ensures traceabilitybackwards all the way to the details of the compound batch test reports. We carry out requalification testing on a regular basis. Quality assurance at Tyco Electronics is not a static, but rather a constantly improving process directed towards our goals: complete customer satisfaction. The Tyco Electronics Energy Division arrester manufacturing sites are accreditedto ISO 9001. Our vendor routine tests and internal incoming inspection confirm performance of all critical components used in the assembly of our arresters.

Automated routine test facility forMetal-Oxide Surge Arresters in themanufacturing area

23

The complete solution...

Polymer Composition

More than 40 years of systematic research into new materials for the needs of the electrical power industry resulted in a wide range of products with a unique combination of properties.

Materials Testing

Non-tracking and low erosion rates in polluted & non-polluted environments Long term weatherability, resistance to thermal ageing UV resistant and chemical resistant Tough, tear & impact resistant Compliant to International specifications, such as ANSI, AS, CEA and IEC

Product Design and Testing

TYCO controls its own materials development, some compounding, product design, testing & qualification, moulding, extrusion and applications through sales. TYCO has its own HV testing facilities in Brighton and Munich.

Manufacturing

TYCO arrester manufacturing sites are accredited to ISO 9001 and 14001. Our vendor routine tests and internal incoming inspection confirm performance of all critical components used in the assembly of our arresters. We offer competitive lead times on all standard products.

Quality Control

Our high quality molding and six sigma approach to process control ensuresthat product housings are shipped defect free to our customers.

Field Experiance

TYCO have over 40 years experience in materials, products and solving customer problems in the electrical utility world. TYCO is the original inventor of the HV polymeric arrester. TYCOs strong brands teams, Raychem, Axicom and Bowthorpe all contribute expertise to the continued development and launching of new and improved products.

Consideration of Environment

TYCO HV surge arrester team supply technical support and training for customers to aid arrester selection to meet the electrical, mechanical and pollution performance requirements.

SUCCESS

TRUST Bowthorpe Surge Arresters.

24

Tyco Electronics Raychem GmbH Offices in CIS Countries RUSSIA


Tyco Electronics Raychem GmbH, Energy Division
127083 Moscow Mishina str. 56 bld.2 Tel.: +7 495-790 790 2-200 Fax: +7 495-721 1892 EN-RU@tycoelectronics.com 192007 St.-Petersburg Tambovskaya str. 12 Office 52-53 Tel.: +7 812-718 8167 Fax: +7 812-718 8176 EN-RU@tycoelectronics.com 630054 Novosibirsk 3 per. Krasheninnikova, 3 Office 104 Tel.: +7 383-355 9992 Fax: +7 383-355 9991 EN-RU@tycoelectronics.com 443096 Samara Michurina str. 52 Office 315 Tel./Fax: +7 846-266 9514 EN-RU@tycoelectronics.com

620085 Ekaterinburg Ferganskaya ul. 16 Office 209 Tel./Fax: +7 343-297 1829 EN-RU@tycoelectronics.com

680000 Khabarovsk Murieva-Amurskogo str. 44 Office 313 Tel./Fax: +7 421-245 1154 EN-RU@tycoelectronics.com

344023 Rostov-na-Donu Lenina str. 118a Tel. /Fax: +7 863-293 0739 EN-RU@tycoelectronics.com

394016 Voronezh Moskovsky Prospect 53 Office 202 Tel./Fax: +7 473-239 2277 EN-RU@tycoelectronics.com

UKRAINE Tyco Electronics Raychem GmbH, Energy Division


04050 Kiev 13, Pimonenko Str., 7A section / 11 Tel.: +380 44-206 2266 Fax: +380 44-206 2268 EN-UA@tycoelectronics.com 883023 Donetsk 16 A Labutenko Str., office 123 Tel./Fax: +380 62-332 3644 EN-UA@tycoelectronics.com

KAZAKHSTAN Tyco Electronics Raychem GmbH, Energy Division


050004 Almaty Naurizbay batyr street 17 Office 215 Tel.: +7 727-244 5875 Fax: +7 727-244 5877 EN-KZ@tycoelectronics.com

Tyco Electronics Raychem GmbH Representative Offices in CIS Countries


ARMENIA
YERENERGO CJSC 375001 Yerevan 11 Toumanyan str., office 7 Tel.: +374 10-542 122 Fax: +374 10-582 060 info@yerenergo.am

AZERBAIJAN
Alifagha ALKHANOV 370010 Baku Rafili str. 11-18 Tel./Fax: +994 12-493 4226 office@pec.baku.az

BELARUS
Vyacheslav DEMICHEV 220050 Minsk K. Marksa 21-39 Tel./Fax: +375 17-226 0333 cerber@parom.com

GEORGIA
Nodar MGEBRISHVILI Tbilisi 0179 Radiani st. 19 .: +995 99-562 791 : +995 32-230 392 nomgeb@wanex.net

MOLDOVA
Igor BEIU 2068 Chiinu Str. Miron Costin, nr.19, bl.5, apt.63 Tel./Fax.: +373 22-322 155 linte@mcc.md

MONGOLIA
Ulziikhishig BAYASGALAN Ulaanbaatar Baga-toiruu-35, Sukhe-baatar District Bld. Hatansuih LLC, Room 101 Tel./Fax.: + 976 11-320 653 bayasgalan_tyco@yahoo.com

TAJIKISTAN
Akmal KAMIROV 734024 Dushanbe Nazarshoev street 143 Tel: +992 37-881 3106 Fax: + 992 37-227 1659 akmal80@bk.ru

TURKMENISTAN
Timur SULTANMURADOV 744007 Ashgabat A. Berdieva 25-307 Tel./Fax: +99 312-326 826 zazel@online.tm

UZBEKISTAN
Iskander KAMILOV 100000 Tashkent Merzo-Ulugbeksky D-t 24 Akmal Ikramov st. Tel: +998 71-152 6256 Tel. +998 71-137 5250 Fax: +998 71-137 5251 iskom@gs.uz

KYRGYZSTAN
is served by Tyco Electronics Raychem GmbH representative in Uzbekistan

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. Raychem, SIMEL TE logo and Tyco Electronics are trademarks.

Tyco Electronics Raychem GmbH Energy Division Finsinger Feld 1, 85521 Ottobrunn/Munich, Germany Phone: + 49 89 6089-521 Fax: + 49 89 6089-741 http://energy.tycoelectronics.com

Tyco Electronics EPP 1386 4/08