Sei sulla pagina 1di 3

Project

Job ref.

Part of structure
Date of Issue
Rev. No.

Sheet no.
0
Type (XLPE for Cable & CU /
AL for Busduct)

Operating Voltage (V)

Length ( Mt)

TotalConected Load in KW

Maximum Demand in KW

Maximum Demand in KVA

Power Factor

ACB/ MCCB Rating

Voltage Drop/A/M (mV)

% Voltage Drop Allowed (%)

Max. Voltage Drop allowed


(V)

Load Current A

Act. Voltage Drop (v)

Act. % Voltage Drop (%)

Installation Type. G/A/D

Cable/ Busduct
Derating Factor

Voltage drop within limit?

Cable or Busduct
Current Rating (A)

Load Current (A)

MCCB Rating (A)

Cable Derated Current (A)

MCCB rating within load


current?

TRANSFORMER 01

1000

XLPE

400

30

1808

1158

1447

0.8

2500

0.160

0.3

1.2

2089

1.43

0.36

0.8

CHECK

8498

2089

2500

6798

OK

CHECK###

Connected To

Cable size can be reduced?

Write "C" for Cable or "B"


for Busduct

MP-AS1-001

Cable Size mm2 or Busduct


Rating

Cable From

Number of Cores

Ref.

Number of Runs

Cable

Single/ Three Phase

VOLTAGE DROP CALCULATIONS

B
1

SMP-AS1-301

MP-AS1-001

120

XLPE

400

25

138

77

97

0.8

250

0.37

2.0

8.0

140

1.29

0.32

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-401

MP-AS1-001

120

XLPE

400

30

138

77

97

0.8

250

0.37

2.0

8.0

140

1.55

0.39

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-501

MP-AS1-001

120

XLPE

400

35

138

77

97

0.8

250

0.37

2.0

8.0

140

1.81

0.5

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-601

MP-AS1-001

120

XLPE

400

40

138

77

97

0.8

250

0.37

2.0

8.0

140

2.06

0.5

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-701

MP-AS1-001

120

XLPE

400

45

138

77

97

0.8

250

0.37

2.0

8.0

140

2.32

0.6

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS2-801

MP-AS1-001

120

XLPE

400

50

138

77

97

0.8

250

0.37

2.0

8.0

140

2.58

0.6

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-901

MP-AS1-001

120

XLPE

400

55

138

77

97

0.8

250

0.37

2.0

8.0

140

2.84

0.7

0.8

OK

353

140

250

282

OK

NO ###

SMP-AS1-1001

MP-AS1-001

120

XLPE

400

60

152

84

106

0.8

250

0.37

2.0

8.0

152

3.38

0.8

0.8

OK

353

152

250

282

OK

NO ###

SMP-AS1-1101

MP-AS1-001

120

XLPE

400

65

152

84

106

0.8

250

0.37

2.0

8.0

152

3.66

0.9

0.8

OK

353

152

250

282

OK

NO ###

10

SMP-AS1-1201

MP-AS1-001

70

XLPE

400

70

72

42

52

0.8

160

0.60

2.0

8.0

75

3.16

0.8

0.8

OK

251

75

160

201

OK

CHECK###

11

SMP-AS1-1301

MP-AS1-001

185

XLPE

400

75

78

78

98

0.8

300

0.26

2.0

8.0

141

2.74

0.7

0.8

OK

463

141

300

370

OK

CHECK###

12

SMP-AS1-001

MP-AS1-001

185

XLPE

400

25

187

150

188

0.8

300

0.26

2.0

8.0

271

1.76

0.4

0.8

OK

463

271

300

370

OK

CHECK###

13

SMP-AS1-002

MP-AS1-001

95

XLPE

400

25

104

83

104

0.8

200

0.45

2.0

8.0

150

1.68

0.4

0.8

OK

304

150

200

243

OK

CHECK###

12

SMP-AS1-B01-CHWP

MP-AS1-001

95

XLPE

400

40

95

95

119

0.8

200

0.45

2.0

8.0

171

3.09

0.8

0.8

OK

304

171

200

243

OK

CHECK###

15

SPARE

16

SPARE

Max. Voltage Drop Allowed (V)


V = Operating Voltage * % of Voltage Drop Allowed

Load Current (A)


A = Total Watts / 1.732 * Operating Voltage * Power Factor

Actual Voltage Drop (V)


1 Run Cable (V) = Voltage Drop/A/M * Load Current * Cable Length / 1000
2 Run Cable (V) = (Voltage Drop/A/M (Load Current / 2) Cable Length / 1000)

Max. Voltage Drop Allowed at Starting (V)


V = Operating Voltage * & of Voltage Drop Allowed at Starting

Actual Voltage Drop at Starting (V)


1 Run Cable (V) = Max. Voltage Drop Allowed * Motor Starting Current * Cable Length / 1000
2 Run Cable (V) = (Max. Voltage Drop Allowed (Motor Starting Current / 2) Cable Length / 1000)

Dearated Current (A)


A = load Current / 0.92 * 0.95 * 0.985 *0.84 * 0.8
IF(ISERROR(AVERAGE(A1:A4)),"No Numbers",AVERAGE(A1:A4))
Derating Factor Calculation for Cables

a) Cables directly buried in ground


Soil resitivity facor = 1.14
Ground temparature factor = 0.86
Depth of laying factor( for 0.6 mtr ) = 0.98
Group factor for Multicore cables = 0.84( 3 ckts)/ 0.77(6 ckts)
Overall Derating factor =1.14* 0.86 * 0.98 * 0.84 = 0.81( 3 ckts)
Overall Derating factor =1.14* 0.86 * 0.98 * 0.77= 0.74( 3 ckts)
b) Cables in ducts
Soil resitivity facor = 1.06
Ground temparature factor = 0.86
Depth of laying factor( for 0.6 mtr ) = 0.99
Group factor for Multicore cables = 0.93( 3 ckts)/ 0.9 (6 ckts)
Overall Derating factor =1.06 * 0.86 * 0.99 * 0.93 = 0.84 (3 ckts)
Overall Derating factor =1.06 * 0.86 * 0.99 * 0.9 = 0.81 (6 ckts)
c)

For Cables in Air


Ambient temparature factor @40oC (inside building) = 0.91
Spacing factor (BS 7671 table 4B1) (4 ckts)= 0.88
Overall Derating factor = 0.91*0.88 = 0.8

Area of
Conductor
.

VD/A/M

Ground

Air

Duct

2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000

16.400
10.200
6.800
4.000
2.500
1.650
1.150
0.870
0.600
0.450
0.370
0.300
0.260
0.210
0.185
0.165
0.180
0.170
0.170
0.160

34
47
57
82
115
150
180
215
265
315
360
405
460
530
590
667
770
840
888
942

25
34
43
60
99
131
162
197
251
304
353
406
463
546
628
728
918
1027
1119
1214

17.5
23
29
39
94
125
150
175
215
260
300
335
380
440
495
570
620
670
692
735

* Single Core Cables

1
2
3
4
5
6
7

Incomer Breaker Ratings


=< 7 kw
40 A
7.1 to
63 A
11kw
11. 1 to 14
80 A
kw
14.1 to
100 A
17.5 kw
17.6 to 22
125 A
kw
22.1 to 28
160 A
kw
28.1 to 35
200 A
kw

Bus bar
Ct. @
35oC
800
1000
1200
1350
1600
2000
2500
3000
3200
4000
5000

*
*
*
*

VD/M
VD/A/M (SQARE D)
(mV)
Cu @ 0.8
P.F
0.108
0.094
0.069
0.063
0.053
0.046
0.033
0.029
0.025
0.020
0.015

0.086
0.094
0.083
0.085
0.085
0.092
0.082
0.087
0.081
0.081
0.075

MCCB

Area of
Condr.

10
16
20
32
40
50
63
80
100
125
160
200
225
250
300
350
400
630
800
1000
1600
2000
3200
4000
5000

1.5
2.5
4
6
10
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
630
630
630
630
630

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

Potrebbero piacerti anche