Product Data Sheet

FOUNDATION FIELDBUS I/O June 2004Page 1

TM

FOUNDATION Fieldbus I/O


H1 cards

Use DeltaV state-of-the-art FOUNDATION fieldbus I/O for your process control system.

Increases input/output Takes advantage of all smart device capabilities Facilitates multi-drop 16 devices on one port Features secure uninterrupted control

that affect your control strategy and alerts operators to device malfunctions. FOUNDATION fieldbus I/O modular design offers flexibility during installation. Its designed to be installed in the field, close to your devices. FOUNDATION fieldbus is equipped with function and field-wiring protection keys to ensure that the correct I/O card is always plugged into the corresponding terminal block. Modularity, protection keys, and increased input/output capacity make FOUNDATION fieldbus I/O a smart choice for your process control system.

Provides third-party device support Introduction


Are you looking for an efficient, yet robust, I/O subsystem? FOUNDATION fieldbus I/O is a modular subsystem that communicates digitally with field devices, increases your input/output capacity, and gives you access to more information about your process than conventional I/O subsystems. If you want an efficient, economical, and secure process control system, use DeltaV FOUNDATION fieldbus I/O. It greatly enhances device diagnostics

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 2

TM

Benefits
Increases input/output. Use FOUNDATION fieldbus I/O instead of Classic I/O to increase information flow. Take advantage of FOUNDATION fieldbus digital communications to access additional information from your smart devices. Get more information over one wire than over multiple wires with Classic I/O. Takes advantage of all smart device capabilities. Increase your ability to communicate with your devices using DeltaV FOUNDATION fieldbus I/O. Field device status is updated continuously using FOUNDATION fieldbus I/O. For multi-variable devices, all process variables are available on the single fieldbus connection. Facilitates multi-drop 16 devices on one port. Save on wiring expenditures by installing FOUNDATION fieldbus I/O in the field, close to the actual field devices.1 Mounting the controller with the I/O further reduces your wiring costs by eliminating the need for long runs of multi-cores. Multi-dropping up to 16 devices on one port reduces your wiring expenses substantially. The integrated design of the FOUNDATION fieldbus I/O can eliminate the need for marshaling panels. This saves you even more. Features secure uninterrupted control. A DeltaV system offers back-up link active schedule (LAS) to ensure secure control when upgrading a card or in the case of card failure. LAS control is automatically transferred to the backup device when upgrading or experiencing card failure. Control is automatically transferred back to the H1 Interface Card when the system detects a new card. This process requires no user interaction. Provides third-party device support. The DeltaV system provides third-party device support for devices that have successfully passed rigorous testing by Emeson Process Management. This testing ensures reliability and safety and allows you to benefit from the open fieldbus architecture when selecting field devices. The tables listing the supported fieldbus devices follow on page 3.

Additional Benefits
Increase your process control systems level of sophistication using FOUNDATION fieldbus I/O. You are already aware of the increased input/output capabilities and improved communication with your smart devices. Now go one step further and use AMSinside with your FOUNDATION fieldbus I/Ofrom the control room. Using AMSinside, access all of your process information from the FOUNDATION fieldbus device database to configure, monitor, and troubleshoot all your smart devices. Using AMSinside you can access status and diagnostic data from smart devices and monitor their performance. Increase product quality and minimize unplanned downtime with this dynamic application. Improve the productivity and profitability of your process control system. Fieldbus devices not manufactured by Emerson Process Management divisions are categorized as third-party devices. The DeltaV system provides third-party device support for devices that have successfully passed rigorous testing by Emerson Process Management and are registered by the Fieldbus Foundation. This allows you to benefit from the open fieldbus architecture when selecting field devices.

Listed Fieldbus Devices on DeltaV


For current fieldbus device information, refer to www.EasyDeltaV.com Click on Key Technologies/Foundation Fieldbus/Device Downloads.

Listed 3rd-party Fieldbus Devices


For current 3rd-fieldbus device information, refer to www.EasyDeltaV.com Click on Key Technologies/Foundation Fieldbus/Device Downloads.

Refer to Zone 2 installation instructions (12P2046) and/or Class 1 Division 2 installation instructions (12P1293) for details.

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 3

TM

Product Description and Specification


The FOUNDATION fieldbus I/O subsystem includes:

H1 card fieldbus power supply fieldbus junction block fieldbus terminator fieldbus power conditioner.
The I/O card is enclosed in a DeltaV-designed common form factor that plugs into the I/O interface carrier. The housing is clearly labeled with the enclosed I/O card type. Clearly visible LEDs on the

top of the I/O card display the power, error, and status to the two channels included in the I/O card. The Fieldbus I/O Card meets ISA G3 corrosion specifications by using superior electronic components and conformal coating. The fieldbus junction blocks provide a convenient means of connecting the field devices to the fieldbus segment. They include provision for up to six field devices, homerun connection, and connection to either the next block or a terminator. The connections are made with plug-and-socket connectors for fast and easy field installation. Cord sets are available for hooking up your field devices to the blocks.

Fieldbus I/O card.

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 4

TM

Fieldbus technology enables multiple intrinsically safe devices to connect on one communications segment. This means that one control system can use multiple-vendor devices. This is known as interoperability. The DeltaV H1 card schedules communications between the devices to implement control strategies. The DeltaV system provides initialization, diagnostics, and run-time monitoring for each segment. Depending on the control strategy, the DeltaV system either executes the control strategy or, if control resides in the fieldbus devices, displays the ongoing parameters.

The fieldbus power supply provides a balanced power feed to the field devices. It is available in both an intrinsically safe and a standard version. The power supplies include one bus terminator that may be switched in.

Intrinsically safe fieldbus power supply.

Fieldbus components

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 5

TM

The Fieldbus Power Conditioner provides for redundant 24V power supplies to be connected to a fieldbus segment. It provides energy limiting and filtering meeting fieldbus and non-incendive field wiring requirements. The Fieldbus Power Conditioner requires +24VDC isolated input power. Circuitry on the conditioner filters the DC power as required per the FOUNDATION fieldbus 31.25kbit/s Physical Layer Profile Specification. It provides energy-limiting circuitry as required for non-incendive field wiring in a Class 1 Division 2 area. It also provides a custom-dedicated H1 fieldbus card input. The Fieldbus Power Conditioner utilizes five terminal blocks. Two 2-position terminal blocks provide primary and secondary input power connections. Two 3-position removable terminal blocks provide fieldbus power connections to the segment. A 3position terminal block provides an H1 input connection . The Fieldbus Power Conditioner can be DIN-rail mounted.

Fieldbus Power Conditioner

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 6

TM

DC Power Considerations The available current to power a field device depends on the length and resistance characteristics of the fieldbus cabling used. The table below shows the maximum distance for a given load on the fieldbus power conditioner. The following assumptions are made about the segment: 1. Each device has an average load of 20 mA. 2. The minimum device voltage = 9 VDC 3. Fieldbus Type A 18 GA cable @ 22ohms/km

4. Devices are connected on the end of the cable opposite the Fieldbus Power Conditioner. Note: To prevent interaction between segments, each segment must be powered from an independent isolated power supply. Each port on the FOUNDATION fieldbus H1 card constitutes a separate segment. If multiple power conditioners are desired on a single segment, it is acceptable to connect two power conditioners to a common 24-volt supply.

Distance per Load on Power Conditioner Maximum Distance (Meters) 1900 1900 1900 1330 830 470 220 30 If your segment layout is different, it will have different restrictions and limitations. Use the table below and the formula Vdrop = Load Current * Loop Number of Devices 1 2 3 4 5 6 7 8 Load (mA) 20 40 60 80 100 120 140 160 Resistance to design for your application. The sum of Vdrop plus the minimum device voltage must be < the Minimum Compliance Voltage for the segment.

Compliance Table Total Segment Current 10 20 30 40 50 60 70 80 Minimum Compliance Voltage 17.81 17.26 16.70 16.16 15.61 15.04 14.47 13.91 Total Segment Current 90 100 110 120 130 140 150 160 Minimum Compliance Voltage 13.35 12.82 12.25 11.62 11.04 10.43 9.83 9.23

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 7

TM

Specifications for H1 card, 2 channel, FOUNDATION Fieldbus Number of channels Number of field devices: Number of Ff function blocks Isolation Nominal signal range (span) Localbus current per card (12 VDC nominal) Field circuit power per card Standards Airborne contaminants 2 16 per port (dependent on device power consumption an IS requirement) 64 per card Each channel is isolated from the system at field to system isolation = 100 VAC (verified by 1700 VDC factory test) Fieldbus FOUNDATION IEC 61158-2 400 mA typical, 600 mA maximum Provided externally IEC 61158 data link layer

ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating

Hazardous area/location* 1) I/O interfaces

CENELEC Zone 2 IIC T4 hazardous area or Class, I Div 2, Groups A, B. C. D T4 hazardous locations.

2) Field circuits

*Refer to Zone 2 installation instructions (12P2046) and/or Class 1 Division 2 installation instructions (12P1293) for information on installing in hazardous areas.

Fieldbus Power Conditioner Specifications* Item


Input Power Rating H1 Input (non fieldbus compliant) Output Power Rating

Specification
+24VDC +/-3% @ 350mAmps Maximum 3VAC 10mAmps Maximum +9.23VDC min @160mAmps Maximum Class I Division 2 non-incendive field circuits*

Maximum Power Dissipation Dimensions Ambient Temperature

10W 8.4 cm. x 16.5 cm. x 5.1 cm. (3.3 in. x 16.5 in. 2in.) 0 to 60 C

*For Class I Division 2 installation information reference drawing 12P1293.

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 8

TM

Ordering Information
Description Simplex H1 Fieldfbus I/O Interface Card and Terminal Block Fieldbus Power Supply Fieldbus Power Supply (Intrinsically Safe) Fieldbus DIN-Rail mount terminator Fieldbus Power Conditioner Model Number VE4017PO VE6951 VE6952 VE6956 VE6965

Description (Cordsets and Connectors) 6-port Fieldbus Junction Block Fieldbus Junction Block Terminator Closure Cap (for junction block connectors) Cordset Connector male Cordset Connector female Device Cable Adapter

Eurofast Model Number VE6954 VE6953 VE6955 VE6957 VE6958 VE6959

Minifast Model Number VE6961 VE6960 VE6962 VE6963 VE6964 N/A

Product Data Sheet


FOUNDATION FIELDBUS I/O June 2004Page 9

TM

Prerequisites
A fieldbus power supply is required for each bus segment. Each fieldbus segment must be terminated at both ends. A fieldbus brick and terminator for each segment are recommended.

To locate a sales office near you, visit our website at: or call us at:

www.EasyDeltaV.com/reach 65.777.8211 41.41.768.6111 +1 800.833.8314 or +1 512.832.3774

Asia Pacific: Europe, Middle East: North America, Latin America:

For large power, water, and wastewater applications contact Power and Water Solutions at: www.emersonprocess-powerwater.com or call us at: Asia Pacific: Europe, Middle East, Africa: North America, Latin America:
Fisher-Rosemount Systems, Inc. 19962004 All rights reserved. DeltaV, the DeltaV design, SureService, the SureService design, SureNet, the SureNet design, and PlantWeb are marks of one of the Emerson Process Management group of companies. All other marks are property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time without notice.

65.777.8211 48.22.630.2443 +1 412.963.4000