TAPCON 240 TAPCON 260 MORE THAN SIMPLE VOLTAGE REGULATION.

T RA N SFO R MER C ONTROL

Tapcon 240, Tapcon 260

TAPCON 240 anD TAPCON 260 VOLTAGE REGULATORS FOR EVERY APPLICATION.

Maschinenfabrik Reinhausen (MR) has been developing and manufacturing voltage regulators for over 40 years. All this time, our goal has been to provide our customers with the best possible solutions. The voltage regulators of the TAPCON series provide the right device for all scenarios.
The modular system used in our TAPCON 240 and TAPCON 260 voltage regulators provides maximum exibility and a comprehensive scope of function. TAPCON 240 and TAPCON 260 allow you to run up to 16 transformers in parallel and support the current control system protocols for station automation ideal for exible and convenient voltage regulation. Commissioning on site is done quickly and, above all, in a user-friendly manner thanks to the TAPCON-trol conguration software.

BETTER VOLTAGE REGULATION.


Modular and flexible design
I The ideal solution for both simple regulation tasks

TAPCON 260 the all-rounder


Our all-rounder, TAPCON 260, is the right choice for challenging regulation work extending beyond the standard scope of the TAPCON 240. On request, it can be individually adapted to your requirements.

and very complex applications such as regulating three-winding transformers or banks of transformers I Parallel operation of up to 16 transformers I Optional: integrated on-load tap-changer monitoring

Maximum operational reliability through integration in redundant networks


With immediate effect, the TAPCON 260 can also support integration in redundant network systems with the RSTP and PRP protocols. Even if a connection to the control system fails, interrupt-free communication is ensured.

Graphic display
I Contrast-rich graphics display with clearly arranged

indicators and freely programmable LEDs


I Line voltage and on-load tap-changer position are

shown in the display, rendering additional displays in the switch cabinet unnecessary I Illustration of time sequences for measured values and/or analog signals

Quick and reliable


Insulation displacement connectors and diverse assembly variants enable rapid installation

Communication
I Support for all common control system protocols I TAPCON 260 can also be integrated into redundant

network systems with the RSTP and PRP protocols

TAPCON 240, TAPCON 260

FUNCTIONAL AND COMFORTABLE VOLTAGE REGULATORS.


We place great emphasis on operator comfort in devices from the TAPCON range. This includes a contrast-rich graphics display with clearly arranged indicators and freely programmable LEDs.
TAPGUARD 240 and TAPGUARD 260 can be installed quickly due to insulation displacement connectors and diverse assembly variants. The standard control system protocols for station automation are supported including IEC 61850 Edition 2 with immediate effect. TAPCON 240 and TAPCON 260 are therefore ideal for exible and convenient voltage regulation.

GRID CONTROL LEVEL

SCADA

Line control system

TAPCON-trol

STATION LEVEL
TAPCON-trol RSP20/25
TAPCON 240

2nd TAPCON 240 or TAPCON 260


TAPCON 240

TAPCON 260

PROCESS LEVEL

Overvoltage limit V > V actual Bandwidth +B

V desired B Bandwidth

Undervoltage limit V <

TAPCON 260 PROVEN TECHNOLOGY, MAXIMUM INDIVIDUALITY.


With the TAPCON 260, there are no limits to your individual voltage regulation requirements.

Extending beyond the function of the TAPCON 240, our professional TAPCON 260 device offers virtually unlimited possibilities. The rmware of the TAPCON 260 is adapted specically to your needs. This produces a voltage regulator which can handle simple regulation tasks as well as complex challenges and thereby satisfy your every requirement including the regulation of three-winding transformers, parallel transformer bank operations, or individual programming for the phase-shift oscillator regulation.

The parallel bank operation solution


Parallel bank operation is the regulation of a bank of transformers comprising three single-phase transformers with three separate motor-drive units and

on-load tap-changers. In this application, one single TAPCON 260 voltage regulator is enough to control the three motor-drive units. The load voltage of a bank of transformers is regulated as per the voltage regulation description.

TAPCON 260

TAPCON 240

V V V

Solution for phase-shifter regulation


Customized regulation functions are available to meet virtually all customer requirements. For example, a phase-shifter regulation project has already been implemented where a TAPCON 260 regulates the desired power splitting.

100 MW generator

TAPCON 260

TAPCON 240

100 MW

Tapcon 240, Tapcon 260

TAPCON 240 anD TAPCON 260 SCOPE OF FUNCTION.


Scope of function
Basic functions Optional functions Voltage regulation, including line drop compensation Parallel mode up to number of transformers Customer-specic topology Cross-monitoring Limit volt On-load tap-changer monitoring (TAPGUARD 240 function) Regulation of three-winding transformers Parallel transformer bank operation of single-phase transformers Phase-shifter application Order-specic programming Communication IEC60870-5-101/103 DNP3 MODBUS ASCII/RTU IEC 61850 Edition 2 Tap position capture BCD Current signal Voltage signal Resistor contact series Housing design

TA TAPCON 240
x 16 x x x x x x x x x x x 19" (1/2 19")

TAPCON 260
x 16 x x x x x x x x x x x x x x x x 19" (1/2 19")

TAPCON 260 APPLICATION EXAMPLE: 3 PHYSICALLY SEPARATE SINGLE-PHASE TRANSFORMERS USED AS PHASE SHIFTERS

We were contacted by an Austrian energy provider with a very challenging job: one phase shifter comprising three single-phase transformers. MR's solution: three sets, each comprising three VACUTAP VR on-load tap-changers combined with two COMTAP ARS off-circuit tap-changers. This complex regulation challenge was solved with special programming on four TAPCON 260 voltage regulators. One TAPCON 260 was tted into each of the tap-changer drives of the individual phases (3 x slave) and one master TAPCON 260 was placed in the control room.

TAPCON 240 anD TAPCON 260 TECHNICAL DATA.


Setting ranges
Desired value 1 ... 3 Sensitivity Delay time 1 Delay time 2 Switching pulse duration LDC Z compensation Undervoltage blocking Overvoltage recording with high-speed return (can be deactivated) Overcurrent blocking Voltage transformer Current transformer 60 160 V 0.5 9 % 1 600 s 1 10 s 1.5 s Ur = 0 25 V Ux = 0 25 V Voltage rise 015 % of desired value Limitation: 0 15 % of desired value 60 100 % of desired value 100 140 % of desired value Cycle 1.5 / 1.5 s 50 210 % 0.1 999 kV / 100 V 100 10,000 A / 5 / 1 / 0.2 A

Operating controls, display


Function keys Manual / automatic Raise / Lower Menu keys Display Monochromatic display with graphics capabilities, 128 x 128 dot 1 LED (green), operating indicator 1 LED (yellow), parallel operation message 1 LED (red) each, message for U<, U>, I> 1 LED (green), NORMset on message 3 LEDs (yellow) for random assignment 1 LED (yellow / green / red) for random assignment Power supply DC 36 72 V, 18 32 V AC, DC 88 265 V Power consumption approx. 25 VA Protective housing 19" housing 483 x 133 x 178 mm (W x H x D) Degree of protection IP00 in accordance with IEC 60529 Weight approx. 5kg Operating temperature Storage temperature -25 +70C -35 +80C

Maschinenfabrik Reinhausen GmbH Falkensteinstrasse 8 93059 Regensburg, Germany Phone: +49 941 4090-0 Fax: +49 941 4090-7001 Email: info@reinhausen.com www.reinhausen.com