SINGLE LINE FLOW DIAGRAM CHILLED WATER SYSTEM

PRIMARY CHILLED WATER PUMP 5 NOS. 109L/s, 17.5 m HEAD, GROUND FLOOR WATER COOLED CHILLERS 4 NOS. 1150 TONS, 109 L/s

TUBE & SHELL HEAT EXCHANGER ,BASEMENT 2 1 NOS., 1824 KW PLATE HEAT EXCHANGER, GROUND FLOOR 3 NOS., 4050 KW CHILLED WATER THERMAL STORAGE TANK 4 NOS., 109 L/s, 40m HEAD VARIABLE SPEED BASEMENT 2

CHILLED WATER HEAT EXCHANGER PUMP 4 NOS. 109 L/s, 21m HEAD

THERMAL ENERGY STORAGE TANK 2 NOS. , 1575 CUBIC METER

EVAPORATOR
PRIMARY CHILLED WATER PUMP

HEAT EXCHANGER

CHILLER

CHILLED WATER SIDE STREAM FILTRATION UNIT

SIDE STREAM FILTRATION UNIT

CHEMICAL TREATMENT UNIT


CONDENSER

TO BUILDING

CHEMICAL TREATMENT UNIT

FROM BUILDING
DRAIN
SAND FILTER

REHEAT COIL WATER PUMP 2 NOS., 72.5 L/s 45m HEAD BASEMENT 2

CHILLED WATER SECONDARY PUMP 4 NOS., 182 L/s, 50m HEAD GROUND FLOOR

COOLING TOWER

PRESSURIZATION UNIT FOR REHEAT COIL WATER BUILDING SIDE PUMP MAKE UP WATER 2 NOS. 72.5 L/s 45m HEAD EXPANSION TANK 1 NOS., 350 LITERS

CONDENSER WATER PUMP 4 NOS.,, 217 L/s, 35m HEAD BASEMENT 2


WATER NETWORK

PRESSURIZATION UNIT FOR CHILLED WATER MAKE UP WATER


EXPANSION TANK

EXPANSION TANK 3 NOS., 16000 LITERS

TO DRAINAGE SYSTEM

FROM WATER NETWORK

CONDENSER WATER CHEMICAL TREATMENT UNIT

CONDENSER WATER SIDE STREAM FILTRATION UNIT