Technical catalogue Low-voltage moulded-case circuit-breakers

604050/012 en

Contents

Presentation

Main features

Ranges

Accessories

Characteristic curves and technical information

Dimensions and circuit diagrams

Order codes

7
1/1

ABB SACE

SACE Isomax S. The greatest project for moulded-case circuit-breakers


A single series for all applications
SACE Isomax S is a project which evolves continually and is today the largest and most complete family of low voltage moulded-case circuit-breakers on the market, able to fulfil all installation requirements, from the small user up to large industrial electrical power distribution plants.

Innovation, Technology and Quality have always been the main guides for ABB SACE in developing products and are at their peak in the SACE Isomax S series the moulded-case circuit-breakers characterised by high quality, reliability, and

performance under all conditions, simplicity of installation and safety of operation. The continual and constant evolution of the series has led to further extending the range of products, thereby making the SACE Isomax S offer increasingly complete over time. The series, which is divided rationally into eight basic sizes from S1 to S8, does, in fact, consist of different ranges destined to fulfil any installation need in a specific and optimal way.

The completeness of the series can also be noted in better rationalisation of use: the overall dimensions, methods of installation and possibility of applying accessories are all the same, regardless of the type of range the circuit-breaker is placed in. Great importance is also put on the microprocessor-based electronic releases (mounted on the circuitbreakers starting from 160A): SACE PR211/P , PR212/P and SACE PR212/MP (International ABB SACE Patent), specifically designed to actuate dedicated functions for motor starting and protection. Thanks to innovative and state-of-the-art protection functions, they ensure reliability and precision and are unaffected by electromagnetic interference. A basic characteristic of these types of releases is their ability to communicate and dialogue with the SACE SD-View 810 self-configuring software, thereby allowing full integration of the circuitbreakers in the management logics relative to electric network supervision and control systems.

1/2

ABB SACE

The new series has been studied respecting the most modern ergonomic criteria. Witness to this is the prize awarded with the IF seal to the circuitbreakers at the Design Forum in Hannover.

ABB SACE

1/3

GSIS9071

A world of solutions for installation design engineering.


An answer to all requirements.
The SACE Isomax S family is divided into eight basic sizes, S1, S2, S3, S4, S5, S6, S7 and S8 with rated uninterrupted currents from 125 to 3200A. The types of devices consist of: fixed, plug-in and withdrawThanks to its special construction char-

able circuit-breakers with seven ultimate rated breaking capacity levels - from 16 to 200kA (380-415V) - identified by the letters:

acteristics, this range of circuit-breakers combines normal Isomax safety characteristics with very high performances. The breaking technique used (double interruption per pole) and the special shape of the breaking parts, allow very high value short-circuit cur-

B, N, S, H, L, V , X.

GSIS9072

rents (200kA) to be tripped

extremely

From this family, which is considered the common nu-

rapidly, making these circuit-breakers ideal wherever protection close to the power supply source is needed.

cleus, a series of dedicated ranges are configured, which keep the same installation characteristics and accessory application possibilities. Within the series there are therefore circuit-breakers
Alternating current

V V~

Direct current

V V

Circuit-breakers with thermomagnetic releases and circuit-breakers fitted with microprocessor-based SACE PR211/P , PR212/P releases are available for protection of alternating current networks. These feature an application field from 10 to 3200A and a rated voltage of 690V . Apart from the more generic applications, they are particularly suited to protection of generators, capacitors, transformers and machine tools.

Pole connection in series allows applications in the most severe operating conditions and in any type of network (insulated, with earthed polarity, and with median point of the power supply earthed). The circuit-breakers for direct current with thermomagnetic releases are available for operating currents between 10A and 800 A, with rated voltages up to 750 V , with 3 poles in series, and 250 and 500V , with two poles in series.

available for alternating and direct current distribution, current-limiting circuit-breakers, circuit-breakers for motor protection, switch-disconnectors, circuit-breakers for applications with voltages up to 1000V , and residual current circuitbreakers, as well as specific ranges (for motor protection and switch-disconnectors) complying with the North
Centralised supervision and control systems
The reliability, efficiency quality of and a LV

American UL489 and CSA C22.2 Standards. This means wider application possibilities both in industrial and civil sectors. They can therefore be mounted in primary (Power Center) and secondary (Panel Board) distribution switchboards, for motor protection and control (Motor Control Center), in generators and for end users. Their performances are, however, of particular interest where critical situations arise (very high rated and fault currents), or where complex plant engineering solutions are needed (special coordination requirements and plant automation). They also guarantee total se-

electrical power distribution service is considerably increased by constant supervision of users and all the parameters of the installation itself. The information regarding the installations is collected using microprocessor-based field components which can be mounted directly on board the apparatus, such as the SACE PR212/P release, or using the devices in the SACE SD family. Moreover, the use of the SACE SD-View 810 software allows a simple personal computer to be converted into a work station for supervising and controlling electrical power distribution plants.

The range for applications at 1000V in alternating current and direct current extends the use of the moulded-case circuit-breakers even further and is a good example of the continual evolution of the SACE Isomax S series. They are particularly suitable for installation in special ambients, such as mines,

GSIS9073

petrochemical plants and for electric traction.

ABB SACE proposes various solutions, which allow type 2 coordinations to be made for switching and protecting motors, from 0.37kW to 355kW. It is possible to select either circuitbreakers suited just to protection against short-circuit, or circuit-breakers fitted with the new SACE PR212/MP

GSIS9074

lectivity of the protections up to full breaking capacity of the circuit-breaker installed on the load side.

electronic release, which is technologically advanced and has been specifically studied for motor protection. The latter integrates protection functions on

1/4

ABB SACE

The switch-disconnectors are derived from the corresponding circuit-breakers, keeping the overall dimensions, versions and

SACE Isomax S current-limiting circuit-breakers


GSIS9091

accessories unchanged. They guarantee operation and isolation in maximum safety and their release device can be activated either by the undervoltage release or by the shunt opening release. They can also be fitted with residual current releases, thereby constructing pure residualcurrent circuit-breakers.

SACE Isomax S switch-disconnectors

SACE Isomax S Power distribution

SACE Isomax S for applications up to 1000V

GSIS9093

SACE Isomax S according to UL/CSA Standards

Thanks to a specific range of SACE Isomax S circuit-breakers complying with the UL489 and CSA22.2 Standards, there are also greater possibilities for those customers operating on markets subject to the specifications defined in the North American standards. The range consists of

seven sizes with rated uninterrupted current from 100A to 2500A and breaking capacities, at 480 V AC, which can reach 100kA. board the circuit-breaker which are normally carried out by other devices, thereby ensuring numerous installation and service advantages. Within the basic series, there are circuit-breakers with magnetic only releases (MCP - Motor Control Protection) for motor protection, and switches (Moulded-Case Switch - MCS) for use as isolators or switching devices for lines, busbars or plant parts.

SACE Isomax S for motor protection classical and advanced

ABB SACE

GSIS9075

1/5

A world of success

The SACE Isomax S offer has been constantly renewed according to market requirements and often even anticipating these and is always to the fore from the technological viewpoint. Meanwhile, the quality and reliability have always remained at the maximum levels expected and the market has shown its appreciation of this.

Behind every reference lies a require-

ABB SACE apparatus is also responsible for protection (sometimes also integrated with control functions) of plants of considerable economic and technological importance, constructed within the sphere of large infrastructure projects. Orders are processed which stand out both for their size (such as the pumping stations of gas pipelines thousands of kilometres long) and for their advanced context (astronomical observatories and international research centres). SACE Isomax S imposes itself on the markets worldwide. For example, apparatus has been supplied to some of the most important European and Middle Eastern electricity boards as well as to North American and Asian electrified transport companies. Protection and control in installations for electric traction

ment fulfilled. It is facts which speak for SACE Isomax S. SACE Isomax S is a highly successful product of recognised quality, with many fields of application and it involves different sectors all over the world, with either

standard or highly personalised products. There is nowhere electrical power is used where SACE Isomax S is not to be found: manufacturing industries, steelworks, refineries and chemical plants, drilling rigs, gas pipelines, water pipelines, hospitals, airports, trains, railway and underground railway stations, calculation centres, offices, congress centres, theatres, and skyscrapers, as well as the most prestigious buildings worldwide. ABB SACE has, moreover, acquired knowledge which is practically unsurpassed in application areas where the highest degree of safety is required, and this has qualified it as the world leader in various sectors. Thousands of ships of all types cruise ships, container ships, bulk carriers, tankers, etc. and flying the flags of all nations are equipped with ABB SACE products, which are also widely used in railway traction and are the favourite product in the depths of mines.

Particularly severe environmental conditions such as mines and steelworks

Refineries and chemical plants as well as gas pipelines, water pipelines

Installation on board ships

1/6

ABB SACE

Offices, theatres, shopping malls and residential complexes

Underground railway stations

Off-shore drilling rigs

Protection and control of motors, generators

ABB SACE

1/7

GSIS9076

Selection and design engineering tools, management flexibility, services and consultancy:
an all-round offer
With the aim of guiding and facilitating selection of its products, ABB SACE ensures 360 support, both before and after the sale. For this purpose, to design and size electrical installations, it makes various work tools available, which facilitate calculations, ensure compliance of the installation with the Standards and reduce the risks of any errors. These are basically divided into calculation, design and estimate software, and manual tools.

D.O.C. (Design Optimization

The calculation methods and data indicated on the slide rules are taken from the CEI, IEC and NFC Standards in force and from installation practice.

& Computation) is a system which allows correct sizing of industrial low voltage electrical installations, able to propose the most suitable design selections regarding cables, busbars and protection devices. It allows the design engineer to develop clear and complete design documentation rapidly, based on the calculation models provided by the most recent standards.

Guide to low voltage installations is a brief


The collection of legal and technical regulations based on the

C.A.T.

(Computer Aided

current standards, regarding design, sizing and installation of an electrical

Technical Selection) is both an electronic catalogue and a technical aid tool for selecting and applying accessories to each individual circuitbreaker. By means of a guided pathway, it is possible to select, configure and order the most suitable apparatus for your own installation requirements.

plant. The guide takes into consideration the user plant from the electric power delivery point (MV/LV substation) in 1 systems.

st

category

Four

Slide rules

of different

colours, which make up the ABB Kits, allow rapid sizing calculations of the electrical installation. The following can be carried out: Cable sizing and calculation of the short-circuit currents (yellow slide rule) Checking the protections against direct contact and short-circuit of the cables (orange slide rule) Selective and back-up coordination (green slide rule) Sizing of motor lines and transformer outgoing feeders (blue slide rule)

Immediate ordering and management flexibility


Rapid ordering procedures have been provided for circuit-breakers in the SACE Isomax S series, and the configuration logic of the series enables efficient and flexible warehouse management. An order file can be generated compatible with the EDIFACT (Metel or ABB) standard, ready to be converted into EDI format and transmitted electronically.

1/8

ABB SACE

1
Using EDI (Electronic Data Interchange) to send orders rationalises the logistics chain, thereby reducing transit times and the risk of errors. EDI transmission allows the order to be loaded automatically at ABB SACE so that the request is immediately sent to production, together with the order acknowledgenotes, under the guidance of experts. Information and training have always been success factors for professional growth and development. Professional refresher training on both technical aspects and product developments, as well as on the standards and legislation, is essential, considering that these have such important implications for the safety of people and plants. The primary aim is to meet the information needs of professionals, especially by converting the technical-standard and legislative concepts into practical terms which can be applied directly to the various products and installations.

ment to the customer. The availability of standardised accessories for

g ro u p s o f c i rcuit-breakers makes it possible duce to rethe

number kept in the warehouse very and short

ABB SACE Service


Training courses are also provided for operators and maintenance personnel who work on ABB SACE apparatus and systems. For this purpose and to meet the need for evaluation and maintenance of existing electrical installations, the company has set up the Service Division within its

procurement times allow

limited stocks to be kept as these can be

rapidly replenished.

Training: an indispensable tool for professionals


By means of its technical training courses, ABB SACE is committed to putting its wealth of experience gained in over more than 60 years of operation at disposal. The courses are an opportunity for all operators in the sector to update their knowledge and compare

own structure, which acts as a qualified interlocutor working in close collaboration with the managers/users of the plants, to carry out maintenance, repair and overhauling activities at ABB SACE and on the users premises. The division also offers a spare parts, assembly and commissioning service for its own switchboards.

ABB SACE

1/9

Just one product for everyone

SACE Isomax S is a product which has been thought up and constructed for all types of customers: the user, the design engineer, the switchboard builder, the installer, the maintenance technician and the wholesaler.

ABB SACE proposes techni-

cal solutions to the

user

which fulfil all requirements and are always up to date with technological innovations in the field of electrical power distribution. It offers high quality products, reliability and precision, which guarantee high performances under any conditions, safe products during service and, when
GSIS9092

necessary, simple replacement of any faulty parts.

The

design engineer

has

simple installation inside the switchboard. The whole range of products is divided into eight sizes and constructed in only three depths, thereby allowing standardisation of the supporting structures and of the switchboards and installation in prefabricated structures. The dimensional uniformity and the possibilities of connection, thanks to the variety of terminal available, considerably facilitates
GSIS9079

products available which comply perfectly with the international technical standards and which are able to do the job simply, safely and reliably at the highest levels of performance. SACE Isomax S circuitbreakers offer the design engineer solutions for sizing, coordination and flexibility of application which allow him to draw up a state-of-the-art project, selecting from among well-known ranges and circuit diagrams to be

connections by means of busbars or cables.

integrated in a complete system, and satisfying all installation requirements and performances according to the standards. ABB SACE provides the

SACE Isomax S circuitbreakers allow easy and safe maintenance to be carried out, enabling the accessories to be inserted conveniently on the front of the circuitbreaker. Construction rationality as well as modularity of the

GSIS9090

to a current-limiting circuitbreaker). Standardisation of Isomax S circuit-breakers and their accessories means simple and economical management of the spare parts warehouse for the

installer

with products for

any type of plant, which are practical to install, simple to use, assemble and connect

The requirements of a

and easy to check, thanks also to the quality of the accessories supplied with the apparatus and the technical support documentation provided.

switchboard builder are fully


satisfied thanks to careful design of the product. The limited volumes of the pieces of apparatus allow the switchboard dimensions to be kept to a minimum and the modularity and compactness the ranges of products are conceived with allow

whole-

saler.
Furthermore, the clarity of product coding considerably helps product ordering, reduces procurement times and allows limited stocks to be kept in the warehouse since the products can be replenished rapidly.

maintenance technician to carry out


structure, allow the replacements without the need for any special adaptation, even when changing from one type of circuitbreaker to another (for example from an automatic

1/10

ABB SACE

Main characteristics

Index
Panorama of the SACE Isomax S family A single series for all applications ...................................................................................... 2/2

Construction characteristics Distinctive features of the series ........................................................................................ 2/4 Conditions of use ................................................................................................................ 2/8 Modularity of the series SACE Isomax S ........................................................................... 2/10

Compliance with the Standards Standards, Approvals, Certifications and company quality system ................................. 2/12

ABB SACE

2/1

Panorama of the SACE Isomax S family


A single series for all applications

SACE Isomax S1 CIRCUIT-BREAKERS FOR AC / DC DISTRIBUTION Poles Iu Ue (AC) Icu (380/415V AC) S1 3-4 125 500 B N S H L V Ue (DC) CURRENT-LIMITING CIRCUIT-BREAKERS Poles Iu Ue Icu (380/415V) Icu (690V) CIRCUIT-BREAKERS FOR MOTOR PROTECTION Poles Iu In Ue Magnetic only release IEC 60947-2 Electronic release PR211/P (I), IEC 60947-2 Electronic release PR212/MP, IEC 60947-4-1 [V] 16 25

SACE Isomax S2 S2 3-4 160 690 16 35 50

[nr.] [A] [V~] [kA]

250

500 S2X 100 3 100 690 70 10 S2X 80 3 80 180 690 -

[nr.] [A] [V~] [kA] [kA]

[nr.] [A] [A] [V~]

CIRCUIT-BREAKERS FOR APPLICATIONS AT 1000 V AC Poles Iu Icu (1000V AC)

[nr.] [A] [kA]

CIRCUIT-BREAKERS FOR APPLICATIONS AT 1000 V AC Poles Iu Icu (1000V DC), 4 poles in series

[nr.] [A] [kA]

SWITCH-DISCONNECTORS according to IEC 60947-3 Standard Poles Ith Ue Icm Icw Circuit-breakers according to UL 489 and CSA 22.2 Standards Poles Maximum continuous current (40 C) Maximum Ampere Breaking Capacity (480 V) Thermal-magnetic trip unit Microprocessor based trip unit MCP MCS

[nr.] [A] [V~] [kA] [kA] S1N 3 100 20 -

S2D 3-4 125 - 160 690 3,1 2,2

[no.] [A] [kA]

2/2

ABB SACE

SACE Isomax S3 S3 3-4 160-250 690

SACE Isomax S4 S4 3-4 160-250 690

SACE Isomax S5 S5 3-4 400-630 690

SACE Isomax S6 S6 3-4 630-800 690

SACE Isomax S7 S7 3-4 1250-1600 690

SACE Isomax S8 S8 3-4 2000-2500-3200 690

35 65 85 750 S3X 3-4 125-200 690 200 75 S3 / S3X 3 160-250 / 125-200 25200 690 -

35 65 100 S4X 3-4 250 690 200 75 S4 / S4X 3 160-250 / 250 100250 690 -

35 65 100 750

35 50 65 100 750 S6X 3-4 400-630 690 200 75

50 65 100 -

85 120 -

2
S7 3 1250-1600 10001600 690 -

S5 3 400-630 320630 690 -

S6 / S6X 3 630-800 / 400-630 320..800 690 -

S3L / S3X 3 160 / 125 6 / 30

S4L / S4X 3 160-250 / 250 8 / 30

S5L 3 400 8

S6L / S6X 3 630-800 / 630 12 / 30

S3L 4 160-250 40

S5L 4 400 40

S6L 4 630 / 800 40 / 50

S3D 3-4 100 - 160 - 250 - 320 690 10 6,5 S3 B/N/H/L 2-3 150 - 225 85 S3L S3 H-D 150/225 S4 N/H/L 2-3 250 100 S4 N/H/L S4 H-D S5 N/H/L 2-3 400 100

S6D 3-4 400 - 630 - 800 690 30 15 S6 N/H/L 2-3 800 100

S7D 3-4 1000 - 1250 - 1600 690 52,5 25 S7H 2-3 1200 65 S7H S7 H-D

S8D 3-4 2000-2500-3200 690 85 40 S8V 3 1600-2000-2500 100 S8V S8 V-D

S5 N/H/L S5 H-D

S6 N/H/L S6 H-D

ABB SACE

2/3

Construction characteristics
Distinctive features of the series

Terminals

Identification nameplate

Fixed contacts

Arcing chamber

Moving contacts

Operating lever

Microprocessor-based electronic release

2/4

GSIS9069

ABB SACE

GSIS9048

Double insulation
The double insulation technique consists of total separation between the power circuits and the auxiliary circuits and is a characteristic of all SACE Isomax S apparatus from size S3 up. The housing of each electrical accessory is completely segregated from the power circuit, thus avoiding all risk of contact with live parts, thereby increasing operator safety conditions during management and inspection of the installations. Moreover, the circuit-breaker has redundant insulation between the internal live parts, both regarding thickness of materials and the distances, which are greater than those required by the IEC Standards and are in accordance with American usage.

Positive operation
The operating lever always indicates the exact position of the circuit-breaker moving contacts, thereby guaranteeing safe and reliable indications (I = Closed; O = Open; yellow-green line = Open due to release trip). The circuit-breaker operating mechanism has free release, regardless of the pressure on the lever or the speed of operation. Release tripping automatically opens the moving contacts: to close them again, it is necessary to reset the operating mechanism by pushing the operating lever from the intermediate position to the lower limit of the open position. For plug-in or withdrawable circuit-breakers, the moving part can only be detached from the fixed part with the circuit-breaker open (moving contacts separate from the relative fixed contacts).

GSIS9051

GSIS0074

Selectivity
The complete range of releases means that the protection functions of the apparatus can be coordinated according to current-type, time-type, energy-type or residual-current selectivity chains. It is therefore possible to isolate only the areas affected by the fault, ensuring maximum service continuity. Circuit-breakers in category B are available from 400 A up.

Possibility of inspection
With the circuit-breaker out of service, it is possible to check the state of the internal parts and live components of the circuit-breaker directly. The arcing chambers and the fixed and moving contacts are accessible simply by removing the circuit-breaker cover. The operation, facilitated by the limited number of components, reduces maintenance times and ensures a higher degree of safety.

ABB SACE

2/5

GSIS9050

Construction characteristics
Distinctive features of the series

GSIS9125

Isolation behaviour

Racking-out with the door closed


This system, starting from 160 A, allows the circuit-breaker to be racked in and out with the compartment door closed, increasing operator safety and allowing construction of internal arc proof low voltage switchboards. Racking out can only take place with the circuit-breaker open, using a special rackingout crank handle supplied with the withdrawable version circuit-breaker.

In the open position, the circuit-breaker guarantees isolation of the circuit in compliance with the IEC 60947-2 Standard. For plug-in or withdrawable version circuit-breakers, in the rackedout or withdrawn position, the power and auxiliary circuits are isolated, ensuring that no parts are live. Under these conditions and by means of special connectors, it is possible to carry out blank tests, operating the circuit-breaker in complete safety. The redundant insulation distances guarantee the absence of leakage currents and dielectric strength in the event of any overvoltages between the input and output.

GSIS9127

Electromagnetic compatibility
By using SACE PR211/P , PR212/P , PR212/MP microprocessorbased overcurrent releases and SACE RC210, RC211, RC212 electronic residual-current releases, the absence of unwarranted trips is guaranteed even in the presence of interference caused by electronic equipment, atmospheric disturbance or discharges of electrical type. Furthermore, the apparatus does not generate interference with other electronic equipment in the vicinity of the installation. This is in compliance with the IEC 60947-2 Appendix F , IEC 1000-4, EN 61000-4, EN 50081-1, EN 50081-2, EN 50082-1, EN 50082-2 European Directive No. 89/ 336 specifications regarding electromagnetic compatibility EMC.

Tropicalisation
The SACE Isomax S series of circuit-breakers and accessories comply with the strictest regulations for use in hot-humid-saline climates (in compliance with climatograph 8 of the IEC 721-2-1 Standards), thanks to: insulating cases made of fibreglass-reinforced synthetic resins; anti-corrosion treatment on all main metal parts (C UNI 356465 environment); Fe/Zn 12 galvanisation (UNI ISO 2081), protected by a conversion layer consisting mainly of chromates (UNI ISO 4520).

2/6

ABB SACE

GSIS9129

GSIS9126

GSIS9128

Installation positions
The circuit-breaker can be installed in any position without any effect on its rated characteristics. In compliance with the IEC 60947-2 Standards, SACE Isomax S circuit-breakers can be supplied through either top or bottom terminals, without jeopardising operation of the apparatus. They can be installed in switchboards, mounted directly on the base plate or on Din rails up to size S5.

Mounting on DIN rail up to 630 A


The brackets for fixing onto standardised DIN EN 50022 rails for S1, S2 and DIN EN 50023 rails for S3, S4, S5 simplify assembly of the circuit-breakers up to 630 A in standard switchboards. This allows standardised supporting structures to be used and facilitates the stage for designing and constructing the switchboard metalwork structure.

GSIS9062

GSIS9131

Resistance to vibration
The circuit-breakers are unaffected by vibrations generated mechanically or due to electromagnetic effects, in compliance with the IEC 68-2-6 Standards and the strictest regulations of the major classification organisations: RINA DET Norske Veritas Lloyds Register of Shipping Germanischer Lloyd Bureau Veritas.

Degrees of protection
Different measures have been taken in SACE Isomax S circuitbreakers to achieve IP20 degree of protection for the fixed, plug-in and withdrawable version circuit-breaker, excluding the terminals, and IP30 for the front parts of the circuit-breakers installed in switchboards. The fixed parts are always provided with IP20 degree of protection. It is possible to achieve IP54 degree of protection in accordance with the IEC 60529 Standard with the circuit-breaker installed in a switchboard fitted with rotary handle operating mechanism transmission on the compartment door and the special insulation gaskets which can be ordered separately.

ABB SACE

2/7

GSIS9130

Construction characteristics
Conditions of use
Degrees of protection (according to CEI EN 60529 Standard file 519) Circuit-breaker IP20 Circuit-breaker in switchboard IP30 IP30

Direct operating mechanism Front for lever operating mechanism without terminal covers

GSIS9081

GSIS9080

IP30

IP40 (1) IP50

GSIS9083

Direct rotary handle Rotary handle transmission

GSIS9084

with terminal covers

IP40

IP54 IP30 (2)

GSIS9086

Special IP54 protection Motor operator

GSIS9087

with terminal covers and direct rotary handle

(1) IP30 for withdrawable circuit-breakers

(2) IP40 for S1-S2 and S6-S7 circuit-breakers

2/8

ABB SACE

GSIS9088

GSIS9085

GSIS9082

Operating temperature
SACE Isomax S circuit-breakers can be used in ambient conditions where the temperature in the surrounding atmosphere varies between -25 C and +70 C and stored in ambients with temperatures between -40 C and +70 C. The circuit-breakers fitted with thermomagnetic overcurrent release have their thermal element set for a reference temperature of +40 C. temperature but, in the case of temperatures higher than 40 C, the maximum setting of the protection against overloads (function L) must be reduced to take into consideration inertial phenomena that occur in the copper parts of the circuitbreaker through which the phase current passes (moving and fixed contacts, and connection terminals) which cause a decrease in the rated uninterrupted current as indicated in the table on page

For temperatures between +40 C and +70 C, with the same setting, there is lowering of the thermal trip threshold due to the temperature-related behaviour of the bimetallic strip of the release itself. For temperatures lower than +40 C, on the other hand, there is an increase in the thermal trip threshold as indicated in the table on page

5/34.

The performances of the circuit-breaker cannot be guaranteed for temperatures above +70 C. T o ensure service continuity of the installations, careful thought must be given as to how to keep the temperature within acceptable levels for operation of all the various devices and not only the circuit-breakers. For example, forced ventilation in the switchboards and in the areas where they are installed may be necessary.

5/39.

The electronic microprocessor-based overcurrent releases do not undergo any variations in performance with changes in

Altitude
Up to an altitude of 2000 m SACE Isomax S circuit-breaker rated performances are unaffected. As the altitude increases, the atmospheric properties change in terms of composition, dielectric strength, cooling capacity and pressure. The circuit-breakers therefore undergo derating, which can basically be measured through the change in significant parameters such as the rated maximum operating voltage and the rated uninterrupted current.

Altitude Rated service voltage, Ue Rated uninterrupted current, Iu

[m] [V~] %Iu

2000 690 100%

3000 600 95%

4000 500 90%

ABB SACE

2/9

Construction characteristics
Modularity of the series SACE Isomax S

Starting from the fixed version circuit-breaker and by means of mounting the conversion kit, all the other versions which are used for the various requirements are obtained. The following are available: kit for conversion from fixed circuit-breaker to moving part of a plug-in or withdrawable circuit-breaker conversion kit for the connection terminals which make it possible to obtain front and rear terminals for Copper or Aluminium cables, and front and rear terminals for flat bar terminals. Various accessories are also available: shunt opening releases undervoltage releases auxiliary contacts position contacts

the bracket for rear fixing onto DIN EN 50022 rail for S1-S2 circuit-breakers, DIN EN 50023 rail for S3-S4-S5 circuit-breakers direct action motor operator, with stored energy and with solenoid. rotary handle operating mechanisms directly on the circuitbreaker and with transmission on the compartment door residual-current releases accessories for microprocessor-based overcurrent releases such as the signalling, dialogue and actuation unit and external CTs. the fixed parts for plug-in or withdrawable circuit-breakers with front terminals for cables or for flat bars and rear terminals for flat bars.

2/10

ABB SACE

ABB SACE

GSIS0159

2/11

Compliance with the Standards


Standards, Approvals, Certifications and company quality system
SACE Isomax S circuit-breakers and their accessories comply with the IEC 609472, EN 60947-2 (unified in 17 countries of CENELEC), CEI EN 60947 and IEC 61000 international Standards and conform with the EC directive: Low Voltage Directives (LVD) no. 73/23 EEC Electromagnetic Compatibility Directive (EMC) no. 89/336 EEC. Certification of compliance with the
GSIS9119

The attention paid to protecting the environment is another important priority for ABB SACE, and as confirmation of this, the environmental management system has been certified by RINA.

above-mentioned product Standards, is carried out, in respect of the European EN 45011 Standard, by the
GSIS9132

Italian certification organisa-

tion, ACAE (Association for Certification of Electrical Apparatus),- member of the European organisation LOVAG (Low Vo l t a g e A g re e m e n t

ABB SACE was the first industrial company in the electro-mechanical sector in Italy to obtain this recognition, and, thanks to a revision of its production process with an eye to ecology, has managed to reduce consumption of raw materials, processing waste and the risk of accidents by 20%.

Group).

ISO 9001
GSIS9119

The attention paid to protecting the environment and to the safety of workers is a priority commitment of ABB SACE and as confirmation of this, the company developed the Environmental Management System in compliance with the Interna-

The ABB SACE Quality System complies with the International ISO 9001 Standard (model for assuring quality in design, development, construction, installation and assistance) and to the equivalent European EN ISO 9001 and Italian UNI EN ISO 9001 Standards. The certification Organisation is RINAQUACER.

tional ISO 14001 Standard, certified in 1997, integrating this in 1999 with the Health and Safety in the Workplace Management System in accordance with BS 8800 (British Standards).

The prizes obtained by ABB SACE at the Forum Design in Hannover and at Electro in Paris bear witness to the consideration given to man and the respect

ABB SACE obtained its first certification in 1990. The ABB SACE Test Room is accredited by SINAL. The apparatus complies with the prescriptions for on-board installations and is approved by major Shipping Registers, such as: LLOYDS REGISTER OF SHIPPING, GERMANlSCHER LLOYD, BUREAU VERITAS, RINA, DET NORSKE VERITAS, POLSKI REIESTR STATKOW and the AMERICAN BUREAU OF SHIPGSIS9118

for ergonomic criteria.

Please contact ABB SACE for information regarding the types of circuit-breakers approved, the performances approved and their relative validity.

PING.

2/12

ABB SACE

The ranges

Index
SACE Isomax S circuit-breakers for power distribution ........................................... 3/3 Electrical characteristics IEC 60947-2 .............................................................................. 3/4 General characteristics ..................................................................................................... 3/6 Thermomagnetic releases ................................................................................................. 3/8 Electronic releases ............................................................................................................ 3/10

SACE Isomax S current-limiting circuit-breakers ...................................................... 3/15 Electrical characteristics IEC 60947-2 .............................................................................. 3/16 General characteristics ..................................................................................................... 3/18

SACE Isomax S circuit-breakers for motor protection (protection against short-circuit) .................................................................................. 3/23 Electrical characteristics IEC 60947-4 .............................................................................. 3/24 General characteristics ..................................................................................................... 3/26

SACE Isomax S circuit-breakers for motor protection (integrated protection) .................................................................................................... 3/28 Electrical characteristics IEC 60947-2 and IEC 60947-4 ................................................. 3/28 General characteristics ..................................................................................................... 3/30

SACE Isomax S circuit-breakers for applications up to 1000V ................................ 3/35 Electrical and general characteristics IEC 60947-2 ......................................................... 3/36

SACE Isomax S switch-disconnectors ........................................................................ 3/39 Electrical and general characteristics IEC 60947-3 ......................................................... 3/40

SACE Isomax S circuit-breakers in accordance with UL489 and CSA C22.2 Standards .......................................................................................................................... 3/43 Electrical and general characteristics ............................................................................... 3/44

ABB SACE

3/1

Circuit-breakers for power distribution

Eight sizes to optimise use for all plant and installation requirements 690V 125-3200 A 16-120 kA (380/415 V)

GSIS9063

3/3

SACE Isomax S circuit-breakers for power distribution


Electrical characteristics IEC 60947-2

GSIS9133

GSIS9134

SACE Isomax S1 Rated uninterrupted current, Iu Poles Rated service voltage, Ue (AC) 50-60Hz (DC) [A] Nr. [V] [V] [kV] [V] [V] B [kA] [kA] [kA] [kA] [kA] [kA] [kA] [kA] [%Icu] [kA] [ms] [kA] A 25 16 10 8 16 50% 32 8 125 3-4 500 250 6 500 3000 N 40 25 16 12 25 50% 52,5 6 B 25 16 10 8 6 16 16

SACE Isomax S2 160 3-4 690 500 6 690 3000 N 50 35 (1) 20 12 8 35 35 75% 74 7 A S 65 50 25 15 10 50 50 75% 105 6 N

SACE Isomax S3 160 - 250 3-4 690 750 8 800 3000 H 100 65 50 40 18 65 50 35 75% 143 7 A L 170 85 65 50 20 (5) 85 65 50 75% 187 6

Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 220/230 V (AC) 50-60 Hz 380/415 V[kA] (AC) 50-60 Hz 440 V (AC) 50-60 Hz 500 V

65 35 (1) 30 25 14 35 35 20 100% 74 8

(AC) 50-60 Hz 690 V (DC) 250 V - 2 poles in series (DC) 500 V - 2 poles in series (DC) 500 V - 3 poles in series (DC) 750 V - 3 poles in series Rated short-circuit service breaking capacity, Ics (2) Rated short-circuit making capacity (415 V) Opening time (415V at Icu) Rated short-time withstand current for 1 s, Icw Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2 Releases: thermomagnetic T fixed, M fixed 5 Ith T fixed, M fixed 10 Ith

100% 32 8

T adjustable, M fixed 3 Ith T adjustable, M fixed 5 Ith T adjustable, M fixed 10 Ith T adjustable, M adjustable magnetic only with microprocessor Interchangeability Versions Terminals fixed plug-in withdrawable (3) Fixing on DIN rail Mechanical life Electrical life (at 415 V) Basic dimensions, fixed F-P FC-R FC-R DIN EN 50022 25000/240 8000/120 78/103 70 120 0,9 /1,2 1 / 1,4 F-P EF - FC - FC CuAl - R FC - R DIN EN 50022 25000/240 8000/120 90/120 70 120 1,1/1,5 1,3/1,7 (4)

M fixed PR211/P (I-LI) PR212/P (LSI-LSIG) F-P-W F- EF - ES - FC FC CuAl - RC - R EF - FC - R EF - FC - R DIN EN 50023 25000/120 10000(160A)-8000(250A)/120 105/140 103,5 170 2,6 / 3,5 3,1 / 4,1 3,5 / 4,5
For the S5 circuit-breaker, the plug-in version is only available for the version with 400 A rated current (5) The SACE S3 circuit-breaker with breaking capacity L at 690 V can only be supplied from above

[No. operations / hourly operations] [No. operations / hourly operations] 3/4 poles L [mm] D [mm] H [mm]

Weights fixed plug-in withdrawable


(1) (2)

3/4 poles 3/4 poles 3/4 poles

[kg] [kg] [kg]


(3)

All the versions with Icu=35kA are certified at 36kA For S3 N/H/L, S4 N/H/L, S5 N/H, and S6 N/S/H circuitbreakers the performance percentage of Ics at 690V is reduced by 25%.

The withdrawable version circuit-breakers must be fitted with the front flange for the lever operating mechanism or with its alternative accessories, such as the rotary handle or the motor operator

3/4

ABB SACE

GSIS9135

GSIS9095

GSIS9096

GSIS9097

GSIS9098

SACE Isomax S4 160 - 250 3-4 690 8 800 N 65 35 (1) 30 25 18 100% 74 8 3000 H 100 65 50 40 22 100% 143 7 A L 200 100 80 65 30 75% 220 6 N

SACE Isomax S5 400 - 630 3-4 690 750 8 800 3000 H 100 65 50 40 25 65 50 35 100% 143 7 L 200 100 80 65 30 100 65 50 75% 220 6 N

SACE Isomax S6 630 - 800 3-4 690 750 8 800 3000 S 85 50 45 35 22 50 35 H 100 65 50 40 25 65 50 L 200 100 80 65 30 100 65 S 85 50 40 35 20 65 35 (1) 30 25 20 35 20 -

SACE Isomax S7 1250 - 1600 3-4 690 8 800 3000 H 100 65 55 45 25 75% 143 22 L 200 100 80 70 35 50% 220 22

SACE Isomax S8 2000 - 2500 - 3200 3-4 690 8 690 2500 H 85 85 70 50 40 50% 187 20 35 B V 120 120 100 70 50 50% 264 20

65 35 (1) 30 25 20 35 35 20 100% 74 8

GSIS9136

16 20 35 50 100% 100% 100% 75% 74 10 105 9 143 8 220 7

100% 105 22

5 (400A) B (400A) - A (630A)

7,6 (630A) - 10 (800A) B

15 (1250A) - 20 (1600A) B

F-P-W F - EF - ES - FC FC CuAl - RC - R EF - FC - R EF - FC - R DIN EN 50023 20000/120 10000(160A)-8000(250A)/120 105/140 103,5 254 4 / 5,3 4,5 / 5,9 4,9 / 6,3
KEY TO VERSIONS F = Fixed P = Plug-in W = Withdrawable

F - P (400) - W F - EF(400A) - ES - FC FC CuAl (400A)-RC (400A)-R EF - FC - R EF(400A) - ES - FC (400A) R - VR (630A) DIN EN 50023 20000/120 7000(400A)-5000(630A)/60 140/184 103,5 254 5/7 6,1 / 8,4 6,4 / 8,7
KEY TO TERMINALS F = Front EF = Extended front ES = Extended spreaded front

F-W F - EF - ES - FC CuAl RC - R EF - HR - VR 20000/120 7000(630A)-5000(800A)/60 210/280 103,5 268 9,5 / 12 12,1 / 15,1

F-W F - EF - ES - FC CuAl (1250A) HR - VR EF - HR - VR 10000/120 7000(1250A)-5000(1600A)/20 210/280 138,5 406 17 / 22 21,8 / 29,2

F F (2000-2500A) - VR 10000/20 2500(2500A)/20-1500(3200A)/10 406/556 242 400 57/76 -

FC = Front for copper cables FC CuAl = Front for copper or aluminium cables R = Rear threaded

RC = Rear for copper or aluminium cables HR = Rear horizontal flat bar VR = Rear vertical flat bar

ABB SACE

3/5

SACE Isomax S circuit-breakers for power distribution


General characteristics
The SACE Isomax S series of moulded-case circuit-breakers conforming to the IEC 60947-2 Standard, is divided into eight basic sizes, with rated uninterrupted currents from 125 to 3200 A and breaking capacities from 16 to 120 kA (380/415 V). Selection of the size allows the basic electrical characteristics to be identified simply and immediately, whereas selection of the overcurrent release depends on the type of application required.

Range of application of the alternating current circuit-breakers

For protection of alternating current networks, SACE S1, S2, and S3 circuit-breakers fitted with thermomagnetic releases and SACE S4, S5, S6, S7, and S8 circuitbreakers fitted with SACE PR211/P or PR212/P electronic releases are available. These are characterised by an application range from 10 to 3200 A and by a rated voltage of 690 V .

KEY TM = Thermomagnetic M = Magnetic only PR211-PR212 = Electronic releases

3/6

ABB SACE

GSIS0078

Range of application of the direct current circuit-breakers

SACE S1, S2, S3, S5, and S6 circuitbreakers fitted with thermomagnetic releases are used in protection of direct current networks, with an application range from 10 to 800 A and a minimum operating voltage of 24 V DC. With 2 poles in series, SACE Isomax S circuit-breakers can be used with rated voltage of 250 and 500 V and breaking

capacities up to 100 kA (250 V DC) and 65 kA (500 V DC); whereas the SACE S3, S5, and S6 circuit-breakers with 3 poles in series can reach 750 V and breaking capacities up to 50 kA. The various possible wiring diagrams and the trip threshold correction factors are indicated on page 5/47.

KEY TM = Thermomagnetic M = Magnetic only

ABB SACE

3/7

GSIS0079

SACE Isomax S circuit-breakers for power distribution


Thermomagnetic releases
SACE Isomax S1, S2, S3, S5, and S6 circuit-breakers can be fitted with thermomagnetic releases and are used for protection of alternating current networks with the S1, S2, and S3 circuit-breakers (for applications from 10A to 250A) and in direct current with the S1, S2, S3, S5, and S6 circuit-breakers (from 10A to 800A). They allow protection against overloads using a thermal device (with fixed threshold for S1 and adjustable threshold for S2, S3, S5, and S6) carried out using the bimetallic strip technique, and protection against short-circuit using a magnetic device (with fixed threshold for S1, S2, and S3 and adjustable threshold for S5 and S6). The four-pole circuit-breakers are always fitted with the neutral protected by the release.
GSIS9058

3
Thermomagnetic releases
L1 - L2 - L3 neutral S1 125 S2 160 S3 160 S3 250 S5 400 S5 630 S6 630 S6 800 10 x Ith L1-L2-L3 neutral 5 x Ith 3 x Ith L1-L2-L3 neutral L1-L2-L3 neutral TM adjustable L1-L2-L3 neutral 500 500 160 160 500 500 160 160 500 500 160 160 500 500 200 200 500 500 200 200 500 500 200 200 500 500 300 300 500 500 200 200 500 500 250 250 500 500 300 300 630 630 320 320 800 800 400 400 1000 1000 500 500 300 300 1250 1250 630 630 1250 800 630 400 375 240 R10 R10 R12,5 R12.5 R16 R16 R20 R20 R25 R25 R32 R32 R32 R32 R40 R40 R50 R50 R50 R50 R63 R63 R80 R80 R100 R100 R125 R125 R125 R80

3/8

ABB SACE

Magnetic only releases


L1 - L2 - L3 neutral S1 125 S2 160 S3 160 S3 250 10 x Ith L1-L2-L3 neutral 5 x Ith L1-L2-L3 neutral 160 160 200 200 500 500 250 250 500 500 300 300 630 630 320 320 800 800 400 400 1000 1000 1250 1250 1250 800 1250 800 630 400 1600 1000 2000 1250 2500 1600 R16 R16 R40 R40 R50 R50 R50 R50 R63 R63 R80 R80 R100 R100 R125 R125 R125 R80 R125 R80 R160 R100 R200 R125 R250 R160

The magnetic only releases which equip the SACE S1, S2, and S3 circuit-breakers have a fixed trip threshold as indicated in the table. For S1, the magnetic only release is available in the version with breaking capacity N = 25 kA; for S2, breaking capacities N = 36 kA and S = 50 kA are available. The latter version is only available in the 10 x Ith version.

GSIS0068

R160 R100

R200 R125

R250 R160

R320 R200

R400 R250

R500 R320

R630 R400

R800 R500

The letter R identifies the setting current for phase (L1-L2-L3) and neutral protection (second line). The ones indicated are the combinations provided as standard. On request, circuit-breakers with neutral at 100% of the phase setting can be supplied.

The thermomagnetic releases which equip the SACE S2 and S3 circuit-breakers have the thermal element with threshold adjustable from 0.7 1 x In. The regulated current value which is obtained by using the appropriate selector must be intended as the rated value at 40 C. The magnetic element has fixed trip threshold, with trip values which vary according to the phase setting. The S2 circuit-breaker with breaking capacity S = 50 kA is only available in the 10 x Ith version.

The thermomagnetic releases which equip SACE S5 and S6 circuit-breakers have the thermal element with threshold adjustable from 0.7 1 x In. The regulated current value which is obtained by using the appropriate selector must be intended as the rated value at 40 C. The magnetic element can be adjusted from 5 10 x In. The table gives the maximum magnetic trip values (10 x In) for protection of the phases (L1 - L2 - L3) and of the neutral.

1600 1000 800 500 480 300

2000 1250 1000 625 600 375

2500 1600 1250 800 750 480 3200 2000 4000 2500 5000 3200 6300 4000 8000 5000

The trip thresholds of the magnetic protection are a function of the setting used both for protection of the phases (L1 - L2 - L3) and of the neutral. The releases denominated 10 x Ith are indicated for all distribution applications, whereas the releases denominated 5 x Ith and 3 x Ith are used where a low magnetic trip threshold is required. With regard to this, the 3 x Ith are particularly suitable for protection of generators.

ABB SACE

3/9

GSIS0070

GSIS0069

SACE Isomax S circuit-breakers for power distribution


Electronic releases
The SACE Isomax S4, S5, S6, S7 and S8 circuit-breakers for protection in alternating current can be fitted with SACE PR211/P or SACE PR212/P overcurrent releases, constructed using electronic microprocessor-based technology. This allows protection functions to be obtained which guarantee a high level of reliability and tripping precision and which are unaffected by the external ambient. The power supply needed for correct operation is supplied directly by the release current transformers, in the presence of a phase current higher than or equal to 18% of their rated current, even with a single phase supplied with voltage. There is only one adjustment for all the phases and the neutral and the release is simultaneous for all the circuit-breaker poles, with trip characteristics which are unaffected by the external ambient. The functions and settings of the release protections can be verified by means of the SACE TT1 and SACE PR010/T T est units.
GSIS9060

SACE PR211/P
The SACE PR211/P release (available from S4 to S7) provides protection functions against overload L and instantaneous short-circuit I, and is available in the versions with functions I and LI. The wide range of adjustments make this

SACE PR212/P
The SACE PR212/P release (available from S4 to S8) provides protection functions against overload L, delayed shortcircuit S and instantaneous short-circuit I, and against earth fault G. It is available in the versions PR212/P with functions PR212/T actuator unit which is always supplied when the dialogue unit is required. It is particularly suitable in applications with selective coordination requirements, for earthing protection against the risk of fire and evolutionary faults, and for remote control and parametrisation, network supervision and centralised load management.

release particularly suitable in all distribution where tripping reliability and precision is required and where magnetic only protection is needed (from 1.5 to 12 x In), using the SACE PR211/P version I release.

LSI and LSIG; both allow use of the PR010/K signalling unit, the PR212/D dialogue unit and the PR212/T actuator unit, which can be used either simultaneously or individually, except for the

In S4 160 S4 250 S5 400 S5 630 S6 630 S6 800 S7 1250 S7 1600 S8 2000 S8 2500 S8 3200 L S I G neutral (50%) neutral (100%)

100 A

160 A

250 A

320 A

40100 1001000 1501200 20100 2050 40100

64160 1601600 2401920 32160 3280 64160

100250 2502500 3753000 50250 50125 100250

128320 3203200 4803840 64320 64160 128320

3/10

ABB SACE

For four-pole circuit-breakers fitted with SACE PR212/P release (LSI-LSIG), protection of the neutral can be set to 50% or 100% of the phase protection setting (by means of dip-switches on the front of the release). For those with SACE PR211/P release (ILI), protection of the neutral at 100% can be ordered by means of an additional code 1SDA037505R1. With three-pole and distributed neutral circuit-breakers, external toroids can be used by connecting these directly either to the SACE PR211/P release, or to the SACE PR212/P release. On request, it is possible to obtain full protection of the neutral with setting equal to 100% of the protection. The SACE PR211/P and SACE PR212/P microprocessor-based releases are self-supplied and ensure correct operation of the protection functions, even with only a single phase supplied with voltage, in the presence of a current higher than or equal to 18% of the rated phase value.

The protection release consists of current transformers (three or four according to the circuit-breaker polarity), the SACE PR211/P or SACE PR212/P protection unit and an OS demagnetising opening solenoid which acts directly on the circuit-breaker operating mechanism group. The current transformers are housed inside the release box and supply the energy needed for correct operation of the protection and the signal required to determine the current. They are available with primary rated current as indicated in the table below. When the protection intervenes, the circuit-breaker opens by means of the opening solenoid (OS), which changes over a contact for signalling release tripped. Resetting the signal is of mechanical type and takes place with resetting of the circuit-breaker operating lever. It is possible to test the opening solenoid (OS) by means of the SACE TT1 test device. A positive result of the test

coincides with circuit-breaker opening. All the protection functions with relative trip times can be verified and tested using the SACE PR010/T accessory unit (only for PR212/P). In the versions with SACE PR212/P - LSI/ LSIG release, it is possible to set the adjustment parameters of the protection functions directly from the front (dipswitch positioned on MAN), or to set the parameters remotely (dip-switch positioned on ELT) thanks to the use of the SACE PR212/D dialogue units. In case of any anomalies in remote parametrisation, the protection automatically uses the set of parameters set manually on the front of the circuitbreaker. The PR010/K signalling or PR212/D dialogue units supply the PR212/P (24 VDC 20%) protection release continuously and this allows the adjustment parameters to be set even with the circuitbreaker open.

400 A

630 A

800 A

1000 A

1250 A

1600 A

2000 A

2500 A

3200 A

160400 4004000 6004800 80400 80200 160400

252630 6306300 9457560 126630 126315 252630

320800 8008000 12009600 160800 160400 320800

4001000 100010000 150012000 2001000 200500 4001000

5001250 125012500 187515000 2501250 250625 5001250

6401600 160016000 240019200 3201600 320800 6401600

8002000 200020000 300024000 4002000 4001000

10002500 250025000 375030000 5002500 5001250

12803200 322032000 480038400 6403200 6401600

ABB SACE

3/11

SACE Isomax S circuit-breakers for power distribution


Electronic releases
Protection functions and parametrisation of the SACE PR211/P, PR212/P releases
Protection function
Against overload with inverse long time delay and trip characteristic according to a time dependent curve (I2t = constant)
CANNOT BE EXCLUDED
I2t=cost ON

Trip threshold
I1 = 0,4 - 0,5 - 0,6 - 0,7 - 0,8 - 0,95 - 1 x In PR211/P (I - LI) I1 = 0,4 - 0,5 - 0,55 - 0,6 - 0,65 - 0,7 - 0,75 - 0,8 - 0,85 - 0,875 0,9 - 0,925 - 0,95 - 0,975 - 1 x In PR212/P (LSI - LSIG) Release between 1,05 ... 1,30 x I1 (IEC 60947-2) I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In Tolerance + 10%

Against short-circuit with inverse short time delay and trip characteristic with dependent time (I2t = constant) or independent time
CAN BE EXCLUDED

I2t=cost OFF

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In Tolerance + 10%

I3 = 1,5 - 2 - 4 - 6 - 8 - 10 - 12 x In (*) Against short-circuit with adjustable instantaneous trip


CAN BE EXCLUDED

Tolerance + 20%
(*) For S5 630, I3 max = 8 x In

3
CAN BE EXCLUDED

Against earth fault with short inverse time delay and trip characteristic according to a dependent time curve (I2t = constant)

I4 = 0,2 - 0,3 -0,4 - 0,6 - 0,8 - 0,9 - 1xIn Tolerance + 20%

SACE PR211/P electronic release, functions I or LI


Protection L
Against overload

Protection I
Against short-circuit with instantaneous trip Socket for Test SACE TT1 Test unit

3/12

ABB SACE

GSIS9054

Characteristics of SACE PR211/P, SACE PR212/P electronic releases


Trip curves
A at 6 x I1 t1 = 3s B at 6 x I1 t1 = 6s C at 6 x I1 t1 = 12s D at 6 x I1 t1 = 18s Operating temperature Relative humidity Service frequency 25 C +70 C 90% 45 ... 66 Hz able to measure harmonics up to 550 Hz

(tolerance: + 10% up to 2 x In; + 20% above 2 x In)

at 8 x In t2 = 0,05s

at 8 x In t2 = 0,1s

at 8 x In t2 = 0,25s

at 8 x In t2 = 0,5s

Electromagnetic compatibility (LF and HF) IEC 60947-2 Annex F Electrostatic discharges IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 15 years (at 45 C)

(tolerance: + 20% ) t2 = 0,05s t2 = 0,1s t2 = 0,25s t2 = 0,5s

Radiated electromagnetic field Short-time transients Mean time between failure (MTBF) Characteristics of the signalling contact Maximum interrupted current Maximum interrupted voltage

(tolerance: + 20% )

0,5 A 24 VDC/AC 3 W/VA 500 VAC 1000 VAC

up to 3,25 x I4 t4 = 100ms

up to 2,25 x I4 t4 = 200ms

up to 1,6 x I4 t4 = 400ms

up to 1,25 x I4 t4 = 800ms

Breaking capacity Contact/contact insulation Contact/coil insulation

(tolerance: + 20% )

SACE PR212/P electronic release, functions LSI or LSIG


Protection L
Against overload

Protection S
Against short-circuit with delayed trip

Protection I
Against short-circuit with instantaneous trip

Protection G
Against earth fault

Socket for Test SACE TT1 Test unit

selection for electronic or manual setting

dip-switch for setting the neutral

Socket for connection of SACE PR010/T Test unit

ABB SACE

3/13

GSIS9056

SACE Isomax S current-limiting circuit-breakers

To interrupt and limit even the worst faults 690V 100-630A 70-200kA (380/415 V)

GSIS9064

3/15

SACE Isomax S current-limiting circuit-breakers


Electrical characteristics IEC 60947-2

SACE Isomax S2X 100 Rated uninterrupted current, Iu Poles Rated service voltage, Ue (AC) 50-60Hz Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 220/230 V (AC) 50-60 Hz 380/415 V (AC) 50-60 Hz 440 V (AC) 50-60 Hz 500 V (AC) 50-60 Hz 690 V [A] No. [V] [kV] [V] 100 3 690 6 690 3000 X 100 70 70 50 10 75% 154 3,5 A

[kA] [kA] [kA] [kA] [kA] [%Icu] [kA] [ms]

Rated service short-circuit breaking capacity, Ics (1) Rated short-circuit making capacity (415 V) Opening time (415V at Icu) Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2 Releases: thermomagnetic - T adjustable, M fixed 10 Ith with microprocessor PR211/P (I-LI)

with microprocessor PR212/P (LSI-LSIG) Interchangeability Versions Terminals fixed plug-in withdrawable Fixing on DIN rail Mechanical life Electrical life (at 415 V) Basic dimensions, fixed [No. operations / hourly operations] [No. operations / hourly operations] L (3/4 poles) D H fixed plug-in withdrawable
(2) For S3X with R32 setting: Icu (690V) = 50 kA and Ics = 100% Icu Icu (500V) = 75 kA and Ics = 100% Icu (3)

F-P EF - FC - FC CuAl - R FC-R DIN EN 50022 25000/240 8000/120 90/120 70 120 1,1/1,5 1,3/1,7 KEY TO VERSIONS F = Fixed P = Plug-in W = Withdrawable

[mm] [mm] [mm] [kg] [kg] [kg]

Weights, 3/4 poles

(1) The value of Ics at 500V and 690V for S3X, S4X and S6X is reduced by 25%

S3X at 690V can only be supplied from above

3/16

GSIS9137

ABB SACE

GSIS9138

SACE Isomax S3X 125-200 3-4 690 8 800 3000 X 300 200 180 150 75 (2)(3) 100% 440 3,5 A

SACE Isomax S4X 250 3-4 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A

GSIS9099

SACE Isomax S6X 400-630 3-4 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A

GSIS9100

F-P-W F - EF - ES - FC - FC CuAl - RC - R EF - R EF - R DIN EN 50023 25000/120 10000(125A)-8000(200A) / 120 105/140 103,5 255 3,6 / 4,8 6,3 / 8,7 7,1 / 9,5
KEY TO TERMINALS F = Front EF = Extended front ES = Extended spreaded front

F-P-W F - EF - ES - FC - FC CuAl - RC - R EF - R EF - R DIN EN 50023 20000/120 800 / 120 105/140 103,5 339 5/7 8,2 / 10,7 9 / 11,5
FC = Front for copper cables FC CuAl = Front for copper or aluminium cables R = Rear threaded

F-W F - EF - ES - FC CuAl - RC - R EF - HR - VR 20000/120 7000(630A)-5000(800A)/60 210/280 103,5 268 9,5 / 12 12,1 / 15,1
RC = Rear for copper or aluminium cables HR = Rear horizontal flat bar VR = Rear vertical flat bar

ABB SACE

3/17

SACE Isomax S current-limiting circuit-breakers


General characteristics
SACE Isomax S2X 100 - S3X - S4X - S6X current-limiting circuit-breakers
These pieces of apparatus are characterised by a rated voltage Ue of 690 V AC, by rated uninterrupted currents from 100 A to 630 A, by service currents from 1 to 630 A and by an ultimate short-circuit breaking capacity up to 200 kA at 380/415 V AC and 75 kA at 690 V AC. The circuit-breakers, which comply with IEC 60947-2 Standards, are available in the three- and four-pole type (only three-pole for S2X 100) in the fixed, plug-in and withdrawable versions. The function carried out by the current-limiting circuit-breakers is to limit the specific let-through energy to a maximum in the case of short-circuit, safeguarding the integrity of the circuits and of the apparatus located on the load side. The breaking system used, which foresees double interruption per pole, allows very
GSIS9028

high value short-circuits to be interrupted extremely rapidly. Moreover, the special shape of the interruptive parts allows the peak values of fault currents to be limited to figures considerably lower than those of the short-circuit current present at the point of installation. For the circuit-breakers on the load side, the rapidity of opening notably reduces exposure to the electrodynamic stresses which occur in the case of a fault.

Integration with the SACE Isomax S family


The range of current-limiting circuitbreakers has been conceived as a product aimed at particularly severe requirements, but comes within the sphere of the general SACE Isomax S project in any case. The user gains considerable advantages because it means being able to optimise stocks, standardise support and installation structures and rationalise circuit-breaker selection thanks to application flexibility which allows all low voltage application requirements to be covered. In the SACE Isomax S series, the current-limiting circuit-breakers offer the same benefits of modular construction. All the other versions can be made from the basic version of the current-limiting circuit-breaker by means of special conversion kits. For S3X, S4X and S6X, conversion from the fixed circuit-breaker into the moving part of plug-in or withdrawable circuit-breaker is carried out by means of special kits listed under the chapter entitled Ordering codes (for S2X 100, the kit is the same as the corresponding S2 B/N/S one). The fixed parts of current-limiting plugin or withdrawable version circuit-breakers can, on the other hand, be used either for the current-limiting circuit-breakers themselves or for the corresponding SACE S2 - S3 - S4 and S6 automatic circuit-breakers.

With regard to accessories, too, the S2X 100, S3X, S4X and S6X current-limiting circuit-breakers use the same accessoGSIS9029 GSIS9114

ries provided for the corresponding automatic circuit-breakers and also keep the same electrical characteristics.

SACE Limitor LN A 32-63-100 LN 100 / LN 125 LN 160 / LN 200 LN 320 (setting 250 A) LN 320 LN 500 / LN 630 3/18

SACE Isomax S S2X 100 S3X 125 S3X 200 S4X 250 S6X 400 S6X 630
The electrical characteristics of the SACE Isomax S currentlimiting circuit-breakers allow a comparison with the circuitbreakers in the previous SACE Limitor series to be established, to determine any replacements in the case of installation upgrading.

ABB SACE

Only the following are an exception: the mechanical interlocking plate for two superimposed circuit-breakers the bracket for fixing onto DIN rail (for S3X and S4X) The wiring diagrams are those of the corresponding SACE S2, S3, S4 and S6 circuit-breakers. Apart from S2X 100 which are identical to the corresponding S2 B/N/S, of the circuit-breakers, the S3X, S4X and S6X current-limiting circuit-breakers keep the standardised depth of 103.5 mm, standardised widths of 105 mm (S3XS4X) / 210mm (S6X) for the three-pole versions and 140 mm (S3X-S4X) /

Applications
The current-limiting circuit-breakers are suitable for installation in all types of civil, industrial and service sector plants, as well as in electrical installations on board ships, in mines, on offshore oil rigs and, generally, wherever very high short-circuit currents can occur due to the high powers of the generators and transformers up to 200 kA at 380/415 V AC, 180 kA at 440 V AC and 75kA at 690 V AC. The circuit-breakers can be placed near the power supply source both for general protection (plants, user groups and electrical lines) and for protection of electric machines (motors, generators, transformers, capacitor banks).

They can also be inserted in plants where back-up protection is foreseen, which allows use on the load side of circuit-breakers with breaking capacity lower than the prospective short-circuit current at the point of installation. The breaking capacities of the SACE Isomax S current-limiting circuit-breakers have exceeded the best performances achieved by other apparatus of this type.

280mm (S6X) for the four-pole versions, identical drilled fixing holes for the plugin and withdrawable versions and identical drilled holes for the compartment door in all the versions and for all the accessories.

Limited let-through current

Prospective short-circuit current


The increased contact opening speed, the dynamic blast action produced by the magnetic field and the structure of the arcing chamber contribute to extinguishing the arc in the shortest possible time, limiting the specific
GSIS0084

let-through energy value I t and the peak current.

ABB SACE

3/19

SACE Isomax S current-limiting circuit-breakers


General characteristics
Thermomagnetic overcurrent releases
The table below summarises the size values for the different types of releases:

Ith Im In

rated current of the thermomagnetic release, referred to an ambient temperature of 40 C magnetic trip current rated current of the electronic release

Thermomagnetic overcurrent releases


Circuit-breaker S2X 100 S3X 125 S3X 200 Setting [A] R1 R 1,6 R 2.5 R4 R 6.3 R 10 R 12.5 L1 - L2 - L3 phases Thermal adjustment [A] 0.7 ... 1 x Ith 0.7 ... 1 1.1 ... 1.6 1.75 ... 2.5 2.8 ... 4 4.4 ... 6.3 7 ... 10 8.7 ... 12.5 11 ... 16 14 ... 20 17.5 ... 25 22.5 ... 32 28 ... 40 35 ... 50 44 ... 63 56 ... 80 70 ... 100 87.5 ... 125 112 ... 160 140 ... 200 Magnetic trip [A] Im = 10 x Ith 10 16 25 40 63 100 125 160 200 250 320 (S2X 100) - 500 (S3X) 400 500 630 800 1000 1250 1600 2000 Neutral Setting [A] R 32 (S3X) R 100 (S3X) R 80 (S3X) R 100 (S3X) R 80 R 100 R 125

R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160 R 200

SACE S2X 100 and S3X circuit-breakers, with thermomagnetic overcurrent releases
3/20 ABB SACE

GSIS9057

Electronic overcurrent releases


SACE PR211/P - PR212/P electronic overcurrent releases
Circuit-breaker S4X 250 S6X 400 S6X 630 Release current In [A] 100 160 250 320 400 630
L S I G (1)
= = = = Protection function against overload Protection function against short-circuit with delayed trip Protection function against short-circuit with instantaneous trip Protection function against earth fault with delayed trip

L1 - L2 - L3 phases L I1 [A] 40 ... 100 64 ... 160 100 ... 250 128 ... 320 160 ... 400 252 ... 630 S I2 [A] I I3 [A] G I4 [A] 20 ... 100 32 ... 160 50 ... 250 64 ... 320 80 ... 400 126 ... 630

Neutral [A] 20 ... 50 32 ... 80 50 ... 125 64 ... 160 80 ... 200

Neutral (1) [A] 40 ... 100 64 ... 160 100 ... 250 128 ... 320 160 ... 400

(50% Ith) (100% Ith)

100 ... 1000 150 ... 1200 160 ... 1600 240 ... 1920 250 ... 2500 375 ... 3000 320 ... 3200 480 ... 3840 400 ... 4000 600 ... 4800 630 ... 6300 945 ... 7560

126 ... 315 252 ... 630

Only for PR212/P . Available on request for PR211/P , with additional ordering code 1SDA037505R1.

N.B. For more detailed information about the protection functions, please see page

3/12.

SACE S4X, S6X circuit-breakers, with microprocessorbased overcurrent releases

ABB SACE

GSIS9115

3/21

3/22

ABB SACE

SACE Isomax S circuit-breakers for motor protection

Protection against short-circuit


Magnetic only and electronic circuit-breakers for classical switching coordinations and motor protection of any power 690V 80-1600 A 70-200 kA (380/415 V)

3
Integrated protection
The evolution of motor protection: intelligence on board the circuit-breaker to design protection around the motor, optimising space and time 690V 160-1250 A 35-200 kA (380/415 V)

GSIS9065

3/23

SACE Isomax S circuit-breakers for motor protection (protection against short-circuit)


Electrical characteristics IEC 60947-2 and IEC 60947-4-1

GSIS9139

S2X 80 Rated uninterrupted current, Iu Rated service current, In Poles Rated service voltage, Ue (AC) 50-60Hz Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 220/230 V (AC) 50-60 Hz 380/415 V (AC) 50-60 Hz 440 V [A] [A] Nr. [V] [kV] [V] [V] [kA] [kA] [kA] [kA] [kA] [%Icu] [kA] [ms] 80 180 3 690 6 690 3000 X 100 70 70 50 10 75% 154 3,5 A N 65 35 (1) 30 25 14 100% 74 8

GSIS9135

S3 160 / 250 3160 / 160200 3 690 8 800 3000 H 100 65 50 40 18 75% 143 7 A L 170 85 65 50 20 75% 187 6

S3X 125 / 200 3 125 / 125200 3 690 8 800 3000 X 300 200 180 150 75 (3) 100% 440 3,5 A

(AC) 50-60 Hz 500 V (AC) 50-60 Hz 690 V Rated service short-circuit breaking capacity, Ics (2) Rated short-circuit making capacity (415 V) Opening time (415V at Icu) Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2 Releases: magnetic only, fixed 13xIn magnetic only, adjustable 412xIn

F-P EF - FC FC CuAl - R FC - R DIN EN 50022 F-P-W F - EF - ES - FC FC CuAl - RC - R EF - FC - R EF - FC - R DIN EN 50023 25000/120 105 103,5 170 2,6 3,1 3,5
KEY TO VERSIONS F = Fixed P = Plug-in W = Withdrawable

F-P-W F - EF - ES - FC FC CuAl - R - RC EF - R EF - R DIN EN 50023 25000/120 105 103,5 255 3,6 6,3 7,1

microprocessor-based, PR211/P (I) Interchangeability Versions Terminals fixed plug-in withdrawable Fixing on DIN rail Mechanical life Basic dimensions fixed, 3 poles [No. operations / hourly operations] L [mm] D [mm] H [mm] Weights fixed, 3 poles plug-in, 3 poles withdrawable, 3 poles
(1) All the versions with Icu=35kA are certified at 36kA

25000/240 90 70 120 1,1 1,3 -

[kg] [kg] [kg]

(2) For S3N/H/L, S4N/H/L, S5N/H, and S6N/H circuit-breakers, the percentage performance of Ics at 690V is reduced by 25% (3) S3X at 690V can only be supplied from above

3/24

ABB SACE

GSIS9138

GSIS9101

GSIS9102

GSIS9103

GSIS9104

S4 160 / 250 100, 160 / 250 3 690 8 800 3000 N 65 35 (1) 30 25 18 100% 74 8 H 100 65 50 40 22 100% 143 7 A L 200 100 80 65 30 75% 220 6

S4X 250 100, 160, 250 3 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A N 65 35 (1) 30 25 20 100% 74

S5 400 / 630 320, 400 / 630 3 690 8 800 3000 H 100 65 50 40 25 100% 143 L 200 100 80 65 30 75% 220 N 65 35 (1) 30 25 20 100% 74 10 S 85 50 45 35 22 100% 105 9

S6 630 / 800 630 / 800 3 690 8 800 3000 H 100 65 50 40 25 100% 143 8 B L 200 100 80 65 30 75% 220 7

S6X 400 / 630 320, 400 / 630 3 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A S 85 50 40 35 20 100% 105 22

GSIS9105

S7 1250 / 1600 1000, 1250 / 1600 3 690 8 800 3000 H 100 65 55 45 25 75% 143 22 B L 200 100 80 70 35 50% 220 22

GSIS9106

8 7 6 B(400A) / A(630A)

F-P-W F - EF - ES - FC FC CuAl - R - RC EF - FC - R EF - FC - R DIN EN 50023 20000/120 105 103,5 254 4 4,5 4,9
KEY TO TERMINALS F = Front EF = Extended front ES = Extended spreaded front

F -P - W F - EF - ES - FC FC CuAl - R - RC EF - R EF - R DIN EN 50023 20000/120 105 103,5 339 5 8,2 9

F - P(400A) - W F - EF - ES - FC FC CuAl - R - RC(400A) EF - FC - R EF - FC - R - VR (630A) DIN EN 50023 20000/120 140 103,5 254 5 6,1 6,4

F-W F - EF - ES FC CuAl - R - RC EF - HR - VR 20000/120 210 103,5 268 9,5 12,1


RC = Rear for copper or aluminium cables HR = Rear horizontal flat bar VR = Rear vertical flat bar

F-W F - EF - ES FC CuAl - R - RC EF - VR - HR 20000/120 210 103,5 406 15 25,4

F-W F - EF - ES FC CuAl (1250A) - HR - VR EF - VR - HR 10000/120 210 138,5 406 17 21,8

FC = Front for copper cables FC CuAl = Front for copper or aluminium cables R = Rear threaded

ABB SACE

3/25

SACE Isomax S circuit-breakers for motor protection (protection against short-circuit)


General characteristics IEC 60947-2 and IEC 60947-4-1
Magnetic and electronic overcurrent releases
Three-phase asynchronous motor starting, switching and protection are essential operations for its correct use. The traditional system used for this purpose has three different devices: a circuit-breaker for protection against short-circuit, a thermal relay for protection against overload and lack of or unbalanced phase, and a counter for the motor operations. Everything must necessarily take into account the problems which arise on start-up. In particular, different factors must be taken into account when selecting these devices, such as: the motor power the starting diagram the type of motor: with cage rotor or with wound rotor the fault current at the point of motor installation in the network. ABB SACE proposes a wide range of circuit-breakers, which by implementing the protection against short-circuit exclusively, are suitable for use inside protected starters of traditional type. The new SACE S2X 80, with fixed magnetic protection at 13 times the rated service current, is an extremely compact circuit-breaker, which stands out for its exceptional performances in terms of breaking capacity and limitation of the specific letthrough energy. Extremely simple and rapid to install, it has the same possibility of mounting accessories and personalisation as the S2B/N/S circuit-breakers. It can be used in a vast range of start-ups, from 0.37kW to 37kW and from 400V-50kA up to 690V-50kA. SACE S3 N/H/L 160/250 circuit-breakers and the S3X 125/200 current-limiting circuit-breaker are fitted with a magnetic only release adjustable from 4 to 12 times the rated service current. They cover coordinations from 37 to 132kW and allow optimal motor protection thanks to their great flexibility due to the wide setting range of the magnetic threshold. Finally, SACE S4 160/250, S5 400/630, S6 630/800, and S7 1250/1600, with different N-S-H-L breaking capacity levels, like the current-limiting S4X and S6X, can be fitted with the

3
Magnetic only fixed overcurrent releases
SACE Isomax S2X 80 Phases L1 - L2 - L3 Setting [A] R1 R1.6 R2 R2.5 R3.2 R4 R5 R6.5 R8.8 R11 R12.5 R16 R20 R25 R32 R42 R52 R63 R80 Magnetic trip Im = 13 x In [A] 13 21 26 32 42 52 65 84 110 145 163 210
GSIS9116

Circuit-breaker with magnetic release

Contactor

Thermal relay

Motor

260 325 415 545 680 820 1040

3/26

ABB SACE

PR211/P (I) electronic microprocessor-based release. Above all, they are used for protection of high power motors and, thanks to adjustment of the protection against short-circuit from 1.5 to 12 times, allow the optimum trip value to be selected for any type of motor.

Magnetic only adjustable overcurrent releases


Circuit-breaker S3N 160 S3H 160 S3L 160 S3N 250 S3H 250 S3L 250 S3X 125 S3X 200 Setting [A] R3 R5 R 10 (*) R 25 R 50 R 100 R 125 R 160 R 160 R 200
(*) Only to be used in coordination with contactors

Phases L1 - L2 - L3 Magnetic adjustment [A] Im = 4 ... 12 x Ith 12 ... 36 20 ... 60 40 ... 120 100 ... 300 200 ... 600 400 ... 1200 500 ... 1500 640 ... 1600 (10 x Ith) 640 ... 1920 800 ... 2400

GSIS9141

SACE PR211/P (I) electronic microprocessor-based overcurrent releases for motor protection
Circuit-breaker S4N 160 S4H 160 S4L 160 S4N 250 S4H 250 S4L 250 S5N 400 S5H 400 S5L 400 S6N 630 S6H 630 S6L 630 S6N 800 S6H 800 S6L 800 S7S 1250 S7S 1600 S7H 1250 S7H 1600 S7L 1250 S7L 1600 S4X 250 S6X 400 S6X 630 Phases L1 - L2 - L3 Rated current of release In [A] I (*) I3 [A]

100 160 250 320 400 630 800 1000 1250 1600
(*) I = Protection function against short-circuit

150 ... 1200 240 ... 1920 375 ... 3000 480 ... 3840 600 ... 4800 945 ... 7560 1200 ... 9600 1500 ... 12000 1875 ... 15000 2400 ... 19200

ABB SACE

3/27

SACE Isomax S circuit-breakers for motor protection (integrated protection)


Electrical characteristics IEC 60947-2 and IEC 60947-4

S4 Rated uninterrupted current, Iu Rated service current, In Poles Rated service voltage, Ue (AC) 50-60Hz Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 220/230 V (AC) 50-60 Hz 380/415 V (AC) 50-60 Hz 440 V [A] [A] Nr. [V] [kV] [V] [V] [kA] [kA] [kA] [kA] [kA] [%Icu] [kA] [ms] N 65 35 (1) 30 25 18 100% 74 8 160 / 250 100, 160 / 200 3 690 8 800 3000 H 100 65 50 40 22 100% 143 7 A L 200 100 80 65 30 75% 220 6

(AC) 50-60 Hz 500 V (AC) 50-60 Hz 690 V Rated service short-circuit breaking capacity, Ics (2) Rated short-circuit making capacity (415 V) Opening time (415V at Icu) Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2, IEC 60947-4-1, EN 60947-4-1 PR212/MP (LRIU) microprocessor-based releases Interchangeability Versions Terminals fixed plug-in withdrawable Fixing on DIN rail DIN EN 50023 Mechanical life Basic dimensions, fixed 3 poles

F-P-W F - EF - ES - FC FC CuAl - R - RC EF - FC - R EF - FC - R [No. operations / hourly operations] L [mm] D [mm] H [mm] 20000/120 105 103,5 254 4 4,5 4,9

Weights

fixed, 3 poles plug-in, 3 poles withdrawable, 3 poles

[kg] [kg] [kg]


KEY TO VERSIONS F = Fixed P = Plug-in W = Withdrawable

(1) All the versions with Icu=35kA are certified at 36kA (2) For S4N/H/L, S5N/H, and S6N/H circuit-breakers the percentage performance of Ics at 500V and 690V is reduced by 25%

3/28

ABB SACE

GSIS9107

GSIS9108

GSIS9109

S4X 250 100, 160, 200 3 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A N 65 35(1) 30 25 20 100% 74 8

S5 400 320 3 690 8 800 3000 H 100 65 50 40 25 100% 143 7 B L 200 100 80 65 30 75% 220 6 N 65 35(1) 30 25 20 100% 74 9

S6 630 630 3 690 8 800 3000 H 100 65 50 40 25 100% 143 8 B L 200 100 80 65 30 75% 220 7

GSIS9110

S6X 400 / 630 320, 400 / 630 3 690 8 800 3000 X 300 200 180 150 75 100% 440 3,5 A S 85 50 40 35 20 100% 105 22

GSIS9111

S7 1250 1000 3 690 8 800 3000 H 100 65 55 45 25 75% 143 22 B

GSIS9112

F-P-W F - EF - ES - FC FC CuAl - R RC EF - R EF - R 20000/120 105 103,5 339 5 8,2 9


KEY TO TERMINALS F = Front EF = Extended front ES = Extended spreaded front

F-P-W F - EF - ES - FC FC CuAl - R - RC EF - FC - R EF - FC - R 20000/120 140 103,5 254 5 6,1 6,4


FC = Front for copper cables

F-W F - EF - ES FC CuAl - R - RC EF - HR - VR 20000/120 210 103,5 268 9,5 12,1

F-W F - EF FC CuAl - R - RC EF - VR - HR 20000/120 210 103,5 406 15 25,4

F-W F - EF - ES FC CuAl - HR - V EF - VR - HR 10000/120 210 138,5 406 17 21,8

RC = Rear for copper or aluminium cables HR = Rear horizontal flat bar VR = Rear vertical flat bar

FC CuAl = Front for copper or aluminium cables R = Rear threaded

ABB SACE

3/29

SACE Isomax S circuit-breakers for motor protection (integrated protection)


General characteristics
SACE PR212/MP electronic microprocessor-based releases
SACE Isomax S4N-H-L 160/250, S5N-H-L 400, S6N-H-L 800, S7S-H 1250 and S4X 250, S6X 400/630 circuit-breakers are fitted with SACE PR212/MP electronic releases constructed using microprocessor-based electronic technology. This allows functions to be obtained which guarantee high trip precision, utmost reliability and insensitivity to variations in the external temperature. The SACE PR212/MP electronic release guarantees complete motor protection as is fully integrated on board the circuit-breaker; moreover, it is able to control contactor opening in the case of a fault (except for short-circuit), by means of the SACE PR212/CI contactor accessory operating mechanism unit. Furthermore, the PR010/T unit for testing the release and checking the protection functions, the PR010/K signalling unit and the PR212/D dialogue unit are available. The electronic microprocessor-based releases are self-supplied and consist of three current transformers, the SACE PR212/MP protection unit and an opening solenoid which acts directly on the circuit-breaker operating mechanism unit. The current transformers housed inside the release box, supply the energy and the signal required for correct operation of the Motor Contactor Circuit-breaker with SACE PR212/MP electronic microprocessor-based release

protection. The release is temperature-compensated and sensitive to lack of phase according to T able IV of the 60947-4-1 7.2.1.5.2 Standard.

SACE PR212/MP electronic microprocessor-based releases for motor protection


Circuit-breaker S4N 160 S4H 160 S4L 160 S4N 250 S4H 250 S4L 250 S5N 400 S5H 400 S5L 400 S6N 800 S6H 800 S6L 800 S7S 1250 S7H 1250 S4X 250 S6X 400 S6X 630 Release rated current In [A] Phases L1 - L2 - L3 L I1 [A] R I5 [A] I I3 [A] U Iu [A]

100 160 200 320 400 630 1000


L
R I U

40 ... 100 64 ... 160 80 ... 200


3 ... 10 x I1

600 ... 1300 960 ... 2080 1200 ... 2600 1920 ... 4160 2400 ... 5200 3780 ... 8190 6000 ... 13000
0,4 x I1

128 ... 320 160 ... 400 252 ... 630 400 ... 1000

= = = =

Protection function against overload with relative setting current (I1 = 0.4 ... 1 x In, with 0.01 steps - Class = 10A, 10, 20, 30) Protection function against rotor block with relative setting current and time (I5 = 3-4-5-6-7-8-10 x I1 - t5 = 1-4-7-10 s) Protection function against short-circuit with relative setting current (I3 = 6-7-8-9-10-11-12-13 x In) Protection function against lack of or unbalance of phase with relative setting current and time (Iu = 0.4 x I1 - t = 4 s)

3/30

ABB SACE

The SACE Isomax S range of mouldedcase circuit-breakers for motor protection is perfectly coordinated with the new ABB line of contactors. The latter, defined as A-Line, together with the line of overload thermal relays and SACE Isomax S moulded-case circuit-breakers, is the basis for the new generation of apparatus specially designed to guarantee a system of products which can be integrated according to the applications required. All this is done with the aim of not only continuously improving the products, but above all to provide designers, installers and end users with the best solutions in terms of performance and reliability, combined with simplicity of the system. In particular, SACE Isomax S circuitbreakers and the A series of contactors are an extraordinary solution in terms of compactness, since they share the same width and design characteristics,

thereby saving space, assembly material, installation time and relative cabling operations. The circuit-breaker-contactor group enhances this characteristic even further with the SACE PR212/MP electronic overcurrent release, which allows construction of an extremely compact protected starter, implementing protection against overload in accordance with the IEC 60947-4-1 Standard.

SACE Isomax S moulded-case circuit-breakers and the new A series contactors share the same width and depth and have been designed to construct a single compact unit

3
GSIS9061

Typical operating characteristic of an asynchronous motor


l1 l3 I5 t5 I6 t6 le la Ip ta tp m c = = = = = = = = = = = = = trip current function L trip current function I trip current function R trip time function R trip current function U trip time function U rated service current of the motor starting current of the motor peak value of the subtransient starting current motor starting time duration of the starting subtransient phase typical motor starting curve example of trip curve of a motor protection circuit-breaker with electronic release

The different curves of the functions, with numerous threshold and time settings, allow an overall trip curve to be drawn which is really close to the

GSIS0082

motor starting curve, thereby optimising its protection

ABB SACE

3/31

SACE Isomax S circuit-breakers for motor protection (integrated protection)


General characteristics
Protection functions and parametrisation of the SACE PR212/MP release
Function L Protection against overload
Function L protects the motor against undesired overloads according to the indications and classes defined in the IEC 60947-4-1 Standards. Protection is based on a pre-established thermal model (ABB SACE International Patent) which, by simulating the copper and iron overtemperatures inside the motor, allows precise safeguarding of the machine. The protection intervenes when the preset

Parametrisation of protection L
l1 = 0,4 ... 1 x In with 0.01 x In steps where l1 is the rated service current of the circuit-breaker, which must be the same or higher than that of the motor to be protected (I1 > Ie), and In is the rated current of the current transformers. t1 = 4 - 8 - 16 - 24 s where t1 is the trip at 7.2 x I1 cold, depending on the class selected Class 10A - 10 - 20 - 30 are the motor starting classes which determine the trip times for overload according to the IEC 60947-4-1 4.7.3 Table II Standards. Release of the contactor: in normal operating mode Tolerances: in accordance with the IEC 60947-4-1 Standard.

overtemperature is reached. The trip time is fixed by selecting the trip class defined in the above-mentioned Standards. The function is temperature-compensated and sensitive to phase missing/unbalance in accordance with the IEC 60947-4-1 Standard. In the case of auxiliary power supply, the thermal memory function is guaranteed, which allows the release to continue calculating the motor temperature even after an opening operation.

Function R Protection against rotor block

Parametrisation of protection R
l5 = OFF - 3 - 4 - 5 - 6 - 7- 8 - 10 x l1 where l5 is the current at which the rotor is considered to be blocked and l1 is the rated service current of the circuit-breaker selected for function L. t5 = 1 - 4 - 7 - 10 s where t5 is the preset time threshold above which the release trips. Release of the contactor: in normal operating mode Tolerances:
10% 20%

Function R protects the motor against any rotor block during operation. This protection is automatically disabled for the whole of the motor starting phase and is then re-activated. The protection already provides its function from low current increases (from 3 times the l1 service current of the circuit-breaker) and can also be disabled. Both the current level to be tripped and the trip time delay can be selected. The protection intervenes when at least one of the phase currents exceeds the preset value and remains above that threshold for the set t5 time.

of the trip thresholds of the trip times

Function I Protection against short-circuit


This protection function intervenes in the case of a short-circuit between phases. It is sufficient for a single phase to exceed the set threshold to cause immediate opening of the circuit-breaker (the protection cannot be excluded). The trip current can be adjusted up to 13 times the rated current of the release, whereas the time is fixed. To prevent unwarranted trips during starting, the protection recognises whether the motor to be protected is in the starting phase or whether there is a short-circuit. This is to allow starting under completely safe conditions.

Parametrisation of protection I
l3 = 6 - 7 - 8 - 9 - 10 - 11 - 12 - 13 x In where I3 is the instantaneous trip current for short-circuit and In is the rated current of the current transformers. To prevent unwarranted trips during the inrush phase of the motor, instantaneous tripping of protection I takes place at 1.5 x I3 (for I3 < 9 x In), whereas for higher values (I3 > 9 x In) tripping takes place at 13.5 x In. Tolerances: 20% of the trip thresholds 20% of the trip times

Function U Protection against lack of and/or unbalance of a phase


Function U can be used in those cases where particularly precise control is needed regarding lack of and/or unbalance of phase currents. This function can be excluded and intervenes if the effective value of one or two currents drops below the level of 0.4 of the l1 current set with function L and remains there for more than 4 seconds.

Parametrisation of protection U
On, (with I6 = 0.4 x l1 and t6 = 4 s). Off, in the Off position, the release remains sensitive to the lack of phase according to the IEC 60947-4-1 Standard, modifying the trip curves for protection L. Release of the contactor: in normal operating mode Tolerances: 20% of the trip thresholds 20% of the trip times

3/32

ABB SACE

Parametrisation of the release


By means of the microswitch located on the front, the release can be fitted for parametrisation: Man. (manual), thresholds and times are adjusted by using the microswitches on the front of the relay Elt. (electronic), thresholds and times are adjusted remotely by means of the SACE PR212/D dialogue unit.

Operating methods
Normal mode: in the case of a fault detected by functions L-R-U, contactor opening can be controlled by means of the accessory SACE PR212/CI module or directly, without the need for external modules, with an ABB contactor fitted with an electronic interface with the circuit-breaker. Heavy duty mode: the circuit-breaker opens for any type of L-R-I-U fault.

Back-up protection
The electronic release verifies whether the circuit-breaker or the contactor is effectively in the open or relay tripped position following an opening command. If this is not so, after a delay set to long or short time, the command for circuit-breaker opening is given again.

Protection L
against motor overload luminous signalling of overload: fixed for I > 0.9 x I1; flashing for I > 1.05 x I1

Protection R
against blocked rotor

Protection I
against instantaneous short-circuit

Protection U
against the lack and/or unbalance of a phase

Man. / Elt.
release parametrisation methods socket for connection of SACE PR010/T Test unit

Class
class of motor starting according to the IEC 60947-4-1 Standards socket for selection between: SACE TT1 - PTC (*) temperature Test unit sensor input - 0/1 generic input setting the back-up time setting the Reset following a trip: - manual - automatic setting the work methods

(*) A special input is available to connect a PTC temperature probe, inserted in the motor to be protected

Characteristics of the SACE PR212/MP electronic microprocessor-based release


Overloading capacity Operating temperature Maximum relative humidity percentage Rated service frequency Current measurement methods 2 x In continuously, 7.2 x In for 35 s at 45 C 25 C ... + 70 C 90% without condensation 45 - 66 Hz, able to measure harmonics up to 550 Hz r.m.s. up to 3 x In (functions L, R, U) peak value for values over 3 x In (functions L, R, U) peak value for function I Electromagnetic compatibility Electrostatic discharges Radiated electromagnetic field Short-time transients Mean time between failure (MTBF) According to: IEC 60947-2 Standard Annex F According to: IEC 61000-4-2 Standard According to: IEC 61000-4-3 Standard According to: IEC 61000-4-4 Standard 15 years (at 45 C)

ABB SACE

GSIS9053

3/33

3/34

ABB SACE

SACE Isomax S circuit-breakers for applications up to 1000V

Taking the SACE Isomax S limits higher and higher 1000 V 160-800 A 6-50 kA

GSIS9066

3/35

SACE Isomax S circuit-breakers for applications up to 1000V


Electrical and general characteristics IEC 60947-2
Within the panorama of Isomax proposals, there is also the range of circuitbreakers and switch-disconnectors for direct current and alternating current applications up to 1000V. The typical application sectors are installations in mines, road or railway tunnels, traction and industrial applications in general. The circuit-breakers for direct current (connection diagrams on page 5/47) are available in the four-pole version, whereas those for alternating current are available in the three-pole version, with adjustable or electronic thermomagnetic releases and have the same dimensions as the standard versions. They can also be combined with all the accessories available for the Isomax series.

Range at 1000 V in a.c.


Rated uninterrupted current, Iu Poles Rated service voltage, Ue (AC) 50-60Hz Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated ultimate short-circuit breaking capacity, Icu (AC) 50-60 Hz 1000 V Rated short-circuit making capacity Opening time Rated short-time withstand current for 1 s, Icw Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2

~ V V~
[A] Nr. [V] [kV] [V] [kA] [kA] [ms] [kA]

S3 160 3 1000 8 1000 3000 L 6 9,2 20 A

Thermomagnetic releases T adjustable, M fixed 10 Ith PR211/P (LI only) microprocessor-based releases PR212/P (LSI-LSIG) microprocessor-based releases Versions Terminals Fixing on DIN rail F F DIN EN 50023 [No. operations / hourly operations] L [mm] D [mm] H [mm] Weights [kg] 25000/120 105 103,5 170 2,6

Mechanical life Dimensions

Range at 1000 V in d.c.


Rated uninterrupted current, Iu Poles Rated service voltage, Ue Rated impulse withstand voltage, Uimp

V V
[A] Nr. [V ] [kV] [V] [kA] [kA] [ms] [kA]

S3 160-250 4 1000 8 1000 3000 L 40 40 25 A

S5 400 4 1000 8 1000 3000 L 40 40 35 5 B

S6 630 4 1000 8 1000 3000 L 40 40 45 7,6 B

S6 800 4 1000 8 1000 3000 L 50 50 50 10 B

Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Ultimate rated short-circuit breaking capacity, Icu (4 poles in series) Rated short-circuit making capacity Opening time Rated short-time withstand current for 1 s, Icw Utilisation category (EN 60947-2) Isolation behaviour IEC 60947-2, EN 60947-2 Thermomagnetic releases, T adjustable - M fixed 10 Ith Thermomagnetic releases, T adjustable - M adjustable Versions Terminals Fixing on DIN rail Mechanical life Basic dimensions, fixed

F F F F DIN EN 50023 20000/120 184 103,5 254 7

F F 20000/120 280 103,5 268 12

F F 20000/120 280 103,5 268 12

[No. operations / hourly operations] L [mm] D [mm] H [mm] [kg]

DIN EN 50023 25000/120 140 103,5 170 3,5

Weights, fixed

3/36

ABB SACE

S3X 125 3 1000 8 1000 3000 X 30 63 10 A

S4 160-250 3 1000 8 1000 3000 L 8 13,6 30 A

S4X 250 3 1000 8 1000 3000 X 30 63 20 A

S5 400 3 1000 8 1000 3000 L 8 13,6 30 5 B

S6 630-800 3 1000 8 1000 3000 L 12 24 30 7,6 (630A)-10 (800A) B

S6X 630 3 1000 8 1000 3000 X 30 63 25 A

F F DIN EN 50023 25000/120 105 103,5 255 3,6

F F DIN EN 50023 20000/120 105 103,5 254 4

F F DIN EN 50023 20000/120 105 103,5 254 4

F F DIN EN 50023 20000/120 140 103,5 254 5

F F 20000/120 210 103,5 268 9,5

F F 20000/120 210 103,5 406 15

Circuit-breakers with electronic release for alternating current


In100 S4L 160 S4L 250 S4X 250 S5L 400 S6L 630 S6X 630 S6L 800 Im = 1,5 12 x In [A] In250 In400 In630 In800


1501200


600 ... 4800


3753000


12009600

9457560

Circuit-breakers with thermomagnetic release for alternating current


(thermal threshold adjustable from 0.7 to 1 x In; fixed magnetic threshold) R32 S3L 160 S3X 125 Im AC (10xIn) [A] 500 500 800 1000 1250

R50

R80

R100

R125

R160

R200

R250

1600

2000

2500

Circuit-breakers with thermomagnetic release for direct current


R32 (1) S3L 160 S3L 250 S5L 400 S6L 630 S6L 800 Im DC (10xIn) [A] Im DC (5-10xIn) [A]
(1) Thermal threshold adjustable from 0.7 and 1 x In; fixed magnetic threshold (2) Thermal threshold adjustable from 0.7 and 1 x In; magnetic threshold adjustable between 5 and 10 x In.

R50 (1)

R80 (1)

R100 (1)

R125 (1)

R160 (1)

R200 (1)

R250 (1)

R400 (2)

R630 (2)

R800 (2)


500


500


800


1000


1250


1600


2000


2500

2000-4000 3150-6300 4000-8000

ABB SACE

3/37

3/38

ABB SACE

SACE Isomax S switch-disconnectors

Close, carry and isolate. The certainty of operating in complete safety. 690 V 125-3200 A 3,1-85 KA (Icm) 2,2-40 kA (Icw)

GSIS9067

3/39

SACE Isomax S switch-disconnectors


Electrical and general characteristics IEC 60947-3

S2D Conventional thermal current at 60 C, Ith Number of poles Rated service voltage, Ue (AC) 50-60Hz (DC) [A] Nr. [V~] [V] [A] [kV] [V] [V] [kA] [kA] 125 / 160 3/4 690 500 125-160 6 690 3000 3,1 2,2

GSIS9142

S3D 100 / 160 / 250 / 320 3/4 690 750 100-160-250-320 8 800 3000 10 6,5

Rated current, Iu Rated impulse withstand voltage, Uimp Rated insulation voltage, Ui Test voltage at industrial frequency for 1 min. Rated short-circuit making capacity (415 V~), Icm Rated short-time withstand current for 1 s, Icw Isolation behaviour IEC 60947-3

Versions Terminals

fixed plug-in

F-P EF - FC - FC CuAl R - RC FC - R 25000/240 90/120 70 120 1,1/1,5

F-P-W F - EF - FC FC CuAl - R - RC F - FC - R F - FC - R 25000/120 105/140 103,5 170 2,6/3,5

Mechanical life

withdrawable [No. of operations / hourly operations] L (3/4 poles) D H 3/4 poles [mm] [mm] [mm] [kg]

Basic dimensions, fixed

Weights, fixed

Coordination with the circuit-breakers (kA at 380-415 V AC)


LOAD SIDE S2D 125 S1B S1N S2B S2N S2S S3N SUPPLY SIDE S3H S5N S5H S6N S6S S6H S7S S7H S8H S8V 16 25 16 35 50 16 35 50 S2D 160 S3D 100 16 25 16 35 50 35 65 16 35 50 35 65 35 65 35 65 35 35 35 50 65 35 35 35 50 65 35 35 35 50 65 50 65 S3D 160 S3D 250 S3D 320 S6D 400 S6D 630 S6D 800 S7D 1000

3/40

ABB SACE

GSIS9143

GSIS9144

GSIS9145

S6D 400 / 630 / 800 3/4 690 750 400-630-800 8 800 3000 30 15

S7D 1000 / 1250 / 1600 3/4 690 750 1000-1250-1600 8 800 3000 52,5 25

S8D 2000 / 2500 / 3200 3/4 690 750 2000-2500-3200 8 800 3000 85 40

GSIS9146

The switch-disconnectors derive from the corresponding circuit-breakers, of which they keep the same overall dimensions, versions, fixing systems and possibility of mounting accessories. They are characterised by a rated voltage of 690 V in alternating current and 750 V in direct current.

Applications
They can be used as general circuit-breakers in sub-switchboards, as switching and isolating parts for lines, busbars or groups of apparatus, or as bus-ties. They can be part of general isolation devices of groups of machines or units for motor switching and protection.

F-W F - EF - FC CuAl R - RC F - HR - VR 20000/120 210/280 103,5 268 9,5/12

F-W F - EF - FC CuAl (1250A) HR - VR F - HR - VR 10000/120 210/280 138,5 406 17/22

F EF (2500A)-R 10000/20 406/556 242 400 57/76

Isolation
The main function carried out by these circuit-breakers consists of isolating the circuit they are inserted in. Once open, the contacts are at a sufficient distance to prevent an arc striking, in accordance with the standard prescriptions relative to isolation behaviour. The position of the operating lever corresponds with certainty to that of the contacts (positive operation).

S7D 1250

S7D 1600

S8D 2000

S8D 2500

S8D 3200

Protection
Each switch-disconnector must be protected on the supply side by a coordinated device which safeguards it against shortcircuits. The coordination table at the side shows the SACE Isomax S circuit-breaker which can carry out the protection function for each switch-disconnector. These are always pieces of apparatus of a size corresponding to or lower than that of the switch-disconnector.

Making capacity
The making capacity, Icm, is of considerable importance, since a switch-disconnector must be able to withstand the dynamic, thermal and current stresses that can occur during closing without being destroyed, up to and including closing under short-circuit conditions.
50 65 50 65 85 120 85 120 85 120

Endurance in the closed position


This identifies the capacity for maintaining the closed position for short-time overcurrents. It is an important parameter which qualifies the performances of these pieces of apparatus.
3/41

ABB SACE

3/42

ABB SACE

SACE Isomax S circuit-breakers according to UL489 and CSA C22.2 Standards

SACE Isomax S quality to conquer New worlds 480/600 V 100-2500 A 25-100 kA (480V)

GSIS9068

3/43

SACE Isomax S circuit-breakers according to UL489 and CSA C22.2 Standards


Electrical and general characteristics
Circuit-breaker type Maximum frame continuous current 40 C Number of poles Rated operational voltage (AC) 50-60 Hz (DC) Test voltage (1min.) 50-60 Hz UL/CSA short-circuit interrupting capacity 240 V AC 480 V AC [A] Nr. [V] [V] [V] [kA rms] [kA rms] [kA rms] S1 100 3 277/480 3000 N 50 14 (R15) 20 (R20-R100) N 65 25 14 35 20 S3 150 150 2-3 600 600 3000 H 100 50 14 50 35 L 150 65 (R15, R30) 85 25 65 50 B 150 50 N 65 25 20 S3 225 225 2-3 240 (B); 480 (N/H/L) 500 3000 H 100 50 35 L 150 65 50 -

600 V AC [kA rms] 500 V DC (2 poles in series)[kA rms] 600 V DC (3 poles in series) [kA rms] Overcurrent trip relays Thermal-magnetic Microprocessor based Interchangeability Dimensions H fixed version W D [in/mm] [in/mm] [in/mm] [op./ frequency] [lbs.]

4,72 / 120 3,07 / 78 2,75 / 70 25000 / 240 2,42

6,70 / 170 4,13 / 105 4,07 / 103,5 25000 / 120 6,75

6,70 / 170 4,13 / 105 4,07 / 103,5 25000 /120 6,75

Mechanical duration Weights (fixed - 3P)

In the field of moulded-case circuit-breakers, complying with the UL489 and CSA22.2 standards, the SACE Isomax S offer is enriched by the following ranges: circuit-breakers for power distribution (fitted with thermomagnetic or electronic releases) circuit-breakers with magnetic only releases for motor protection (Motor Control Protection MCP) switch-disconnectors for use as isolators or switching devices for lines, busbars or parts of a plant circuit-breakers (Moulded Case Switch MCS). The SACE Isomax S offer in compliance with UL/CSA Standards is completed with the introduction of three new sizes. There are therefore increasing possibilities for those customers who also operate on markets subject to the standards defined in the UL/CSA Standards, with a whole range of moulded-case circuit-breakers available, with rated currents which go from 100A to 2500A and breaking capacities, at 480 V AC, which can reach 100kA. Apart from lowering the range of rated currents, introduction of

the S1 size allows all those applications typical of power subdistribution where a circuit-breaker characterised by limited dimensions, but guaranteeing great versatility of application of accessories and installation, is particularly convenient. They further increase the possibility of selection, thanks to the introduction of the new rating for S3, Iu=225A, with three levels of breaking capacity (N/H/L), up to service voltage values of Ue=480V AC and 500 V DC. Finally, the S8 circuit-breaker according to the UL/CSA Standard also allows completion towards higher rated currents. Isomax S8V 1600, 2000 and 2500 are suited to installation immediately to the load side of power supply sources of low voltage systems and can operate safely under the most severe service conditions required by modern installations. Their high performances, great flexibility in mounting accessories, simple coordination with the devices on the load side and the possibility of limiting the depth of the switchboards thanks to their compact overall dimensions, make Isomax S8 a particularly advantageous choice.

3/44

ABB SACE

S4 250 2-3 600 3000 N 65 25 18 H 150 65 22 L 200 100 35 N 65 35 22 35 20

S5 400 2-3 600 600 3000 H 150 65 22 50 35 L 200 100 35 65 50 N 65 50 25 35 20

S6 800 2-3 600 600 3000 H 150 65 35 50 35 L 200 100 42 65 50

S7 1200 2-3 600 3000 H 100 65 50 -

S8 1600-2000-2500 3 600 3000 V 120 100 85 -

10,00 / 254 4,13 / 105 4,07 / 103,5 20000 / 120 8,8

10,00 / 254 (300A); 13,62 / 346 (400A) 5,51 / 140 4,07 / 103,5 20000 / 120 11

14,25 / 268 8,27 / 210 4,07 / 103,5 20000 / 120 22

16 / 406 8,27 / 210 5,45 / 138.5 10000 / 120 37,5

15,75 / 400 15,98 / 406 9,25 / 235 10000 / 20 135

Motor Control protection - MCP


Type Poles Trip Unit Adjustable magnetic only (4...12xIn) PR211/P - I Rating [A] 325 L 50 25 10 65 50
(1) (1)

S3L 3

S4 N/H/L 3

S5 N/H/L 3

S6 N/H/L 3

S7H 3

S8V 3

50150 L 150 85 25 65 50 N 65 25 18 -

100-250 H 150 65 22 L 200 100 35 -

400 N 65 35 22 -

400 H 150 65 22 -

400 L 200 100 35 -

600-800 600-800 600-800 N 65 50 25 H 150 65 35 L 200 100 42 -

1000-1200 H 100 65 50 -

1600-2000-2500 V 120 100 85 -

Interrupting capacity 240 V AC 480 V AC 600 V AC 500 V DC 600 V DC


(1)

Performance available only for the 25 A rating version

Moulded Case Switches - MCS


Type Rating Poles Magnetic trip Rated voltage [A] [A] S3 H-D 150 150 3 1500 600 600 S3 H-D 225 225 3 2250 480 500 S4 H-D 250 3 3000 600 600 S5 H-D 400 3 5000 600 600 S6 H-D 800 3 10000 600 600 S7 H-D 1200 3 20000 600 600 S8 V-D 2500 3 35000 600 600

(AC) 50-60 Hz [V~] (DC) 3 poles in series [V]

ABB SACE

3/45

3/46

ABB SACE

Accessories

Index
Versions ............................................................................................................................. 4/3 Connection terminals ..................................................................................................... 4/6 Service releases ............................................................................................................... 4/10 Electric signals ................................................................................................................. 4/14 Remote controls .............................................................................................................. 4/17 Operating mechanisms and locks ................................................................................ 4/22 Residual current releases ............................................................................................... 4/26 Accessories for electronic releases .............................................................................. 4/30 Installation accessories and spare parts ..................................................................... 4/35

ABB SACE

4/ 1

4/2

ABB SACE

GSIS9070

Accessories
Versions

SACE Isomax S circuit-breakers are available in the FIXED, PLUG-IN or WITHDRAWABLE, three-pole or four-pole versions.

GSIS9121

F
FIXED
The FIXED version circuit-breaker with three or four-poles has: the same upper and lower terminals lever operating mechanism thermomagnetic or electronic release flange for the front door of the switchboard possibility of assembly on base plate or on DIN rail (up to 630A) circuit-breakers featuring only four depths (70mm for S1-S2, 103.5 for S3...S6, 138.5 for S7 and 242 for S8) standardised front for groups of circuitbreakers (45mm for S1...S5, 105mm for S3...S7). sists of:

GSIS9120

P
PLUG-IN
The PLUG-IN version circuit-breaker con-

W
WITHDRAWABLE
The WITHDRAWABLE version circuitbreaker is made up of: fixed part, to be installed directly on the base plate of the cubicle with the side group mounted on the fixed part to allow the racking-out/racking-in movement moving part obtained from the fixed circuit-breaker with the addition of the isolating contacts in correspondence with the connection terminals, of the rear frame (which is coupled with the side piece provided on the fixed part for sliding) for fixing to the fixed part, and of the terminal covers. accessory to be applied on the front of the circuit-breaker with selection between front for lever operating mechanism, motor operator and rotary han-

fixed part to be installed directly on the base plate of the cubicle moving part obtained from the fixed circuit-breaker with the addition of the isolating contacts in correspondence with the connection terminals, of the rear frame for fixing to the fixed part and of the terminal covers. Circuit-breaker racking out is carried out by unscrewing the top and bottom fixing screws. A special lock prevents the circuit-breaker from being racked in and out with the contacts in the closed position.

GSIS9122

F Fixed S1 125 S2 160 S3 160 S3 250 S4 160 S4 250 S5 400 S5 630 S6 630 S6 800 S7 1250 S7 1600 S8 2000 S8 2500 S8 3200

P Plug-in

W Withdrawable

dle operating mechanism; application of one of these accessories allows the circuit-breaker lock to be made in the withdrawn position. Racking-in/out of the moving part is carried out by means of the special operating lever supplied with the circuit-breaker in the moving part for withdrawable version or with the conversion kit of the fixed circuit-breaker into moving part of withdrawable circuit-breaker. The special mechanism allows the circuit-breaker to be put into the isolated position (with

power and auxiliar y circuits disconnected) with the compar tment door closed, providing increased operator safety. The lever can only be inserted with the circuit-breaker open. Once racked out or withdrawn, the circuit-breaker can be operated in the open/ closed position and, by means of the special connection extensions, blank operating tests of the auxiliary control circuits can be carried out.

ABB SACE

4/ 3

Accessories
Versions

Starting from the fixed version with front terminals, SACE Isomax S circuit-breakers can be converted into the various versions using the Conversion kits. This makes management of the product, its versions and stocks as a whole highly flexible. It is, in case, always possible to ask for the circuit-breaker in the required version fully prepared in the factory. any

Conversion kit into moving part for plug-in circuit-breaker


This allows the fixed circuit-breaker with front terminals to be converted into the moving part of a plug-in circuit-breaker. The kit consists of: tulip isolating contacts frame assembly screws and nuts. The fixed part is needed to complete the circuit-breaker.

S1-S2

S3-S4

GSIS0101

4
Fixed part
The fixed part allows the circuit-breaker to be constructed in the plug-in or withdrawable version. It can also be provided in the switchboard as a reserve power supply to be completed with a circuit-breaker at the appropriate time. For plug-in or withdrawable version circuit-breakers, different circuit-breaker positions are possible: Plug-in: racked-in racked-out Withdrawable: racked-in racked-out - withdrawn. The fixed part for withdrawable version circuit-breaker is fitted with a guide for supporting the moving part during the isolation or withdrawal operations of the moving part. For SACE S6-S7 circuitGSIS9124 GSIS9123

breakers, there are two guides.

4/4

GSIS9036

ABB SACE

GSIS0102

Conversion kit into moving part for withdrawable circuit-breaker


This allows the fixed circuit-breaker with front terminals to be converted into the moving part of a withdrawable circuitbreaker. The kit consists of isolating contacts, frame, assembly screws and nuts. The circuit-breakers in the withdrawable version must always be completed, alternatively, with one of the following accessories: front for lever operating mechanism rotary handle operating mechanism motor operator, in order to make the racking-out lock if necessary. The fixed part is needed to complete the circuit-breaker.

GSIS9037

Conversion kit for fixed part of plug-in into fixed part of withdrawable
A guide for converting the fixed part of a plug-in version circuit-breaker into the fixed part of a withdrawable version circuit-breaker is available for SACE S3-S4S5 circuit-breakers.

Racking-out handle
This allows racking-out and racking-in even with the door closed of the circuit-breaker in the fixed part. The handle is the same for the whole range of circuit-breakers and is supplied
GSIS9012

as standard with the Conversion kit or with the circuit-breakers supplied in the withdrawable version.

ABB SACE

GSIS9047

4/ 5

Accessories
Connection terminals

The basic version of the circuit-breaker is supplied with: front terminals for SACE S3, S4, S5, S6, S7, and S8 circuitbreakers front terminals for copper cables for SACE S1, and S2 circuit-breakers. Different types of terminals are available, which can be combined in different ways (upper of one type, lower of another type), allows the circuit-breaker to be connected to the plant in the most suitable way for installation requirements. The following distinctions can be made between:

The information needed to make the connections is summarised for each type of terminal on pages

4/8-9.

Flat bars of

different dimensions and composition are recommended for connection with busbars. Furthermore, the minimum depth the flat bar to be connected must have is also indicated, if it is of a different composition to the one recommended. The minimum and maximum cross-section of the cables which can be tightened in the terminals and the diameter of the terminal are indicated for connection with bare cables The torque values to be applied to the tightening screws of the terminals for cable and to the screws used for connecting the busbars to the flat bar terminals are given.

front terminals which allow connection of cables or busbars


by acting directly from the front of the circuit-breaker.

rear terminals

which allow installation of the circuit-breakThe circuit-breakers can be ordered complete with the terminals required, mounted directly in the factory, or the terminals can be ordered individually in packs of 3 - 4 - 6 - 8 pieces. Codes for ordering circuit-breakers directly in the configuration able. with upper / lower terminals of the same type are avail-

ers in switchboards with rear access to both cable and busbar connections. T erminals for connection of busbars or cables terminated with cable terminals and terminals for direct connection of bare cable are available.

EF

ES

FC Cu

4
GSIS0086 GSIS0087 GSIS0088

Front terminals S1 125 S2 160 S2X 80, S2X 100 S3 160 / 250 S3X 125 / 200 S4 160 / 250 S4X 250 S5 400 / 630 S6 630 / 800 S6X 400 / 630 S7 1250 / 1600 S8 2000 / 2500 / 3200 F F F F F F F F F (2000A / 2500A) F = Fixed 4/6 P = Plug-in

Front extended terminals F F F-P-W F-P-W F-P-W F-P-W F(400A)-P(400A)-W(400A) F-W F - W (only at the bottom) F-W W = Withdrawable

Front extended spreaded terminals F F F F F - W(630A) F F F

Front terminals for copper cables F-P F-P F-P F-P-W F-P-W F-P-W F-P-W F - P(400A) - W(400A)

ABB SACE

GSIS0089

Insulating terminal covers


The terminal covers are applied to the terminals of the circuitbreaker to prevent accidental contacts with live parts and thereby guarantee protection against indirect contacts. The following are available:

lower terminal covers,

which guarantee IP40 degree of


GSIS9052

protection for fixed circuit-breakers with rear terminals and for moving parts of plug-in or withdrawable circuit-breakers.

upper terminal covers

for fixed circuit-breakers with front

terminals, front terminals for cables and rear terminals, which guarantee IP40 degree of protection.

terminal covers for fixed parts

of plug-in or withdrawable

Screws for sealing the terminal covers


These are applied to the terminal covers of fixed circuit-breakers or to the moving parts of plug-in or withdrawable circuitbreakers. They prevent removal of the upper or lower terminal covers, and can be locked with wire and a lead seal.

circuit-breakers, guarantee IP40 degree of protection on the front with moving part connected. They are available in a single version. The degrees of protection indicated are valid for circuit-breakers installed in switchboards.

FC CuAl

RC

HR

VR

4
GSIS0190 GSIS0191 GSIS0192 GSIS0193

Front terminals for Cu/Al cables F F F F F F F(400A) F F(1250A)

Rear threaded terminals F-P F-P F-P F-P-W F-P-W F-P-W F-P-W F - P(400A) - W F F

Rear terminals for Cu/Al cables F F F F F(400A) F F

Rear terminals in horizontal flat bar W W F-W

Rear terminals in vertical flat bar W(630A) W W F-W F

ABB SACE

4/ 7

GSIS0194

Accessories
Connection terminals
Front terminals
These allow busbars or cables terminated with a cable terminal to be connected

S3-S4-S5

S6

Type S3 160, S3X 125 S3 250, S3X 200 S4 160 S4 250, S4X 250 S5 400 S5 630 S6 630, S6X 400-630 S6 800 S7 1250 S7 1600 S8 2000 S8 2500

version pieces F F F F F F F F F F F F 1 1 1 1 2 2 2 2 2 2 3 4 L 20 20 20 20 25 25 40 50 50 50 100 100

S7

busbars [mm] H P 10 4 10 6 10 4 10 6 12 5 12 8 12 12 20 20 5 5 8 10 5 5

hole 9 9 9 9 11 11 2x7 2x7 2 x 11 2 x 11 4 x 15 4 x 15

tightening B [Nm] 9 9 9 9 18 18 9 9 18 18 70 (2) 70 (2)

terminal covers upper lower fixed part R R R R R R R R R R R R R R R R R R R

S2

S3-S4-S5

S6 630

Front extended terminals


These allow busbars or cables terminated with a cable terminal to be connected

S6 800

S7

Type S2 160 S3 160, S3X 125 S3 250, S3X 200 S4 160 S4 250, S4X 250 S5 400 S6 630, S6X 400-630 S6 800 S7 1250 S7 1600

version F F-P-W F-P-W F-P-W F-P-W F-P-W F-W F-W F-W F-W

pieces 1 1 1 1 1 2 2 2 2 2

busbars [mm] L P hole 20 4 8 20 4 8.5 20 6 8.5 20 4 8.5 20 6 8.5 25 5 11 40 50 50 50 5 5 8 10 11 14 4x11(4) 4x11(4)

cable term. [mm ] L hole 20 8 20 8.5 20 8.5 20 8.5 20 8.5 25 11 40 50 11 14

tightening [Nm] A B 5 9 9 9 9 9 9 9 9 9 18 18 9 9 45 45 18 30 18 18

terminal covers upper lower fixed p. R R R R R R R R R R R R R R R R R R R R R

PF S3-S4-S5 PF S6

PF S7

Front extended spreaded terminals


These allow busbars or cables terminated with a cable terminal to be connected

Type S3 S4 S5 400 S5 630 S6 S3-S4-S5 PF S5 630 S7 1600

version F F F F-W F F

pieces L 1 1 2 2 2 2

busbars [mm] P hole 4 4 5 5 5 10 8.5 8.5 11 11 3 x 13 3 x 13

cable term. [mm] L hole 30 30 40 40 4 x 45 4 x 45 8.5 8.5 11 11 13 13

tightening [Nm] A B 9 9 18 18 9 45 9 9 18 18 30 20

terminal covers upper lower fixed p. S S S S

30 30 40 40 50 50

Front terminals for copper cables


These allow bare copper cables to be connected directly to the circuit-breaker. They are not suitable for tube cable terminals

Type S6 S7 S1 S2 S3 S3 S4 S4 S5 S5 S1-S2 S3-S4-S5 Key 125 160 160, S3X 125 250, S3X 200 160 250, S4X 250 400 630

version F-P F-P F-P-W F-P-W F-P-W F-P-W F-P-W F-W

pieces 1 1 1 1 1 1 1 2

[mm2 ]

cable

1.5...50 1.5...70 6...185 6...185 6...185 6...185 16...240 50...185

busbars cable term. tightening L [mm] L [mm] B [Nm] max.10 max.10 2.5-5 (1) max.12 max.12 2.5-5 (1) 16 16 16 16 25 31

clamps
[mm]

11 12.5 18 18 18 18 24 20

terminal covers upper lower fixed p. R R R R R R S R R S R R S R R S R R S S

4/8

GSIS0095

(1) Tightening torque of 2.5 Nm for < 10 mm2 cable cross-section (2) M12 class 8.8 screws (3) M16 class 8.8 screws (4) Only use two holes diagonally

A = Tightening of the terminal onto the circuit-breaker B = Tightening the cable/busbar or cable terminal onto the terminal R = On request S = Standard

ABB SACE

Front terminals for copper or aluminium cables


These allow copper or aluminium cables to be connected directly to the circuit-breaker (it is not possible to use solid aluminium cables). For the SACE S2 circuit-breaker, these terminals must be connected to the front extended terminals, which are supplied if the circuit-breaker is ordered fitted directly in the factory , whereas the front extended terminal kit must be specified if they are ordered as loose parts..

S2-S3-S4-S5

S5

Type S2 160 S3 160 (R100A) S3 160, S3X 125 S3 250, S3X 200 S4 160 S4 250, S4X 250 S5 400 S6 630, S6X400-630 S6 800 S7 1250

version F F F F F F F F F F F F

pieces 1 1 1 1 1 1 1 2 1 2 3 4

[mm2]

cable

tightening A [Nm] B [Nm] 9 9 9 9 9 9 9 18 18 5 9 37 5.6 13.5 5.6 13.5 31 13.5 31 31 43 31 43 43

clamps
[mm]

terminal covers upper lower fixed p. S S R R R R R S R R S S

S6 630

S6 800

2.5...50 35...95 2.5...50 35...95 25...150 35...95 25...150 95...120 120...240 120...240 70...185 95...240

9.5 13.5 10 14.2 17 14.2 17 15.5 21.5 21.5 19 21.5

S7

S3-S4-S5

S6 630

Rear terminals for copper or aluminium cables


These allow copper or aluminium cables to be connected directly to the circuit-breaker.

Type S3 160, S3X 125 S3 250, S3X 200 S4 160 S4 250, S4X 250 S5 400 S6 630, S6X400-630 S6 800

version F F F F F F F

pieces 1 1 1 1 1 2 3 A [Nm] 9 9 9 9 18 9 9

tightening B [Nm] 31 31 31 31 43 43 31

clamps
[mm]

16 16 16 16 21 21 17.5

terminal covers upper lower fixed p. S S S S S S S

S6 800

Rear threaded terminals


These allow rear connection of busbars.

S1-S2 busbars [mm] L P hole 16 3 16 3 18 4 18 4 20 4 12.5 20 4 12.5 20 6 12.5 20 6 12.5 20 4 12.5 20 4 12.5 20 6 12.5 20 6 12.5 25 5 16.5 25 5 16.5 40 5 25 40 5 25 40 5 25 50 5 25 cable term. [mm] tightening terminal covers L hole A B upper lower fixed p. 5 8 S 8 5 8 S 8 20 12.5 10 20 S 20 12.5 10 20 20 12.5 10 20 S 20 12.5 10 20 20 12.5 10 20 S 20 12.5 10 20 20 12.5 10 20 S 20 12.5 10 20 25 16.5 18 40 S 25 16.5 18 40 40 25 18 100 S 40 25 18 100 40 25 18 100 S 50 25 18 100 S

S3-S4-S5-S6

Type S1 125 S2 160 S3 160, S3X 125 S3 250, S3X 200 S4 160 S4 250, S4X 250 S5 400 S5 630 S6 630, S6X 400-630 S6 800

version F P F P F P-W F P-W F P-W F P-W F P-W F P-W F F

pieces 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2

4
PF S3-S4-S5-S5 630

S7

PF S6 630

Rear terminals in horizontal and vertical flat bar


These allow rear connection of busbars.

PF S6 cable term. [mm] tightening L hole B [Nm] 40 11 20 40 14 30 50 14 30 20 20 70 (2) 70 (2) 100 (3) terminal covers upper lower fixed p.

Type S5 630 S6 630, S6X 400-630 S6 800 S7 1250 S7 1600 S8 2000 S8 2500 S8 3200

version W W W F-W F-W F F F

pieces 2 2 2 2 2 3 4 6

ABB SACE

4/ 9

GSIS0096

busbars [mm] L P hole 40 5 11 40 5 14 50 5 14 50 8 4x11 (4) 50 10 4x11 (4) 100 5 4x15 100 5 4x15 100 5 4x18

PF S7 S S

Accessories
Service releases

The service releases, shunt opening and undervoltage releases, housed and fixed in a slot in the left part of the circuit-break er are always alternative to each other. The power supply is made by means of special connectors for sizes S3 to S7, whereas for S1-S2, it is made by means of free wires 0.6 m long or with plug-socket connectors which can be supplied on request. Assembly is carried out by pressure into the appropriate housing in the left part of the circuit-breaker.

Shunt opening release


This allows circuit-breaker opening by means of an electric command. Release operation is guaranteed for a voltage between 70% and 110% of the rated power supply voltage Un, both in AC and in DC. It is always fitted with an auxiliary
GSIS0107

S1-S2

S3-S4-S5

limit contact.

(*)

S6-S7
GSIS9001

S8

GSIS0109

GSIS0108

4
Power supply voltages
S1 - S2 50-60 Hz [V~] 24 30 48 100 130 220 250 380 440 24 48 110 220 250 60 24 48 60 DC [V] [V~]

(*) For the SACE S1-S2 circuit-breakers , the service releases are fixed to the circuit-breaker cover

S3 -S4 - S5 50-60 Hz DC [V] 12 24 48 60 ... 72 110 125 220 250 24 48 60 110 120 220 240 380 400 480 50-60 Hz [V~]

S6 - S7 DC [V] 12 24 48 60 110 125 220 250 100 ... 127 127 ... 150 150 ... 180 200 ... 255 380 ... 500 24 48 50-60 Hz [V~]

S8 DC [V] 24 30 48 60 100 ... 27 160 200 ... 250

110 120 220 240 380 400 480

Powers absorbed on inrush


S1...S5 AC [VA] 100 DC [W] 120 S6...S7 AC [VA] 150 DC [W] 150 AC [VA] 200 S8 DC [W] 150

Circuit-breaker opening times


S3 [ms] < 15 S4...S7 [ms] < 15 S8 [ms] < 20

Number of operations
S3-S4 [nr.] 10000 S5 [nr.] 7500 S6-S7 [nr.] 2500

4/10

ABB SACE

GSIS0110

Undervoltage release
This opens the circuit-breaker due to a power supply failure to the release, or voltage drops to minimum values of 0.7 x Un with a trip range from 0.7 to 0.35 x Un. After tripping, the circuit-breaker can be closed again, starting with a voltage higher than 0.85 x Un. With the undervoltage release de-energised, neither circuit-breaker nor main contact closure is possible.
(*)

S1-S2

S3-S4-S5

GSIS0111

S6-S7

S8

GSIS9002

GSIS0109

GSIS0108

Power supply voltages


S1 - S2 50 Hz [V~] 24 48 110 110 220 380 380 440 24 48 60 110 220 48 60 Hz [V~] DC [V]

(*) For the SACE S1-S2 circuit-breakers , the service releases are fixed to the cover of the circuit-breaker

S3 -S4 - S5 50-60 Hz [V~] 24 48 60 110 127 220 250 380 440 480 24 48 60 110 125 220 250 DC [V] 50-60 Hz [V~] 24 48 60 110 127 220 250 380 440 480

S6 - S7 DC [V] 50 Hz [V~] 24

S8 60 Hz [V~] DC [V] 24 30 30 48 48 60 24 48 60 110 125 120 220 250 127...130 208...220 220...250 220 230...240 277 240 310 380 380...400 415...440 500 440 480 100 110...115 110...115 125 .. 127 110...125 60

GSIS0112

Powers absorbed during continuous service


S1...S5 AC [VA] 6 DC [W] 3 S6 - S7 AC [VA] 10 DC [W] 4 AC [VA] 30 S8 DC [W] 15

Circuit-breaker opening times


S1...S2 [ms] < 15 S3 [ms] < 18 S4...S7 [ms] < 25 S8 [ms] < 25

Number of operations
S3-S4 [nr.] 10000 S5 [nr.] 7500 S6-S7 [nr.] 2500

ABB SACE

4/11

Accessories
Service releases
Time-delayed undervoltage release
The undervoltage release can be combined with an external electronic power supply time-delay device, which allows circuit-breaker opening to be delayed in the case of a power cut to the release

itself, according to fixed time-delays of


GSIS9042

0.5-1-2-3 [s], so as to avoid unwarranted trips caused by temporary malfunctions. It is available for the SACE S3, S4, S5, S6, and S7 circuit-breakers with power supply voltages at 110-220 V (50-60 Hz) only coupled with an undervoltage release at 310 V DC. Different power supply voltages are possible for S8.

Shunt closing release


This allows circuit-breaker closure by means of an electric command. Operation of the release is guaranteed for a voltage between 80% and 110% of the rated power supply voltage Un, both in AC and in DC.

S8

Power supply voltages


S8 50 Hz [V~] 24 24 24 30 30 48 48 60 60 100 110...115
GSIS9003

60 Hz [V~]

DC [V]

GSIS0112

110...115 110...125 125...127 120

127...130 220 208...220 220...250 230...240 277 240 310 380...400 415 ... 440 500 440 380 480

Powers absorbed on inrush


S8 AC [VA] 200 DC [W] 220

Circuit-breaker closing times


S8 [ms] < 55

4/12

ABB SACE

Connectors for service releases


These allow the shunt opening release or the undervoltage release to be connected to the power supply circuit. They are available in the following versions:
GSIS0114

S1 - S2

plug-socket for S1-S2 circuit-breakers


GSIS0113

(free cables always supplied) for fixed S3 ... S7 circuit-breakers for plug-in/withdrawable S3 ... S7 circuit-breakers. Assembly is by means of pressure into special slots in the left side of the circuitbreaker. Cables of different lengths are available.

S3 ... S7

GSIS9013

GSIS0115

GSIS0116

4
Extension for testing service releases
Available for SACE S3, S4, S5, S6, and S7 circuit-breakers, this allows supply to the service releases with the circuitbreaker in the racked-out position. It is therefore possible to carry out blank opGSIS9017

erating tests of the circuit-breaker with the circuit-breaker in safe conditions, i.e. isolated in relation to the power circuits.

ABB SACE

4/13

Accessories
Electric signals

These allow information relative to the circuit-breaker state of operation to be taken outside the circuit-breaker. Installation of these accessories is carried out directly from the front of the circuit-breaker in special slots, completely se gregated from the live parts, with increased operator safety.

Auxiliary contacts
These carry out electrical signalling of the operating state of the circuit-breaker: Open/closed: indicates the position of the circuit-breaker contacts. Release trip: signals circuit-breaker opening because the overcurrent release has tripped (for an overload or
GSIS0117

S1-S2

S3-S4-S5

shor t-circuit), the residual current, shunt opening or undervoltage release has tripped, or the emergency opening pushbutton of the motor operator or the test pushbutton has been
(*)

pressed. Signalling is reset when the circuit-breaker is reset (recovery). For SACE S3, S4, S5, S6, and S7 circuitbreakers the auxiliary contacts of the circuit-breaker are also available in the gold-plated version for digital signals, also suitable for use with voltages Un < 24 V with the same type of signalling and versions. The signals indicated in the table are available:

S6-S7

(*) For SACE S1-S2 circuit-breakers the auxiliary contacts are fixed to the cover of the circuit-breaker

Signals 2 contacts during open/closed changeover 1 contact during open/closed changeover + 1 contact during release tripped changeover 1 circuit-breaker open signal + 1 circuit-breaker closed signal + 1 release tripped signal 3 NO or NC contacts release tripped signal microswitch for signalling closing springs charged

GSIS0119

S1...S2

S3

S4...S7

GSIS0118

S8

GSIS9004

S1-S2 Rated voltage Un V ~ (50-60 Hz) V 127 220 30 In [A] 4 4 4 ohmic load inductive In [A] 2A (cosj = 0,3) 2A (cosj = 0,3)

S3-S4-S5-S6-S7 Rated voltage Un V ~ (50-60 Hz) V 250 400 125 250 ohmic load In [A] 0,3 0,15 6 3

S8 Rated voltage Un V ~ (50-60 Hz) V 380 500 220 ohmic load In [A] 1 6 3

4/14

ABB SACE

Connectors for auxiliary contacts


These allow the auxiliary contacts to be connected to the relative power supply circuit. For S1, S2 circuit-breakers, the power supply is made by means of free
GSIS0114

S1 - S2

wires or with mobile plug-socket connecGSIS0113

tors. For SACE S3, S4, S5, S6, and S7 circuit-breakers, the auxiliary contacts (fitted with plug connector) can only be supplied by means of the specific connection connectors to be ordered specifying the size and version of the circuitbreaker (fixed or plug-in/withdrawable). Assembly is carried out by pressure into special slots in the right side of the circuit-breaker.

S3 ... S7

(*)

GSIS9015

(*) Connectors for auxiliary contacts, for fixed, plug-in or withdrawable circuit-breakers

GSIS0120

GSIS0121

Extension for testing auxiliary contacts


Available for SACE S3, S4, S5, S6, and S7 circuit-breakers, this allows the auxiliary contacts to be connected to the relative power supply circuit with the circuitbreaker in the racked-out position. With the circuit-breaker in safe conditions, i.e. isolated in relation to the power circuits, blank tests of circuit-breaker operation can be carried out.
GSIS9089

ABB SACE

4/15

Accessories
Electric signals
Early auxiliary contact for undervoltage release
The early auxiliary contact for the undervoltage release, interlocked with the rotary handle operating mechanism, keeps the release de-energised with the circuitbreaker open. It is supplied complete with socket connector of the type with double slide for simultaneous connection of the undervoltage release and the accept contact.
GSIS0123 GSIS0122

S3 ... S7

Circuit-breaker position contacts


For the fixed part of the SACE S2, S3, S4, S5, S6, and S7 circuit-breakers, these carry out electrical position signalling of

GSIS9038

S3 ... S7

the circuit-breaker in relation to the fixed part: racked-in, racked-out. They can only be connected by means of free wires and are available in the following versions: Contacts for signalling circuit-breaker
GSIS0160 GSIS9006

racked in Contacts for signalling circuit-breaker racked out. A maximum of three contacts for S2, two contacts for S3, three contacts for S4-S5 and five contacts for S6-S7 can be installed on the fixed part, in any combination. The circuit-breaker position contacts are also available in the gold-plated version for digital signals also suitable for use with voltages Un < 24 V with the same type of signals and combinations.

S2 Rated voltage Un V ~ (50-60 Hz) V 127 220 30 ohmic load In [A] inductive In [A] 4 4 4 2A (cosj = 0,3) 2A (cosj = 0,3)

S3-S4-S5-S6-S7 Rated voltage Un V ~ (50-60 Hz) V 250 400 125 250 ohmic load In [A] 0,3 0,15 6 3

4/16

ABB SACE

Accessories
Remote controls

These allow remote control of circuit-breaker opening and closing and are particularly suitable for use in electrical network supervision and control systems. They are complete with manual operating lever and emergency opening pushbutton (starting from S3). A selector allows changeover from automatic to manual operation. They are always fitted with a padlock and, on request, can be fitted with a key lock in the open position.

Solenoid operating mechanism for SACE S1-S2 circuit-breakers S1-S2


This operates both opening and closing of the circuit-breaker, acting directly on its lever. There are two versions available, one placed beside the circuit-breaker (for installation on a panel or DIN EN 50022
GSIS0124

rail), the other on the front, suitable for being installed directly on the front of the circuit-breaker. Both versions can be used either for S1

version.

Rated voltage, Un [V] [V]


GSIS9022

AC 110 220 ... 230 85 ... 110% Un 2300-2500 [VA] opening [s] closing [s] [no. operations] < 0.1 < 0.1 25000 IP 30 [ms] > 100

DC 48 60 110 220 85 ... 110% Un 700-900 [W]

[V] [V] Operating voltage Inrush power absorption, Ps Duration Mechanical life Minimum duration of the opening and closing command impulse

GSIS0125

or for S2 and in the three- and four-pole

Degree of protection, on the front

ABB SACE

GSIS9023

4/17

Accessories
Remote controls

Direct action motor operator for SACE S3-S4 and S5 circuit-breakers


Both the opening and closing command is controlled by the motor, which acts directly on the circuit-breaker lever. The table shows the power supply voltage values Un [V].

S3-S4-S5

GSIS9021

Rated voltage, Un [V] [V] [V] [V] [V] [V] Operating voltage Inrush power absorption, Ps Service power absorption, Pc Operating frequency Time constant Duration Mechanical life Minimum duration of the opening and closing command impulse [Hz] [ms] opening [s] closing [s] [no. operations] Degree of protection, on the front [ms]

GSIS0126

AC 110-127 220-240 380 440 85 ... 110% Un 500 [VA] 350 [VA] 50-60 18 0.1 0.1

DC 24 48-60 110-125 220-250 85 ... 110% Un 500 [W] 350 [W]

15000 (S3-S4) / 10000 (S5) IP 30 > 150

4/18

ABB SACE

GSIS0127

Stored energy motor operator for SACE S6-S7 circuit-breakers


With the stored energy operating mechanism, during circuit-breaker opening the release mechanism automatically precharges a system of springs: the stored energy is exploited for closing the circuitbreaker. It is supplied complete with shunt closing release (Ps=100VA~/
GSIS0129

S6-S7

100W) and flange for the compartment


GSIS0128

door. The table shows the power supply voltage values Un [V]. In the case of interlocked circuit-breakers, the key lock against manual operation is necessary.

Rated voltage, Un [V] [V] [V] [V] [V] [V] [V]


GSIS9020

AC 110 120-127 220-250 380 85 ... 110% Un 660 [VA] 180 [VA] [Hz] [ms] closing opening resetting 50-60 22 0.09 1.2 2 10000 (S6) / 5000 (S7) IP 30 [ms] > 100

DC 24 48 60 110 120-127 220-250 85 ... 110% Un 600 [W] 180 [W]

[V] Operating voltage Inrush power absorption, Ps Service power absorption, Pc Operating frequency Time constant Duration

Mechanical life Minimum duration of the opening and closing command impulse

[no. operations]

Degree of protection, on the front

ABB SACE

4/19

Accessories
Remote controls
Geared motor for SACE S8 circuit-breaker
This allows the springs of the circuitb re a k e r closing mechanism to be

Rated voltage, Un [V] [V] [V] [V] Inrush power absorption, Ps Service power absorption, Pc Charging time Mechanical life [s] [no. operations]

AC 100-130 220-250 1000 [VA] 230 [VA] 7 ... 10 5000

DC 24-30 48-60 100-130 220-250 1000 [W] 230 [W]

charged automatically, immediately following an closing operation. It includes a limit microswitch for electrical signalling of closing springs charged.

Connectors for motor operators


The motor operators, from S3 to S7, can only be supplied by means of the specific connection connectors. They are of the slide type and allow simultaneous connection of both the motor operator and the auxiliary contacts to the relative power supply circuit. They are an alternative to the corresponding connectors for the auxiliary contacts only since they
GSIS0130

GSIS9007

S3 ... S7

are housed in the same seat. They must be ordered specifying the size and version of the circuit-breaker (fixed or plugin/withdrawable).

Extension for testing motor operators For the SACE S3, S4, S5, S6, and S7 cirS3 ... S7
cuit-breakers, this allows both motor operators and the auxiliary contacts to be connected to the relative power supply circuit with the circuit-breaker in the racked-out position. With the circuitbreaker in safe conditions, i.e. isolated
GSIS9016

in relation to the power circuits, blank operating tests of the circuit-breaker can be carried out. It must be ordered specifying the size and version of the circuitbreaker (fixed or plug-in/withdrawable) and automatically excludes the corresponding extension for testing the auxiliary contacts

4/20

ABB SACE

GSIS9014

Rotary handle operating mechanism


The rotary handle operating mechanism facilitates operation thanks to its ergonomic handle. It is always fitted with a padlock in the open position, which prevents the circuit-breaker being closed. The lock slot can take up to 3 padlocks stem 6 mm (not supplied). On request it can be fitted with a compartment door lock or a key lock in the open position. For SACE S2, S3, S4, S5, S6, and S7 circuit-breakers, application of the rotary handle operating mechanism is an alterGSIS0131

S1-S2

native to the front flange for the lever operating mechanism and for the motor operator. Different types of rotary handle operating mechanism are available. The position of the rotary handle indicates with certainty the position of the contacts: open, closed, relay tripped. The release settings and the nameplate data remain accessible to the user. For the SACE S6, S7 circuit-breakers, the direct rotary handle operating mechanism on the circuitbreaker is always supplied complete with flange for the compartment door. The rotary handle operating mechanism in the emergency version, complete with red-yellow handle and yellow plate, suitable for machine tool control, is also available for all the circuit-breakers.

S6-S7 S3-S4-S5

GSIS0123

GSIS0132

S1-S2
GSIS9025

S3-S4-S5 F/P W 300 mm 500 mm F

S6-S7 W

F/P Direct Direct emergency Transmitted with fixed distance Transmitted with fixed emergency distance Transmitted with adjustable distance Transmitted with adjustable emergency distance
GSIS9024

119,5 mm 119,5 mm 180/500 mm

300 mm 300 mm

500 mm 500 mm 500 mm

Extension for transmitted handle

ABB SACE

4/21

Accessories
Operating mechanisms and locks
Front flange for lever operating mechanism
This can be installed on SACE S3, S4, S5, S6, and S7 fixed, plug-in or withdrawable circuit-breakers. In the case of withdrawable circuit-breakers installed in compartments, it allows the IP40 degree of protection to be kept for the whole isolation run of the circuit-breaker. It is always fitted with a padlock in the open position (stem 6 mm - up to three padlocks - not supplied) which prevents closing of the circuit-breaker. On request, it can be fitted with a key lock in the open position for one or more circuit-breakers and with the compartment door lock. It is available in the following versions: for fixed or plug-in circuit-breaker. for withdrawable circuit-breaker. For the SACE S6, S7 circuit-breakers, it is always supplied complete with flange for the compartment door, whereas for the SACE S3, S4, and S5 circuit-breakers the flange supplied with the circuitbreaker can be used.
GSIS0133

S3-S4-S5

S6-S7

4
Key lock in open position
This allows the mechanical closing operation of the circuit-breaker to be locked. The following versions are available: lock with different key for each circuitbreaker lock with the same key for groups of circuit-breakers. Different locks are supplied for direct action motor operator, for stored energy
GSIS0135 GSIS0136

GSIS9026

S3 ... S7

motor operator, and for rotary handle or front flange for lever operating mechanism. The circuit-breaker lock in the open position ensures circuit isolation in compliance with the IEC 947-2 Standard.

4/22

GSIS9008

ABB SACE

GSIS0134

Compartment door lock


This prevents the compartment door being opened with the circuit-breaker closed. It can be used with the SACE S3, S4, S5, S6, and S7 circuit-breakers in the fixed, plug-in or withdrawable version and fitted with rotary handle operating mechanism or front flange for lever operating mechanism. It consists of two eleGSIS9010

S3...S7

ments: one applied to the rotary handle operating mechanism or to the front flange for the lever operating mechanism, the other, consisting of a metal striker, to be applied onto the compartment door.
GSIS0137

For the SACE S1-S2 circuit-breakers it is an integral part of the rotary handle operating mechanism.

Lock for fixed part of withdrawable circuit-breaker


Key locks or padlocks are available to be applied to the guide of the fixed part of a withdrawable circuit-breaker to prevent the moving part from being rackedin. The following different versions are available: Padlock, which can take up to three padlocks with stem 6 mm (not supplied). Key lock in the open position with different key for each circuit-breaker Key lock in the open position between two or more circuit-breakers with the same key for groups of circuit-breakers Key lock of Ronis type (without key).
GSIS0138 GSIS0139

S3...S7

ABB SACE

GSIS9009

GSIS0140

4/23

Accessories
Operating mechanisms and locks
Padlock for operating lever
This is applied on the cover of the SACE S1-S2 circuit-breakers to prevent the

S1-S2

operating lever movement. If activated, the circuit-breaker remains locked in the open position, guaranteeing circuit isolation in compliance with the IEC 947-2 Standard.
GSIS0141

Anti-tampering lock

This is applied on the cover of the SACE S2, S3 circuit-breakers in correspondence with the regulator of the thermal element of the thermomagnetic release and prevents it being tampered with.

GSIS9035

S2-S3

GSIS9049

GSIS0142

4/24

GSIS0144

ABB SACE

GSIS0143

Mechanical interlock between two circuit-breakers


This allows installation of two circuitbreakers on a single support and, by means of special lever mechanism, makes them mechanically inter-dependent. It prevents operation in parallel of two power supply sources (e.g.: normal emergency). It consists of a kit with levers and assembly accessories and a metallic support. The circuit-breakers and any operating mechanism accessories must be ordered separately. The mechanical interlock is available for SACE S3, S4, S5, S6, and S7 circuit-breakers in side by side and superimposed versions. To be able to take the circuit-breakers mounted directly on the interlocking plate, the code 1SDA050093R1 must be specified as an accessory of the second circuit-breaker (or fixed part) which is to be interlocked.
GSIS0145 GSIS0146

S3 ... S7

N.B. for the S3X, S4X , S6X circuit-breakers, only the version side by side can be used.

ABB SACE

4/25

Accessories
Residual current releases

All the circuit-breakers in the SACE Isomax S series are preset for combined assembly with residual current releases. In partic ular, the SACE S1, S2, and S3 circuit-breakers can be combined with residual current releases in the SACE RC210, RC211 or RC212 series, in the version side by side or underneath the circuit-breaker. Apart from the protection against overloads and short-circuits typical of circuit-breakers, the residual current circuit-breake rs which are derived from them also guarantee protection against earth fault currents, thereby ensuring protection against the ris of fire. The residual current releases can also be mounted on the SACE S2D and S3D switch-disconnectors. In that case, the derived apparatus is a pure residual-current circuit-breaker, which therefore guarantees only residual current protection an d k

not the protections typical of circuit-breakers. The pure residual-current circuit-breakers are only sensitive to the earth f ault current and are generally applied as main isolators in small distribution switchboards towards end users. The use of pure and non-pure residual-current circuit-breakers allows continuous monitoring of the state of insulation of t he installation, ensuring effective protection against the risk of fire and explosion and, in the case of devices with I

Dn

30mA, they

guarantee protection of people against indirect and direct contacts to integrate the compulsory measures foreseen by the standards and by the accident prevention regulations. The residual-current releases are constructed in compliance with the following standards: IEC 947-2 appendix B IEC 255-3 and IEC 1000: for protection against unwarranted trips.

SACE RC210 polarised residual-current release


The SACE RC210/1 polarised residualcurrent release is available for four-pole SACE Isomax S1 circuit-breakers for assembly side by side on DIN 50022 rail. The release is constructed using polarised type technology and acts directly on the release operating mechanism of
GSIS0147

S1

the circuit-breaker, by means of a small

piston which passes through a pre-cut window on the side of the circuit-breaker. It is fitted with a test button for periodically checking the circuit-breaker.

SACE RC211, RC212 electronic residual current releases


The SACE RC211 and RC212 residual SACE RC211/2, RC212/2 for S2 circuitbreakers SACE RC211/3, RC212/3 for S3 circuitbreakers. They are constructed using analogue technology and act directly on the circuit-breaker by means of an opening solenoid, supplied with the release, to be housed in the special slot made in the area of the third pole. They do not require an auxiliary power supply since they are supplied directly The following releases are available: SACE RC211/1, RC212/1 for S1 circuitbreakers from the network and their operation is guaranteed even with only a single phase supplied with voltage and in the presence of one-direction pulsating currents with continuous components. The operating conditions of the apparatus can be controlled constantly by means of the test pushbutton of the electronic circuit and the residual current trip magnetic indicator. The circuit-breaker complete with residual current release can be fitted with the electrical accessories normally available for the circuit-breaker. The opening and undervoltage releases are housed in the special slot made in the fourth pole. current releases can be installed both on the SACE S1, S2 and S3 circuit-breakers and on the SACE S2D and S3D switch-disconnectors, in the fixed fourpole version, and can be supplied in two versions as follows: for assembly in position beside the circuit-breaker for assembly in position under the circuit-breaker.

4/26

ABB SACE

GSIS9027

Residual current release beside the four-pole version circuit-breaker


This is supplied complete with: power cables for connection to the lower terminals of the circuit-breaker (respecting correspondence with the neutral and phases) an opening solenoid to be housed in the area of the third pole, complete with plug-socket connector for connection to the residual current release 2 brackets for fixing on DIN rail (one for the circuit-breaker and one for the residual current release) plug connector to make the connection of the remote opening pushbutton (to be provided by the customer). For SACE S1-S2 circuit-breakers the residual current release is fitted with front terminals for cables. For the SACE S3 circuit-breaker, the residual current release is fitted with front terminals and is also supplied with a front flange H= 45 mm for the circuit-breaker. On request, the front terminals for cables can be mounted, using the standard circuit-breaker kit.
GSIS0148

S1-S2-S3

beside

Residual current release under the four-pole version circuit-breaker


This is supplied complete with: an opening solenoid to be housed in the area of the third pole, complete with plug-socket connector for connection to the residual current release plug connector to make the connection of the remote opening pushbutton (to be provided by the customer) with the SACE RC212 residual current release flange for compartment door (one for SACE S1, S2; two for SACE S3) protection for assembly in the area
GSIS0149

S1-S2-S3

between the circuit-breaker and residual current release. For SACE S1, S2 circuit-breakers, the residual current release is supplied with front terminals for cables On request, the rear threaded terminals can be mounted, using standard kit of the circuit-breaker. For SACE S3 circuit-breakers, the residual current release is supplied with front terminals (together with a front flange H= 45mm for circuit-breaker). On request, using the standard kit of the circuit-breaker, front terminals for cables, extended front terminals, or rear termi-

under

nals for cables can be mounted or the rear terminals using the kit with 4 pieces for the circuit-breaker can be mounted (code 1SDA023365R1) and the kit for residual current release (code

1SDA025543R1).

ABB SACE

4/27

Accessories
Residual current releases
Technical characteristics
Residual current releases Technology Action Primary operating voltage Operation frequency Range of test operation Rated service current Trip thresholds IDn Tolerance for IDn Trip times Tolerance over trip times Trip signalling Self-supply Input for remote opening Indication of pre-alarm at 50% AC type only for alternating current Type A for alternating current, pushbutton Low sensitivity High sensitivity Mounting under the circuit-breaker Mounting beside the circuit-breaker Dimensions (L x H x P) [mm] 103 x 120 x 70 120 x 120 x 70 140 x 170 x 108 [V] [Hz] [V] [A] [A] [%] [s] [%] instantaneous SACE RC210 polarised type direct up to 500 50 60 Hz 10% 230 ... 500 up to 125 0,3 - 0,5 SACE RC211 electronic with solenoid 220 ... 500 50 60 Hz 10% 220 ... 500 up to 250 0,03 - 0,1 - 0,3 +0, -25 instantaneous SACE RC212 electronic with solenoid 50 ... 500 50 60 Hz 10% 50 ... 500 up to 250 0,03 - 0,1 - 0,3 - 0,5 - 3 +0, -20 0 - 0,1 - 0,25 - 0,5 - 1 - 1,5 20

Connection to the residual current circuit-breaker network

4
Network connection diagrams for which the protection is active even with only one phase supplied with voltage

is active with at least two phases supplied with voltage

(1) T erminal to be connected to the neutral or to the earthing conductor .

4/28

ABB SACE

GSIS0077

Network connection diagrams for which the protection

SACE RCQ switchboard residual-current relays


The SACE Isomax S4, S5, S6, and S7 circuit-breakers can be combined with the SACE RCQ switchboard residual-current relay with separate toroid (to be installed externally on the line conductors) and satisfies requirements with trip thresholds up to 30 A and times up to 5 s or where the installation conditions are particuGSIS9046

larly restrictive, such as circuit-breakers already installed, limited space in the circuit-breaker compartment. Thanks to its wide setting range, the SACE RCQ switchboard residual-current relay is suitable for applications where a coordinated residual current protection system is to be constructed at the various distribution levels, from the main switchboard to the end user. It is particularly suitable where low sensitivity residual current protection is required, for example in partial (current-type) or total (time-type) selective chains, and for high sensitivity applications (with physiological sensitivity) to realise protection of people against direct contacts On a drop in the auxiliary power supply voltage, the opening command intervenes after a minimum time of 100 ms and after the time set plus 100 ms. The SACE RCQ relay is suitable for use in the presence of earth currents of alternating type only (AC Type), for alternating current and/or pushbutton with continuous components (Type A) and is suitable for carrying out residual current selectivity . The SACE RCQ relay is of the type with indirect action and acts on the release mechanism of the circuit-breaker by means of the circuit-breaker shunt opening release (to be ordered by the user) to be housed in the special slot made on the third pole of the circuit-breaker.

Residual-current relay Power supply voltage Operation frequency Trip threshold adjustment IDn - 1a range of adjustments - 2a range of adjustments Trip time adjustment Pre-alarm threshold adjustment Range of use of the closed transformers - Toroidal transformer 60 [mm] - Toroidal transformer 110 [mm] - Toroidal transformer 185 [mm] - Toroidal transformer 110 [mm] - Toroidal transformer 180 [mm] - Toroidal transformer 230 [mm] Alarm pre-threshold signalling [A] [A] [s] [%] x IDn IDn [A] [A] [A] [A] [A] [A] AC [V] DC [V] [Hz]

SACE RCQ 80 ... 500 48 ... 125 50 60 Hz 10% 0,03 - 0,05 - 0,1 - 0,3 - 0,5 1 - 3 - 5 - 10 - 30 0 - 0,1 - 0,2 - 0,3 - 0,5 - 0,7 - 1 - 2 - 3 - 5 25 ... 75% x IDn 0,03 ... 30 0,03 ... 30 0,1 ... 30
I

Range of use of the transformers which can be opened

Dn

0,3 ... 30 0,3 ... 30 1 ... 30 Yellow flashing LED 1 N.O. changeover contact 6 A - 250 V AC 50/60 Hz

Residual-current relay trip signalling

Yellow flashing LED 2 changeover contacts (N.O. N.C.; N.O.) 6 A - 250 VAC 50/60 Hz

Remote opening command Connection to the toroidal transformer Dimensions L x H x D Drilling for assembly on door [mm] [mm]

N.O. Contact Trip time 15 ms By means of 4 twisted conductors Maximum length 5 m 96 x 96 x 131,5 92 x 92

ABB SACE

4/29

Accessories
Accessories for electronic releases
SACE PR212/D-M Modbus and SACE PR212/D-L Lon dialogue unit
The dialogue unit is a device which allows two-way communication from the circuit-breaker to the outside and vice versa. ABB SACE has built two distinct dialogue units able to support two different standard market protocols: SACE PR212/D-M (Modbus RTU protocol) and SACE PR212/D-L (LonTalk protocol by Echelon). Both units are housed in external modules, which can be installed on DIN rails, and can be used with the S4, S5, S6, and S7 circuit-breakers fitted with SACE PR212/P electronic release, both in the LSI and LSIG versions, or SACE PR212/MP release. They must be supplied with a stabilised voltage of 24 VDC (20% with maximum ripple 5%) and be earthed. Communication towards the outside is generally addressed to a supervision and control unit, which has the task of collecting and storing the information regarding the part of the plant controlled. In the case of an error in the serial communication due to a fault in the dialogue unit or lack of auxiliary power supply, the SACE PR212/P protection unit works according to the last parameters set and, in any case, in accordance with what has been set manually. The SACE PR212/ D-M and SACE PR212/D-L dialogue units are always fitted in combination with the SACE PR212/T actuator unit, which allows remote closing or opening operation of the circuit-breaker (Remote Control) by means of two digital outputs which can be disabled thanks to the dip-switch (LOC/REM) positioned on LOC.

Information available
State of the circuit-breaker: open; closed; tripped Installation alarms: pre-alarm L; tripped L-S-I-G-R-V-PTC Measurements: currents; N operations; N trips Reading and writing curves and trip t h re s h o l d s : only manual re a d i n g

(MAN), electronic reading and writing (ELT) Circuit-breaker commands: opening; closing; reset.

4
PR212/DM Protocol Physical means of transmission Speed Architecture PR212/D-M Modbus RTU EIA RS485 9600 19200 bit/s bus PR212/D-L LonTalk TP (Twisted Pair) 78Kbit/s bus

4/30

ABB SACE

SACE PR212/T actuator unit


The SACE PR212/T actuator unit allows circuit-breaker opening and closing by means of the motor operator mounted on the circuit-breaker. It is always supplied in combination with the SACE PR212/D dialogue unit. An auxiliary power supply with a stabilised voltage of 24 VDC (20%, with maximum ripple - 5%) and earthed is required for operation of the unit. The PR212/D dialogue unit sends the digital opening and closing commands, received from the supervision and control system, to the inputs of the SACE
GSIS9043 GSIS9031

PR212/T actuator unit, which carries out circuit-breaker closing and opening by means of a power relay. The motor operator of the circuit-breaker (use the versions with power supply voltage at 110 V AC/DC or 220 V AC) must be connected to these relays.

SACE TT1 Test unit


This allows control of tripping of the SACE PR211/P, SACE PR212/P, and SACE PR212/MP electronic releases and the trip test of the opening solenoid OS. The device is supplied by means of a 12 V replaceable battery and is fitted with a two-pole polarised connector-tracer point housed on the bottom of the box, which allows connection of the device to the test input bushings located on the front of the SACE PR211/P , SACE PR212/P , or SACE PR212/MP releases. The limited dimensions of the accessory make it practically pocket-type. The trip test device can be used on the SACE Isomax S4, S5, S6, S7, and S8 circuitbreakers.

4
SACE PR212/K signalling unit
The SACE PR212/K signalling unit, only available for S8, is able to convert the digital signals supplied by the SACE PR212/P - (LSIG) protection unit into electric signals by means of normally open electrical contacts. An auxiliary power supply is needed to operate the unit. It is connected to the internal bus of the protection unit by means of a dedicated serial line over which the information regarding the state of activation of the protection functions passes, on the basis of which the relative power contacts are closed to signal: pre-alarm for protection function L (I>0.9 x I1) protection function L, S, I, G trip release trip communication error with protection unit.
GSIS9041

PR212/K Auxiliary power supply Maximum current interrupted Maximum voltage interrupted Breaking capacity resistive load Breaking capacity - inductive load Contact/contact insulation Contact/coil insulation 24 V DC 20% maximum ripple 5% 5A 250 V AC / 130 V DC 50 W / 800 VA (48 V DC and 220 V AC) 25 W / 500 VA (48 V DC and 220 V AC) 1000 Veff 2000 Veff

ABB SACE

4/31

Accessories
Accessories for electronic releases
SACE PR010/K signalling unit
The SACE PR010/K signalling unit can convert the signals received via the bus from the SACE PR212/P (LSI or LSIG) and SACE PR212/MP (LRIU) protection units into electric signals by means of normally open electrical power contacts. An auxiliary power supply with a voltage stabilised at 24V DC (20% with maximum ripple - 5%) and ear thed is needed to operate the unit. It is connected to the Internal Bus of the protection unit by means of a dedicated serial line over which the information regarding the state of activation of the protection functions passes, on the basis of which the relative power contacts are closed. In particular, the following signals are available: Alarm signalling remains active for the whole duration of the overload up to any release trip. The protection trip signals remain active during the timing phase and remain that way even after release trip.
GSIS9147

A Reset pushbutton on the front of the unit allows the state of all signals to be reset. There are also two LEDs available on the unit for visually signalling the following information: Power ON: auxiliary power supply present TX (Int Bus): flashing synchronised with the communication activity with the Internal Bus The table below shows the characteristics of the signalling relays available in the SACE PR010/K unit.

K51 1 2

PR212/P (LSI-LSIG) Protection L alarm Protection S alarm Protection I alarm Protection G alarm Bus K.O. Release trip Protection L pre-alarm Auxiliary power supply Maximum current interrupted Maximum voltage interrupted Breaking capacity resistive load Breaking capacity inductive load Contact/contact insulation Contact/coil insulation

PR010/K 24 V DC 20% maximum ripple 5% 5A 250 V AC / 130 V DC 50 W / 800 VA (48 V DC and 220 V AC) 25 W / 500 VA (48 V DC and 220 V AC) 1000 Veff 2000 Veff

3 4 5 7 8

K51 1 2 3 4

PR212/MP (LRIU) Protection L alarm Protection R alarm Protection I alarm Protection U alarm Welded contactor alarm contacts Bus K.O. PTC alarm (temperature sensor on motor) (*) Generic input 0/1 Release trip Protection L pre-alarm Back-up protection alarm

5 6

7 8

(*) alternatively by means of dip-switch

4/32

ABB SACE

SACE PR010/T Test and Configuration Unit


The SACE PR010/T unit is an instrument able to carry out the Test, programming and parameter readout functions for the protection units which equip the SACE Isomax S moulded-case circuit-breakers and the SACE Emax air circuit-breakers. In particular, for circuit-breakers fitted with SACE PR212/P or SACE PR212/MP releases, the test, programming and readout parameter functions are available. All the functions mentioned can be carried out ON BOARD by connection of the SACE PR010/T unit to the multipin front flange connector on the protection unit; connection is guaranteed by means of special interfacing cables supplied as standard with the unit. The man-machine interface is guaranteed by using a membrane keyboard and a multi-line alphanumerical display. There are also two LEDs on the unit which signal the following respectively: POWER-ON and STAND BY situation situation of the battery charging state. possible to upgrade the SW of the SACE PR010/T unit to allow adaptation of the T est unit to evolution of new products. The results of most importance regarding the test can also be stored in the unit itself and sent to the Personal Computer on explicit request for issue of report. Both in automatic and manual mode, the SACE PR010/T unit is able to test the following: protection functions L, S, I, G; protection functions LRIU for SACE
GSIS9045

PR212/MP; monitoring of correct operation of the microprocessor. The SACE PR010/T unit is of the portable type and operates with rechargeable batteries and/or with an external power supply . In its standard supply, the unit includes: SACE PR010/T Test unit complete with rechargeable batteries SACE TT1 Test unit 100...240 V AC /12 V DC external power supply connection cables between the unit and the multipin connector present on the ranges of releases which equip the SACE Isomax S and the SACE Emax series

connection cable between the unit and the PC (serial RS232) power supply cable instruction manual and diskette with application SW plastic container.

Two different types of Test are provided: automatic and manual. By means of connection to the PC (with software provided by ABB SACE), it is

SACE PR212/CI contactor control unit


The SACE PR212/CI accessory unit can be associated with all the circuit-breakers fitted with SACE PR212/MP electronic release for motor protection. When the appropriate dip-switch on the front of the release is positioned on the Normal mode, it allows the contactor to be
GSIS9040

opened in the case of fault for overload L, blocked rotor R or phase missing/ unbalance U. The SACE PR212/CI unit can always be installed both on a DIN rail and on the rear of the door.

ABB SACE

4/33

Accessories
Accessories for electronic releases
CT for external neutral
This is applied to the neutral conductor and allows protection against earth faults with three-pole circuit-breakers to be realised. The circuit-breaker must be fitted with SACE PR212/P LSIG release. The transformer must be connected to the
GSIS9005
Connectors X3

S4 [A] 100 160 250

S5 [A] 320 400 630

S6 [A] 630 800

S7 [A] 1000 1250 1600

S8 [A] 1600 2000 2500 3200

release by means of the specific X3-X4 connectors, selected according to the version of the circuit-breaker and the type of protection release used.

Connectors
These allow connection of the microprocessor-based release to units or components of external plants. They are, in fact,

used to make the relay tripped signal available outside and to connect the protection transformer of the neutral conductor outside the circuit-breaker or to the actuator, dialogue and signalling units, if
GSIS0151
Connectors X4

these are provided.


GSIS0150 GSIS9030

Connector X3 for circuit-breaker fixed fitted with releases SACE PR211/P Connector X3 for plug-in/withdrawable circuit-breaker (to be applied in the fixed part) fitted with SACE PR211/P release Connectors X3-X4 for fixed circuitbreaker fitted with SACE PR212/P release Connectors X3-X4 for plug-in/withdrawable circuit-breaker fitted with SACE PR212/P release

4/34

ABB SACE

Accessories
Installation accessories and spare parts
Bracket for fixing on DIN rail
This is applied to the fixed circuit-breaker and allows installation on standardised DIN rails. It simplifies assembly of circuitbreakers up to 630 A in standard switchboards. Bracket for fixing on DIN EN 50022 rail for SACE S1-S2 circuit-breakers.
GSIS0152

S1-S2

S3-S4-S5

Bracket for fixing on DIN EN 50023 rail


GSIS0153

for SACE S3-S4-S5 circuit-breakers. The fixing bracket kit for SACE S3-S4-S5 circuit-breakers also includes the front flange H = 45mm.

Flange for compartment door


This is always supplied with the circuitbreaker and can also be used with the rotary handle operating mechanism for the SACE S3, S4, S5, S6, and S7 circuitbreakers, the front flange for lever operating mechanism and the motor operator. In case of use of these accessories with SACE S6, S7 circuit-breakers, a flange is supplied to be used instead of the one supplied with the circuit-breaker. It is not supplied for SACE S1, S2, and S3 circuit-breakers which are complete with SACE RC210, RC211, RC212 residual current releases in the version beside the circuit-breaker.
GSIS0154

GSIS9011

S1-S2

S3 ... S7 fixed

S3 ... S7 withdrawable

S8

GSIS9018

GSIS0156

ABB SACE

GSIS0157

GSIS0155

4/35

Accessories
Installation accessories and spare parts
IP54 protection for rotary handle
This allows IP54 degree of protection to be attained. It is available in the following versions: for rotary handle operating mechanism on compartment door with fixed distance for SACE S1-S2 circuit-breakers for rotary handle operating mechanism
GSIS0158 GSIS9034

S1-S2

on compartment door with adjustable distance for circuit-breakers SACE S3S4-S5-S6 and S7 circuit-breakers.

Spare parts
The following spare parts are available: operating lever cover group arcing chambers isolating contacts opening solenoid for the SACE For further details, please ask the Service Division of ABB SACE for the spare parts catalogue. kit with washers, screws and dowels for assembly of the connection terminals.

RC211and RC212 residual current releases

4/36

ABB SACE

Characteristic curves and technical information

Index
Characteristic curves
Trip curves for distribution Circuit-breakers with thermomagnetic releases ................................................................ 5/2 Circuit-breakers with SACE PR211/P, SACE PR212/P electronic releases ..................... 5/7 Trip curves for motor protection Circuit-breakers with magnetic only releases ................................................................... 5/9 Use of the trip curves of circuit-breakers with SACE PR212/MP electronic release ...... 5/10 Circuit-breakers with electronic release SACE PR212/MP ............................................... 5/12 Limitation curves 230 V .................................................................................................................................... 5/14 400-440 V ............................................................................................................................ 5/17 500 V .................................................................................................................................... 5/20 690 V .................................................................................................................................... 5/21 Specific let-through energy curves 230 V .................................................................................................................................... 5/24 400-440 V ............................................................................................................................ 5/27 500 V .................................................................................................................................... 5/30 690 V .................................................................................................................................... 5/31

Technical information
Temperature performance Circuit-breakers with electronic releases .......................................................................... 5/34 Circuit-breakers with thermomagnetic releases ................................................................ 5/39 Power loss values ............................................................................................................. 5/40 Operation and protection of the low-voltage side of three-phase transformers .. 5/42 Operation and protection of three-phase AC capacitors .......................................... 5/44 Protection of three-phase AC generators .................................................................... 5/46 Applications in direct current ......................................................................................... 5 /47 Backup protection (backup table) ................................................................................. 5/50 ABB SACE 5/1

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE S1 125 - S2 160
Magnetic tripping threshold Im = 10 x Ith

t [s]

104

103

102

10

S1

R50125 R50160 R40 R32 R25 R20 R16 R12,5 R10

10-1

S2

10-2
1,05
GSIS0201 GSIS0202

10-1

10

102 x Ith

SACE S1 125 - S2 160


Magnetic tripping threshold Im = 5 x Ith

t [s]

104

103

102

5
10

S1

R40125 R40160 R32 R25 R16 R20 R12,5 R10

10-1

S2

10-2
1,05

10-1

10

102 x Ith

5/2

ABB SACE

SACE S2X 100


Magnetic tripping threshold Im = 10 x Ith

t [s]

104

103

102

10

10-1

10-2
1,05
GSIS0203

10-1

10

102 x Ith

SACE S3 160
= 70

Y
= 70 70 650 120 70 = 70 70 = 46 13.5 284

Magnetic tripping threshold Im = 10 x Ith

= 375 =

30

= 350 =

101 A

= 331 =

273 =

101

525

5
65 103.5 288

10.5

4 2
Y

27.5

Y
51.5 70 70 70 48.5

5
= 273 26

293 =

20

280

109 129 = 109 101 109 779

1
=

= 525 = 9

820 =

175

129 = 109

273

26

2
Y
= = 27.5 17 310

65

288

ABB SACE

5/3

GSIS0204

GSIS0024

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE S3 160 - S3 250
Magnetic tripping threshold Im = 10 x Ith

t [s]

104

103

102

10

S3 160 R80R160

10-1

S3 250 R200, R250

10-2
1,05
GSIS0205 GSIS0206

10-1

10

102 x Ith

SACE S3 160
Magnetic tripping threshold Im = 5 x Ith

t [s]

104

103

102

10

10-1
R50 R32

10-2
1,05

10-1

10

102 x Ith

5/4

ABB SACE

SACE S3 160 - S3 250


Magnetic tripping threshold Im = 3 x Ith Magnetic tripping threshold Im = 5 x Ith

t [s]

104

103

102

10

S3 160 R80R160

10-1

S3 250 R200, R250

10-2
1,05
GSIS0207

10-1

10

102 x Ith

SACE S5 400 (R320-400) SACE S5 630 (R500)


Thermal tripping threshold In = 0,71 x Ith Magnetic tripping threshold Im = 510 x Ith

t [s]

104

103

102

10

10-1

10-2
1,05
GSIS0208

10-1

10

102 x Ith

ABB SACE

5/5

Trip curves for distribution


Circuit-breakers with thermomagnetic releases
SACE S6 630 (R630)
Thermal tripping threshold In = 0,71 x Ith Magnetic tripping threshold Im = 510 x Ith

t [s]

104

103

102

10

10-1

10-2
1,05
GSIS0209 GSIS0210

10-1

10

102 x Ith

SACE S6 800 (R800)


Thermal tripping threshold In = 0,71 x Ith Magnetic tripping threshold Im = 510 x Ith

t [s]

104

103

102

10

10-1

10-2
1,05

10-1

10

102 x Ith

5/6

ABB SACE

Trip curves for distribution


Circuit-breakers with electronic releases
SACE S4-S5-S6-S7
SACE PR211/P Functions LI - I
103

t [s]

104

0,5 0,4

0,7 0,95 0,6 0,8 1 0,9 1,5

N.B. For S5 630 The maximum threshold that can be set for the I function is 8 x In

102

D C B A

4 6 8

10

D C B A

10 12

10-1

10-2
1,05
GSIS0211

10-1

10

102 x In

SACE S4-S5-S6-S7-S8
SACE PR212/P Function LSI, S inverse short delay (I2t = constant ON)
N.B. For S5 630 The maximum threshold that can be set for the I function is 8 x In

t [s]

104
0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1 0,4 1

103
1,5

102

D C B
1

4 6

5
8

10

C B A

2 3 4 6

D C B A
8

10 12

10

10-1

I2t ON

10-2
1,05
GSIS0212

10-1

10

102 x In

ABB SACE

5/7

Trip curves for distribution


Circuit-breakers with electronic releases
SACE S4-S5-S6-S7-S8
SACE PR212/P Function LSI, S definite short delay (I2t = constant OFF)
N.B. For S5 630 The maximum threshold that can be set for the I function is 8 x In

t [s]

104
0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1

0,4

103
1,5 2

102

D C B A
1

4 6 8

10

2 3 4

D C B A
6

10 12

1
D C

8 10

10-1

B A

I2t OFF

10-2
1,05
GSIS0213 GSIS0214

10-1

10

102 x In

SACE S4-S5-S6-S7-S8
SACE PR212/P Function G

t [s]

104

0,2

0,3 0,4

0,6

0,8 0,9 1

103

102

10

D C B

10-1

10-2
1,05

10-1

10

102 x In

5/8

ABB SACE

Trip curves for motor protection


Circuit-breakers with magnetic only releases
SACE S2X 80
Fixed magnetic tripping threshold Im = 13 x Ith

t [s]

104
13 4 12

103

SACE S3
Adjustable magnetic tripping threshold Im = 412 x Ith

S2X80

102

S3

S3

10

10-1

10-2
1,05
GSIS0215

10-1

10

102 x In

ABB SACE

5/9

Trip curves for motor protection


Use of the trip curves of circuit-breakers with SACE PR212/MP electronic release
For correct parameter setting of the SACE PR212/MP electronic release, it may be useful to compare the overall circuit-breaker curve with the motor starting curve. For this purpose, with the protection function graphics shown on the following pages, it is possible to draw the overall curve required for the circuit-breaker fitted with SACE PR212/MP release simply and immediately.

N.B. For function L, as for all the other functions, make sure you place a glossy tracing sheet over the curve so that the time the axis of the co-ordinates coincide.

s on

Function L (cannot be excluded) Protection against overload


T o protect the motor against any overloads, as a first step it is necessary to adjust function L to a current or equal to the rated current of the motor Ie:

Function I (cannot be excluded) Protection against short-circuit


This protection function against short-circuit recognises whether the motor is in the starting phase, thereby avoiding unwarranted trips; the trip threshold can be set from 6 x In to 13 x In. To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function I so that I/In = 1 (on the glossy sheet) corresponds to I/In = 1 (on the graph) and draw the desired curve.

I1 higher than I1 > Ie.

For example, if Ie = 135 A, an S4H160 circuit-breaker can be selected with In = 160 A and the following adjustment carried out: I1 = 0.85 x In = 136 A. The second step is to select the trip class according to the motor starting time

ta.

For a motor with a start-up overload

of 6 seconds, class 10 can be selected, with a trip time of 8s at 7.2 x I1. T o trace the curve correctly on the glossy sheet, according to

I/In,

simply place the glossy sheet over the graph of

function L so that I/In = 0.85 (on the glossy sheet) corresponds to I/I1 = 1 (on the graph) and draw the curve relative to class 10.

Function U (can be excluded) Protection against loss and/or unbalance of a phase


Protection against loss or unbalance of a phase, if set to ON, intervenes when one or two phases have a current lower than 0.4xI1 (0.4 x 0.85 x In = 0.4 x 0.85 x 160 A = 54.4A in this case).

Function R (can be excluded) Protection against rotor blockage


Protection against rotor blockage can be set both with re-

To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function U so that I/In = I1/In (on the glossy sheet) corresponds to I/I1 = 1 (on the graph). In this case I/In = I1/In = 0.85, desired curve. and draw the

I5 = 3 ... 10xI1 (in this case I5 = 3 ... 10 x 0.85 x 160), and with regard to the trip time t5.
gard to the trip current To trace the curve correctly on the glossy sheet, simply place the glossy sheet over the graph of function R so that I/In = I1/In (on the glossy sheet) corresponds to I/I1 = 1 (on the graph). In this case I/In = I1/In = 0.85, desired curve. and draw the

5/10

ABB SACE

Typical operating characteristic of an asynchronous motor


l1 l3 I5 t5 I6 t6 le la Ip ta tp m c
= = = = = = = = = function L trip current function I trip current function R trip current function R trip time function U trip current function U trip time rated service current of the motor motor starting current peak value of the sub-transient starting current = = = = motor starting time duration of the sub-transient starting phase typical motor starting curve example of trip curve of a motor protection circuit-breaker with electronic release

ABB SACE

GSIS0082

5/11

Trip curves for motor protection


Circuit-breakers with electronic releases SACE PR212/MP
SACE S4-S5-S6-S7
SACE PR212/MP Function L (hot and cold trip)

t [s]

105

hot

104

cold

103

102

10
30 20 10 30 20 10 10A

10A

10-1
1,05
GSIS0216 GSIS0217

10-1

10

102 I / I1

SACE S4-S5-S6-S7
SACE PR212/MP Function L (hot trip with 1 or 2 phases supplied)

t [s]

105

hot

104

103

5
102

10

30

20 10 10A

10-1
1,05

10-1

10

102 I / I1

5/12

ABB SACE

SACE S4-S5-S6-S7
SACE PR212/MP Function R - U

t [s]

105

Function U

104

Function R

103

102

4 5 6 7 8 10

10

10 7 4

10-1
1,05
GSIS0218

10-1

10

102 I / I1

SACE S4-S5-S6-S7
SACE PR212/MP Function I

t [s]

103
13 12 11

102
9 8

10

10
6

10-1

10-2

10-3
1,05
GSIS0219

10-1

10

102 x In

ABB SACE

5/13

Limitation curves
230 V
SACE S1

Ip [kA] 100

50

20
125 100 80

10 1 5

63 50 40 32 25 20 16 12,5 10

1
GSIS0220 GSIS0221

10

20

50

100

200

500

1000 Is [kA]

SACE S2

Ip [kA] 100

50

20
160 125 100

10

80 63 50 40

32 25 20 16 12,5

1 1 2 5 10 20 50 100 200 500 1000 Is [kA]

5/14

ABB SACE

SACE S3 160, S3 250

Ip [kA] 100

50
250 200 160 125

20

100 80 50 32

10

1 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0222

SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

Ip [kA] 300 200


S7 S8

100
S6 800 S6 630

50

S5 S4 250 S4 160

20

10

3
GSIS0223

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/15

Limitation curves
230 V
SACE S2X 80, S2X 100

Ip [kA] 100

10

42-52-6380-100 25-32 20 16 12,5 11

8,5 6,5 5 4 3,2 2,5

0,1

2 1,6 1

SACE S3X 125, S3X 200, S4X, S6X

Ip [kA] 100

50
S6X

S4X

20

S3X 200 In200 S3X 200 In160

10

S3X 200 In125 S3X 125 In125 S3X 125 In100

S3X 125 In80 S3X 125 In50 S3X 125 In32

1
GSIS0225

10

20

50

100

200

500

1000 Is [kA]

5/16

ABB SACE

GSIS0224

0,01 0,01

0,1

10

100

1000 Is [kA]

Limitation curves
400-440 V
SACE S1

Ip [kA] 100

50

20
125 100 80

10

63 50 40 32

25 20 16 12,5 10

1
GSIS0226

10

20

50

100

200

500

1000 Is [kA]

SACE S2

Ip [kA] 100

50

160

20

125 100 80 63

10

50 40 32 25

20 16 12,5

1
GSIS0227

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/17

Limitation curves
400-440 V
SACE S3 160, S3 250

Ip [kA] 100

50
250 200

160

20

125 100 80

10

50 32

1
GSIS0228 GSIS0229

10

20

50

100

200

500

1000 Is [kA]

SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

Ip [kA] 300 200


S8 S7

100
S6 800

S6 630

50

S5 S4 250 S4 160

20

10

3 1 2 5 10 20 50 100 200 500 1000 Is [kA]

5/18

ABB SACE

SACE S2X 80, S2X 100

Ip [kA] 100

42-52-6380-100

10

25-32 20 16 12,5 11 8,5

6,5 5 4 3,2 2,5 2 1,6

0,1

0,01 0,01 1 10
GSIS0230

0,1

100

1000 Is [kA]

SACE S3X 125, S3X 200, S4X, S6X

Ip [kA] 100
S6X

50
S4X S3X 200 In 200 S3X 200 In 160

20

S3X 200 In 125 S3X 125 In 125 S3X 125 In 100

10

S3X 125 In 80 S3X 125 In 50

S3X 125 In 32

1
GSIS0231

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/19

Limitation curves
500 V
SACE S1

Ip [kA] 100

50

20

125

10

100 80 63 50

40 32 25 20 16

12,5 10

1 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0232

5/20

ABB SACE

Limitation curves
690 V
SACE S2

Ip [kA] 100

50

20

10

160 125 100 80

63 50 40 32 25

20 16 12,5

1
GSIS0233

10

20

50

100

200

500

1000 Is [kA]

SACE S3 160, S3 250

Ip [kA] 100

50

20

250 200 160 125

10

100 80 50 32

1
GSIS0234

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/21

Limitation curves
690 V
SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

Ip [kA] 300 200

100

S8

S7

50
S6 800 S6 630 S5 S4 250

20

S4 160

10

SACE S2X 80, S2X 100

Ip [kA] 100

10

42-52-6380-100 25-32

5
1

20 16 12,5 11 8,5 6,5 5 4 3,2

0,1

2,5 2 1,6 1

5/22

ABB SACE

GSIS0236

0,01 0,01

0,1

10

100

1000 Is [kA]

GSIS0235

10

20

50

100

200

500

1000 Is [kA]

SACE S3X 125, S3X 200, S4X, S6X

Ip [kA] 100

S6X

50
S4X S3X 200 In 200 S3X 200 In 160

20

S3X 200 In 125 S3X 125 In 125

10

S3X 125 In 100 S3X 125 In 80 S3X 125 In 50

S3X 125 In 32

1
GSIS0237

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/23

Specific let-through energy curves


230 V
SACE S1

I2t [A2s] 108

107

106

125 100 80 63 50 40

105

32 25 20 16 12,5 10

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0238 GSIS0239

SACE S2

I2t [A2s] 108

107

5
160

106

125 100 80 63 50 40

105

32 25 20 16 12,5

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]

5/24

ABB SACE

SACE S3 160, S3 250

I2t [A2s] 108

107

250 200

106

160 125 100 80 50 32

105

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0240

SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

I2t [A2s] 109

S8

108

S7

5
S6 800

107
S6 630 S5 S4 250 S4 160

106

105
GSIS0241

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/25

Specific let-through energy curves


230 V
SACE S2X 80, S2X 100

I2t [A2s] 106

105

42-52-6380-100 25-32 20 16 12,5

104

11 8,5 6,5 5 4

103

3,2 2,5

102

1,6

10
GSIS0242 GSIS0243

0,01

0,1

10

100

1000 Is [kA]

SACE S3X 125, S3X 200, S4X, S6X

I2t [A2s] 108

107
S6X

5
S4X

106

S3X 200 In 200 S3X 200 In 160 S3X 200 In 125 S3X 125 In 125

105

S3X 125 In 100 S3X 125 In 80 S3X 125 In 50 S3X 125 In 32

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]

5/26

ABB SACE

Specific let-through energy curves


400-440 V
SACE S1

I2t [A2s] 108

107

125 100 80

106

63 50 40 32

105

25 20 16 12,5 10

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0244

SACE S2

I2t [A2s] 108

107

160 125 100

106

80 63 50 40 32

105

25 20 16 12,5

104
GSIS0245

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/27

Specific let-through energy curves


400-440 V

SACE S3 160, S3 250

I2t [A2s] 108

107

250 200 160 125

106

100 80 50 32

105

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0246 GSIS0247

SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

I2t [A2s] 109

S8

S7

108

5
S6 800 S6 630

107

S5 S4 250 S4 160

106

105

10

20

50

100

200

500

1000 Is [kA]

5/28

ABB SACE

SACE S2X 80, S2X 100

I2t [A2s] 106


42-52-6380-100

105

25-32 20 16 12,5 11 8,5

104

6,5 5 4 3,2 2,5

103
2 1,6

102
1

10
GSIS0248

0,01

0,1

10

100

1000 Is [kA]

SACE S3X 125, S3X 200, S4X, S6X

I2t [A2s] 108

107

S6X

S4X S3X 200 In 200

106

S3X 200 In 160 S3X 200 In 125 S3X 125 In 125 S3X 125 In 100

105

S3X 125 In 80 S3X 125 In 50 S3X 125 In 32

104
GSIS0249

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/29

Specific let-through energy curves


500 V
SACE S1

I2t [A2s] 108

107

106

125 100 80 63 50 40

105

32 25 20 16 12,5 10

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0250

5/30

ABB SACE

Specific let-through energy curves


690 V
SACE S2

I2t [A2s] 108

107

160

106

125 100 80 63 50 40

105

32 25 20 16 12,5

104 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0251

SACE S3 160, S3 250

I2t [A2s] 108

107

250 200 160

106

125 100 80 50 32

105

104
GSIS0252

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/31

Specific let-through energy curves


690 V
SACE S4 160, S4 250, S5, S6 630, S6 800, S7, S8

I2t [A2s] 109

108
S8

S7 S6 800

107

S6 630 S5 S4 250 S4 160

106

105 1 2 5 10 20 50 100 200 500 1000 Is [kA]


GSIS0253 GSIS0254

SACE S2X 80, S2X 100

I2t [A2s] 106

42-52-6380-100 25-32

105

20 16 12,5

5
104

11 8,5 6,5 5 4 3,2 2,5

103

2 1,6 1

102

10 0,01 0,1 1 10 100 Is [kA]

5/32

ABB SACE

SACE S3X 125, S3X 200, S4X, S6X

I2t [A2s] 108

S6X

107

S4X S3X 200 In 200 S3X 200 In 160

106

S3X 200 In 125 S3X 125 In 125 S3X 125 In 100 S3X 125 In 80

105

S3X 125 In 50 S3X 125 In 32

104
GSIS0255

10

20

50

100

200

500

1000 Is [kA]

ABB SACE

5/33

Temperature performance
Circuit-breakers with electronic releases

SACE S4 160
Fixed
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I1 Imax [A] 160 1 160 160 1 160 160 1 160 160 1 160 I1 1 1 1 1 60 C Imax [A] 160 160 160 160 I1 1 1 1 1 70 C Imax [A] I1 160 1 160 1 152 0.95 152 0.95

Plug-in - Withdrawable
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I 1 Imax [A] 160 1 160 160 1 160 160 1 160 160 1 160 60 C I 1 Imax [A] 1 160 1 160 1 160 1 160 70 C I1 Imax [A] I1 1 152 0.95 1 152 0.95 1 144 0.9 1 144 0.9

Front flat bar Front for cables

Front flat bar Front for cables

Rear for cables Rear threaded

Rear for cables Rear threaded

SACE S4 250
Fixed
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I1 Imax [A] 250 1 250 250 1 250 250 1 250 250 1 250 I1 1 1 1 1 60 C Imax [A] 250 250 250 250 I1 1 1 1 1 70 C Imax [A] I1 237.5 0.95 237.5 0.95 225 0.9 225 0.9

Plug-in - Withdrawable
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I 1 Imax [A] 250 1 250 250 1 250 250 1 250 250 1 250 60 C I 1 Imax [A] 1 250 1 250 1 250 1 250 70 C I1 Imax [A] I1 1 225 0.9 1 225 0.9 1 200 0.8 1 200 0.8

5
Front flat bar Front for cables Front flat bar Front for cables

Rear for cables Rear threaded

Rear for cables Rear threaded

5/34

ABB SACE

GSIS0257

GSIS0256

SACE S5 400
Fixed
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I 1 Imax [A] 400 1 400 400 1 400 400 1 400 400 1 400 I1 1 1 1 1 60 C Imax [A] 400 400 400 400 I1 1 1 1 1 70 C Imax [A] I1 380 0.95 380 0.9 360 0.9 320 0.8

Plug-in - Withdrawable
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C 60 C 70 C Imax [A] I 1 Imax [A] I 1 Imax [A] I 1 Imax [A] I1 400 1 400 1 400 1 380 0.95 400 1 400 1 380 0.95 360 0.9 400 1 400 1 380 0.95 360 0.9 400 1 380 0.95 360 0.9 320 0.8

Front flat bar

Front flat bar Front for cables Rear for cables Rear threaded

Front for cables Rear for cables

Rear threaded

SACE S5 630
Fixed
Front flat bar Front for cables Rear threaded up to 40 C 50 C 60 C 70 C Imax [A] I 1 Imax [A] I1 Imax [A] I1 Imax [A] I1 630 1 598.5 0.95 567 0.9 504 0.8 630 1 567 0.9 504 0.8 441 0.7 630 1 504 0.8 441 0.7 378 0.6

Withdrawable
Front flat bar Rear flat bar Rear threaded up to 40 C 50 C 60 C 70 C Imax [A] I 1 Imax [A] I 1 Imax [A] I 1 Imax [A] I1 630 1 504 0.8 441 0.7 378 0.6 630 1 567 0.9 504 0.8 441 0.7 630 1 441 0.7 378 0.6 315 0.5

GSIS0258

5
Front flat bar Rear flat bar

Front for cables Front flat bar

Rear threaded

Rear threaded

ABB SACE

5/35

GSIS0259

Temperature performance
Circuit-breakers with electronic releases

SACE S6 630
Fixed
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I1 Imax [A] 630 1 630 630 1 630 630 1 630 630 1 630 I1 1 1 1 1 60 C 70 C Imax [A] I1 Imax [A] I1 630 1 598.5 0.95 598.5 0.95 567 0.9 598.5 0.95 567 0.9 567 0.9 504 0.8

Withdrawable
Front flat bar Rear vertical flat bar Rear horizontal flat bar up to 40 C 50 C 60 C 70 C Imax [A] I 1 Imax [A] I 1 Imax [A] I1 Imax [A] I1 630 1 630 1 598.5 0.95 567 0.9 630 1 630 1 598.5 0.95 567 0.9 630 1 598.5 0.95 567 0.9 504 0.8

Front flat bar

Front flat bar Rear vertical flat bar

Rear horizontal flat bar Front for cables

Rear threaded

SACE S6 800
Fixed
Front flat bar Front for cables Rear for cables Rear threaded up to 40 C 50 C Imax [A] I1 Imax [A] 800 1 800 800 1 800 800 1 800 800 1 800 I1 1 1 1 1 60 C 70 C Imax [A] I1 Imax [A] I1 800 1 760 0.95 760 0.95 720 0.9 760 0.95 720 0.9 720 0.9 640 0.8

Plug-in - Withdrawable
Front flat bar Rear vertical flat bar Rear horizontal flat bar up to 40 C 50 C 60 C 70 C Imax [A] I 1 Imax [A] I 1 Imax [A] I1 Imax [A] I1 800 1 800 1 760 0.95 720 0.9 800 1 800 1 760 0.95 720 0.9 800 1 760 0.95 720 0.9 640 0.8

Front flat bar

Front flat bar Rear vertical flat bar

Rear horizontal flat bar

Front for cables Rear for cables

Rear threaded

5/36

ABB SACE

GSIS0261

GSIS0260

SACE S7 1250
Fixed
Front flat bar Rear vertical flat bar Front for cables Rear horizontal flat bar up to 40 C Imax [A] I1 1250 1 1250 1 1250 1 1250 1 50 C Imax [A] 1250 1250 1250 1250 I1 1 1 1 1 60 C 70 C Imax [A] I1 Imax [A] I1 1250 1 1187.5 0.95 1250 1 1187.5 0.95 1187.5 0.95 1125 0.9 1250 1 1125 0.9

Withdrawable
Front flat bar Rear vertical flat bar Rear horizontal flat bar up to 40 C Imax [A] I1 1250 1 1250 1 1250 1 50 C Imax [A] 1250 1250 1250 60 C 70 C I 1 Imax [A] I 1 Imax [A] I1 1 1187.5 0.95 1125 0.9 1 1187.5 0.95 1125 0.9 1 1125 0.9 1000 0.8

Front flat bar Rear vertical flat bar

Front flat bar Rear vertical flat bar

Rear horizontal flat bar

Front for cables

Rear horizontal flat bar

SACE S7 1600
Fixed
Front flat bar Rear vertical flat bar Rear horizontal flat bar up to 40 C Imax [A] I1 1600 1 1600 1 1600 1 50 C 60 C Imax [A] I1 Imax [A] I1 1520 0.95 1440 0.9 1520 0.95 1440 0.9 1440 0.9 1280 0.8 70 C Imax [A] I1 1280 0.8 1280 0.8 1120 0.7

Withdrawable
Front flat bar Rear vertical flat bar Rear horizontal flat bar up to 40 C Imax [A] I1 1600 1 1600 1 1600 1 50 C Imax [A] I1 1440 0.9 1440 0.9 1280 0.8 60 C 70 C Imax [A] I 1 Imax [A] I1 1280 0.8 1120 0.7 1280 0.8 1120 0.7 1120 0.7 906 0.6

GSIS0262

Front flat bar Rear vertical flat bar

Front flat bar Rear vertical flat bar

Rear horizontal flat bar

Rear horizontal flat bar

ABB SACE

5/37

GSIS0263

Temperature performance
Circuit-breakers with electronic releases

SACE S8 2000
Fixed
Front flat bar Rear vertical flat bar up to 40 C Imax [A] I1 2000 1 2000 1 50 C Imax [A] I1 2000 1 2000 1 60 C 70 C Imax [A] I1 Imax [A] I1 1900 0,95 1715 0,85 2000 1 1785 0,9

SACE S8 2500
Fixed
Front flat bar Rear vertical flat bar up to 40 C 50 C Imax [A] I1 Imax [A] I1 2500 1 2500 1 2500 1 2500 1 60 C 70 C Imax [A] I1 Imax [A] I1 2270 0,9 2040 0,8 2375 0,95 2130 0,85

2050
Rear vertical flat bar

2550
Rear vertical flat bar

2500 2000 2450 1950 2400 2350

1900

2300 1850 2250 1800


Front flat bar

2200

Front flat bar

1750

2150 2100

1700 2050 1650 30 35 40 45 50 55 60 65 70 2000 30 35 40 45 50 55 60 65 70


GSIS0264

SACE S8 3200
Fixed
Rear vertical flat bar up to 45 C 50 C 60 C 70 C Imax [A] I1 Imax [A] I1 Imax [A] I1 Imax [A] I1 3200 1 3060 0,95 2780 0,85 2510 0,8

3300

3200

3100

3000

2900

2800

Rear vertical flat bar


2700

2600

30

35

40

45

50

55

60

65

70

5/38

GSIS0265

2500

ABB SACE

Temperature performance
Circuit-breakers with thermomagnetic releases
SACE S1
10 C R 10 R 12,5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 13 13 20 24 30 38 49 60 75 96 120 145 20 C 12 12 18,5 22,5 28 36 45 56 71 91 114 138 30 C 11 11 17 21 26,5 34 43 53 67 86 108 132 40 C 10 10 16 20 25 32 40 50 63 80 100 125 50 C 9 9 15 19 23 30 37 47 59 74 94 120 60 C 8 8 14 18 21 28 35 44 55 68 88 112 70 C 7 7 13 17 19 26 34 41 51 62 82 104

SACE S2
R 12,5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160 11...15,5 14...19 18...24,5 21...30 28...38 33...47 44...58 53...74 66...94 84...118 102...145 130...184 10...14,5 13...18 16,5...23 19,5...28 25,5...36 32...45 39...56 50...70 63...90 80...112 100...140 125...176 9,5...13 11,5...17 15...21,5 18,5...26,5 24...34 30...42 38...53 47...66 59...85 76...106 93...133 120...168 9...12,5 11...16 14...20 17,5...25 22,5...32 28...40 35...50 44...63 56...80 70...100 88...125 112...160 8...11,5 10,5...15 13...18 16,5...23 20,5...29 26...37 33...47 42...60 52...75 65...94 81...116 106...150 7,5...10,5 9,5...14 12...17 15...21 19...27 24...34 30...43 38...56 49...70 59...85 75...108 100...140 6,5...9,5 8,5...13 11...16 13...19 17...25 21...31 27...40 34...52 44...65 49...75 58...101 90...130

SACE S3
R 32 R 50 R 80 R 100 R 125 R 160 R 200 R 250 26...43 37...62 59...98 83...118 103...145 130...185 162...230 200...285 24...39 35...58 55...92 80...113 100...140 124...176 155...220 193...275 22...36 33...54 52...86 74...106 94...134 118...168 147...210 183...262 19...32 30...50 48...80 70...100 88...125 112...160 140...200 175...250 16...27 27...46 44...74 66...95 80...115 106...150 133...190 168...240 14...24 25...42 40...66 59...85 73...105 100...104 122...175 160...230 11...21 22...39 32...58 49...75 63...95 90...130 107...160 150...220

SACE S5 400/630
R 320 R 400 R 500 260...368 325...465 435...620 245...350 310...442 405...580 234...335 295...420 380...540 224...320 280...400 350...500 212...305 265...380 315...450 200...285 250...355 280...400 182...263 230...325 240...345

SACE S6 630/800
R 630 R 800 520...740 685...965 493...705 640...905 462...660 605...855 441...630 560...800 405...580 520...740 380...540 470...670 350...500 420...610

ABB SACE

5/39

Power loss values

Power [W]
Setting R 10 R 12,5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160 R 200 R 250 R 320 R 400 R 500 R 630 R 800 In= 100 In= 160 In= 250 In= 320 In= 400 In= 630 In= 800 In= 1000 In= 1250 In= 1600 Iu [A] 10 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250 320 400 500 630 800 100 160 250 320 400 630 800 1000 1250 1600 2000 2500 3200 F 4 6 8 8 9 13 11 13 15 19 16 20

S1
P 4,5 6,5 8,5 8,5 9,5 14 12 14 16 20 17 22 6 7,5 8 10 14 10 13 16 21 18 24 30 F

S2
P F

S3
P-W F

S4
P-W F

S5
P-W F

S6
W F

S7
W

S8
F

6,5 8,5 9 11 15 11 14 17 23 20 26 35 18 21 20 30 36 50 21 25 26 40 46 65 60 65 90 96 92 93 5 15 40 8 22 55 45 60 170 65 90 200 90 96 115 125 102 160 260 140 220 360 200 315 500 117 119 16 18 12 13

In= 2000 In= 2500 In= 3200

The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and fourpole fixed version apparatus. For the latter, the current of the neutral is nil by definition.

5/40

ABB SACE

Power [W]
Setting R1 R 1,6 R 2,5 R 4,3 R 6,3 R 10 R 12,5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 200 In= 250 In= 400 In= 630 Iu [A] 1 1,6 2,5 4,3 6,3 10 12,5 16 20 25 32 40 50 63 80 100 125 200 250 400 630 F 8 8 11 11 11 16 20 10 13 13 26 26 22 22 26

S2X 80
P 8,2 8,2 11,2 11,2 11,2 16,3 20,3 10,6 13,6 13,7 26,6 26,9 23,3 24,1 29,1 F 8 8 11 11 11 16 20 10 13 13 26 26 22 22 26 30

S2X 100
P 8,2 8,2 11,2 11,2 11,2 16,3 20,3 10,6 13,6 13,7 26,6 26,9 23,3 24,1 29,1 34,4 30,8 48 F

S3X
P-W F

S4X
P-W F

S6X
W

37,8 58 60 75 80,4 126,6 101 151,6

The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and fourpole fixed version apparatus. For the latter, the current of the neutral is nil by definition.

Shock resistance
T ests according to IEC 60068-2-27

Shock value [g] S1 ** S2 ** S3-S3X * S4X-S4X * S5 * S6-S6X * S7 *


12 12 12 12 12 12 12

* for fixed/plug-in/withdrawable circuitbrakekers with motor operator, undervoltage release and auxiliary contacts ** for fixed/plug-in circuit-brakekers with

undervoltage release and auxiliary contacts

ABB SACE

5/41

Operation and protection of the low-voltage side of three-phase transformers

In order to choose the SACE Isomax S circuit-breakers to install both on the transformer risers and on the lines branching downstream of them, reference can be made to the following table dealing with transformers with no-load voltage on the secondary equal to 400 V which is the most common condition

of use. The table has been drawn up considering infinite power upstream and the most unfavourable case has been assumed, that is, that the short circuit occurs on the transformer clamps. As regards users, the short circuit is considered downstream of the user circuit-breaker clamps.

Power supply transformers


P [kVA] 1 x 63 2 x 63 1 x 100 2 x 100 1 x 125 2 x 125 1 x 160 2 x 160 1 x 200 2 x 200 1 x 250 2 x 250 1 x 315 2 x 315 1 x 400 2 x 400 1 x 500 2 x 500 1 x 630 2 x 630 4 4 4 4 4 4 4 4 4 Ucc % 4 Ib riser [A] 91 91 144 144 180 180 231 231 289 289 361 361 455 455 577 577 722 722 909 909 909 5 1155 1155 1155 5 1443 1443 1443 5 1804 1804 1804 6,25 2309 2309 2309 6,25 2887 2887 2887 Ib total [A] 91 182 144 288 180 360 231 462 289 578 361 722 455 910 577 1154 722 1444 909 1818 2727 1155 2310 3465 1443 2886 4329 1804 3608 5412 2309 4618 6927 2887 5774 8661

Circuit-breaker "A"(secondary of transformer)


Icc riser [kA] 2,2 2,2 3,6 3,6 4,5 4,5 5,8 5,8 7,2 7,2 9 9 11,3 11,3 14,4 14,4 18 18 23 23 46 23 23 46 29 29 58 36 36 72 37 37 74 46 46 92 SACE Isomax S type S1B125 S1B125 S2B160 S2B160 S3N/S4N250 S3N/S4N250 S3N/S4N250 S3N/S4N250 S5N400 S5N400 S5N400 S5N400 S6N630 S6N630 S6N630/S6N800 S6N630/S6N800 S6N800/S7S1250 S6N800/S7S1250 S7S1250 S7S1250 S7S1250 S7S1250/S7S1600 S7S1250/S7S1600 S7S1250/S7S1600 S7S1600 S7S1600 S7H1600 S8H2000 S8H2000 S8H2000 S8H2500 S8H2500 S8H2500 S8H3200 S8H3200 S8V3200 Release TM / PR211-212 type R100 R100 R160 R160 R200/In = 250 A R200/In = 250 A R250/In = 250 A R250/In = 250 A In = 320 A In = 320 A In = 400 A In = 400 A In = 630 A In = 630 A In = 630/800 A In = 630/800 A In = 800/1000 A In = 800/1000 A In = 1000 A In = 1000 A In = 1000 A In = 1250/1600 A In = 1250/1600 A In = 1250/1600 A In = 1600 A In = 1600 A In = 1600 A In = 2000 A In = 2000 A In = 2000 A In = 2500 A In = 2500 A In = 2500 A In = 3200 A In = 3200 A In = 3200 A settings 0,95 0,95 0,95 0,95 0,95/0,8 0,95/0,8 0,95/0,95 0,95/0,95 0,95 0,95 0,95 0,95 0,8 0,8 0,95/0,8 0,95/0,8 0,95/0,8 0,95/0,8 0,95 0,95 0,95 0,95/0,8 0,95/0,8 0,95/0,8 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,95 0,95 ABB SACE

3 x 630 1 x 800 2 x 800 3 x 800 1 x 1000 2 x 1000 3 x 1000 1 x 1250 2 x 1250 3 x 1250 1 x 1600 2 x 1600 3 x 1600 1 x 2000 2 x 2000 3 x 2000 5/42

Circuit-breaker "B" (user outgoing)


Icu user [kA] 2,2 4,4 3,6 7,2 4,5 9 5,8 11,6 7,2 14,4 9 18 11,3 22,6 14,4 28,8 18 36 23 46 69 23 46 69 29 58 87 36 72 108 37 74 111 46 92 138 ABB SACE 32 A S250 S250 S250 S250 S250 S250 S250 S1B125 S250 S1B125 S250 S1N125 S1B125 S1N125 S1B125 S2N160 S1N125 S2N160 S1N125 S2S160 S2X100 S1N125 S2S160 S2X100 S2N160 S2X100 S4L160 S2N160 S3L160 S3X125 S2S160 S3L160 S3X125 S2S160 S4L160 S3X125 63 A S250 S250 S250 S250 S250 S250 S250 S1B125 S250 S1B125 S250 S1N125 S1B125 S1N125 S1B125 S2N160 S1N125 S2N160 S1N125 S2S160 S2X100 S1N125 S2S160 S2X100 S2N160 S2X100 S4L160 S2N160 S4L160 S3X125(R80) S2S160 S3L160(R80) S3X125(R80) S2S160 S4L160 S3X125(R80) S1B125 S1B125 S1B125 S1B125 S1B125 S1B125 S1B125 S1B125 S1B125 S1B125 S1N125 S1B125 S1N125 S1B125 S2N160 S1N125 S2N160 S1N125 S2S160 S3L160 S1N125 S2S160 S3L160 S2N160 S3H160 S4L160 S2N160 S3L160 S3X125 S2S160 S3L160 S3X125 S2S160 S4L160 S3X125 S2B160 S2B160 S2B160 S2B160 S2B160 S2B160 S2B160 S2N160 S2B160 S2N160 S2B160 S2N160 S2N160 S2N160 S2N160 S2S160 S3L160 S2N160 S2S160 S3L160 S2N160 S3H160 S4L160 S2N160 S3L160 S3X200 S2S160 S3L160 S3X200 S2S160 S4L160 S3X200 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3N250 S3H250 S3L250 S3N250 S3H250 S3L250 S3N250 S3H250 S4L250 S3N250 S3L250 S4X250 S3H250 S3L250 S4X250 S3H250 S4L250 S4X250 S5N400 S5N400 S5N400 S5N400 S5N400 S5N400 S5N400 S5N400 S5N400 S5H400 S5L400 S5N400 S5H400 S5L400 S5N400 S5H400 S5L400 S5N400 S5L400 S6X400 S5H400 S5L400 S6X400 S5H400 S5L400 S6X400 S5N / S6N630 S5N / S6N630 S5N / S6N630 S5N / S6N630 S5N / S6N630 S5H / S6S630 S5L / S6L630 S5N / S6N630 S5H / S6S630 S5L / S6L630 S5N / S6N630 S5H / S6H630 S5L/S6L630 S5N/S6N630 S5L/S6L630 S6X630 S5H/S6S630 S5L/S6L630 S6X630 S5H/S6S630 S5L/S6L630 S6X630 S6N800 S6N800 S6S800 S6L800 S6N800 S6S800 S6L800 S6N800 S6H800 S6L800 S6N800 S6L800 S8V2000 S6S800 S6L800 S8V2000 S6S800 S6L800 S7S1250 S7L1250 S7S1250 S7L1250 S7S1250 S7H1250 S7L1250 S7S1250 S7L1250 S8V2000 S7S1250 S7L1250 S8V2000 S7S1250 S7L1250 S7H1250 S7L1250 S7S1600 S7L1250 S8V2000 S7S1600 S7L1600 S8V2000 S7S1600 S7L1600 5/43 125 A User rated current and type of circuit-breaker 160 A 250 A 400 A 630 A 800 A 1250 A 1600 A

GSIS0272

Operation and protection of three-phase AC capacitors

T able for choosing SACE Isomax S circuit-breakers in relation to the rated current of the bank and the power of the transformer installed.

Circuit-breaker

Icu 380/415 V

Rated current of release

Rated current of capacitor

Max electronic/ magnetic release setting PR... / TM - / Im=10 In - / Im=10 In - / Im=10 In - / Im=10 In I3=OFF / I3=OFF / I3=OFF / Im=10 In I3=OFF / Im=10 In I3=OFF / Im=10 In I3=OFF / Im=10 In

Maximum rating of capacitor bank in kVAR-50 Hz 400 [V] 58 74 74 115 74 115 185 231 291 369 577 739 924 1155 1478 440 [V] 64 81 81 127 81 127 203 254 320 406 635 813 1016 1270 1626 500 [V] 72 92 92 144 92 144 231 288 364 462 722 924 1155 1443 1847 690 [V] 100 127 127 199 127 199 319 398 502 637 996 1275 1593 1992 2550

Mechanical endurance

Electrical endurance

Type S1 B/N 125 S2 B/N/S 160 S3 N/H/L 160 S3 N/H/L 250 S4 N/H/L 160 S4 N/H/L 250 S5 N/H/L 400 S5 N/H/L 630 S6 N/S/H/L 630 S6 N/S/H/L 800 S7 S/H/L 1250 S7 S/H/L 1600 S8 H/V 2000 S8 H/V 2500 S8 H/V 3200

[kA] 16 / 25 16 / 35 / 50 35 / 65 / 85 35 / 65 / 85 35 / 65 / 100 35 / 65 / 100 35 / 65 / 100 35 / 65 / 100 35/50/65/100 35/50/65/100 50 / 65 / 100 50 / 65 / 100 85 / 120 85 / 120 85 / 120

[A] 125 160 160 250 160 250 400 500/630 630 800 1250 1600 2000 2500 3200

[A] 83 107 107 167 107 167 267 333 420 533 833 1067 1333 1667 2133

man 25000 25000 25000 25000 20000 20000 20000 20000 20000 20000 10000 10000 10000 10000 10000

man/h 240 240 120 120 120 120 120 120 120 120 120 120 120 120 120

man 8000 8000 10000 8000 10000 8000 7000 5000 7000 5000 7000 5000 3000 2500 1500

man/h 120 120 120 120 120 120 60 60 60 60 20 20 20 20 10

I3=OFF / I3=OFF / I3=OFF / I3=OFF / I3=OFF / -

5/44

ABB SACE

Coefficient for calculating capacitor bank power in kVAR/kW to increase the cos

value.

Cosj to be obtained Initial Cosj 0,60 0,61 0,62 0,63 0,64 0,65 0,66 0,67 0,68 0,69 0,70 0,71 0,72 0,73 0,74 0,75 0,76 0,77 0,78 0,79 0,80 0,81 0,82 0,83 0,84 0,85 0,86 0,87 0,88 0,89 0,90 0,81 0,584 0,549 0,515 0,483 0,450 0,419 0,388 0,358 0,329 0,299 0,270 0,242 0,213 0,186 0,159 0,132 0,105 0,079 0,053 0,026 0,85 0,714 0,679 0,645 0,613 0,580 0,549 0,518 0,488 0,459 0,429 0,400 0,372 0,343 0,316 0,289 0,262 0,235 0,209 0,182 0,156 0,130 0,104 0,078 0,052 0,026 0,9 0,849 0,815 0,781 0,749 0,716 0,685 0,654 0,624 0,595 0,565 0,536 0,508 0,479 0,452 0,425 0,398 0,371 0,345 0,319 0,292 0,266 0,240 0,214 0,188 0,162 0,136 0,109 0,083 0,054 0,028 0,91 0,878 0,843 0,809 0,777 0,744 0,713 0,682 0,652 0,623 0,593 0,564 0,536 0,507 0,400 0,453 0,426 0,399 0,373 0,347 0,320 0,294 0,268 0,242 0,216 0,190 0,164 0,140 0,114 0,085 0,059 0,031 0,92 0,905 0,870 0,836 0,804 0,771 0,740 0,709 0,679 0,650 0,620 0,591 0,563 0,534 0,507 0,480 0,453 0,426 0,400 0,374 0,347 0,321 0,295 0,269 0,243 0,217 0,191 0,167 0,141 0,112 0,086 0,058 0,93 0,939 0,904 0,870 0,838 0,805 0,774 0,743 0,713 0,984 0,654 0,625 0,597 0,568 0,541 0,514 0,487 0,460 0,434 0,408 0,381 0,355 0,329 0,303 0,277 0,251 0,225 0,198 0,172 0,143 0,117 0,089 0,94 0,971 0,936 0,902 0,870 0,837 0,806 0,775 0,745 0,716 0,686 0,657 0,629 0,600 0,573 0,546 0,519 0,492 0,466 0,440 0,413 0,387 0,361 0,335 0,309 0,283 0,257 0,230 0,204 0,175 0,149 0,121 0,95 1,005 0,970 09,36 0,904 0,871 0,840 0,809 0,779 0,750 0,720 0,691 0,663 0,634 0,607 0,580 0,553 0,526 0,500 0,474 0,447 0,421 0,395 0,369 0,343 0,317 0,291 0,264 0,238 0,209 0,183 0,155 0,96 1,043 1,008 0,974 0,942 0,909 0,878 0,847 0,817 0,788 0,758 0,729 0,701 0,672 0,645 0,618 0,591 0,564 0,538 0,512 0,485 0,459 0,433 0,407 0,381 0355 0,329 0,301 0,275 0,246 0,230 0,192 0,97 1,083 1,048 1,014 0,982 0,949 0,918 0,887 0,857 0,828 0,798 0,769 0,741 0,712 0,685 0,658 0,631 0,604 0,578 0,552 0,525 0,499 0,473 0,447 0,421 0,395 0,369 0,343 0,317 0,288 0262 0,234 0,98 1,131 1,096 1,062 1,030 0,997 0,966 0,935 0,905 0,876 0,840 0,811 0,783 0,754 0,727 0,700 0,673 0,652 0,620 0,594 0,567 0,541 0,515 0,489 0,462 0,437 0,417 0,390 0,364 0,335 0,309 0,281 0,99 1,192 1,157 1,123 1,091 1,058 1,007 0,996 0,966 0,937 0,907 0,878 0,850 0,821 0,794 0,767 0,740 0,713 0,687 0,661 0,634 0,608 0,582 0,556 0,530 0,504 0,478 0,450 0,424 0,395 0,369 0,341 1 1,334 1,299 1,265 10233 1,200 1,169 1,138 1,108 1,079 1,049 1,020 0,992 0,963 0,936 0,909 0,882 0,855 0,829 0,803 0,776 0,750 0,724 0,698 0,672 0,645 0,620 0,593 0,567 0,538 0,512 0,484

ABB SACE

5/45

Protection of three-phase AC generators (Ue = 400 V)

Power
generator

In

S1
125

S2
160

S3
160

S3
250

S4
160

S4
250

S5
400

S5
630

S6
630

S6
800

S7
1250

S7
1600

S8
2000

S8
2500

S8
3200

[kVA] 40 50 63 100 160 200 250 315 400 500 630 800 1000 1120 1250 1400 1600 2000

[A]

In [A] 100 100

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

In [A]

91 144,5 231,2 289 361 455 578 723 910 1156 1445 1617 1804 2021 2309 2887

100

100 160

100 160 200 250

100 160 250 250 320 320 320 400 630 630 630 630 630 630 630 630 800 800 800 800 1000 1000 1000 1000 1250 1600 1600 1600 1600 1600 2000 2500 2500 3200

5/46

ABB SACE

Applications in direct current


Connection diagrams

Suitable connection arrangements must be adopted to obtain the number of poles in series necessary to guarantee the

breaking capacity required at the various operating voltages.

Circuit protection and isolation with three-pole circuit-breakers


Diagram A: breaking
with 1 pole per polarity

Diagram B:breaking

with 2 poles in series 1 pole for the

Diagram C: breaking

with 3 poles in series

per polarity and other polarity

per polarity

Load

Load

Load

Poles in parallel
Diagram D:breaking
with 2 poles in parallel

Diagram E: breaking

with series of 2 poles in

per polarity

parallel per polarity

Load

Load

Use at 1000 V DC with four-pole circuit-breakers


Diagram F: breaking
with 4 poles in series

Diagram G: 3+1

poles in series

Diagram H: 2+2

poles in series

for one polarity

Load Load Load

The following table shows which connection arrangement to adopt according to the number of poles to connected in series

to obtain the required breaking capacity for the type of distribution network.

Rated voltage < 250 < 500 < 750 < 1000

Protection

Function Isolation

Distribution network isolated from earth A, D A, D B G, H with one polarity* to earth A, D E B C, E G C F with median point to earth A, D A, D H H * The negative pole is assumed to be earthed.

Notes
1) The risk of a double fault to earth being sufficient for the fault current to affect only one side of the circuit breaking poles is considered negligible. 2) For rated voltages greater than 750V the 1000 VDC range is required. 3) Diagram D and diagram E only for S6.

ABB SACE

GSIS0271

5/47

Applications in direct current


Connection diagrams

Example of tripping threshold adjustment in DC - diagram A


Setting Ith R 10 R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160 R 200 R 250
N.B. For the lower settings R10, R12.5, R16 only the version I = 5
m

S1 125 Im=10Ith Im=5Ith 208 208 208 650 650 650 650 650 819 1040 1300 1625 260 260 260 260 325 416 520 650 819 912,5 11,216 1420 17,525 22,532 2840 3550 4463 5680 70100 87,5125 112160 Ith

S2 160 Im=10Ith Im=5Ith Ith

S3 160 Im=10Ith Im=5Ith Ith

S3 250 Im=10Ith Im=5Ith

10 12,5 16 20 25 32 40 50 63 80 100 125

208 208 650 650 650 650 650 819 1040 1300 1625 2080 260 260 260 260 325 416 520 650 819 1040 4880 70100 87,5125 112160 1040 1300 1625 2080 520 650 819 1040 140200 175250
can be used

1932

650

390

3050

650

390

2600 3250

1300 1625

Ith

The correction value to adopt for the protection thresholds of each circuit-breaker is shown in the following table.

Circuit-breaker S1

Diagram A km= 1 km= 1 km= 1 km= 1,1 km= 1,1

Diagram B km= 1 km= 1 km= 1,15 km= 1 km= 1

Diagram C km= 1 km= 1 km= 1,15 km= 1 km= 1

Diagram F km= 1 km= 1,1 km= 0,9

Diagram G km= 1 km= 1,1 km= 0,9

Diagram H km= 1 km= 1,1 km= 0,9

S2 S3 S5 S6

5/48

ABB SACE

Setting

S5 400 Ith=0,71xIn Im=510xIn 17603520 22004400 350500

S5 630 Ith=0,71xI n Im=510xIn

S6 630 Ith=0,71xI n Im=510xIn

S6 800 Ith=0,71xIn Im= 510xIn

R 320 R 400 R 500 R 630 R 800

225320 280400

27505500 440630 30656930 560800 44008800

Using these the correction factors means that the tripping current values will be higher for the same tripping threshold, or, vice versa, that having identified the tripping value one needs to set the tripping threshold following the reclassified scale range.

therefore in this specific case, having chosen circuit-breaker S6 R630 (ln = 630 A), the magnetic threshold setting value will be:

set =
Example
Operating current: Ib = 600 A Magnetic protection required: Im = 5000 A Magnetic protection required to set:

5000 1,1 x 630

set =

Im km x In

ABB SACE

5/49

Backup protection
(backup table with Ue = 400 V~)

The table below shows the backup protection available, with the related breaking capacities for the rated voltage Ue=400V~, between ABB moulded-case and air low voltage

circuit-breakers (SACE Isomax S, SACE Limitor LNA and SACE Emax) and pro

system modular circuit-breakers.

CIRCUIT-BREAKER UPSTREAM S270 S280/20 S280/20 S290 S500 In [A] < Icu [kA] 15 20 25 15 50

S1B 125 16

S2B 160 16

S1N 125 25

S2N 160 35

S3N 250 35

S4N 250 35

S5N 630 35

S6N 800 35

S2S 160 50

S6S 800 50

S7S 1600 50

CIRCUIT-BREAKER DOWNSTREAM
10 15 16 20 S240 S250 S270 S240 S250 S270 S240 S240 S250 S240 S250 S250 S250 S250 S250 S250 S250 S270 S1B S2B S1B S2B S250 S1B S2B S240 S240 S240 S240 S240

25

S270 S280/20 S280/25 S1B

S270

S270 S280/20 S280/20 S1B S2B

S270

30

S280/20 S280/25 S280/25 S280/25 S1B S1N S2B S1B S1N S2B S1N S1N S1N

S280/20 S280/25

35

S250 40

S1N

S3N S4N S5N S6N

50

S270 S280/20 S280/25 S1B S1N

S1B S1N S2B S2N

S2N S3N S4N S5N

65

85

100

130 150 170

200

5/50

ABB SACE

In the interest of facilitating clear representation, the latter must be read using the follow key:

S250: S270:

S250, S260, S270K S270 (B-C-D), S280 (In = 3 ... 8 A), S280 (In = 50 ... 63 A), S290

S280/20: S280 S280/25: S280

(In = 32 ... 40 A) (In = 10... 25 A)

S3H 250 65

S4H 250 65

S5H 630 65

S6H 800 65

S7H 1600 65

S2X 100 70

S3L 250 85

S4L 250 100

S5L 630 100

S6L 800 100

S7L 1600 100

S3X 125 200

S3X 200 200

S4X 250 200

S6X 630 200

E2L 1600 130

E3L 2500 130

S240

S250

S250 S270

S250 S1B S2B S1B S2B S240

S250 S270

S1B S2B

S1B S2B

S250

S250

S250

S1B S2B

S270 S280/20 S280/20

S250

S270 S280/20 S280/20

S270

S270 S270 S280/20 S280/20

S280/25 S280/25 S1B S2B

S240

S280/25 S280/25

S280/20 S280/25 S280/25

S280/25

S1B S2B

S1N

S1N

S3N S4N S5N S6N

S270

S1B S2B

S1N

S1N

S3N S4N S5N S6N S1N

S5N

S6N

S1N S280/20 S280/25 S1B S1N S1N S2N S2S S3N S2N S2S S3N S2N S2S S3N S4N S2N S2S S3N S4N S5N

S2B S1B

S6N

S2N S3N S4N

S2N S3N S4N

S1B S2B

S6S

S1N S2N S2S S3N S3H

S1N

S5N

S5H S6S S6H

S1B

5
S2B S2N S3N S4N S5H S6S S6H S7S S7H S5L S6L S7L S6H S7S S7H

S2N S2S S3N S3H S3L

S2S S3H S3L S4H

S2S S3H S3L S4H S5H S1B S2B

S1N

S2S

S6L S7L

S1N S1N S500 LNA S2N S2S S500 LNA S2N S2S S3N S3H S3L LNA S2N S2S S3N S3H S3L S5N S3H S3L S4H S4L S5H S5L S6S S6H S6L

ABB SACE

5/51

5/52

ABB SACE

Overall dimensions and circuit diagrams

Index
Overall dimensions
SACE Isomax S1-S2 Fixed circuit-breaker ............................................................................................................ Plug-in circuit-breaker .......................................................................................................... Circuit-breaker with SACE RC210-RC211-RC212 residual current releases ..................... Accessories .......................................................................................................................... SACE Isomax S3-S4-S5-S3X-S4X Fixed circuit-breaker ............................................................................................................ Mounting parts for fixed circuit-breaker ............................................................................... Plug-in circuit-breaker - withdrawable circuit-breaker ......................................................... Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker ........................... SACE S3 circuit-breaker with SACE RC211/3 - RC212/3 residual current releases ......... Accessories .......................................................................................................................... SACE Isomax S6-S6X Fixed circuit-breaker ............................................................................................................ Mounting parts for fixed circuit-breaker ............................................................................... Withdrawable circuit-breaker ............................................................................................... Mounting parts for withdrawable circuit-breaker ................................................................. Accessories .......................................................................................................................... SACE Isomax S7 Fixed circuit-breaker ............................................................................................................ Mounting parts for fixed circuit-breaker ............................................................................... Withdrawable circuit-breaker ............................................................................................... Mounting parts for withdrawable circuit-breaker ................................................................. Accessories .......................................................................................................................... 6/2 6/3 6/4 6/5

6/7 6/9 6/10 6/11 6/12 6/14

6/18 6/20 6/22 6/23 6/24

6/28 6/29 6/30 6/31 6/32

SACE Isomax S8 Fixed circuit-breaker ............................................................................................................ 6/36 Mounting parts for fixed circuit-breaker ............................................................................... 6/37 Distances to be respected .............................................................................................. Minimum distance between centres ............................................................................. 6/38 6/39

Circuit diagrams
Index ................................................................................................................................... 6/41

ABB SACE

6/1

Overall dimensions
SACE S1-S2
Fixed circuit-breaker
Mounting on sheet metal
Y
B A E E E
(4 POL) (3 POL)

Mounting on DIN EN 50022 channel

Terminal covers
(to order when not included in supply) (*) 75 with sealable screws

G 71 1.52

4 4
2 40

71(*)

1
120 96 = =

X
48

X 45
=

X 45 X
=

Low

High

2
D F C
(3 POL) (4 POL)

75

Terminals
Front for Cu cables or flat bars
(with separator plates between the phases)
3

Front for Cu cables or flat bars


(with high or low terminal covers)

Extended front for S2


(*) high terminal covers included in supply
23.5 5 17.5 (*) 15 E E 8.5

Threaded rear
(**) low terminal covers included in supply (protection class IP20)

View A
42 L (**) M8 11

3
24.5

I H H

27.5

102 E

X
39 M 75

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm) For front terminals For threaded rear terminals
Y Y
(3-4 POL) E = = O Q 62 62 63 R 1.5 102 100 E 4 POL 3 POL E E 18

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 1.5 - 2 mm)

Key
Y

1 2

Flange for compartment door Bracket for fitting circuit-breaker on DIN channel (to order) Separator plate Sealable screws

100

64

53

3 4

4 M4/4.5 = = E M4/4.5 N P
GSIS0001

B
103 120

C
39 45

D
91 103

E
25 30

F
116 133

G
91 93

H
25.5 27.5

I
10.5 x 11 12.5 x 12.5

L
29 27

M
62 60

N
3 POL 4 POL 83.5 108.5 95.5 125.5 86 98

O
3 POL 4 POL 111 128

P
42 48

Q
43 49

...
... ...

...
... ...

...
... ...

S1 S2
6/2

78 90

ABB SACE

Plug-in circuit-breaker
Fixed parts mounted on sheet metal or channel
(terminal covers for mobile part with IP20 always included in supply)
B E = E

Y
A = E

(4 POL) (3 POL)

2.5 10

123 (*)

(*)127 mm with sealable screws

1.52 mm

Key
1
SAC

2 1

1
= 45 = 124 50 X

Flange for compartment door Sealable screws Fixed part Moving part complete with terminal covers

X 70

I O

o off

96 163

2 3 4

75
C D F

42
(3 POL) (4 POL)

52

Terminals
Front
2.5 H I 2.5

Threaded rear
10

View A
A
76 40 26 M8

102 39

E E

65.5

Drilling template for support (5) or channel (6)


(minimum thickness of sheet metal: 2.5 mm) For front terminals
Y
L M (4 POL) (3 POL) R

For threaded rear terminals


Y
L M (4 POL) (3 POL) R

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 1.5 - 2 mm)

5
O

Y
Q

84

144

60 MAX

35

5.5

144

60 102 MAX

35

5.5

63

84

64 R 13

R 1.5

53

6
GSIS0002

M4 4.5

4 M4 4.5 R R E (3 POL) M (4 POL) E M (3 POL) (4 POL) N

B
103 120

C
39 45

D
91 103

E
25 30

F
116 133

G
91 93

H
28 28

I
10.5 x 11 12.5 x 12.5

L
75 90

M
50 60

N
3 POL 4 POL 83.5 108.5 95.5 125.5 86 98

O
3 POL 4 POL 111 128

P
42 48

Q
43 49

R
12.5 15

...
... ...

...
... ...

S1 S2
ABB SACE

78 90

6/3

Overall dimensions
SACE S1-S2
Circuit-breaker with SACE RC210-RC211-RC212 residual current release
Vertical installation RC211-RC212
(*) Without terminal covers (**) With low terminal covers (***) With high terminal covers

(mounting on sheet metal) Threaded rear terminals


(low terminal covers included in supply)

Front terminals for Cu cables or flat bars


(high terminal covers to order)

Version with high terminal covers: front or rear output cables

Y
C A B

71 24.5

4 3

71()

1.52 mm

71()

1.52 mm

3 3

SAC

X1
245 (*)

45

= =

I O

o off

96 249 325 (**) (***)

X1
245 249 227

80

3
SAC

325

X2
48

45

= =

96

X2

75

75 () 75 with sealable screws 75

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm)
4 POL 3 POL = = D D D 20 18 96.5 63 62 100
25
M4 - 4,5

Template for drilling compartment door and fitting flange (thickness of sheet metal: 1.5 - 2 mm)
G H E

X1
293

38

X1
125 100

Holes for rear terminals only

Holes for cables with rear outlet only

X1 53 64
125 4 G R1.5 F

X2
71.5

39

38 18 20 = = D

X2 X2 53 64

Y
70

Horizontal installation SACE RC210-RC211-RC212


= 24.5 D = D I D = =

Key
1

1 2

Front terminals for cables and flat bars Bracket for mounting on DIN EN 50022 channel Flange for compartment door Separator plate

2
120

X
48

= =

= 45 =

3
X

75

B
39 45

C
116 133

D
25 25 30

E
43 49

F
41.7 47.7

G
111 128

H
108.5 125.5

I
206 206 240

S1 - RC210 S1 - RC211/RC212 S2 - RC211/RC212


6/4

103 120

ABB SACE

GSIS0003

~70

Note See the various different versions for the dimensions of the terminals

Accessories
Solenoid operator at the side of the circuit-breaker
B A 24.5 Y

3 4

92 70.2 6.7

Key 1
Y E F 66 0.15
+

1 2
X

Drilling for fixing the circuitbreaker and solenoid operator assembly onto sheet Plate for fixing circuitbreaker onto DIN EN 50022 rail (a richiesta) Separator plates between the phases Spacer (for SACE S1 only)

120 X 48

SACE S

= 45 =

124 = X =
+0.15 100 X X

62

52 +0.15 80

50

2
C Y 3 D

4 E
25 0.15 30 0.1

A 3 POL B 3 POL C 4 POL D 4 POL

F
38.5 0.2 36 0.2

S1 S2

78 90

162 168

64 75

187 198

Key

Solenoid operator on the front of the circuit-breaker


B A 78 24.5 Y 150 147

Flange for compartment door Template for drilling compartment door and fitting flange Separator plates between the phases A 3 POL B 4 POL

2
1.5-2

1 3
SACE S

= = X 96 = 50 =

83.5 124 X X 45
+0.15 X 64

+0.15

2
X 53

R1.5 85

GSIS0004

S1 S2

78 90

103 120

Y 91

140.5

23

Interlock across two horizontally-installed circuit-breakers


Y

120 (S2S2) 117.5 (S1S2) 115 (S1S1)

Y1

62 100 X

30

90 S2S2 4.5-M4

30 X

6
30 X

25
SACE

90 S1S2

2
X
X

Key 1 2 Interlock device Template for drilling sheet metal support Tightening torque 1,1 Nm Remove the screws for stirruping the cover and replace them with the ones in the KIT. 6/5

25 X

90 S1S1

30 X
GSIS0005

Y1 Y

Note
See the various different versions for the dimensions of the circuit-breakers

ABB SACE

Overall dimensions
SACE S1-S2
Accessories
Compartment door-mounted rotary handle operating mechanism for fixed or plug-in circuit-breakers
Fixed depth
119.5
68 51.5 49.5 (*) 18 20 (*) 68

Adjustable depth (max 300 mm)


23 max 47
A =168 min. 300 max (298*) 137.5

23 max 47

Shaft lenght= A+B-137.5


B = 18 (20*)

45
=

45
=

7 5 2
(*) If protection class IP54 required

8
2.5

2.5

5 2 1
(*) If protection class IP54 required A = 298 B = 20

Adjustable depth (max 621,5 mm)


C = 340 min. 621.5 max (619.5*) 137.5 68

23 max 47

Shaft lenght= C+B-137.5

6.8 X
65

9
X
=

B = 18 (20*)

45
=

42 2.5 R min. 200

5 2 4

2.5

45

(*) If protection class IP54 required C max = 619.5 B = 20

6.8 X 33 X

Key 1 2 3 4 5 6 7 Padlock device for open position (max 3 padlocks with 6 to be provided by customer) Transmission assembly Rotary handle assembly Minimum radius of rotation for fulcrum of compartment door Circuit-breaker operating lever Drilling of compartment door Joint Shaft Support ABB SACE

53 Y

Note See the various different versions for the circuitbreaker mounting holes 6/6

8 9

GSIS0006

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Fixed circuit-breaker

Mounting on sheet metal


Y
117

Mounting on DIN EN 50023 channel

Terminal covers
(to order when not included in supply)

B = A =

(4 POL) (3 POL)

Z V F

3 25

135 101.5 H

108

4.5

46 2.5

1
= 10.25 105 = H

X
C

I O

o off

161

X1

22.5

o off

I O

o off

45
O

1 4
E E E 5 103.5 107 2 105

Low

High

Terminals
Front for flat bars
10 (S3-S3X) 15 (S4-S5) 3 (*) M8 (S3/S3X-S4/S4X) M10 (S5)

57 (S5 630) 53.8 (S5 400)

Front for cables


L 31.2 21

31.8

15.5 (S5 400) 20 (S5 630)

(**)

(**) high terminal covers included in the supply


I 5 20 I
GSIS0007

(*) 3 mm = minimum admissible thickness for S5 400

1 x 240 mm2 (S5 400)

2 x 120 mm2

For SACE S3 - S4 S5 400 - S3X - S4X only

For SACE S5 400 - S5 630 only

Key 1 2 Flange for compartment door Bracket for mounting on DIN EN 50023 channel 45 mm front flange Tightening torque 2 Nm

3 4

B
140 140 183.75 183.75 140 140

C
170 254 254 254 255 359

D
87.25 125.25 125.25 125.25 175.25 210.25

E
35 35 43.75 43.75 35 35

F
8 8 10 10 8 8

G
143 218 218 218 228 307.5

H
10 11 12 12 10 11

I
73.75

L
18x18

V
24 24 31 31 24 24

Z
17.5 17.5 19.5 19.5 17.5 17.5

S3 S4 S5 400 S5 630 S3X S4X


ABB SACE

105 105 140 140 100 105

107.25 18x18 107.25 24x24 107.25

158.75 18x18 196.75 18x18

6/7

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Fixed circuit-breaker
Terminals
For rear Cu/Al cables Extended front
25 13.5 (S3/S3X-S4/S4X) 16.5 (S5)

(**) L

Y
O

(***)

6 P 46 12.5

33.5

N I D I

I O

o off

(**) high terminal covers included in supply

(***) Separator plates between the phases to order

Extended front spreaded


A1 C1 F1 G1 E1 C1 F1 G1 E1 D1 B1 D1 D1 I1 101 L1 5

H1 2.5 2.5

H1

60

I O

o off

I O

o off

3 POL

4 POL

Threaded rear
25 Q R

View A
A
(**) S U

6
S3 S4 S5 400 S5 630 S3X S4X
6/8

X
T

(**) low terminal covers included in supply

D
87.25

I
73.75

L
16 16 21 16 16

N
20 20 25 20 20

O
8.5 8.5 11 8.5 8.5

P
100 100 100 100 100

Q
81.5 81.5 86.5 106 81.5 81.5

R
36.5 36.5 39.5 41 36.5 36.5

S
55 55 62 70 55 55

T
100 100 108 135 100 100

U
M 12 M 12 M 16 M 24 M 12 M 12

A1
130 130 ... 158 130 130

B1
165 165 ... 202 165 165

C1
50 50 ... 59 50 50

D1
45 45 ... 54 45 45

E1
30 30 ... 40 30 30

F1
155 155 ... 189
max

GSIS0008

G1
... ... ... ... ... ...

H1
8.5 8.5 ... 11 8.5 8.5

I1
12.5 12.5 ... 15 12.5 12.5

L1
45 45 ... 49 45 45

125.25 107.25 125.25 107.25 125.25 107.25 175.25 158.75 210.25 196.75

155 155

ABB SACE

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm) For terminals: Front for flat bars Extended front Front for cables
Y
A B
(3 POL) (4 POL)

For terminals for rear Cu/Al cables

For threaded rear terminals

Y
A B
(3 POL) (4 POL)

Y
A M A M A A

Y
A M5/5.5

D D

F G

C A

C E

M5/5.5

E B

A
(3 POL) (3 POL) (4 POL)

M5/5.5

(4 POL)

For SACE S3 - S4 - S5 400 -S3X - S4X only

For threaded rear terminals


Y
43.75 43.75 32 32

Y
43.75 43.75 43.75 M5/5.5

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
Y
112 = = 80 = =

105.25

107.25

105.25

87.5 = = 112 142 = =

X 214
43.75

218 X

214 22

8 7

Y
(3 POL) (4 POL) GSIS0009

M5/5.5

For SACE S5 630 only

6
G
185 260 272 270 350

B
70 70 87.5 70 70

C
139 214 214 224

D
71.75 105.25 105.25 156.75

E
17.5 17.5 22 17.5 17.5

F
94.75 128.25 134.25 179.75 218

H
R15 R15 R20 R15 R15

I
105 105

L
73.75 107.25

M
24 24 30 24 24

N
143 218 218 228 307.5

S3 S4 S5 S3X S4X

35 35 43.75 35 35

131.25 107.25 105 105 158.5 196.75

303.5 194.75

ABB SACE

6/9

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Plug-in circuit-breaker - withdrawable circuit-breaker
Plug-in SACE S3-S4-S5 400-S3X-S4X
Y
117 B = A = 27.5
(4 POL) (3 POL)

Witdrawable SACE S3-S4-S5 400-S3X-S4X


isolating travel
3 B A = =

Y
(4 POL) (3 POL)

1 3 2
T =

3 5
G = 105 =

5
G 5.5 1.75 C 161

X C

I O

o off

161 =

X 105
=

5
E E 105 E F 153 156.5 184.5 2 2 167 190 195.5 74 E E 105 H 96 E F

Key 1 2 3 4 5 Fixed part

Witdrawable SACE S5 630


27.5 isolating travel

Y
3 = B A =
(4 POL) (3 POL)

Moving part complete with IP20 protection class terminal covers Flange for compartment door (included in supply) Lock for compartment door (to order)
=

1
D 1

3
133.25

5
C 161 G 270

Tightening torque 1,1 Nm (S3-S4-S3X-S4X) - 2 Nm (S5) The withdrawable circuit-breaker must be completed with one of the following accessories: front flange for operating lever mechanism rotary handle operating mechanism motor operator

X 105
=

5.5 1.75

Note

5
E E E F 78,5 H 96

167 190 195.5

Terminals
Front for flat bars (up to 400 A and S5 630-400A)
I M 17,5 (S3X-S4X) P L L L N S R

Front for cables (up to 400 A)


Q

Threaded rear
A

View A
U

Front spreaded for SACE S5 630


158 201,7

Vertical flat bar rear terminals for SACE S5 630


8 V

31 (S3-S4-S3X-S4X) 34 (S5 400) 54,5 (S5 630)

184 15 11 59 54

5,5
59.5

11
35 40 5,5 43.75 40 83 (S3-S4-S3X-S4X) 84 (S5 400) 118 (S5 630) Z
GSIS0010

6
S3 S4

59,5 108

A
105 105 140 140 105 105

B
140 140 183.75 183.75 140 140

C
175 259 259 259 260 344

D
89.75 127.75

E
35 35

F
52.5 52.5 70 70 52.5 52.5

G
143 218 218 218 143 218

H
84 84 101.5 101.5 84 84

I
10 10 14 14 10 10

L
33.5 33.5 43.5 49 33.5 33.5

M
8.2 8.2 10.2 10.2 8.2 8.2

N
20 20 25 25 20 20

O
5 5 6 6 5 5

P
37.5 37.5 47.5 55.75

Q
79.5 79.5 91.5 91.5

R
36 36 37 37

S
18x18

T
73.75

U
48 48 58 80 48 48

V
M12 M12 M16 M24x2 M12 M12

Z
100 100 108 143 100 100

18x18 107.25 24x24 107.25 24x24 109.25 73.75 107.25

S5 400 S5 630 S3X S4X


6/10

127.75 43.75 127.75 43.75 174.5 212.75 35 35

ABB SACE

Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

SACE S3-S4-S5 400-S3X-S4X


For terminals: Front for flat bars Front for cables For terminals Threaded rear

SACE S5 630
For terminals: Vertical flat bar rear terminals Threaded rear
Y
(3 POL) (4 POL) 115 (3 POL) 160 (4 POL) 115 (3 POL) 160 (4 POL)

For terminals: Front Front for Cu cables Front spreaded


Y

Y
A

Y
A B
(3 POL) (4 POL)

F G D D C H
65.75

6 (M5)

52

65

6 (M5)

83.25

65.75

83.25

X
135 135 86.75 57.5 57.5 86.75

F E

N E L M

52

R4

72

65

(3 POL) (4 POL)

132,5 (3 POL) 177,5 (4 POL)

144 (3 POL) 188 (4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
4 80

Y
112 = = 80 = =

Y
135 63 45 Nr. 3 8

72.5

= 126 =

94 27.5

= 142 X =

112 142 = =

16

7 7

For plug in circuit-breaker

For withdrawable circuit-breaker

B
105 117 160

C
100 135 135

D
52.25 65.75 65.75

E
25 41 58

H
143 218 218

I
35 35 43.75

L
70 70 87.5

M
105 105 131.25

N
R14 R14 R18

S3 - S3X S4 - S4X S5
ABB SACE

70 82 115

M4-5 73.75 M4-5 107.25 M5-6 107.25

GSIS0011

81 125 R min. 200

6/11

Overall dimensions
SACE S3-S4-S5-S3X-S4X
SACE S3 circuit-braker with SACE RC211/3 - RC212/3 residual current release
Vertical installation
(mounting on sheet metal)

(*) Without terminal covers (**) with low terminal covers (***) with high terminal covers

Front terminals for cables


(terminal covers to order)

Rear terminals
(low terminal covers included in supply)

Y
153 140

109

1.52 109 1.52 81,5

25

2
97.5

2
X1
279

36,5

X1

45

= =

96

X1

X1
305 280

X1

X1
310

35 35 35

12

305 (*) 90.5

310 397 (**) (***)

X2

45

= =

96

X2

X2

X2

X2

X2
55 100

52.5

50

Version with extended front terminals


Y
153 140 35 35 35 109 31 1.52

Terminals for rear Cu/Al cables


(high terminal covers included in supply)

3 12.5

109

1.52

Key 1 Tightening torque 2 Nm Flange for compartment door


2

97.5

2
= = 96

2
X1
305 279

X1

45

X1

X1
346 305 279

X1

X1
397

90.5

X2

45

= =

96

X2

X2

X2

X2

X2

Note See the various different versions for the dimensions of the terminals

8.5

6 3 45

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm)
Y
70 0.1 17.5 R1

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 1.5 - 2 mm)
Y
145.5 0.1 55.25

6
X1

105.5 82 84

4 64 0.1 53

X1
321 274 0.15 5.5 - M5 279

Holes for threaded Holes for rear rear terminals only terminals for cables only

X1

X1
135.5

X2
24

64 0.1 53

X2

148

6/12

ABB SACE

GSIS0012

35 35 35

56.5

SACE S3 circuit-braker with SACE RC211/3 - RC212/3 residual current release

Horizontal installation
140 140 25 35

Y
35 35

2
97.5 170
SACE S3

X1

I O

o off
TEST

X1

X1
=

= 45 =

X1

50

3.5

108

Key 1 2 Front terminals for cables Bracket for mounting on DIN EN 50023 channel

GSIS0013

ABB SACE

6/13

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Accessories
Motor operator for fixed circuit-breaker
Y
A 2 220 = B = C (4 POL) (3 POL)

Key 1
Y
112 80

Flange for compartment door (included in supply) Dimensions with connectors Drilling of compartment door

1 2

= =

= =

2 3
= =

Note
See the various different versions for the circuit-breaker mounting holes

161 =

112 142 X = =

A
7

B
105

C
58

Y
225.5 = 105 117 =

S3-S4 S3X-S4X S5

140

183.75

140

75.5

Motor operator for plug in circuit-breakers


Y
27.5 2 isolating travel 269.5 A = B = C (4 POL) (3 POL)

Key 1 2 Flange for compartment door (included in supply) Dimensions with connectors Drilling of compartment door

Y
112 = = 80 = =

1 2

Note
= =

= 161 =

See the various different versions for the circuit-breaker mounting holes X

105 =

112 142 = =

B
105

C
58

S3-S4 S3X-S4X
7 = 117 =

140

S5

183.75

140

75.5

Motor operator for withdrawable circuit-breaker


Y
78.5 27.5 2 isolating travel 269.5 = A B = C 96 (4 POL) (3 POL)

Key 1 2
Y

Flange for compartment door (included in supply) Drilling of compartment door

Note
See the various different versions for the circuit-breaker mounting holes
63 Nr. 3 8

6
= 1.75 = 161 5.5 =

1
7

135

= 126 =

94 27.25

= 142 X =

X 105
=

16

2
167

GSIS0014

7 81 125 R min. 200

B
105

C
58

S3-S4 S3X-S4X S5

140

183.75

140

101.5

6/14

ABB SACE

Accessories
Interlock across two horizontally-installed circuit-breakers
Y
= B B B A C = = = B B B = N

Y
M P N = =

Key 1 2 Interlock device Template for drilling mounting holes in sheet metal Drilling template for all versions with rear terminals Dimensions with four-pole withdrawable version mounted on right

F 105 G

R Q O R =

(S5)

1 (S3-S4)

2
65

3 5

Tightening torque 3,7 Nm

103.5

Y
275

Note
Y

See the various different versions for the dimensions of the circuitbreakers

27.5

B
35 35 43.75 35 35

C
66 66 119 66 66

D
265 350 350 265 350

E
134.5 173.5 173.3 135 173.3

F
87.2 125.3 125.3 172 210

G
170 254 254 255 339

H
12 12 16 12 12

I
227.5 315 315 227.5 315

L
116 156 156 116 156

M
324 324 472 324 324

N
155 155 202 155 155

O
R15 R15 R15 R15 R15

P
16 16 48 16 16

Q
68 143 114 68*, 153** 143*, 232.5**

R
75 75 117 75 75

S3 S4 S5 S3X S4X

350 350 500 350 350

* Per interruttore estraibile con terminals posteriori ** Per interruttore fisso con terminals posteriori (uscita posteriore)

Interlock across two vertically-installed circuit-breakers (S3-S4-S5)


Y
103.5 65 = A = =

Y
H N Q =

Key 3
P

2
M F N M

1 2

Interlock device Drilling template for mounting circuit-breakers on sheet metal Drilling template for all versions with rear terminals Dimensions with four-pole withdrawable version Tightening torque 3,7 Nm

5
= 105 = C G

1
E O I

4 5

D F = 105 = G

M N M

6
R P

11.5 isolating travel 27.5 275 B B B

GSIS0015

4
Nr. 8 7

Note
Y

See the various different versions for the dimensions of the circuitbreakers

B
35 35 43.75

C
152.5 198.5 198.5

D
157.5 195.5 195.5

E
578 750 750

F
87.5 125.3 125.3

G
170 254 254

H
157.5 157.5 201

I
350 490 490

L
155 155 202

M
75 75 107

N
68 143 114

O
92 101 66

P
14 23.5 9

Q
77.5 77.5 98.5

R
R15 R15 R15

S3 S4 S5
ABB SACE

180 180 220

6/15

Overall dimensions
SACE S3-S4-S5-S3X-S4X
Accessories
Rotary handle operating mechanism on fixed or plug in circuit-breaker
Y
= 105 =

Key 1 5 2
4 80

Rotary handle operating mechanism Lock for compartment door (to order) Drilling of compartment door Dimensions for connector for early contact for undervoltage release Flange for compartment door (included in supply) A 4

2 3

45 == =

X 105

161

= = 142 112 = =
7

72.5

80 = = 112 = =

3
R min 200

= A

117

S3-S4 S3X-S4X S3-S4 S3X-S4X

III IV III IV

58

93

Note
See the various different versions for the circuit-breaker mounting holes

S5 S5

75.5 119.25

Compartment door-mounted rotary handle operating mechanism with adjustable depth for fixed or plug in circuit-breaker 7
Y

105

1 2
11.5

X
52.5

90

105

8
26 46.5 26 59

6 10 3

Y
5 11.5

= 33

46

R min 200

5
27
GSIS0016

Key
54 R min 200

1 2 3

Transmission assembly Rotary handle assembly with door lock device Padlock device for open position (maximum 3 padlocks with max 6mm to be provided by customer) Minimum radius of rotation for fulcrum of door Drilling of door

6 Support for depths of up to 500 mm 7 66 ... 300 mm (with IP54 protection min. 90) 8 Distance 7 + 2 mm (shaft length) 9 301...500 mm (with IP54 protection min.325) 10 Distance 9 + 2 mm (Shaft length) ABB SACE

Note
See the various different versions for the circuit-breaker mounting holes

4 5

6/16

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Y
170 = 105 = 2 38.5 22 4 80

Key 1 Rotary handle operating mechanism Lock for compartment door (to order) Padlock device for open position (maximum 3 padlocks max. 6 mm to be provided by user)

Y
135 63 45

2
Nr. 5 7 27.25 = 142 X =

X 105
=

161

72.5 = 126 X =

94 16 81 125

3 1

R min. 200

Note
See the various different versions for the circuitbreaker mounting holes

Y
35 35 37 42.5

Front flange for operating lever mechanism


Y
= 105 = 37 2

Key
4 80

1 2

Front flange for lever operating mechanism Lock for compartment door (to order) Drilling of compartment door Flange for compartment door (included in supply)

Y
45 == = = = 161 X = = 112 = =
7

72.5

3
X

X 105
=

142

4
80 = = 112 = =

Y
42.5

Note
See the various different versions for the circuitbreaker mounting holes

117

External neutral for SACE S4-S5 circuit-breakers


50 25 = = =
In 5 6 Line Load
100 160 200 250 320 400

76.5 36.25 4

6
95

120

66 40

= = =
1 4 5 6

11

X3

ABB SACE

GSIS0017

6/17

Overall dimensions
SACE S6 - S6X
Fixed circuit-breaker (S6)

Y
104.75 279.5 210 140 = (4 POL) (3 POL) 3 107 101.5 12 125.25 111.75 = 161 241 = 105 2

Terminal covers
(to order when not included in the supply)

2 low high
47

X 268

2.5

16.5

152

=
Mounting on sheet metal

14

9 103.5 159

Key 1 2 Flange for compartment door (included in supply) Tightening torque 2 Nm

Terminals
Front extended
70 40 70 70 11 48.5 62 41.5 5 15 6.5 47 12

Front
40 22.5 0.1 23 5 min.

S6 630
41.5 50 14 53.5 8 67 20

S6 630 - S6 800 Threaded rear


(low terminal covers included in supply) 70 70 70 2.5 73 44

47

M24x2

S6 800 Front extended spreaded


Y 45 116 90 116 22.5 23 116 22.5 13 49.5 8 20 45

S6 630 - S6 800 Front for Cu/Al cables


(IP20 high terminal covers included in the supply for S6 800) 21.5 47 32 19.5 116.5

For rear Cu/Al cables


(IP20 high terminal covers included in the supply)

21 12

S6 630 S6 630 - S6 800


25 59 20 42 16.75

S6 630

17.5 12

S6 800 S6 800

6/18

ABB SACE

GSIS0018

Fixed circuit-breaker (S6X)

Y
105 280 210 140 (4 POL) (3 POL) = -3 107 101.5 12 2

Terminal covers
(to order when not included in the supply)

1
=

249.75 263.25

low

high

47 105

X 406

161

379 =

2.5

16.5

Key
14 = 152 =
Mounting on sheet metal

9 103.5 115 159

1 2

Flange for compartment door (included in supply) Tightening torque 2 Nm

Terminals
Extended front
70 40 70 70 11 48.5 62 41.5 5 15

Front for Cu/Al cables


21.5 47 32

47

For rear Cu/Al cables


(IP54 high terminal covers included in the supply)

Front
40 22.5 0.1 6.5 21 12 12 14 9 23 5 min.

19.5

Threaded rear
(low terminal covers included in supply) 73 44
GSIS0019

6
23

70

70

70

2.5

M24x2

ABB SACE

6/19

Overall dimensions
SACE S6 - S6X
Mounting parts for fixed circuit-breaker (S6)
Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

For terminals: Front for flat bars Front extended Front for cables

For terminals for rear Cu/Al cables

SACE S6 630
Y

SACE S6 800
Y
(3 POL) (4 POL) 70 140 35 (3 POL) (4 POL)

Y
70 140 (3 POL) (4 POL)

70 140 35

109.75 109.75

141.75

109.75 301 237

141.75

237

237

301 M5/5.5 R21.5

M5/5.5 M5/5.5 R18

35

84 168 (3 POL) (4 POL) 171.5 241.5

85.75 (3 POL) (4 POL)

238

Template for drilling compartment door and fitting flange


For terminals threaded rear (thickness of sheet metal: 2 mm)
Y Y
= 70 70 70 = 115

3 POL

4 POL

147 = =

109.75

70 70 70

111.75 241

109.75 237 8

105

35

111.75 241

237 8 M5/5.5

112 142 = =

35

M5/5.5

35 7
GSIS0021

6/20

ABB SACE

Mounting parts for fixed circuit-breaker (S6X)


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)

For terminals: Front for flat bars Front extended Front for cables
Y
70 140 (3 POL) (4 POL)

For terminals for rear Cu/Al cables

Y
70 140 35 (3 POL) (4 POL)

247.75

247.75

279.75

109.75

109.75

375 M5/5.5

375

439 M5/5.5 R18

35

84 168 (3 POL) (4 POL)

238

For terminals threaded rear


3 POL
Y

Template for drilling compartment door and fitting flange


4 POL
70 70

Y
70

(thickness of sheet metal: 2 mm)

Y
105 35 = 247.75 249.75 109.75 379 375 70 8 M5/5.5 35 70 8 M5/5.5 35 7 247.75 249.75 109.75 = 115 147 = =

70

379

375

112 142 = =

Y Y Y

ABB SACE

GSIS0020

6/21

Overall dimensions
SACE S6 - S6X
Withdrawable circuit-breaker

Y
27.5 isolating travel 280 (4 POL) 210 70 70 70 (3 POL)

Key 1 2 3 4
196 X

Fixed part Moving part Flange for compartment door (included in supply) Lock for compartment door (to order) Tightening torque 9 Nm

133 = 5.5 89.5 58 14.5 145 208 295 A

140 =

5
152

A
167 2 190 195.5 193.5

S6
96 123.5 131 136.5

273 411

S6X

Terminals
Front for SACE S6 630, S6 800
31 10 20 3 70 14 70 40 70

158

Horizontal or vertical rear flat bar for SACE S6 630, S6 800


3 80.5 20 14 40

6
X X

10

6/22

GSIS0022

ABB SACE

Mounting parts for withdrawable circuit-breaker


Template for drilling sheet metal support
(minimum thickness of sheet metal: 3 mm)
Y
140 210 70 (3 POL) (4 POL (4 POL)

77.5 R2 57.5

45.5 120

X
86.5 8.5 (M8)

77.5

107 214 284

(4 POL) (3 POL) (4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)

4 80

Y
170 80.5 45 == Nr. 5 8

90

9 161 39

= 177 =

19.75 16 101 162.5 121 R min 200

GSIS0023

ABB SACE

6/23

Overall dimensions
SACE S6 - S6X
Accessories
Interlock across two horizontally-installed circuit-breakers

Y
= = 70 70 70 650 120 70 = 70 70 = 46 13.5 284

Key
Y

1 2
30
101 = A 9 101 331 =

Interlock device Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Dimensions with withdrawable version mounted on right Tightening torque 9 Nm

= 375 =

= 350 =

3
X

273 =

525

5
65 103.5 288

10.5

4 2
Y

Note See the various different versions for the dimensions of the circuit-breakers

isolating travel

27.5

A mm

S6 S6X

129 (fixed, withdrawable) 267 (fixed) 129 (withdrawable)

Interlock across two vertically-installed circuit-breakers (for S6 only)


Y
51.5 70 70 70 48.5

Key
Y

1 2
=

Interlock device Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Dimensions with withdrawable version mounted underneath Tightening torque 9 Nm

5
= 273 26

293

R 20

109

3
129 = 109 101 779 109

280

1
=

= 525 = 9

820 =

175

129 = 109

6
17 = 310 =

273

26

2
Y
27.5 isolating travel

65

288

6/24

GSIS0024

Note See the various different versions for the dimensions of the circuitbreakers

ABB SACE

Accessories
Motor operator for fixed circuit-breaker

Y
222.5 91.5

198.5

23.5 81.250.1

Y
81.250.1 19.75 8 (7 fori)

192.25 338 270 125.25 304 R8 319 72.25 159.5 22.75 174 1220.1 R. min.200

X
102.25 94.75 111.75 67 140 = 215.5 285.5 =

96.5

Key 1 Flange for compartment door (included in supply) Template for drilling compartment door Dimensions with connectors

Note See the various different versions for the circuit-breaker mounting holes

2 3

Motor operator for withdrawable circuit-breakers


Y
27.5 isolating travel 222.5 91.5

1
81.250.1

Y
81.250.1 19.75 8 (7 fori)

186.5 270 338 304 R 319 72.25 159.5 22.75

X
A 117.5 174 1220.1 R. min.200 23.5 2 = 247.5 = B

6
GSIS0025

140

Key A B
100.5

S6 S6X
ABB SACE

108

102.25 94.75

Note See the various different versions for the circuit-breaker mounting holes

1 2

Flange for compartment door (included in supply) Template for drilling compartment door 6/25

Overall dimensions
SACE S6 - S6X
Accessories
Rotary handle operating mechanism on fixed circuit-breaker
Y
104.75 = 152 140 = 2 44.5 22

Key
4 5
103.5 37

1
4 80

Rotary handle operating mechanism on circuitbreaker Lock for compartment door (to order) Drilling of compartment door Flange for compartment door (included in supply) Tightening torque 2 Nm

Y
= = 196 = = 177 147 = =
7

45 2.75 90

2 3
X

140 = =

4
= 115 147 = = R min 200

1
42.5

Drilling only required for version with rear terminals

Y
70 70 70

3 POL
70 237 (S6) 375 (S6X) 104 106 (S6) 244 (S6X) 70 241 (S6) 379 (S6X)

4 POL

Note See the various different versions for the circuit-breaker mounting holes
106 (S6) 244 (S6X) 241 (S6) 379 (S6X)

237 (S6) 375 (S6X) 104 133 8

105

35

X
133 8 M5/5.5

70

35

M5/5.5

35

Compartment door-mounted rotary handle mechanism with adjustable depth for fixed circuit-breaker
Y

6
31 103.5 23

105 41.5

63

22

Key
5
Y
41.5 5 = 46

1 2

Transmission assembly Rotary handle assembly with door lock device Padlock device (maximum 3 padlocks max 6 mm to be provided by customer only for circuit-breaker open position) Minimum radius of rotation for fulcrum of door Drilling template for mounting circuit-breaker on sheet metal 72...506 mm (with IP54 protection min. 96) Distance 6 -4 mm (shaft length)

19

28 105 36

28 33

3
2 27 54 R min 200 168

6
3 POL
70 237 (S6) 375 (S6X) 104

4
R min 200

Drilling only required for version with rear terminals

6
Y
70 70 70

4 POL
106 (S6) 244 (S6X) 70 241 (S6) 379 (S6X)

7
106 (S6) 244 (S6X) 241 (S6) 379 (S6X)

237 (S6) 375 (S6X) 104 133 8

105

35

X
133 8 M5/5.5

70

35

M5/5.5

35

Note See the various different versions for the circuit-breaker mounting holes ABB SACE

6/26

GSIS0026

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Key
Y
210 4 80

2 44.5

22

1
Y
170 80.5 45 == 90 9 39 Nr. 5 8

Rotary handle on circuit-breaker Lock for compartment door (to order) Padlock device for open position (maximum 3 padlocks max. 6 mm to be provided by user)

3
196

= 177 =

161

3
151

1
37 222.5 91.5 123.5 131 136.5 42.5

16 19.75 101 162.5 121 R min 200

Note See the various different versions for the circuit-breaker mounting holes

Front flange for operating lever mechanism


Y
104.75 = 152 140 =

103.5

37

2 4 80

Key 1 2
90

Front flange for operating lever mechanism Lock for compartment door (to order) Drilling of compartment door Flange for compartment door (included in supply) Tightening torque 2 Nm

Y
45 = = 196 = = 177 147 = =
7

2.75

140 = =

3 4

= =

115 147

= =

3 5

1
Y
42.5

3 POL
106 (S6) 244 (S6X) 237 (S6) 375 (S6X) 104 70 70 70 241 (S6) 379 (S6X)

Drilling only required for version with rear terminals

Note See the various different versions for the circuit-breaker mounting holes

External neutral
75 40 = 52.5 25 115 10

X
133 8 M5/5.5

35

4 POL

Y
70 70 70 =
5 6 Line In
100 A 160 A 200 A 250 A

185 77 49 106 (S6) 244 (S6X) 237 (S6) 375 (S6X) 104 105 35 241 (S6) 379 (S6X) =

115

320 A 400 A

Load

X
133 8 35

X
=
6 X 1 4

25
GSIS0027

= M5/5.5

11

ABB SACE

6/27

Overall dimensions
SACE S7
Fixed circuit-breaker
Y
280 = 70 7 7 37 217 30.5 70 210 152 = 70 (4 POL) (3 POL)

Terminal covers
2 low

1
177

406

= 161 =

326

105 =

37 7 140 3 138.5 140.5 146.5 214.5

Key 1 2
2

Flange for compartment door (included in supply) Tightening torque 2 Nm

Terminals
Front
Y
140 50 22 11 10 10 10 33.5

Front extended
Y
70 22 70 70 50 11 22 107 71 22 22 39 15

Front for Cu/Al cables for S7 1250


97 78 57 70 38 21.4

Y
70 70

37

30.5

Horizontal or vertical flat bar rear terminals


Y
70 70 70 85

16

171.5

Front extended spreaded


Y
45 116 90 116 22.5 23 116 22.5 13 45 50 15 315

B
107 50 11 14 22 22
GSIS0028

A = horizontal installation B = vertical installation 6/28 ABB SACE

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support
(Minimum thickness of sheet metal:3 mm)

For terminals: Front Front extended Front for Cu/Al cables


Y
70 140 (3 POL) (4 POL)

For flat bar rear terminals

3 POL

4 POL

Y
220 3.6 H12 50 80 203 171.5 R40 70 = = 70 70 203 378 315 R40 70 70 171.5 290

Y
3.6 H12 50 80 140

203

378

378

315

X
70

M5/5.5 35 5.5 - M5 35

5.5 - M5

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
Y
147 = = 115 = =

112 142 = =

GSIS0029

ABB SACE

6/29

Overall dimensions
SACE S7
Withdrawable circuit-breaker

Y
241.5 280 3 210 140 (4 POL) (3 POL)

Key 1 2 3 Fixed part Moving part Flange for compartment door (included in supply) Lock for compartment door (to order) Tightening torque 9 Nm

2
2

1
211.25 143.25

3
4 5

140 =

8.25

160 max

270

406

196

5
5.5 218.5 247 27.5 isolating travel 193.5 96 123.5 131 136.5

Terminals
Front
31 16 67 22 3 70 70

Y
70 50 22 14

11

Horizontal or vertical flat bar rear terminals


108 3

11 22 50

6
22 14

143.25

X
16

70

70

70

6/30

GSIS0030

ABB SACE

Mounting parts for withdrawable circuit-breaker


Template for drilling sheet metal support or channel
(Minimum thickness of sheet metal: 3 mm)
Y
140 210 70 (3 POL) (4 POL)

120.5

92.5

68.25 8.5 (M8)

120

X
76

120.5

107 214 284 (3 POL) (4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)

4 80

Y
170 7 80.5 45 ==

Nr. 5 8

90

9 161 39 7 19.75 101 162.5 121 R min 200 16

= 177 =

ABB SACE

GSIS0031

6/31

Overall dimensions
SACE S7
Accessories
Interlock across two horizontally-installed circuit-breakers
Y
660 = 70 70 70 120 70 70 70 = 300 7
20

Y
30

Key 1
300 6.5

Interlock device Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Dimensions with withdrawable version mounted on right Tightening torque 9 Nm

= 420 =

115 =

3
X
406 450 = 117 407 =

115 6.5

5
65

5.5

40

550

40

4 2
Y

140.5 336

isolating travel

27.5

Note See the various different versions for the dimensions of the circuitbreakers

Interlock across two vertically-installed circuit-breakers


Y

Key 1 2 Interlock device Drilling template for mounting circuit-breaker on sheet metal Drilling template for all versions with rear terminals Tightening torque 9 Nm

= 406 =

Y
315 =

3 4
115

1
= = 7 = = 875 = R30 290 =

= = 408 = = 9 994

1100 =

166 7

6
=

406 =

2 4
7

70

70 340

70

= 65 336 27.5

isolating travel

GSIS0032

Note See the various different versions for the dimensions of the circuitbreakers ABB SACE

6/32

Accessories
Motor operator for fixed circuit-breaker
Y
222.5 91.5 140 = = 2

Y
23.5 81.250.1 19.75 Nr. 7 8 81.250.1

1
7

231.5

195.75 338 270

217 304 319 72.25 159.5 108.25 98.75 91.25 22.75 174 1220.1 R. min.200 215.5 285.5 91

R8

Key
Y

1 Note See the various different versions for the circuit-breaker mounting holes 2 3

Flange for compartment door (included in supply) Template for drilling compartment door Dimensions with connectors

Motor operator for withdrawable circuit-breaker


27.5 isolating travel

Y
222.5 91.5 140 = = 7

81.250.1 19.75 Nr. 7 8

81.250.1

211.25 270

190 338 304 R8 319 72.25 159.5 104.5 114 174 1220.1 R. min.200 97 22.75

2
GSIS0033

23.5 2

295.5

Y Y

Key Note See the various different versions for the circuit-breaker mounting holes ABB SACE 1 2 Flange for compartment door (included in supply) Template for drilling compartment door 6/33

Overall dimensions
SACE S7
Accessories
Rotary handle operating mechanism on fixed circuit-breaker
Y

44.5

22

105 = 140 =

140.5

37 4 80

Key 1 Rotary handle operating mechanism on circuitbreaker Lock for compartment door (to order) Drilling of compartment door Drilling template for mounting circuit-breaker on sheet metal Flange for compartment door (included in supply) Tightening torque 2 Nm

= 211.25 =
X

2 1
406
= = 2.75

Y
45

2
90

196 140

177147 = =

3 4

7
= = 115 147 = = R min 200

3
5 6

152

42.5

Drilling only required for version with rear terminals

3 POL

Y
50

4 POL

Y
50

197.25 165.75

70 70 70 5.5- M5

197.25 165.75 378 315 70 70 140

35

378

315

X
70 5.5- M5

Note See the various different versions for the dimensions of the circuitbreakers

R 40

R 40

Compartment door-mounted rotary handle operating mechanism for fixed circuit-breaker


Y

105 105 41.5 31

1 7
19
63 22

Key 1 Transmission assembly Rotary handle assembly with door lock device Padlock device (maximum 3 padlocks max 6 mm to be provided by customer only for circuit-breaker open position) Minimum radius of rotation for fulcrum of door Template for drilling compartment door Drilling template for mounting circuit-breaker on sheet metal 72 ... 506 mm (with IP54 protection min. 96) Distance lenght) 7 - 4 mm (shaft
Y
41.5 5 =

2 3
X

211.25

2
406 90

23
46

105 28 36

28 33

3
2
27 54

4
R min 200

5 6

6
3 POL
197.25 165.75

205

4
R min 200

Drilling only required for version with rear terminals Y


50 70 70 70 5.5- M5 R 40 220 3.6 H12 197.25 165.75 378 315 70 70 140 35

4 POL

Y
50

7 8
X
70 5.5- M5 80
GSIS0034

378

315

80 R 40 290

3.6 H12

Note See the various different versions for the dimensions of the circuitbreakers ABB SACE

6/34

Accessories
Rotary handle operating mechanism on withdrawable circuit-breaker
Y
= 210 =

4 2 44.5 22

80

Key 1 Rotary handle operating mechanism on circuitbreaker Lock for compartment door (to order) Padlock device for open position (maximum 3 padlocks max. 6 mm to be provided by user)

Y
170 80.5

211.25

45 == 90 9 39

Nr. 7 7

2
X 3

= 177 =

X
406

196 =

161

3 1
222.5 131 136.5

16 19.75 101 162.5 121 R min 200

91.5 123.5

37 42,5

Note See the various different versions for the circuit-breaker mounting holes

Front flange for operating lever mechanism


Y

105 = 140 =

Key
4 80

140.5

37

= 211.25 =

Front flange for lever operating mechanism Lock for compartment door (to order) Drilling of compartment door Drilling template for mounting circuit-breaker on sheet metal Flange for compartment door (included in supply) Tightening torque 2 Nm

2
=

45

2
90

196 140

406

= =

2.75

177 147 =

3 4

= =

115 147

= =

Y
152
42.5

5 6

3 POL

Y
50 197.25 165.75 70 70 70

Drilling only required for version with rear terminals


4

Note See the various different versions for the circuit-breaker mounting holes

External neutral
X
75 5.5- M5 40 = 52.5 25 115 10

378

315

R 40 =

4 POL

=
5 6 Line In
100 A 160 A 200 A 250 A 320 A 400 A

50 197.25 165.75 35 70 70 140 70

185 77 49

115

4
X
=

Load

X 378

315

5.5- M5 R 40

X 1 4

25 =
GSIS0035

11

ABB SACE

6/35

Overall dimensions
SACE S8
Fixed circuit-breaker
= 380 = 556 242

2 3

2.5

20 9

20

400 313

X 280

280 400

20 15 120 120 150 120 120 203 406 = 530 =

20 236,5 286,5

Y
3 POL

Y
4 POL

Terminals
Front (S8 2000-2500)
Y 324 80 20 15 = 40 = 20 65 20 20 80

Rear (S8 2000-2500)


Y 324 = 40 = 20 = 80 40 40 40 = 15 40 15 20 120 115 85 65

20

150

120 Y

120

150

120 Y

120

20

Rear (S8 3200)


100 95 50 324 17,5 85

Y
100

20 40 20 20 40 3

580

520

6
20 65 15 65

25 50 15 25 18 = 150 120 40 = 120 80 15

20

1 2 3 6/36

Flange for compartment door Circuit-breaker mounting holes Internal side of compartment door

ABB SACE

GSIS0036

Key

Mounting parts for fixed circuit-breaker


Template for drilling sheet metal support
(Minimum thickness of sheet metal: 3mm)

Template for drilling compartment door and fitting flange


(Minimum thickness of sheet metal: < 2,5mm)

N. 8 9

N. 8 9

3 POL

4 POL

Key 1 2 Hole for rear terminals only Minimum radius of rotation of compartment door

Accessories
External neutral

ABB SACE

6/37

Overall dimensions
Distances to be respected
Insulation distances for installation in metal compartment with wall to chassis ground or wall to chassis ground protected with insulating plate

Wall to chassis ground [mm]

B
B C

A (Ub 415V)

A(*) (Ub 440V) 50 50 100 100 100 100 100 200

S1 S2 S3 S4 S5 S6 S7 S8

25 25 35 35 35 35 50 200

20 20 25 25 25 25 30 30

20 20 20 20 20 20 20 120

I O

o off

(*) these distances are valid for operating voltages of > 440 V and for circuit-breakers with breaking capacity level L.

E 3 POL 3 POL

S2X100 S3X S4X S6X

25 50 60 60

20 25.5 25.5 30.5

20 30 30 30

169 340 430 500

135 161 161 275

196 196 345

73 112 112 152

E B A B

A - B - C = Distances inside compartment walls D - E - F = Distances outside compartment

Insulation distances for installation in insulated compartment


Insulated wall [mm]

B 0 0 0 0 0 10 10 15

C 20 20 20 20 20 20 20 120

D
I O
o off

S1 S2 S3 S4 S5 S6 S7 S8
6/38

25 25 35 35 35 35 50 120

The dimensions shown apply for operating voltages Ub of up to 690 V . The dimensions to be respected must be added to the maximum dimensions of the various different versions of the circuit-breakers, including the terminals.

ABB SACE

GSIS0071

GSIS0038

Minimum distance between centres for two horizontally or vertically-installed circuit-breakers


For horizontal or vertical installation, make sure that the connection busbars or cables dont reduce the air insulation distan ces.

Minimum distance between centres for horizontallyinstalled circuit-breakers


Circuit-breaker width [mm]

I
[mm]

3 POL

4 POL 103 120 140 140 184 280 280 585

3 POL 78/93(*) 90/105 (*) 105/119(*) 105/119(*) 140 210 210 435

4 POL 103/118(*) 120/135(*)

S1 S2 S3 S4 S5 S6 S7 S8

78 90 105 105 140 210 210 435

on

on off

140 140 185 280 280 585

off

l
Y Y

(*) these are the distances to be respected for circuit-breakers fitted with a flange for the compartment door or side conductor outlets.

The distances between centres are for the installation of fixed and plug in circuit-breakers. When installing withdrawable SACE S3, S4, S5, S6, S7 circuit-breakers you should also take into account the dimensions of the metal supporting channel that needs to be fitted between the guides of the fixed parts of two adjacent circuit-breakers.

Minimum distance between centres for verticallyinstalled circuit-breakers


H [mm]

S1 S2 S3 S4 S5 S6 S7 S8

60 90 140 140 140 180 180 300


1 2 3 Connection not insulated Insulated cable Cable terminals
GSIS0040

1 H

3 H

2 H

ABB SACE

6/39

6/40

ABB SACE

Circuit-diagrams

Index
Operating status shown ................................................................................................. 6/42 Duty releases ..................................................................................................................... 6/44 Auxiliary contacts ............................................................................................................. 6/46 Position contacts ............................................................................................................. 6/48 Auxiliary circuits of electronic releases ........................................................................ 6/50 Motor operators ................................................................................................................ 6/53 Graphic symbols for circuit-diagrams (IEC 617 and CEI 3-14 3-26) ..................... 6/54 Key and reference notes ................................................................................................. 6/55

ABB SACE

6/41

Circuit diagrams
Operating status shown

The circuit is shown in the following conditions: fixed, plug in or withdrawable circuit-breaker (depending on type of circuit-breaker), open and racked in circuits de-energised releases not tripped

motor operator with springs loaded (for S6-S7 circuit-breakers)

The circuit-breaker is only fitted with those accessories specified in the ABB SACE confirmation of order. Consult this catalogue for information on how to make out an order.

SACE S1-S2-S3-S5-S6
Three-pole or four-pole circuit-breaker with thermomagnetic release

SACE S3D-S6D-S7D-S8D
Three-pole or four-pole switch-disconnector

GSIS0045

SACE S1-S2-S3
Four-pole fixed circuit-breaker with vertically-installed residual-current release SACE RC211 o RC212 Four-pole fixed circuit-breaker with horizontally-installed residual-current release SACE RC210, RC211 o RC212

6
GSIS0047

GSIS0046

RC211 RC212

RC210 RC211 RC212


GSIS0048

6/42

ABB SACE

SACE S4-S5-S6-S7
Three-pole or four-pole circuit-breaker with SACE PR211/P microprocessor-based release Three-pole or four-pole circuit-breaker with SACE PR212/P microprocessor-based release
Three-pole circuit-breaker with SACE PR212/MP microprocessor-based release

GSIS0049

SACE S4-S5-S6-S7
Three-pole fixed circuit-breaker with current transformer on neutral conductor outside circuit-breaker Three-pole plug-in or withdrawable circuit-breaker with current transformer on neutral conductor outside circuit-breaker
Circuit of current transformer on neutral conductor outside circuitbreaker (for withdrawable circuit-breaker)

GSIS0050

Term.X5

Internal circuit
Term.X5

External circuit

GSIS0051

N.B.

If using a fixed circuit-breaker with a current transformer on the neutral conductor outside the circuitbreaker, you must short-circuit the terminals of the TI/N transformer when you want to remove the circuitbreaker.

GSIS0052

6
GSIS0053

ABB SACE

External circuit

6/43

Circuit diagrams
Duty releases
SACE S1-S2
Opening release Opening solenoid of SACE RC211 residualcurrent release Opening solenoid of SACE RC212 residual-current release Instantaneous undervoltage release

Conn. X1

Conn. X1

External circuit

Internal circuit

External circuit

SACE S3
Opening release Opening solenoid of SACE RC211 residualcurrent release Opening solenoid of SACE RC212 residual-current release Instantaneous Version of instantaneous undervoltage undervoltage release for machine tools release Undervoltage release with electronic time-lag device outside the circuit-breaker

Term. XV

Term. XV

External circuit

Internal circuit

External circuit

GSIS0054

6/44

ABB SACE

GSIS0055

SACE S4-S5
Opening release Instantaneous Version of instantaneous undervoltage undervoltage release for release machine tools Undervoltage release with electronic time-lag device outside the circuit-breaker

Incompatibility
The circuits indicated in the following figures cannot be powered simultaneously on the same circuit-breaker 1 - 4 - 5 - 6 2 - 3

Availability
External circuit
Connectors X1 and X2 are only supplied to order for circuit-breakers S1 - S2.

Notes
Conn. X1 Term. XV
(*A) The undervoltage release is powered from upstream of the circuit-breaker or by an independent power supply: closing of the circuit-breaker is only allowed when the release is energised (the clos-

Internal circuit

ing lock is implemented mechanically).

(*B) Contact S4 shown in Fig. 5 opens the circuit when the circuitbreaker is open and closes it again upon a manual closing command

Term. XV Conn. X1

from the rotary handle, in conformity with the Standards governing machine tools (the circuitbreaker will not close, however, if

External circuit

the undervoltage release is not powered).


GSIS0056

SACE S6-S7
Opening release Instantaneous undervoltage release Undervoltage release with electronic time-lag device outside the circuit-breaker

Conn. X1 Term. XV

External circuit

Term. XV Conn. X1

External circuit

Internal circuit

ABB SACE

GSIS0057

6/45

Circuit diagrams
Auxiliary contacts
SACE S1-S2
Two change-over contacts for electrical signalling of circuitbreaker open/closed One change-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic releases YO, YO1, YU (tripped position)

Conn. X2

Conn. X2

External circuit

Internal circuit

External circuit

SACE S3-S4-S5-S6-S7
Two change-over contacts for electrical signalling of circuitbreaker open/closed One change-over contact for electrical signalling of circuit-breaker open or closed and one changeover contact for electrical signalling of circuitbreaker open due to tripping of thermomagnetic releases YO, YO1, YU (tripped position)

Conn. X2

Term. XV

Term. XV Conn. X2

External circuit

Internal circuit

External circuit

6/46

GSIS0059

GSIS0058

ABB SACE

SACE S6-S7
One contact for electrical signalling of circuit-breaker open, one change-over contact for electrical signalling of circuit-breaker closed and one contact for electrical signalling of circuit-breaker not open due to tripping of thermomagnetic releases YO1, YO1, YU (not tripped/tripped position) to be used, for example, for the enabling shown in Fig.8 External circuit

Incompatibility
The circuits indicated in the following figures cannot be powered simultaneously circuit-breaker: 11-12-13-14 on the same

Availability
Connectors X1 and X2 are only supplied to order for circuit-breakers S1 - S2.

Notes
Conn. X2 Term. XV
(*C) The electrical signalling contact for the microprocessor-based overcurrent release, shown in Fig. 41, has the following electrical characteristics: rated voltage = 125V AC /

Internal circuit

30V DC breaking capacity (resistive load = 3 W/VA) maximum interrupted current = 0.5 A

Term. XV Conn. X2

External circuit

SACE S4-S5-S6-S7

Contact for signalling release Y01 tripped

External circuit

GSIS0080

Term. X6 Term. X5

Term. X5 Term. X6

External circuit

Internal circuit

ABB SACE

GSIS0060

6/47

Circuit diagrams
Position contacts
SACE S2

First circuitbreaker position contact, for electrical signalling of inserted External circuit

Second circuitbreaker position contact, for electrical signalling of inserted

Third circuitbreaker position contact, for electrical signalling of inserted

Term. XV

Term. XV

External circuit

Internal circuit

SACE S3
First circuitbreaker position contact, for electrical signalling of inserted External circuit Second circuitbreaker position contact, for electrical signalling of inserted First circuit-breaker position contact, for electrical signalling of racked out or removed

Term. XV

Term. XV

External circuit

Internal circuit

GSIS0061

6/48

GSIS0062

ABB SACE

SACE S4-S5

First circuitbreaker position contact, for electrical signalling of inserted External circuit

Second circuitbreaker position contact, for electrical signalling of inserted

Third circuitbreaker position contact, for electrical signalling of inserted

First circuit-breaker position contact, for electrical signalling of racked out or removed

Second circuitbreaker position contact, for electrical signalling of racked out or removed

Third circuit-breaker position contact, for electrical signalling of racked out or removed

Term. XV

Term. XV

External circuit

Internal circuit

SACE S6-S7

Incompatibility
The circuits indicated in the

First circuit-breaker position contact, for electrical signalling of inserted

Second circuit-breaker position contact, for electrical signalling of inserted

Third circuit-breaker position contact, for electrical signalling of inserted

Fourth circuit-breaker position contact, for electrical signalling of inserted

Fifth circuit-breaker position contact, for electrical signalling of inserted

First circuit-breaker position contact, for electrical signalling of racked out

Second circuit-breaker position contact, for electrical signalling of racked out

Third circuit-breaker position contact, for electrical signalling of racked out

Fourth circuit-breaker position contact, for electrical signalling of racked out

Fifth circuit-breaker position contact, for electrical signalling of racked out

following figures cannot be powered simultaneously on the same circuitbreaker: 20 - 21 - 31 22 - 32 24 - 34 23 - 33 25 - 35

GSIS0063

Notes
(*D) The circuitbreaker can be

Term. XV

fitted with position contacts S75I and S75S in any combination up to a maximum of

Internal circuit

total of 2 contacts for S3 total of 3 contacts for S4, S5 total of 5 contacts for S6, S7

Term. XV

ABB SACE

GSIS0064

6/49

Circuit diagrams
Auxiliary circuits of SACE PR212/P electronic releases
SACE S4-S5-S6-S7

SACE PR212/P release connected to the dialogue unit SACE PR212/D and actuator unit SACE PR212/T

SACE S4-S5-S6-S7

SACE PR212/P release connected to the dialogue unit SACE PR212/D, signalling unit SACE PR010/K and actuator unit SACE PR212/T

6/50

ABB SACE

GSIS0162

GSIS0161

Circuit diagrams
Auxiliary circuits of SACE PR212/MP electronic releases for motor protection
SACE S4-S5-S6-S7
SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L and actuator unit SACE PR212/T

SACE S4-S5-S6-S7

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L, actuator unit SACE PR212/T and contactor operator unit SACE PR212/CI

GSIS0164

ABB SACE

6/51

GSIS0163

Circuit diagrams
Auxiliary circuits of SACE PR212/MP electronic releases for motor protection
SACE S4-S5-S6-S7
SACE PR212/MP release connected to the signalling unit SACE PR010/K and contactor operator unit SACE PR212/CI

GSSC0318

SACE S4-S5-S6-S7

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L, actuator unit SACE PR212/T, signalling unit SACE PR010/K and contactor operator unit SACE PR212/CI

GSSC0319

6/52

ABB SACE

GSIS0166

GSIS0165

SACE S4-S5-S6-S7

SACE PR212/MP release connected to the dialogue unit SACE PR212/D-L and actuator unit SACE PR212/T

GSIS0167

ABB SACE

6/53

Circuit diagrams
Motor operators
SACE S1-S2 SACE S3-S4-S5

Solenoid operator

Direct action motor operator

External circuit

Conn. X2

Conn. X2 Term. XV

Internal circuit

Term. XV Conn. X2 Conn. X2

External circuit

GSIS0081

External circuit

Internal circuit

External circuit

SACE S6-S7
Stored-energy motor operator

Conn. X2

Term. XV

Term. XV Conn. X2

External circuit

Internal circuit

External circuit

6/54

GSIS0066

ABB SACE

GSIS0065

Circuit diagrams
Graphic symbols for circuit diagrams (Standards IEC 617 and CEI 3-14...3-26)
Thermal effect Terminal or clamp Make contact with held position

Electromagnetic effect

Socket (female) or pole of a socket

Make position contact (limit contact)

Time delay

Socket and plug (female and male)

Opening position contact (limit contact)

Mechanical connection

Temperature dependent resistor

Change-over position contact with temporary interruption (limit contact)

Manual mechanical control (general case)

Resistor (general symbol)

Switch-disconnector

Pushbutton actuator

Induction motor, threephase, squirrel cage

Contactor (closing contact)

Key control

Motor (general symbol)

Circuit-breaker with automatic release

Cam control

Brush

Control coil (general symbol)

Earth (general symbol)

Motor energised in series

Instantaneous overcurrent relay

Equipotentiality

Current transformer with primary formed by 4 through conductors and wound secondary, with socket

Overcurrent relay with adjustable short time-delay trip

Galvanically separated converter

Current transformer

Overcurrent relay with short inverse time-delay trip

Shielded cable conductors (example: two conductors)

Make contact

Overcurrent relay with inverse long time delay

Conductors or stranded cables (example: two conductors)

Break contact

Earth fault overcurrent relay with inverse short time-delay trip

Connection of conductors

Change-over contact with temporary interruption

Residual current relay

ABB SACE

6/55

Circuit diagrams
Key and notes

=
* A1 A2 A4

Figure number of diagram

Q Q/0 ... 2 R

= Main switch = Auxiliary contacts of the circuit-breaker = Resistor outside the circuit-breaker, supplied for motor power supply voltages of more than 220 V

= See the note indicated by the letter = Applications of the circuit-breaker = Applications of the motor operators = Example switchgear and connections for control and signalling, outside the circuit-breaker

S1

= For S3 - S4 - S5: position contact operated by a circuitbreaker cam For S6 - S7: contact controlled by the motor operator cam: closes when the circuit-breaker reaches its closed position and opens when the circuitbreaker reaches its open position (doesnt switch when the circuit-breaker goes into its tripped position)

A11

= PR212/D-L dialogue unit, for connection to a centralised control system

A12

= PR212/T actuator unit, with auxiliary relays for executing commands from the dialogue unit

A12/KC A12/KO A13

= Actuator unit closing control = Actuator unit opening control = PR010/K signalling unit with auxiliary relays for electrical signalling of the protection functions of the microprocessor-based overcurrent release

S2

= For S3 - S4 - S5: safety contact operated by: - key lock (if fitted) - padlock device - manual control selector. For S6 - S7: contact controlled by the motor operator cam: opens when the circuit-breaker reaches its closed position and closes when the circuit-breaker reaches its open position (doesnt switch when the circuit-breaker goes into its tripped position).The contact is also operated by the key lock device (if present)

A14 D

= Interface unit with SACE PR212/CI operator unit = Electronic time-lag device of undervoltage release (outside the circuit-breaker)

K51

= PR211, PR212/P or PR212/MP microprocessor-based overcurrent release tions: - L overload protection with inverse long time-delay trip - S short-circuit protection with inverse or definite short time-delay trip (only available with PR212/P release) - I short-circuit protection with instantaneous trip - G earth fault protection with inverse short time-delay trip (only available with PR212/P release) S4 with the following protection funcS3

= Contact controlled by the motor operator cam: opens after contact KO has closed and closes when the circuit-breaker reaches its open position (doesnt switch when the circuit-breaker goes into its tripped position) = Contact operated by the circuit-breaker rotary handle Contacts for electrical signalling of circuit-breaker in inserted position (only for plug in or withdrawable circuit-breakers)

S75I/1...5 =

K51/X

= Electrical signalling of alarm for internal communication fault

S75S/1...5 = Contacts for electrical signalling of circuit-breaker in removed or racked-out position (only for plug in or withdrawable circuit-breakers) SC = Pushbutton or contact for closing the circuit-breaker or for motor start. For circuit-breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100ms SO = Pushbutton or contact for opening the circuit-breaker or for motor stop SO1, S02 = Pushbuttons or contacts for opening the circuit-breaker. For circuit-breakers S3 - S4 - S5, the operating mechanism must have a time of not less than 100 ms (see Instructions for resetting the circuit-breaker after the releases have tripped) SY = Contact for electrical signalling of circuit-breaker open due to tripping of thermomagnetic releases, YO, YO1, YU (tripped position) TI TI/L1 TI/L2 TI/L3 TI/N = Toroidal current transformer = Current transformer located on phase L1 = Current transformer located on phase L2 = Current transformer located on phase L3 = Current transformer located on neutral

K51/X

= Electrical signalling of alarm for protection function G in tripping zone

K51/X

= Electrical signalling of alarm for protection function I in tripping zone

K51/X

= Electrical signalling of alarm for protection function L in tripping zone

K51/X

= Electrical signalling for protection function L in pre-alarm zone

K51/X

= Electrical signalling of alarm for protection function S in tripping zone

K51/X

= Electrical signalling of alarm for release YO1 tripped due to overcurrent or trip test (Fig. 41)

K87

= RC211-RC212 residual-current release (for circuitbreakers S1-S2-S3) or RC210 (for circuit-breaker S1)

KO

= For S3 - S4 - S5: auxiliary opening relay. For S6 - S7: opening and spring-loading relay with heldposition make contact, released by a cam of the motor operator when the circuit-breaker reaches its open position and the closing springs have been loaded

= For S3 - S4 - S5: motor with energising in series for opening and closing of the circuit-breaker. For S6 - S7: motor for opening the circuit-breaker and loading the closing springs of the circuit-breaker

M1

= Three-phase asinchronous motor

6/56

ABB SACE

Circuit diagrams
Graphic symbols for circuit diagrams (Standards IEC 617 and CEI 3-14...3-26)
W1 = Serial interface with monitoring system (EIA RS485 interface) X1, X2 = Connectors for the auxiliary circuits of the circuit-breaker. For circuit-breakers S1 - S2 supplied to order only. X3, X4 = Connectors for the circuits of the microprocessor-based overcurrent release (with plug in or withdrawable circuit-breakers, the connectors are pulled out at the same time as the circuit-breaker) X5, X6 = Terminal deliver y block for microprocessor-based overcurrent release circuits XO XV YC YO YO1 = Connector for the opening solenoid YO1 = Terminal blocks for accessories = Closing release = Opening release = Opening solenoid of the RC211 or RC212 residual current release (for S1 - S2 - S3) and of the overcurrent release (for S4 ... S8) YU = Undervoltage release Manual resetting is always allowed in each of these examples.

3) Electrical resetting always enabled


The electrical opening control (contact SO2) is connected in series directly to relay KO for S3 - S4 - S5 or connected directly to pole A3 of connector X2 (for S6 - S7) and is therefore always enabled. Example of use: automatic resetting of the circuit-breaker immediately after the releases have been tripped N.B. If an overcurrent release is fitted, it will be necessary to identify the causes that brought it to its tripped position in order to prevent it from closing again in short-circuit conditions.

The circuit-breaker can open both through the action of the motor operator and due to the following releases tripping: overcurrent undervoltage opening with consequent opening of contact SY (if fitted) in series with relay KO. A reset operation involving manual or electric opening will have to be carried out in order to close the circuit-breaker again after tripping. Contact SY closes again at the end of the operation. The type of resetting should be chosen to suit the design requirements and duty conditions. A number of possible solutions are suggested below:

Conn.X1 Term.XV

1) Manual resetting only


The electrical opening control (contact SO1) must be connected

in series with contact SY. Opening (for S3 - S4 - S5 using the auxiliary relay KO) is therefore prevented until the circuit-breaker is in its tripped position. To reset the circuit-breaker one needs to operate the related lever until the circuit-breaker is in its open position and the closing springs are fully loaded.

Conn.X1

External circuit

GSIS0067

Term.XV

Internal circuit

External circuit

Instructions for resetting the circuit-breaker after the releases have tripped

2) Electrical resetting, responsibility of the operator


The normal electric opening control (contact SO1) must be connected in series with contact SY. Another opening control is provided (contact SO2), connected in series directly to relay KO for S3 - S4 - S5 or connected directly to pole A3 of connector X2 for S6 - S7. This control must be protected by, for example, a pushbutton keyswitch. It should only be used if the information relayed to the control station manager allows one to rule out the possibility of the tripping having been caused by a short circuit, or if the causes of the short circuit have been removed.

ABB SACE

6/57

6/58

ABB SACE

Order codes

Index
General information .......................................................................................................... 7/2 Circuit-breakers for power distribution SACE Isomax S1 ................................................................................................... SACE Isomax S2 ................................................................................................... SACE Isomax S3 ................................................................................................... SACE Isomax S4 ................................................................................................... SACE Isomax S5 ................................................................................................... SACE Isomax S6 ................................................................................................... SACE Isomax S7 ................................................................................................... SACE Isomax S8 ................................................................................................... Current-limiting circuit-breakers SACE Isomax S2X 100 ......................................................................................... SACE Isomax S3X ................................................................................................. SACE Isomax S4X ................................................................................................. SACE Isomax S6X ................................................................................................. Circuit-breakers for motor protection SACE Isomax S2X 80 ........................................................................................... SACE Isomax S3 ................................................................................................... SACE Isomax S4 ................................................................................................... SACE Isomax S5 ................................................................................................... SACE Isomax S6 ................................................................................................... SACE Isomax S7 ................................................................................................... SACE Isomax S3X-S4X-S6X ................................................................................

7/3 7/6 7/13 7/26 7/32 7/41 7/47 7/51

7/52 7/53 7/56 7/58

7/60 7/61 7/62 7/63 7/63 7/63 7/64

Circuit-breakers for applications up to 1000 V .............................................................. 7/65 Switch-disconnectors SACE Isomax S2D SACE Isomax S3D SACE Isomax S6D SACE Isomax S7D SACE Isomax S8D

................................................................................................ ................................................................................................ ................................................................................................ ................................................................................................ ................................................................................................

7/67 7/68 7/70 7/71 7/72

Accessories ....................................................................................................................... 7/73

7
ABB SACE 7/1

Order codes
General information
Interpretation of abbreviations used for article description

F = Front terminals

FC Cu = Front terminals for copper cables

RC = Rear terminals for cables

EF = Extended front terminals

FC CuAl = Front terminals for copper / aluminium cables R = Threaded rear terminals

VR = Vertical flat-bar rear terminals

ES = Spreaded extended front terminals

HR = Horizontal flat-bar rear terminals

Im

Magnetic trip current

PR211 P

Im = 3 Ith

Microprocessorbased electronic release SACE PR211/P (functions I - LI) Microprocessorbased electronic release SACE PR212/P (functions LSI - LSIG)

DC

Direct current circuit-breakers for applications up to 1000V Alternate current circuit-breakers for applications up to 1000V Rated uninterrupted current of the circuitbreaker Rated current of electronic release

Im = 5 Ith

AC ~ PR212 P

Im = 10 Ith

Im = 5...10 Ith

Iu
PR212 MP

Microprocessorbased electronic release for motor protection SACE PR212/MP (functions LRIU)

In

Ith

Rated current of thermomagnetic release Rated short-time withstand current

Icw

Icu

Rated ultimate short-circuit breaking capacity

Icm

Rated duty shortcircuit making capacity (peak value)

7
7/2 ABB SACE

Order codes
SACE Isomax S1 circuit-breaker

F = FIXED

S1B 125
Thermomagnetic release

Iu (40 C) =

125 A

Icu (415 V) =

16 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

code 1SDA0 . . . . . R1 3 poles 4 poles

FC Cu = Front terminals for copper cables S1B 125 F FC Cu R 10 S1B 125 F FC Cu R 12.5 S1B 125 F FC Cu R 16 S1B 125 F FC Cu R 20 S1B 125 F FC Cu R 25 S1B 125 F FC Cu R 32 S1B 125 F FC Cu R 40 S1B 125 F FC Cu R 50 S1B 125 F FC Cu R 63 S1B 125 F FC Cu R 80 S1B 125 F FC Cu R 100 S1B 125 F FC Cu R 125 R = Terminali posteriori filettati S1B 125 F R R 10 S1B 125 F R R 12.5 S1B 125 F R R 16 S1B 125 F R R 20 S1B 125 F R R 25 S1B 125 F R R 32 S1B 125 F R R 40 S1B 125 F R R 50 S1B 125 F R R 63 S1B 125 F R R 80 S1B 125 F R R 100 S1B 125 F R R 125

PSIS9601

160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A

23645 23647 23649 23651 23653 23655 23657 23659 23661 23663 23665 23667 23765 23767 23769 23771 23773 23775 23777 23779 23781 23783 23785 23787

24245 24247 24249 24251 24253 24255 24257 24259 24261 24263 24265 24267 23885 23887 23889 23891 23893 23895 23897 23899 23901 23903 23905 23907

500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A

00002 00004 00006 00008 00010 00012 00014 00016 00018 00020 00022 00024 00027 00029 00031 00033 00035 00037 00039 00041 00043 00045 00047 00049

00052 00054 00056 00058 00060 00062 00064 00066 00068 00070 00072 00074 00077 00079 00081 00083 00085 00087 00089 00091 00093 00095 00097 00099

7
ABB SACE 7/3

Order codes
SACE Isomax S1 circuit-breaker

F = FIXED

S1N 125
Thermomagnetic release

Iu (40 C) =

125 A

Icu (415 V) =

25 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

code 1SDA0 . . . . . R1 3 poles 4 poles

FC Cu = Front terminals for copper cables S1N 125 F FC Cu R 10 S1N 125 F FC Cu R 12.5 S1N 125 F FC Cu R 16 S1N 125 F FC Cu R 20 S1N 125 F FC Cu R 25 S1N 125 F FC Cu R 32 S1N 125 F FC Cu R 40 S1N 125 F FC Cu R 50 S1N 125 F FC Cu R 63 S1N 125 F FC Cu R 80 S1N 125 F FC Cu R 100 S1N 125 F FC Cu R 125 R = Threaded rear terminals S1N 125 F R R 10 S1N 125 F R R 12.5 S1N 125 F R R 16 S1N 125 F R R 20 S1N 125 F R R 25 S1N 125 F R R 32 S1N 125 F R R 40 S1N 125 F R R 50 S1N 125 F R R 63 S1N 125 F R R 80 S1N 125 F R R 100 S1N 125 F R R 125

PSIS9601

160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A

23669 23671 23673 23675 23677 23679 23681 23683 23685 23687 23689 23691 23789 23791 23793 23795 23797 23799 23801 23803 23805 23807 23809 23811

24269 24271 24273 24275 24277 24279 24281 24283 24285 24287 24289 24291 23909 23911 23913 23915 23917 23919 23921 23923 23925 23927 23929 23931

500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A

00152 00154 00156 00158 00160 00162 00164 00166 00168 00170 00172 00174 00177 00179 00181 00183 00185 00187 00189 00191 00193 00195 00197 00199

00202 00204 00206 00208 00210 00212 00214 00216 00218 00220 00222 00224 00227 00229 00231 00233 00235 00237 00239 00241 00243 00245 00247 00249

Magnetic release
FC Cu = Front terminals for copper cables S1N 125 F FC Cu In 16A S1N 125 F FC Cu In 40A S1N 125 F FC Cu In 50A S1N 125 F FC Cu In 63A S1N 125 F FC Cu In 80A S1N 125 F FC Cu In 100A S1N 125 F FC Cu In 125A R = Threaded rear terminals S1N 125 F R In 16A S1N 125 F R In 40A S1N 125 F R In 50A S1N 125 F R In 63A S1N 125 F R In 80A S1N 125 F R In 100A S1N 125 F R In 125A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

160A 200A 250A 320A 400A

33676 33684 33686 33688 33690

33772 33780 33782 33784 33786

500A 630A 800A 1000A 1250A

33662 33664 33666 33668 33670

33758 33760 33762 33764 33766

160A 200A 250A 320A 400A

33724 33732 33734 33736 33738

33820 33828 33830 33832 33834

500A 630A 800A 1000A 1250A

33710 33712 33714 33716 33718

33806 33808 33810 33812 33814

S1N 125 Curva D


Thermomagnetic release
FC Cu = Front terminals for copper cables S1N 125 F FC Cu R 63A S1N 125 F FC Cu R 80A S1N 125 F FC Cu R 100A S1N 125 F FC Cu R 125A R = Threaded rear terminals S1N 125 F R R 63A S1N 125 F R R 80A S1N 125 F R R 100A S1N 125 F R R 125A

Iu (40 C) =

125 A

Icu (415 V) =
Im = 10 Ith

25 kA

code 1SDA0 . . . . . R1 4 poles

1250A 1250A 1400A 1500A 1250A 1250A 1400A 1500A

45084 45087 45089 45091 45093 45095 45097 45099

7
7/4

ABB SACE

Order codes
SACE Isomax S1 circuit-breaker

P = PLUG-IN

Moving part S1B 125 Iu (40 C) = 125 A


PSIS9601

Icu (415 V) =

16 kA
Im = 10 Ith

Thermomagnetic release
S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP S1B 125 P MP R 10 R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


24005 24007 24009 24011 24013 24015 24017 24019 24021 24023 24025 24027 24125 24127 24129 24131 24133 24135 24137 24139 24141 24143 24145 24147

code 1SDA0 . . . . . R1 3 poles 4 poles


00102 00104 00106 00108 00110 00112 00114 00116 00118 00120 00122 00124 00127 00129 00131 00133 00135 00137 00139 00141 00143 00145 00147 00149

160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A

500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A

S1N 125
Thermomagnetic release
S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP

Iu (40 C) =

125 A
24029 24031 24033 24035 24037 24039 24041 24043 24045 24047 24049 24051

Icu (415 V) =

25 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


24149 24151 24153 24155 24157 24159 24161 24163 24165 24167 24169 24171

code 1SDA0 . . . . . R1 3 poles 4 poles


00252 00254 00256 00258 00260 00262 00264 00266 00268 00270 00272 00274 00277 00279 00281 00283 00285 00287 00289 00291 00293 00295 00297 00299

R 10 R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125

160A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A

500A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A

Magnetic release
S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP S1N 125 P MP In In In In In In In 16A 40A 50A 63A 80A 100A 125A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


33964 33972 33974 33976 33978 34012 34020 34022 34024 34026

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

160A 200A 250A 320A 400A

500A 630A 800A 1000A 1250A

33950 33952 33954 33956 33958

33998 34000 34002 34004 34006

S1N 125 Curva D


Thermomagnetic release
FC Cu = Front terminals for copper cables S1N 125 P MP R 63A S1N 125 P MP R 80A S1N 125 P MP R 100A S1N 125 P MP R 125A

Iu (40 C) =

125 A

Icu (415 V) =
Im = 10 Ith

25 kA

code 1SDA0 . . . . . R1 4 poles

1250A 1250A 1400A 1500A

45101 45103 45105 45107

7
ABB SACE 7/5

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2B 160
Thermomagnetic release

Iu (40 C) =

160 A

Icu (415 V) =

16 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

code 1SDA0 . . . . . R1 3 poles 4 poles

EF = Extended front terminals S2B 160 F EF R 12.5 S2B 160 F EF R 16 S2B 160 F EF R 20 S2B 160 F EF R 25 S2B 160 F EF R 32 S2B 160 F EF R 40 S2B 160 F EF R 50 S2B 160 F EF R 63 S2B 160 F EF R 80 S2B 160 F EF R 100 S2B 160 F EF R 125 S2B 160 F EF R 160 FC Cu = Front terminals for copper cables S2B 160 F FC Cu R 12.5 S2B 160 F FC Cu R 16 S2B 160 F FC Cu R 20 S2B 160 F FC Cu R 25 S2B 160 F FC Cu R 32 S2B 160 F FC Cu R 40 S2B 160 F FC Cu R 50 S2B 160 F FC Cu R 63 S2B 160 F FC Cu R 80 S2B 160 F FC Cu R 100 S2B 160 F FC Cu R 125 S2B 160 F FC Cu R 160 FC CuAl = Front terminals for copper/aluminium cables S2B 160 F FC CuAl* R 12.5 S2B 160 F FC CuAl* R 16 S2B 160 F FC CuAl* R 20 S2B 160 F FC CuAl* R 25 S2B 160 F FC CuAl* R 32 S2B 160 F FC CuAl* R 40 S2B 160 F FC CuAl* R 50 S2B 160 F FC CuAl* R 63 S2B 160 F FC CuAl* R 80 S2B 160 F FC CuAl* R 100 S2B 160 F FC CuAl* R 125 S2B 160 F FC CuAl* R 160
S2B 160 F FC CuAl** R 12.5 S2B 160 F FC CuAl** R 16 S2B 160 F FC CuAl** R 20 S2B 160 F FC CuAl** R 25 S2B 160 F FC CuAl** R 32 S2B 160 F FC CuAl** R 40 S2B 160 F FC CuAl** R 50 S2B 160 F FC CuAl** R 63 S2B 160 F FC CuAl** R 80 S2B 160 F FC CuAl** R 100 S2B 160 F FC CuAl** R 125 S2B 160 F FC CuAl** R 160 R = Threaded rear terminals S2B 160 F R R 12.5 S2B 160 F R R 16 S2B 160 F R R 20 S2B 160 F R R 25 S2B 160 F R R 32 S2B 160 F R R 40 S2B 160 F R R 50 S2B 160 F R R 63 S2B 160 F R R 80 S2B 160 F R R 100 S2B 160 F R R 125 S2B 160 F R R 160 * Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

PSIS9604

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

34056 34058 34060 34062 34064 34066 34068 34070 34072 34074 34076 34078

34440 34442 34444 34446 34448 34450 34452 34454 34456 34458 34460 34462

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

34032 34034 34036 34038 34040 34042 34044 34046 34048 34050 34052 34054

34416 34418 34420 34422 34424 34426 34428 34430 34432 34434 34436 34438

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

23693 23695 23697 23699 23701 23703 23705 23707 23709 23711 23713 23715

24293 24295 24297 24299 24301 24303 24305 24307 24309 24311 24313 24315

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

00302 00304 00306 00308 00310 00312 00314 00316 00318 00320 00322 00324

00352 00354 00356 00358 00360 00362 00364 00366 00368 00370 00372 00374

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

34200 34202 34204 34206 34208 34210 34212 34214 34216 34218 34220 34222 34296 34298 34300 34302 34304 34306 34308 34310 34312 34314 34316 34318 23813 23815 23817 23819 23821 23823 23825 23827 23829 23831 23833 23835

34584 34586 34588 34590 34592 34594 34596 34598 34600 34602 34604 34606 34680 34682 34684 34686 34688 34690 34692 34694 34696 34698 34700 34702 23933 23935 23937 23939 23941 23943 23945 23947 23949 23951 23953 23955

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

34176 34178 34180 34182 34184 34186 34188 34190 34192 34194 34196 34198 34272 34274 34276 34278 34280 34282 34284 34286 34288 34290 34292 34294 00327 00329 00331 00333 00335 00337 00339 00341 00343 00345 00347 00349

34560 34562 34564 34566 34568 34570 34572 34574 34576 34578 34580 34582 34656 34658 34660 34662 34664 34666 34668 34670 34672 34674 34676 34678 00377 00379 00381 00383 00385 00387 00389 00391 00393 00395 00397 00399

7
7/6

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2N 160
Thermomagnetic release

Iu (40 C) =

160 A

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

code 1SDA0 . . . . . R1 3 poles 4 poles

EF = Extended front terminals S2N 160 F EF R 12.5 S2N 160 F EF R 16 S2N 160 F EF R 20 S2N 160 F EF R 25 S2N 160 F EF R 32 S2N 160 F EF R 40 S2N 160 F EF R 50 S2N 160 F EF R 63 S2N 160 F EF R 80 S2N 160 F EF R 100 S2N 160 F EF R 125 S2N 160 F EF R 160 FC Cu = Front terminals for copper cables S2N 160 F FC Cu R 12.5 S2N 160 F FC Cu R 16 S2N 160 F FC Cu R 20 S2N 160 F FC Cu R 25 S2N 160 F FC Cu R 32 S2N 160 F FC Cu R 40 S2N 160 F FC Cu R 50 S2N 160 F FC Cu R 63 S2N 160 F FC Cu R 80 S2N 160 F FC Cu R 100 S2N 160 F FC Cu R 125 S2N 160 F FC Cu R 160 FC CuAl = Front terminals for copper/aluminium cables S2N 160 F FC CuAl* R 12.5 S2N 160 F FC CuAl* R 16 S2N 160 F FC CuAl* R 20 S2N 160 F FC CuAl* R 25 S2N 160 F FC CuAl* R 32 S2N 160 F FC CuAl* R 40 S2N 160 F FC CuAl* R 50 S2N 160 F FC CuAl* R 63 S2N 160 F FC CuAl* R 80 S2N 160 F FC CuAl* R 100 S2N 160 F FC CuAl* R 125 S2N 160 F FC CuAl* R 160
S2N 160 F FC CuAl** R 12.5 S2N 160 F FC CuAl** R 16 S2N 160 F FC CuAl** R 20 S2N 160 F FC CuAl** R 25 S2N 160 F FC CuAl** R 32 S2N 160 F FC CuAl** R 40 S2N 160 F FC CuAl** R 50 S2N 160 F FC CuAl** R 63 S2N 160 F FC CuAl** R 80 S2N 160 F FC CuAl** R 100 S2N 160 F FC CuAl** R 125 S2N 160 F FC CuAl** R 160 R = Threaded rear terminals S2N 160 F R R 12.5 S2N 160 F R R 16 S2N 160 F R R 20 S2N 160 F R R 25 S2N 160 F R R 32 S2N 160 F R R 40 S2N 160 F R R 50 S2N 160 F R R 63 S2N 160 F R R 80 S2N 160 F R R 100 S2N 160 F R R 125 S2N 160 F R R 160 * Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

PSIS9604

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

34826 34828 34830 34832 34834 34836 34838 34840 34842 34844 34846 34848

35210 35212 35214 35216 35218 35220 35222 35224 35226 35228 35230 35232

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

34802 34804 34806 34808 34810 34812 34814 34816 34818 34820 34822 34824

35186 35188 35190 35192 35194 35196 35198 35200 35202 35204 35206 35208

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

23717 23719 23721 23723 23725 23727 23729 23731 23733 23735 23737 23739

24317 24319 24321 24323 24325 24327 24329 24331 24333 24335 24337 24339

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

00452 00454 00456 00458 00460 00462 00464 00466 00468 00470 00472 00474

00502 00504 00506 00508 00510 00512 00514 00516 00518 00520 00522 00524

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A 160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

34970 34972 34974 34976 34978 34980 34982 34984 34986 34988 34990 34992 35066 35068 35070 35072 35074 35076 35078 35080 35082 35084 35086 35088 23837 23839 23841 23843 23845 23847 23849 23851 23853 23855 23857 23859

35354 35356 35358 35360 35362 35364 35366 35368 35370 35372 35374 35376 35450 35452 35454 35456 35458 35460 35462 35464 35466 35468 35470 35472 23957 23959 23961 23963 23965 23967 23969 23971 23973 23975 23977 23979

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

34946 34948 34950 34952 34954 34956 34958 34960 34962 34964 34966 34968 35042 35044 35046 35048 35050 35052 35054 35056 35058 35060 35062 35064 00477 00479 00481 00483 00485 00487 00489 00491 00493 00495 00497 00499

35330 35332 35334 35336 35338 35340 35342 35344 35346 35348 35350 35352 35426 35428 35430 35432 35434 35436 35438 35440 35442 35444 35446 35448 00527 00529 00531 00533 00535 00537 00539 00541 00543 00545 00547 00549

7
7/7

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

Thermomagnetic release
EF = Extended front terminals S2N 160 F EF In 16A S2N 160 F EF In 40A S2N 160 F EF In 50A S2N 160 F EF In 63A S2N 160 F EF In 80A S2N 160 F EF In 100A S2N 160 F EF In 125A S2N 160 F EF In 160A FC Cu = Front terminals for copper cables S2N 160 F FC Cu In 16A S2N 160 F FC Cu In 40A S2N 160 F FC Cu In 50A S2N 160 F FC Cu In 63A S2N 160 F FC Cu In 80A S2N 160 F FC Cu In 100A S2N 160 F FC Cu In 125A S2N 160 F FC Cu In 160A FC CuAl = Front terminals for copper/aluminium cables S2N 160 F FC CuAl* In 16A S2N 160 F FC CuAl* In 40A S2N 160 F FC CuAl* In 50A S2N 160 F FC CuAl* In 63A S2N 160 F FC CuAl* In 80A S2N 160 F FC CuAl* In 100A S2N 160 F FC CuAl* In 125A S2N 160 F FC CuAl* In 160A
S2N 160 F FC CuAl** In 16A S2N 160 F FC CuAl** In 40A S2N 160 F FC CuAl** In 50A S2N 160 F FC CuAl** In 63A S2N 160 F FC CuAl** In 80A S2N 160 F FC CuAl** In 100A S2N 160 F FC CuAl** In 125A S2N 160 F FC CuAl** In 160A R = Threaded rear terminals S2N 160 F R In 16A S2N 160 F R In 40A S2N 160 F R In 50A S2N 160 F R In 63A S2N 160 F R In 80A S2N 160 F R In 100A S2N 160 F R In 125A S2N 160 F R In 160A * Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

160A 200A 250A 320A 400A

34876 34884 34886 34888 34890

35260 35268 35270 35272 35274

PSIS9604

500A 630A 800A 1000A 1250A 1600A

34862 34864 34866 34868 34870 34872

35246 35248 35250 35252 35254 35256

160A 200A 250A 320A 400A

34924 34932 34934 34936 34938

35308 35316 35318 35320 35322

500A 630A 800A 1000A 1250A 1600A

34910 34912 34914 34916 34918 34920

35294 35296 35298 35300 35302 35304

160A 200A 250A 320A 400A

35020 35028 35030 35032 35034

35404 35412 35414 35416 35418

500A 630A 800A 1000A 1250A 1600A

35006 35008 35010 35012 35014 35016

35390 35392 35394 35396 35398 35400

160A 200A 250A 320A 400A

35116 35124 35126 35128 35130

35500 35508 35510 35512 35514

500A 630A 800A 1000A 1250A 1600A

35102 35104 35106 35108 35110 35112

35486 35488 35490 35492 35494 35496

160A 200A 250A 320A 400A

35164 35172 35174 35176 35178

35548 35556 35558 35560 35562

500A 630A 800A 1000A 1250A 1600A

35150 35152 35154 35156 35158 35160

35534 35536 35538 35540 35542 35544

7
7/8 ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S2S 160
Thermomagnetic release

Iu (40 C) =

160 A

Icu (415 V) =

50 kA
Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

EF = Extended front terminals S2S 160 F EF R 12.5 S2S 160 F EF R 16 S2S 160 F EF R 20 S2S 160 F EF R 25 S2S 160 F EF R 32 S2S 160 F EF R 40 S2S 160 F EF R 50 S2S 160 F EF R 63 S2S 160 F EF R 80 S2S 160 F EF R 100 S2S 160 F EF R 125 S2S 160 F EF R 160 FC Cu = Front terminals for copper cables S2S 160 F FC Cu R 12.5 S2S 160 F FC Cu R 16 S2S 160 F FC Cu R 20 S2S 160 F FC Cu R 25 S2S 160 F FC Cu R 32 S2S 160 F FC Cu R 40 S2S 160 F FC Cu R 50 S2S 160 F FC Cu R 63 S2S 160 F FC Cu R 80 S2S 160 F FC Cu R 100 S2S 160 F FC Cu R 125 S2S 160 F FC Cu R 160 FC CuAl = Front terminals for copper/aluminium cables S2S 160 F FC CuAl* R 12.5 S2S 160 F FC CuAl* R 16 S2S 160 F FC CuAl* R 20 S2S 160 F FC CuAl* R 25 S2S 160 F FC CuAl* R 32 S2S 160 F FC CuAl* R 40 S2S 160 F FC CuAl* R 50 S2S 160 F FC CuAl* R 63 S2S 160 F FC CuAl* R 80 S2S 160 F FC CuAl* R 100 S2S 160 F FC CuAl* R 125 S2S 160 F FC CuAl* R 160
S2S 160 F FC CuAl** R 12.5 S2S 160 F FC CuAl** R 16 S2S 160 F FC CuAl** R 20 S2S 160 F FC CuAl** R 25 S2S 160 F FC CuAl** R 32 S2S 160 F FC CuAl** R 40 S2S 160 F FC CuAl** R 50 S2S 160 F FC CuAl** R 63 S2S 160 F FC CuAl** R 80 S2S 160 F FC CuAl** R 100 S2S 160 F FC CuAl** R 125 S2S 160 F FC CuAl** R 160 R = Threaded rear terminals S2S 160 F R R 12.5 S2S 160 F R R 16 S2S 160 F R R 20 S2S 160 F R R 25 S2S 160 F R R 32 S2S 160 F R R 40 S2S 160 F R R 50 S2S 160 F R R 63 S2S 160 F R R 80 S2S 160 F R R 100 S2S 160 F R R 125 S2S 160 F R R 160 * Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

PSIS9604

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

35570 35572 35574 35576 35578 35580 35582 35584 35586 35588 35590 35592

35762 35764 35766 35768 35770 35772 35774 35776 35778 35780 35782 35784

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

00602 00604 00606 00608 00610 00612 00614 00616 00618 00620 00622 00624

00652 00654 00656 00658 00660 00662 00664 00666 00668 00670 00672 00674

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A 500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

36197 36199 36201 36203 36205 36207 36209 36211 36213 36215 36217 36219 36221 36223 36225 36227 36229 36231 36233 36235 36237 36239 36241 36243 00627 00629 00631 00633 00635 00637 00639 00641 00643 00645 00647 00649

35834 35836 35838 35840 35842 35844 35846 35848 35850 35852 35854 35856 35882 35884 35886 35888 35890 35892 35894 35896 35898 35900 35902 35904 00677 00679 00681 00683 00685 00687 00689 00691 00693 00695 00697 00699

7
7/9

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

Magnetic release
EF = Extended front terminals S2S 160 F EF In 50A S2S 160 F EF In 63A S2S 160 F EF In 80A S2S 160 F EF In 100A S2S 160 F EF In 125A S2S 160 F EF In 160A FC Cu = Front terminals for copper cables S2S 160 F FC Cu In 50A S2S 160 F FC Cu In 63A S2S 160 F FC Cu In 80A S2S 160 F FC Cu In 100A S2S 160 F FC Cu In 125A S2S 160 F FC Cu In 160A FC CuAl = Front terminals for copper/aluminium cables S2S 160 F FC CuAl* In 50A S2S 160 F FC CuAl* In 63A S2S 160 F FC CuAl* In 80A S2S 160 F FC CuAl* In 100A S2S 160 F FC CuAl* In 125A S2S 160 F FC CuAl* In 160A
S2S 160 F FC CuAl** In 50A S2S 160 F FC CuAl** In 63A S2S 160 F FC CuAl** In 80A S2S 160 F FC CuAl** In 100A S2S 160 F FC CuAl** In 125A S2S 160 F FC CuAl** In 160A R = Threaded rear terminals S2S 160 F R In 50A S2S 160 F R In 63A S2S 160 F R In 80A S2S 160 F R In 100A S2S 160 F R In 125A S2S 160 F R In 160A * Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

500A 630A 800A 1000A 1250A 1600A

35631 35633 35635 35636 35638 35640

35798 35800 35802 35804 35806 35808

PSIS9604

500A 630A 800A 1000A 1250A 1600A

35678 35680 35682 35684 35686 35688

35822 35824 35826 35828 35830 35832

500A 630A 800A 1000A 1250A 1600A 500A 630A 800A 1000A 1250A 1600A 500A 630A 800A 1000A 1250A 1600A

35702 35704 35706 35708 35710 35712 35726 35728 35730 35732 35734 35736 35750 35752 35754 35756 35758 35760

35870 35872 35874 35876 35878 35880 35918 35920 35922 35924 35926 35928 35942 35944 35946 35948 35950 35952

7
7/10 ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

P = PLUG-IN

Moving part S2B 160 Iu (40 C) = 160 A


PSIS9604

Icu (415 V) =

16 kA
Im = 10 Ith

Thermomagnetic release
S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP S2B 160 P MP R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


24053 24055 24057 24059 24061 24063 24065 24067 24069 24071 24073 24075 24173 24175 24177 24179 24181 24183 24185 24187 24189 24191 24193 24195

code 1SDA0 . . . . . R1 3 poles 4 poles


00402 00404 00406 00408 00410 00412 00414 00416 00418 00420 00422 00424 00427 00429 00431 00433 00435 00437 00439 00441 00443 00445 00447 00449

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 8000A

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

S2N 160
Thermomagnetic release
S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP

Iu (40 C) =

160 A
24077 24079 24081 24083 24085 24087 24089 24091 24093 24095 24097 24099

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


24197 24199 24201 24203 24205 24207 24209 24211 24213 24215 24217 24219

code 1SDA0 . . . . . R1 3 poles 4 poles


00552 00554 00556 00558 00560 00562 00564 00566 00568 00570 00572 00574 00577 00579 00581 00583 00585 00587 00589 00591 00593 00595 00597 00599

R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160

160A 160A 200A 200A 200A 200A 250A 320A 400A 500A 630A 800A

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

Magnetic release
S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP S2N 160 P MP In In In In In In In In 16A 40A 50A 63A 80A 100A 125A 150A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


36076 36084 36086 36088 36090 36124 36132 36134 36136 36138

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles

160A 200A 250A 320A 400A

500A 630A 800A 1000A 1250A 1600A

36062 36064 36066 36068 36070 36072

36110 36112 36114 36116 36118 36120

7
ABB SACE 7/11

Order codes
SACE Isomax S2 circuit-breaker

P = PLUG-IN

Moving part S2S 160 Iu (40 C) = 160 A


PSIS9604

Icu (415 V) =

50 kA
Im = 10 Ith

Thermomagnetic release
S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100 R 125 R 160

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


00702 00704 00706 00708 00710 00712 00714 00716 00718 00720 00722 00724 00727 00729 00731 00733 00735 00737 00739 00741 00743 00745 00747 00749

500A 500A 500A 500A 500A 500A 500A 630A 800A 1000A 1250A 1600A

Magnetic release
S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP S2S 160 P MP In In In In In In 50A 63A 80A 100A 125A 150A 500A 630A 800A 1000A 1250A 1600A

code 1SDA0 . . . . . R1 3 poles 4 poles


36158 36160 36162 36164 36166 36168 36182 36184 36186 36188 36190 36192

7
7/12 ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

S3N 160
Thermomagnetic release
F = Front terminals S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F (N50%)

Iu (40 C) =

160 A

Icu (415 V) =

35 kA

Im = 3 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


48539 48540 48541 48549 48550 48551 48559

R 100 R 125 R 160 R 160

300A 375A I480A I480A

PSIS9607

Thermomagnetic release

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13359 13361 13363 13365 13367 13369 13383 13385 13387 13389 13391 13393

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13346 13348 13350 13352 13354 13356 13371 13373 13375 13377 13379 13381

F = Front terminals S3N 160 F F R 32 250A S3N 160 F F R 50 250A S3N 160 F F R 80 400A S3N 160 F F R 100 500A S3N 160 F F R 125 625A S3N 160 F F R 160 800A EF = Extended front terminals S3N 160 F EF R 32 250A S3N 160 F EF R 50 250A S3N 160 F EF R 80 400A S3N 160 F EF R 100 500A S3N 160 F EF R 125 625A S3N 160 F EF R 160 800A FC Cu = Front terminals for copper cables S3N 160 F FC Cu R 32 250A S3N 160 F FC Cu R 50 250A S3N 160 F FC Cu R 80 400A S3N 160 F FC Cu R 100 500A S3N 160 F FC Cu R 125 625A S3N 160 F FC Cu R 160 800A FC CuAl = Front terminals for copper/aluminium cables S3N 160 F FC CuAl R 32 250A S3N 160 F FC CuAl R 50 250A S3N 160 F FC CuAl R 80 400A S3N 160 F FC CuAl R 100 500A S3N 160 F FC CuAl R 125 625A S3N 160 F FC CuAl R 160 800A R = Threaded rear terminals S3N 160 F R R 32 250A S3N 160 F R R 50 250A S3N 160 F R R 80 400A S3N 160 F R R 100 500A S3N 160 F R R 125 625A S3N 160 F R R 160 800A RC = Rear terminals for cables S3N 160 F RC R 32 250A S3N 160 F RC R 50 250A S3N 160 F RC R 80 400A S3N 160 F RC R 100 500A S3N 160 F RC R 125 625A S3N 160 F RC R 160 800A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3N 160 F R Res. Cur R 32 250A S3N 160 F R Res. Cur R 50 250A S3N 160 F R Res. Cur R 80 400A S3N 160 F R Res. Cur R 100 500A S3N 160 F R Res. Cur R 125 625A S3N 160 F R Res. Cur R 160 800A

500A 500A 800A 1000A 1250A 1600A

00764 00766 00768 00770 00772 00774

01389 01391 01393 01395 01397 01399

500A 500A 800A 1000A 1250A 1600A

00752 00754 00756 00758 00760 00762

01377 01379 01381 01383 01385 01387

00914 00916 00918 00920 00922 00924

01539 01541 01543 01545 01547 01549

500A 500A 800A 1000A 1250A 1600A

00902 00904 00906 00908 00910 00912

01527 01529 01531 01533 01535 01537

01064 01066 01068 01070 01072 01074 01364 01366 01368 01370 01372 01374

01689 01691 01693 01695 01697 01699 14243 14245 14247 14249 14251 14253

500A 500A 800A 1000A 1250A 1600A 500A 500A 800A 1000A 1250A 1600A

01052 01054 01056 01058 01060 01062 01352 01354 01356 01358 01360 01362

01677 01679 01681 01683 01685 01687 14231 14233 14235 14237 14239 14241

01214 01216 01218 01220 01222 01224

01839 01841 01843 01845 01847 01849

500A 500A 800A 1000A 1250A 1600A

01202 01204 01206 01208 01210 01212

01827 01829 01831 01833 01835 01837

25459 25461 25463 25465 25467 25469

500A 500A 800A 1000A 1250A 1600A

25447 25449 25451 25454 25455 25457

7
7/13

ABB SACE

Order codes
SACE Isomax S2 circuit-breaker

F = FIXED

Magnetic release
F = Front terminals S3N 160 F F In 50A S3N 160 F F In 80A S3N 160 F F In 100A S3N 160 F F In 125A S3N 160 F F In 160A EF = Extended front terminals S3N 160 F EF In 50A S3N 160 F EF In 80A S3N 160 F EF In 100A S3N 160 F EF In 125A S3N 160 F EF In 160A FC Cu = Front terminals for copper cables S3N 160 F FC Cu In 50A S3N 160 F FC Cu In 80A S3N 160 F FC Cu In 100A S3N 160 F FC Cu In 125A S3N 160 F FC Cu In 160A FC CuAl = Front terminals for copper/aluminium cables S3N 160 F FC CuAl In 50A S3N 160 F FC CuAl In 80A S3N 160 F FC CuAl In 100A S3N 160 F FC CuAl In 125A S3N 160 F FC CuAl In 160A R = Threaded rear terminals S3N 160 F R In 50A S3N 160 F R In 80A S3N 160 F R In 100A S3N 160 F R In 125A S3N 160 F R In 160A RC = Rear terminals for cables S3N 160 F RC In 50A S3N 160 F RC In 80A S3N 160 F RC In 100A S3N 160 F RC In 125A S3N 160 F RC In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25817 25819 25823 25889 25891 25895

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25804 25807 25809 25811 25813 25877 25879 25881 25883 25885

250A 400A 625A

PSIS9607

500A 800A 1000A 1250A 1600A

250A 400A 625A

27930 27932 27936

29706 29708 29712

500A 800A 1000A 1250A 1600A

27918 27920 27922 27924 27926

29694 29696 29698 29700 29702

250A 400A 625A

28074 28076 28080

29850 29852 29856

500A 800A 1000A 1250A 1600A

28062 28064 28066 28068 28070

29838 29840 29842 29844 29846

250A 400A 625A

28218 28220 28224

29994 29996 30000

500A 800A 1000A 1250A 1600A 500A 800A 1000A 1250A 1600A

28206 28208 28210 28212 28214 28494 28496 28498 28500 28502

29982 29984 29986 29988 29990 30270 30272 30274 30276 30278

250A 400A 625A

28506 28508 28512

30282 30284 30288

250A 400A 625A

28362 28364 28368

30138 30140 30144

500A 800A 1000A 1250A 1600A

28350 28352 28354 28356 28358

30126 30128 30130 30132 30134

7
7/14 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3H 160
Thermomagnetic release
F = Front terminals S3H 160 F F S3H 160 F F S3H 160 F F S3H 160 F F (N50%)

Iu (40 C) =

160 A

Icu (415 V) =

65 kA

Im = 3 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


48542 48543 48544 48552 48553 48554 48560

R 100 R 125 R 160 R 160

300A 375A 480A 480A

PSIS9607

Thermomagnetic release

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13407 13409 13411 13413 13415 13417 13431 13433 13435 13437 13439 13441

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13395 13397 13399 13401 13403 13405 13419 13421 13423 13425 13427 13429

F = Front terminals S3H 160 F F R 32 250A S3H 160 F F R 50 250A S3H 160 F F R 80 400A S3H 160 F F R 100 500A S3H 160 F F R 125 625A S3H 160 F F R 160 800A EF = Extended front terminals S3H 160 F EF R 32 250A S3H 160 F EF R 50 250A S3H 160 F EF R 80 400A S3H 160 F EF R 100 500A S3H 160 F EF R 125 625A S3H 160 F EF R 160 800A FC Cu = Front terminals for copper cables S3H 160 F FC Cu R 32 250A S3H 160 F FC Cu R 50 250A S3H 160 F FC Cu R 80 400A S3H 160 F FC Cu R 100 500A S3H 160 F FC Cu R 125 625A S3H 160 F FC Cu R 160 800A FC CuAl = Front terminals for copper/aluminium cables S3H 160 F FC CuAl R 32 250A S3H 160 F FC CuAl R 50 250A S3H 160 F FC CuAl R 80 400A S3H 160 F FC CuAl R 100 500A S3H 160 F FC CuAl R 125 625A S3H 160 F FC CuAl R 160 800A R = Threaded rear terminals S3H 160 F R R 32 250A S3H 160 F R R 50 250A S3H 160 F R R 80 400A S3H 160 F R R 100 500A S3H 160 F R R 125 625A S3H 160 F R R 160 800A RC = Rear terminals for cables S3H 160 F RC R 32 250A S3H 160 F RC R 50 250A S3H 160 F RC R 80 400A S3H 160 F RC R 100 500A S3H 160 F RC R 125 625A S3H 160 F RC R 160 800A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3H 160 F R Res. Cur R 32 250A S3H 160 F R Res. Cur R 50 250A S3H 160 F R Res. Cur R 80 400A S3H 160 F R Res. Cur R 100 500A S3H 160 F R Res. Cur R 125 625A S3H 160 F R Res. Cur R 160 800A

500A 500A 800A 1000A 1250A 1600A

02089 02091 02093 02095 02097 02099

02689 02691 02693 02695 02697 02699

500A 500A 800A 1000A 1250A 1600A

02077 02079 02081 02083 02085 02087

02677 02679 02681 02683 02685 02687

02239 02241 02243 02245 02247 02249

14268 14270 14272 14274 14276 14278

500A 500A 800A 1000A 1250A 1600A

02227 02229 02231 02233 02235 02237

14256 14258 14260 14262 14264 14266

02364 02366 02368 02370 02372 02374 02664 02666 02668 02670 02672 02674

14343 14345 14347 14349 14351 14353 03139 03141 03143 03145 03147 03149

500A 500A 800A 1000A 1250A 1600A 500A 500A 800A 1000A 1250A 1600A

02352 02354 02356 02358 02360 02362 02652 02654 02656 02658 02660 02662

14331 14333 14335 14337 14339 14341 03127 03129 03131 03133 03135 03137

02514 02516 02518 02520 02522 02524

02989 02991 02993 02995 02997 02999

500A 500A 800A 1000A 1250A 1600A

02502 02504 02506 02508 02510 02512

02977 02979 02981 02983 02985 02987

25483 25485 25487 25489 25491 25493

500A 500A 800A 1000A 1250A 1600A

25471 25473 25475 25477 25479 25481

7
7/15

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

Magnetic release
F = Front terminals S3H 160 F F In 50A S3H 160 F F In 80A S3H 160 F F In 100A S3H 160 F F In 125A S3H 160 F F In 160A EF = Extended front terminals S3H 160 F EF In 50A S3H 160 F EF In 80A S3H 160 F EF In 100A S3H 160 F EF In 125A S3H 160 F EF In 160A FC Cu = Front terminals for copper cables S3H 160 F FC Cu In 50A S3H 160 F FC Cu In 80A S3H 160 F FC Cu In 100A S3H 160 F FC Cu In 125A S3H 160 F FC Cu In 160A FC CuAl = Front terminals for copper/aluminium cables S3H 160 F FC CuAl In 50A S3H 160 F FC CuAl In 80A S3H 160 F FC CuAl In 100A S3H 160 F FC CuAl In 125A S3H 160 F FC CuAl In 160A R = Threaded rear terminals S3H 160 F R In 50A S3H 160 F R In 80A S3H 160 F R In 100A S3H 160 F R In 125A S3H 160 F R In 160A RC = Rear terminals for cables S3H 160 F RC In 50A S3H 160 F RC In 80A S3H 160 F RC In 100A S3H 160 F RC In 125A S3H 160 F RC In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25841 25843 25847 25913 25915 25919

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25829 25831 25833 25835 25837 25901 25903 25905 25907 25909

250A 400A 625A

PSIS9607

500A 800A 1000A 1250A 1600A

250A 400A 625A

28530 28532 28536

30306 30308 30312

500A 800A 1000A 1250A 1600A

28518 28520 28522 28524 28526

30294 30296 30298 30300 30302

250A 400A 625A

28674 28676 28680

30450 30452 30456

500A 800A 1000A 1250A 1600A

28662 28664 28666 28668 28670

30438 30440 30442 30444 30446

250A 400A 625A

28818 28820 28824

30594 30596 30600

500A 800A 1000A 1250A 1600A 500A 800A 1000A 1250A 1600A

28806 28808 28810 28812 28814 29094 29096 29098 29100 29102

30582 30584 30586 30588 30590 30870 30872 30874 30876 30878

250A 400A 625A

29106 29108 29112

30882 30884 30888

250A 400A 625A

28962 28964 28968

30738 30740 30744

500A 800A 1000A 1250A 1600A

28950 28952 28954 28956 28958

30726 30728 30730 30732 30734

7
7/16 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3L 160
Thermomagnetic release

Iu (40 C) =

160 A

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13455 13457 13459 13461 13463 13465 13479 13481 13483 13485 13487 13489

code 1SDA0 . . . . . R1 3 poles 4 poles


13443 13445 13447 13449 13451 13453 13467 13469 13471 13473 13475 13477

F = Front terminals S3L 160 F F R 32 250A S3L 160 F F R 50 250A S3L 160 F F R 80 400A S3L 160 F F R 100 500A S3L 160 F F R 125 625A S3L 160 F F R 160 800A EF = Extended front terminals S3L 160 F EF R 32 250A S3L 160 F EF R 50 250A S3L 160 F EF R 80 400A S3L 160 F EF R 100 500A S3L 160 F EF R 125 625A S3L 160 F EF R 160 800A FC Cu = Front terminals for copper cables S3L 160 F FC Cu R 32 250A S3L 160 F FC Cu R 50 250A S3L 160 F FC Cu R 80 400A S3L 160 F FC Cu R 100 500A S3L 160 F FC Cu R 125 625A S3L 160 F FC Cu R 160 800A FC CuAl = Front terminals for copper/aluminium cables S3L 160 F FC CuAl R 32 250A S3L 160 F FC CuAl R 50 250A S3L 160 F FC CuAl R 80 400A S3L 160 F FC CuAl R 100 500A S3L 160 F FC CuAl R 125 625A S3L 160 F FC CuAl R 160 800A R = Threaded rear terminals S3L 160 F R R 32 250A S3L 160 F R R 50 250A S3L 160 F R R 80 400A S3L 160 F R R 100 500A S3L 160 F R R 125 625A S3L 160 F R R 160 800A RC = Rear terminals for cables S3L 160 F RC R 32 250A S3L 160 F RC R 50 250A S3L 160 F RC R 80 400A S3L 160 F RC R 100 500A S3L 160 F RC R 125 625A S3L 160 F RC R 160 800A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3L 160 F R Res. Cur R 32 250A S3L 160 F R Res. Cur R 50 250A S3L 160 F R Res. Cur R 80 400A S3L 160 F R Res. Cur R 100 500A S3L 160 F R Res. Cur R 125 625A S3L 160 F R Res. Cur R 160 800A

500A 500A 800A 1000A 1250A 1600A

PSIS9607

03264 03266 14486 03269 03271 03273

03864 03866 14511 03869 03871 03873

500A 500A 800A 1000A 1250A 1600A

03252 03254 03256 03258 03260 03262

03852 03854 03856 03858 03860 03862

03408 03410 14492 03413 03415 03417

04008 04010 14517 04013 04015 04017

500A 500A 800A 1000A 1250A 1600A

03396 03398 03400 03402 03404 03406

03996 03998 04000 04002 04004 04006

03552 03554 14498 03557 03559 03561 03840 03842 14510 03845 03847 03849

04152 04154 14523 04157 04159 04161 04440 04442 14535 04445 04447 04449

500A 500A 800A 1000A 1250A 1600A 500A 500A 800A 1000A 1250A 1600A

03540 03542 03544 03546 03548 03550 03828 03830 03832 03834 03836 03838

04140 04142 04144 04146 04148 04150 04428 04430 04432 04434 04436 04438

03696 03698 14504 03701 03703 03705

04296 04298 14529 04301 04303 04305

500A 500A 800A 1000A 1250A 1600A

03684 03686 03688 03690 03692 03694

04284 04286 04288 04290 04292 04294

25507 25509 25511 25513 25515 25517

500A 500A 800A 1000A 1250A 1600A

25495 25497 25499 25501 25503 25505

7
ABB SACE 7/17

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

Magnetic release
F = Front terminals S3L 160 F F In 50A S3L 160 F F In 80A S3L 160 F F In 100A S3L 160 F F In 125A S3L 160 F F In 160A EF = Extended front terminals S3L 160 F EF In 50A S3L 160 F EF In 80A S3L 160 F EF In 100A S3L 160 F EF In 125A S3L 160 F EF In 160A FC Cu = Front terminals for copper cables S3L 160 F FC Cu In 50A S3L 160 F FC Cu In 80A S3L 160 F FC Cu In 100A S3L 160 F FC Cu In 125A S3L 160 F FC Cu In 160A FC CuAl = Front terminals for copper/aluminium cables S3L 160 F FC CuAl In 50A S3L 160 F FC CuAl In 80A S3L 160 F FC CuAl In 100A S3L 160 F FC CuAl In 125A S3L 160 F FC CuAl In 160A R = Threaded rear terminals S3L 160 F R In 50A S3L 160 F R In 80A S3L 160 F R In 100A S3L 160 F R In 125A S3L 160 F R In 160A RC = Rear terminals for cables S3L 160 F RC In 50A S3L 160 F RC In 80A S3L 160 F RC In 100A S3L 160 F RC In 125A S3L 160 F RC In 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25865 25867 25871 25937 25939 25943

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


25853 25855 25857 25859 25861 25925 25927 25929 25931 25933

250A 400A 625A

PSIS9607

500A 800A 1000A 1250A 1600A

250A 400A 625A

29130 29132 29136

30906 30908 30912

500A 800A 1000A 1250A 1600A

29118 29120 29122 29124 29126

30894 30896 30898 30900 30902

250A 400A 625A

29274 29276 29280

31050 31052 31056

500A 800A 1000A 1250A 1600A

29262 29264 29266 29268 29270

31038 31040 31042 31044 31046

250A 400A 625A

29418 29420 29424

31170 31172 31176

500A 800A 1000A 1250A 1600A 500A 800A 1000A 1250A 1600A

29406 29408 29410 29412 29414 44376 44378 44380 44382 44384

31158 31160 31162 31164 31166 31446 31448 31450 31452 31454

250A 400A 625A

44388 44390 44394

31458 31460 31464

250A 400A 625A

29562 29564 29568

31314 31316 31320

500A 800A 1000A 1250A 1600A

29550 29552 29554 29556 29558

31302 31304 31306 31308 31310

7
7/18 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

P = PLUG-IN

Moving part S3N 160 Iu (40 C) = 160 A


Thermomagnetic release
S3N 160 P MP S3N 160 P MP S3N 160 P MP S3N 160 P MP S3N 160 P MP S3N 160 P MP R 32 R 50 R 80 R 100 R 125 R 160
PSIS9607

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


01989 01991 01993 01995 01997 01999 02039 02041 02043 02045 02047 02049

code 1SDA0 . . . . . R1 3 poles 4 poles


01977 01979 01981 01983 01985 01987 02027 02029 02031 02033 02035 02037

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3N 160 P MP S3N 160 P MP S3N 160 P MP S3N 160 P MP S3N 160 P MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31482 31484 31488 31530 31532 31536

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31470 31472 31474 31476 31478 31518 31520 31522 31524 31526

250A 400A 625A

500A 800A 1000A 1250A 1600A

S3H 160
Thermomagnetic release
S3H 160 P MP S3H 160 P MP S3H 160 P MP S3H 160 P MP S3H 160 P MP S3H 160 P MP

Iu (40 C) =

160 A
03164 03166 03168 03170 03172 03174

Icu (415 V) =

65 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


03214 03216 03218 03220 03222 03224

code 1SDA0 . . . . . R1 3 poles 4 poles


03152 03154 03156 03158 03160 03162 03202 03204 03206 03208 03210 03212

R 32 R 50 R 80 R 100 R 125 R 160

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3H 160 P MP S3H 160 P MP S3H 160 P MP S3H 160 P MP S3H 160 P MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31578 31580 31584 31626 31628 31632

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31566 31568 31570 31572 31574 31614 31616 31618 31620 31622

250A 400A 625A

500A 800A 1000A 1250A 1600A

S3L 160
Thermomagnetic release
S3L 160 P MP S3L 160 P MP S3L 160 P MP S3L 160 P MP S3L 160 P MP S3L 160 P MP

Iu (40 C) =

160 A
04464 04466 14536 04469 04471 04473

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


04512 04514 14538 04517 04519 04521

code 1SDA0 . . . . . R1 3 poles 4 poles


04452 04454 04456 04458 04460 04462 04500 04502 04504 04506 04508 04510

R 32 R 50 R 80 R 100 R 125 R 160

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3L 160 P MP S3L 160 P MP S3L 160 P MP S3L 160 P MP S3L 160 P MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31674 31676 31680 31722 31724 31728

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31662 31664 31666 31668 31670 31710 31712 31714 31716 31718

250A 400A 625A

500A 800A 1000A 1250A 1600A

7
ABB SACE 7/19

Order codes
SACE Isomax S3 circuit-breaker

W = WITHDRAWABLE Moving part S3N 160 Iu (40 C) = 160 A


Thermomagnetic release
S3N 160 W MP S3N 160 W MP S3N 160 W MP S3N 160 W MP S3N 160 W MP S3N 160 W MP R 32 R 50 R 80 R 100 R 125 R 160
PSIS9607

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


02014 02016 02018 02020 02022 02024 02064 02066 02068 02070 02072 02074

code 1SDA0 . . . . . R1 3 poles 4 poles


02002 02004 02006 02008 02010 02012 02052 02054 02056 02058 02060 02062

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3N 160 W MP S3N 160 W MP S3N 160 W MP S3N 160 W MP S3N 160 W MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31506 31508 31512 31554 31556 31560

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31494 31496 31498 31500 31502 31542 31544 31546 31548 31550

250A 400A 625A

500A 800A 1000A 1250A 1600A

S3H 160
Thermomagnetic release
S3H 160 W MP S3H 160 W MP S3H 160 W MP S3H 160 W MP S3H 160 W MP S3H 160 W MP

Iu (40 C) =

160 A
03189 03191 03193 03195 03197 03199

Icu (415 V) =

65 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


03239 03241 03243 03245 03247 03249

code 1SDA0 . . . . . R1 3 poles 4 poles


03177 03179 03181 03183 03185 03187 03227 03229 03231 03233 03235 03237

R 32 R 50 R 80 R 100 R 125 R 160

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3H 160 W MP S3H 160 W MP S3H 160 W MP S3H 160 W MP S3H 160 W MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31602 31604 31608 31650 31652 31656

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31590 31592 31594 31596 31598 31638 31640 31642 31644 31646

250A 400A 625A

500A 800A 1000A 1250A 1600A

S3L 160
Thermomagnetic release
S3L 160 W MP S3L 160 W MP S3L 160 W MP S3L 160 W MP S3L 160 W MP S3L 160 W MP

Iu (40 C) =

160 A
04488 04490 14537 04493 04495 04497

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


04536 04538 14539 04541 04543 04545

code 1SDA0 . . . . . R1 3 poles 4 poles


04476 04478 04480 04482 04484 04486 04524 04526 04528 04530 04532 04534

R 32 R 50 R 80 R 100 R 125 R 160

250A 250A 400A 500A 625A 800A

500A 500A 800A 1000A 1250A 1600A

Magnetic release
S3L 160 W MP S3L 160 W MP S3L 160 W MP S3L 160 W MP S3L 160 W MP In In In In In 50A 80A 100A 125A 160A

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31698 31700 31704 31746 31748 31752

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


31686 31688 31690 31692 31694 31734 31736 31738 31740 31742

250A 400A 625A

500A 800A 1000A 1250A 1600A

7
7/20 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3N 250
Thermomagnetic release
F = Front terminals S3N 250 F F S3N 250 F F S3N 250 F F (N50%) S3N 250 F F (N50%)

Iu (40 C) =

250 A

Icu (415 V) =

35 kA

Im = 3 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


48545 48546 48555 48556 48561 48562

R 200 R 250 R 200 R 250

600A 750A 600A 750A

PSIS9607

Thermomagnetic release

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13495 13497 13503 13505

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13491 13493 13499 13501

F = Front terminals S3N 250 F F R 200 1000A S3N 250 F F R 250 1250A EF = Extended front terminals S3N 250 F EF R 200 1000A S3N 250 F EF R 250 1250A FC Cu = Front terminals for copper cables S3N 250 F FC Cu R 200 1000A S3N 250 F FC Cu R 250 1250A FC CuAl = Front terminals for copper/aluminium cables S3N 250 F FC CuAl R 200 1000A S3N 250 F FC CuAl R 250 1250A R = Threaded rear terminals S3N 250 F R R 200 1000A S3N 250 F R R 250 1250A RC = Rear terminals for cables S3N 250 F RC R 200 1000A S3N 250 F RC R 250 1250A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3N 250 F R Res. Cur R 200 1000A S3N 250 F R Res. Cur R 250 1250A

2000A 2500A

04552 04554

04777 04779

2000A 2500A

04548 04550

04773 04775

04606 04608

14419 14421

2000A 2500A

04602 04604

14415 14417

04660 04662 04768 04770

14455 14457 04912 04914

2000A 2500A 2000A 2500A

04656 04658 04764 04766

14451 14453 04908 04910

04714 04716

04858 04860

2000A 2500A

04710 04712

04854 04856

25523 25525

2000A 2500A

25519 25521

Magnetic release
F = Front terminals S3N 250 F F In 200A S3N 250 F F In 250A EF = Extended front terminals S3N 250 F EF In 200A S3N 250 F EF In 250A FC Cu = Front terminals for copper cables S3N 250 F FC Cu In 200A S3N 250 F FC Cu In 250A FC CuAl = Front terminals for copper/aluminium cables S3N 250 F FC CuAl In 200A S3N 250 F FC CuAl In 250A R = Threaded rear terminals S3N 250 F R In 200A S3N 250 F R In 250A RC = Rear terminals for cables S3N 250 F RC In 200A S3N 250 F RC In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


27388 27390 27476 27478

2000A 2500A

2000A 2500A

31756 31758

32337 32339

2000A 2500A

31804 31806

32385 32387

2000A 2500A 2000A 2500A

31844 31846 31940 31942

32433 32435 32529 32531

2000A 2500A

31892 31894

32481 32483

7
ABB SACE 7/21

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3H 250
Thermomagnetic release
F = Front terminals S3H 250 F F S3H 250 F F S3H 250 F F (N50%) S3H 250 F F (N50%)

Iu (40 C) =

250 A

Icu (415 V) =

65 kA

Im = 3 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


48547 48548 48557 48558 48563 48564

R 200 R 250 R 200 R 250

600A 750A 600A 750A

PSIS9607

Thermomagnetic release

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13511 13513 13519 13521

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13507 13509 13515 13517

F = Front terminals S3H 250 F F R 200 1000A S3H 250 F F R 250 1250A EF = Extended front terminals S3H 250 F EF R 200 1000A S3H 250 F EF R 250 1250A FC Cu = Front terminals for copper cables S3H 250 F FC Cu R 200 1000A S3H 250 F FC Cu R 250 1250A FC CuAl = Front terminals for copper/aluminium cables S3H 250 F FC CuAl R 200 1000A S3H 250 F FC CuAl R 250 1250A R = Threaded rear terminals S3H 250 F R R 200 1000A S3H 250 F R R 250 1250A RC = Rear terminals for cables S3H 250 F RC R 200 1000A S3H 250 F RC R 250 1250A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3H 250 F R Res. Cur R 200 1000A S3H 250 F R Res. Cur R 250 1250A

2000A 2500A

04957 04959

05182 05184

2000A 2500A

04953 04955

05178 05180

05011 05013

05236 05238

2000A 2500A

05007 05009

05232 05234

05065 05067 05173 05175

05290 05292 05398 05400

2000A 2500A 2000A 2500A

05061 05063 05169 05171

05286 05288 05394 05396

05119 05121

05344 05346

2000A 2500A

05115 05117

05340 05342

25531 25533

2000A 2500A

25527 25529

Magnetic release
F = Front terminals S3H 250 F F In 200A S3H 250 F F In 250A EF = Extended front terminals S3H 250 F EF In 200A S3H 250 F EF In 250A FC Cu = Front terminals for copper cables S3H 250 F FC Cu In 200A S3H 250 F FC Cu In 250A FC CuAl = Front terminals for copper/aluminium cables S3H 250 F FC CuAl In 200A S3H 250 F FC CuAl In 250A R = Threaded rear terminals S3H 250 F R In 200A S3H 250 F R In 250A RC = Rear terminals for cables S3H 250 F RC In 200A S3H 250 F RC In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


27564 27566 27652 27654

2000A 2500A

2000A 2500A

31948 31950

32537 32539

2000A 2500A

31996 31998

32585 32587

2000A 2500A 2000A 2500A

32044 32046 32097 32099

32633 32635 32729 32732

2000A 2500A

32089 32091

32681 32683

7
7/22 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

F = FIXED

S3L 250
Thermomagnetic release

Iu (40 C) =

250 A

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


13527 13529 13535 13537

code 1SDA0 . . . . . R1 3 poles 4 poles


13523 13525 13531 13533

F = Front terminals S3L 250 F F R 200 1000A S3L 250 F F R 250 1250A EF = Extended front terminals S3L 250 F EF R 200 1000A S3L 250 F EF R 250 1250A FC Cu = Front terminals for copper cables S3L 250 F FC Cu R 200 1000A S3L 250 F FC Cu R 250 1250A FC CuAl = Front terminals for copper/aluminium cables S3L 250 F FC CuAl R 200 1000A S3L 250 F FC CuAl R 250 1250A R = Threaded rear terminals S3L 250 F R R 200 1000A S3L 250 F R R 250 1250A RC = Rear terminals for cables S3L 250 F RC R 200 1000A S3L 250 F RC R 250 1250A R Res. Cur = Threaded rear terminals + kit of threaded rear terminals for residual-current release installed below the circuit-breaker S3L 250 F R Res. Cur R 200 1000A S3L 250 F R Res. Cur R 250 1250A

PSIS9607

2000A 2500A

05443 05445

05668 05670

2000A 2500A

05439 05441

05664 05666

05497 05499

05722 05724

2000A 2500A

05493 05495

05718 05720

05551 05553 05659 05661

05776 05778 05884 05886

2000A 2500A 2000A 2500A

05547 05549 05655 05657

05772 05774 05880 05882

05605 05607

05830 05832

2000A 2500A

05601 05603

05826 05828

25539 25541

2000A 2500A

25535 25537

Magnetic release
F = Front terminals S3L 250 F F In 200A S3L 250 F F In 250A EF = Extended front terminals S3L 250 F EF In 200A S3L 250 F EF In 250A FC Cu = Front terminals for copper cables S3L 250 F FC Cu In 200A S3L 250 F FC Cu In 250A FC CuAl = Front terminals for copper/aluminium cables S3L 250 F FC CuAl In 200A S3L 250 F FC CuAl In 250A R = Threaded rear terminals S3L 250 F R In 200A S3L 250 F R In 250A RC = Rear terminals for cables S3L 250 F RC In 200A S3L 250 F RC In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


27748 27750 27828 27830

2000A 2500A

2000A 2500A

32137 32139

32737 32739

2000A 2500A

32185 32187

32785 32787

2000A 2500A 2000A 2500A

32233 32235 32329 32331

32833 32835 32921 32923

2000A 2500A

32281 32283

32761 32763

7
ABB SACE 7/23

Order codes
SACE Isomax S3 circuit-breaker

P = PLUG-IN

Moving part S3N 250 Iu (40 C) = 250 A


Thermomagnetic release
PSIS9607

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


04921 04923 04939 04941

code 1SDA0 . . . . . R1 3 poles 4 poles


04917 04919 04935 04937

S3N 250 P MP S3N 250 P MP

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3N 250 P MP S3N 250 P MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


32929 32931 32945 32947

2000A 2500A

S3H 250
Thermomagnetic release
S3H 250 P MP S3H 250 P MP

Iu (40 C) =

250 A
05407 05409

Icu (415 V) =

65 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


05425 05427

code 1SDA0 . . . . . R1 3 poles 4 poles


05403 05405 05421 05423

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3H 250 P MP S3H 250 P MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


32961 32963 32977 32979

2000A 2500A

S3L 250
Thermomagnetic release
S3L 250 P MP S3L 250 P MP

Iu (40 C) =

250 A
05893 05895

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


05911 05913

code 1SDA0 . . . . . R1 3 poles 4 poles


05889 05891 05907 05909

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3L 250 P MP S3L 250 P MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


32993 32995 33009 33011

2000A 2500A

7
7/24 ABB SACE

Order codes
SACE Isomax S3 circuit-breaker

W = WITHDRAWABLE Moving part S3N 250 Iu (40 C) = 250 A


Thermomagnetic release
PSIS9607

Icu (415 V) =

35 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


04930 04932 04948 04950

code 1SDA0 . . . . . R1 3 poles 4 poles


04926 04928 04944 04946

S3N 250 W MP S3N 250 W MP

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3N 250 W MP S3N 250 W MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


32937 32939 32953 32955

2000A 2500A

S3H 250
Thermomagnetic release
S3H 250 W MP S3H 250 W MP

Iu (40 C) =

250 A
05416 05418

Icu (415 V) =

65 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


05434 05436

code 1SDA0 . . . . . R1 3 poles 4 poles


05412 05414 05430 05432

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3H 250 W MP S3H 250 W MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


32969 32971 32985 32987

2000A 2500A

S3L 250
Thermomagnetic release
S3L 250 W MP S3L 250 W MP

Iu (40 C) =

250 A
05902 05904

Icu (415 V) =

85 kA
Im = 10 Ith

Im = 5 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


05920 05922

code 1SDA0 . . . . . R1 3 poles 4 poles


05898 05900 05916 05918

R 200 R 250

1000A 1250A

2000A 2500A

Magnetic release
S3L 250 W MP S3L 250 W MP In 200A In 250A

Im = 10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


33001 33003 33017 33019

2000A 2500A

7
ABB SACE 7/25

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4N 160
F = Front terminals S4N 160 F F
S4N 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

35 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


15548 15550 15549 15551 15836 15838 15837 15839

code 1SDA0 . . . . . R1 3 poles 4 poles


15553 15558 15554 15559 15841 15846 15842 15847

EF = Extended front terminals S4N 160 F EF


S4N 160 F EF

PSIS9610

In 100 A In 160 A

I LI I LI

15632 15633 05924 05925

15920 15921 06080 06081

LSI LSIG LSI LSIG

15635 15637 05926 05929

15923 15925 06082 06085

FC Cu = Front terminals for copper cables S4N 160 F FC Cu In 100 A


S4N 160 F FC Cu In 160 A

I LI I LI

15680 15681 05960 05961

15968 15969 06116 06117

LSI LSIG LSI LSIG

15683 15685 05962 05965

15971 15973 06118 06121

FC CuAl = Front terminals for copper/aluminium cables S4N 160 F FC CuAl In 100 A
S4N 160 F FC CuAl In 160 A

I LI I LI I LI I LI

15728 15729 05996 05997 15830 15831 06074 06075

16016 16017 06152 06153 16112 16113 06224 06225

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

15731 15733 05998 06001 15833 15835 06076 06079

16019 16021 06154 06157 16115 16117 06226 06229

R = Threaded rear terminals S4N 160 F R In 100 A


S4N 160 F R In 160 A

RC = Rear terminals for cables S4N 160 F RC


S4N 160 F RC

In 100 A In 160 A

I LI I LI

15782 15783 06038 06039

16064 16065 06188 06189

LSI LSIG LSI LSIG

15785 15787 06040 06043

16067 16069 06190 06193

S4H 160
F = Front terminals S4H 160 F F
S4H 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

65 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


16142 16144 16143 16145 16424 16426 16425 16427

code 1SDA0 . . . . . R1 3 poles 4 poles


16146 16152 16147 16153 16428 16434 16429 16435

EF = Extended front terminals S4H 160 F EF


S4H 160 F EF

In 100 A In 160 A

I LI I LI

16226 16227 06254 06255

16508 16509 06404 06405

LSI LSIG LSI LSIG

16228 16231 06256 06259

16510 16513 06406 06409

FC Cu = Front terminals for copper cables S4H 160 F FC Cu In 100 A


S4H 160 F FC Cu In 160 A

I LI I LI

16274 16275 06290 06291

16556 16557 06440 06441

LSI LSIG LSI LSIG

16276 16279 06292 06295

16558 16561 06442 06445

FC CuAl = Front terminals for copper/aluminium cables S4H 160 F FC CuAl In 100 A
S4H 160 F FC CuAl In 160 A

7
7/26

I LI I LI

16322 16323 06326 06327

16604 16605 06476 06477

LSI LSIG LSI LSIG

16324 16327 06328 06331

16606 16609 06478 06481

ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

Microprocessor-based release
R = Threaded rear terminals S4H 160 F R In 100 A
S4H 160 F R In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


16418 16419 06398 06399 16700 16701 06548 06549

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


16420 16423 06400 06403 16702 16705 06550 06553

RC = Rear terminals for cables S4H 160 F RC


PSIS9610

In 100 A In 160 A

S4H 160 F RC

I LI I LI

16370 16371 06362 06363

16652 16653 06512 06513

LSI LSIG LSI LSIG

16372 16375 06364 06367

16654 16657 06514 06517

S4L 160
F = Front terminals S4L 160 F F
S4L 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

100 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


16730 16732 16731 16733 17012 17014 17013 17015

code 1SDA0 . . . . . R1 3 poles 4 poles


16734 16740 16735 16741 17016 17022 17017 17023

EF = Extended front terminals S4L 160 F EF


S4L 160 F EF

In 100 A In 160 A

I LI I LI

16814 16815 06578 06579

17096 17097 06728 06729

LSI LSIG LSI LSIG

16816 16819 06580 06583

17098 17101 06730 06733

FC Cu = Front terminals for copper cables S4L 160 F FC Cu In 100 A


S4L 160 F FC Cu In 160 A

I LI I LI

16862 16863 06614 06615

17144 17145 06764 06765

LSI LSIG LSI LSIG

16864 16867 06616 06619

17146 17149 06766 06769

FC CuAl = Front terminals for copper/aluminium cables S4L 160 F FC CuAl In 100 A
S4L 160 F FC CuAl In 160 A

I LI I LI I LI I LI

16910 16911 06650 06651 17006 17007 06722 06723

17192 17193 06800 06801 17288 17289 06872 06873

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

16912 16915 06652 06655 17008 17011 06724 06727

17194 17197 06802 06805 17290 17293 06874 06877

R = Threaded rear terminals S4L 160 F R In 100 A


S4L 160 F R In 160 A

RC = Rear terminals for cables S4L 160 F RC


S4L 160 F RC

In 100 A In 160 A

I LI I LI

16958 16959 06686 06687

17240 17241 06836 06837

LSI LSIG LSI LSIG

16960 16963 06688 06691

17242 17245 06838 06841

7
ABB SACE 7/27

Order codes
SACE Isomax S4 circuit-breaker

P = PLUG-IN

Moving part S4N 160 Iu (40 C) = 160 A


Microprocessor-based release
S4N 160 P MP S4N 160 P MP
PSIS9610

Icu (415 V) =

35 kA
PR212 P LSI LSIG LSI LSIG

PR211 P I LI I LI

code 1SDA0 . . . . . R1 3 poles 4 poles


16118 16119 06230 06231 16130 16131 06242 06243

code 1SDA0 . . . . . R1 3 poles 4 poles


16121 16123 06232 06235 16133 16135 06244 06247

In 100 A In 160 A

S4H 160
S4H 160 P MP S4H 160 P MP

Iu (40 C) =

160 A
16706 16707 06554 06555

Icu (415 V) =

65 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


16718 16719 06566 06567

code 1SDA0 . . . . . R1 3 poles 4 poles


16708 16711 06556 06559 16720 16723 06568 06571

S4L 160
S4L 160 P MP S4L 160 P MP

Iu (40 C) =

160 A
17294 17295 06878 06879

Icu (415 V) =

100 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17306 17307 06890 06891

code 1SDA0 . . . . . R1 3 poles 4 poles


17296 17299 06880 06883 17308 17311 06892 06895

W = WITHDRAWABLE Moving part S4N 160 Iu (40 C) = 160 A


Microprocessor-based release
S4N 160 W MP S4N 160 W MP
PSIS9610

Icu (415 V) =

35 kA
PR212 P LSI LSIG LSI LSIG

PR211 P I LI I LI

code 1SDA0 . . . . . R1 3 poles 4 poles


16124 16125 06236 06237 16136 16137 06248 06249

code 1SDA0 . . . . . R1 3 poles 4 poles


16127 16129 06238 06241 16139 16141 06250 06253

In 100 A In 160 A

S4H 160
S4H 160 W MP S4H 160 W MP

Iu (40 C) =

160 A
16712 16713 06560 06561

Icu (415 V) =

65 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


16724 16725 06572 06573

code 1SDA0 . . . . . R1 3 poles 4 poles


16714 16717 06562 06565 16726 16729 06574 06577

S4L 160
S4L 160 W MP

Iu (40 C) =

160 A
17300 17301 06884 06885

Icu (415 V) =

100 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 100 A In 160 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17312 17313 06896 06897

code 1SDA0 . . . . . R1 3 poles 4 poles


17302 17305 06886 06889 17314 17317 06898 06901

7
7/28

S4L 160 W MP

ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4N 250
F = Front terminals S4N 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

35 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 250 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17318 17319 06902 06903 17384 17385 07052 07053

code 1SDA0 . . . . . R1 3 poles 4 poles


17320 17323 06904 06907 17386 17389 07054 07057

EF = Extended front terminals S4N 250 F EF In 250 A


PSIS9610

FC Cu = Front terminals for copper cables S4N 250 F FC Cu In 250 A FC CuAl = Front terminals for copper/aluminium cables S4N 250 F FC CuAl In 250 A R = Threaded rear terminals S4N 250 F R In 250 A

I LI

06938 06939

07088 07089

LSI LSIG

06940 06943

07090 07093

I LI I LI

06974 06975 07046 07047 07010 07011

07124 07125 07196 07197 07160 07161

LSI LSIG LSI LSIG LSI LSIG

06976 06979 07048 07051 07012 07015

07126 07129 07198 07201 07162 07165

RC = Rear terminals for cables S4N 250 F RC In 250 A I LI

S4H 250
F = Front terminals S4H 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

65 kA
PR212 P LSI LSIG LSI LSIG

Microprocessor-based release
In 250 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17450 17451 07226 07227 17516 17517 07376 07377

code 1SDA0 . . . . . R1 3 poles 4 poles


17452 17455 07228 07231 17518 17521 07378 07381

EF = Extended front terminals S4H 250 F EF In 250 A FC Cu = Front terminals for copper cables S4H 250 F FC Cu In 250 A FC CuAl = Front terminals for copper/aluminium cables S4H 250 F FC CuAl In 250 A R = Threaded rear terminals S4H 250 F R In 250 A

I LI

07262 07263

07412 07413

LSI LSIG

07264 07267

07414 07417

I LI I LI

07298 07299 07370 07371 07334 07335

07448 07449 07520 07521 07484 07485

LSI LSIG LSI LSIG LSI LSIG

07300 07303 07372 07375 07336 07339

07450 07453 07522 07525 07486 07489

RC = Rear terminals for cables S4H 250 F RC In 250 A I LI

7
ABB SACE 7/29

Order codes
SACE Isomax S4 circuit-breaker

F = FIXED

S4L 250
F = Front terminals S4L 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

100 kA
PR212 P

Microprocessor-based release
In 250 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17582 17583 07550 07551 17648 17649 07700 07701

code 1SDA0 . . . . . R1 3 poles 4 poles


17584 17587 07552 07555 17650 17653 07702 07705

LSI LSIG LSI LSIG

EF = Extended front terminals S4L 250 F EF In 250 A


PSIS9610

FC Cu = Front terminals for copper cables S4L 250 F FC Cu In 250 A FC CuAl = Front terminals for copper/aluminium cables S4L 250 F FC CuAl In 250 A R = Threaded rear terminals S4L 250 F R In 250 A

I LI

07586 07587

07736 07737

LSI LSIG

07588 07591

07738 07741

I LI I LI

07622 07623 07694 07695 07658 07659

07772 07773 07844 07845 07808 07809

LSI LSIG LSI LSIG LSI LSIG

07624 07627 07696 07699 07660 07663

07774 07777 07846 07849 07810 07813

RC = Rear terminals for cables S4L 250 F RC In 250 A I LI

7
7/30 ABB SACE

Order codes
SACE Isomax S4 circuit-breaker

P = PLUG-IN

Moving part S4N 250 Iu (40 C) = 250 A


Microprocessor-based release
S4N 250 P MP In 250 A I LI PR211 P 07202 07203

Icu (415 V) =

35 kA
PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


07214 07215

code 1SDA0 . . . . . R1 3 poles 4 poles


07204 07207 07216 07219

PSIS9610

S4H 250
S4H 250 P MP

Iu (40 C) =

250 A
07526 07527

Icu (415 V) =

65 kA
PR212 P LSI LSIG

Microprocessor-based release
In 250 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


07538 07539

code 1SDA0 . . . . . R1 3 poles 4 poles


07528 07531 07540 07543

S4L 250
S4L 250 P MP

Iu (40 C) =

250 A
07850 07851

Icu (415 V) =

100 kA
PR212 P LSI LSIG

Microprocessor-based release
In 250 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


07862 07863

code 1SDA0 . . . . . R1 3 poles 4 poles


07852 07855 07864 07867

W = WITHDRAWABLE Moving part S4N 250 Iu (40 C) = 250 A


Microprocessor-based release
S4N 250 W MP In 250 A I LI PR211 P 07208 07209

Icu (415 V) =

35 kA
PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


07220 07221

code 1SDA0 . . . . . R1 3 poles 4 poles


07210 07213 07222 07225

PSIS9610

S4H 250
S4H 250 W MP

Iu (40 C) =

250 A
07532 07533

Icu (415 V) =

65 kA
PR212 P LSI LSIG

Microprocessor-based release
In 250 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


07544 07545

code 1SDA0 . . . . . R1 3 poles 4 poles


07534 07537 07546 07549

S4L 250
S4L 250 W MP

Iu (40 C) =

250 A
07856 07857

Icu (415 V) =

100 kA
PR212 P LSI LSIG

Microprocessor-based release
In 250 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


07868 07869

code 1SDA0 . . . . . R1 3 poles 4 poles


07858 07861 07870 07873

7
ABB SACE 7/31

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5N 400
Thermomagnetic release

Iu (40 C) =

400 A

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38438 38439 38440 38441

F = Front terminals S5N 400 F F R 320 S5N 400 F F R 400 EF = Extended front terminals S5N 400 F EF R 320 S5N 400 F EF R 400 FC Cu = Front terminals for copper cables S5N 400 F FC Cu R 320 S5N 400 F FC Cu R 400 FC CuAl = Front terminals for copper/aluminium cables S5N 400 F FC CuAl* R 320 S5N 400 F FC CuAl* R 400 S5N 400 F FC CuAl** R 320 S5N 400 F FC CuAl** R 400 R = Threaded rear terminals S5N 400 F R R 320 S5N 400 F R R 400 RC = Rear terminals for cables S5N 400 F RC R 320 S5N 400 F RC R 400

3200A 4000A

PSIS9613

3200A 4000A

38442 38443

38444 38445

3200A 4000A

38446 38447

38448 38449

3200A 4000A 3200A 4000A 3200A 4000A

38450 38451 38466 38467 38486 38487

38452 38453 38480 38481 38488 38489

3200A 4000A

38482 38483

38484 38485

Microprocessor-based release
F = Front terminals S5N 400 F F
S5N 400 F F In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17714 17716 17715 17717 17846 17848 17847 17849

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


17718 17724 17719 17725 17850 17856 17851 17857

EF = Extended front terminals S5N 400 F EF


S5N 400 F EF

In 320 A In 400 A

I LI I LI

07874 07876 07875 07877

08174 08176 08175 08177

LSI LSIG LSI LSIG

07878 07884 07879 07885

08178 08184 08179 08185

FC Cu = Front terminals for copper cables S5N 400 F FC Cu In 320 A


S5N 400 F FC Cu In 400 A

I LI I LI

07946 07948 07947 07949

08246 08248 08247 08249

LSI LSIG LSI LSIG

07950 07956 07951 07957

08250 08256 08251 08257

FC CuAl = Front terminals for copper/aluminium cables S5N 400 F FC CuAl* In 320 A
S5N 400 F FC CuAl* In 400 A

S5N 400 F FC CuAl** In 320 A S5N 400 F FC CuAl** In 400 A

I LI I LI I LI I LI I LI I LI

08018 08020 08019 08021 38454 38456 38455 38457 08162 08164 08163 08165

08318 08320 08319 08321 38468 38470 38469 38471 08450 08452 08451 08453

LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG

08022 08028 08023 08029 38458 38464 38459 38465 08166 08172 08167 08173

08322 08328 08323 08329 38472 38478 38473 38479 08454 08460 08455 08461

R = Threaded rear terminals S5N 400 F R In 320 A


S5N 400 F R In 400 A

7
7/32

RC = Rear terminals for cables S5N 400 F RC


S5N 400 F RC

In 320 A In 400 A

I LI I LI

08090 08092 08091 08093

08390 08392 08391 08393

LSI LSIG LSI LSIG

08094 08100 08095 08101

08394 08400 08395 08401

* Cable section = 1 x 240 mm2 ** Cable section = 2 x 120 mm2

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5H 400
Thermomagnetic release

Iu (40 C) =

400 A

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38522 38523 38526 38527 38524 38525 38528 38529

F = Front terminals S5H 400 F F R 320 S5H 400 F F R 400 EF = Extended front terminals S5H 400 F EF R 320 S5H 400 F EF R 400 FC Cu = Front terminals for copper cables S5H 400 F FC Cu R 320 S5H 400 F FC Cu R 400 FC CuAl = Front terminals for copper/aluminium cables S5H 400 F FC CuAl* R 320 S5H 400 F FC CuAl* R 400 S5H 400 F FC CuAl** R 320 S5H 400 F FC CuAl** R 400 R = Threaded rear terminals S5H 400 F R R 320 S5H 400 F R R 400 RC = Rear terminals for cables S5H 400 F RC R 320 S5H 400 F RC R 400

3200A 4000A 3200A 4000A

PSIS9613

3200A 4000A

38530 38531

38532 38533

3200A 4000A 3200A 4000A 3200A 4000A 3200A 4000A

38534 38535 38550 38551 38570 38571 38566 38567

38536 38537 38564 38565 38572 38573 38568 38569

Microprocessor-based release
F = Front terminals S5H 400 F F
S5H 400 F F In 320 A In 400 A I LI I LI I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17990 17992 17991 17993 08510 08512 08511 08513 18122 18124 18123 18125 08810 08812 08811 08813

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


17994 18000 17995 18001 08514 08520 08515 08521 18126 18132 18127 18133 08814 08820 08815 08821

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

EF = Extended front terminals S5H 400 F EF In 320 A


S5H 400 F EF In 400 A

FC Cu = Front terminals for copper cables S5H 400 F FC Cu In 320 A


S5H 400 F FC Cu In 400 A

I LI I LI

08582 08584 08583 08585

08882 08884 08883 08885

LSI LSIG LSI LSIG

08586 08592 08587 08593

08886 08892 08887 08893

FC CuAl = Front terminals for copper/aluminium cables S5H 400 F FC CuAl* In 320 A
S5H 400 F FC CuAl* S5H 400 F FC CuAl** S5H 400 F FC CuAl** In 400 A In 320 A In 400 A

I LI I LI I LI I LI I LI I LI I LI I LI

08654 08656 08655 08657 38538 38540 38539 38541 08798 08800 08799 08801 08726 08728 08727 08729

08954 08956 08955 08957 38552 38554 38553 38555 09098 09100 09099 09101 09026 09028 09027 09029

LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG

08658 08664 08659 08665 38542 38548 38543 38549 08802 08808 08803 08809 08730 08736 08731 08737

08958 08964 08959 08965 38556 38563 38557 38562 09102 09108 09103 09109 09030 09036 09031 09037

R = Threaded rear terminals S5H 400 F R In 320 A


S5H 400 F R In 400 A

RC = Rear terminals for cables S5H 400 F RC In 320 A


S5H 400 F RC In 400 A

* Cable section = 1 x 240 mm2 ** Cable section = 2 x 120 mm2

7
7/33

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5L 400
Thermomagnetic release

Iu (40 C) =

400 A

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38606 38607 38610 38611 38608 38609 38612 38613

F = Front terminals S5L 400 F F R 320 S5L 400 F F R 400 EF = Extended front terminals S5L 400 F EF R 320 S5L 400 F EF R 400 FC Cu = Front terminals for copper cables S5L 400 F FC Cu R 320 S5L 400 F FC Cu R 400 FC CuAl = Front terminals for copper/aluminium cables S5L 400 F FC CuAl* R 320 S5L 400 F FC CuAl* R 400 S5L 400 F FC CuAl** R 320 S5L 400 F FC CuAl** R 400 R = Threaded rear terminals S5L 400 F R R 320 S5L 400 F R R 400 RC = Rear terminals for cables S5L 400 F RC R 320 S5L 400 F RC R 400

3200A 4000A 3200A 4000A

PSIS9613

3200A 4000A

38614 38615

38616 38617

3200A 4000A 3200A 4000A 3200A 4000A 3200A 4000A

38618 38619 38634 38635 38654 38655 38650 38651

38620 38621 38648 38649 38656 38657 38652 38653

Microprocessor-based release
F = Front terminals S5L 400 F F
S5L 400 F F In 320 A In 400 A I LI I LI I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18254 18256 18255 18257 09158 09160 09159 09161 18386 18388 18387 18389 09458 09460 09459 09461

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18258 18264 18259 18265 09162 09168 09163 09169 18390 18396 18391 18397 09462 09468 09463 09469

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

EF = Extended front terminals S5L 400 F EF In 320 A


S5L 400 F EF In 400 A

FC Cu = Front terminals for copper cables S5L 400 F FC Cu In 320 A


S5L 400 F FC Cu In 400 A

I LI I LI

09230 09232 09231 09233

09530 09532 09531 09533

LSI LSIG LSI LSIG

09234 09240 09235 09241

09534 09540 09535 09541

FC CuAl = Front terminals for copper/aluminium cables S5L 400 F FC CuAl* In 320 A
S5L 400 F FC CuAl* S5L 400 F FC CuAl** S5L 400 F FC CuAl** In 400 A In 320 A In 400 A

I LI I LI I LI I LI I LI I LI I LI I LI

09302 09304 09303 09305 38622 38624 38623 38625 09446 09448 09447 09449 09374 09376 09375 09377

09602 09604 09603 09605 38636 38638 38637 38639 09746 09748 09747 09749 09674 09676 09675 09677

LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG LSI LSIG

09306 09312 09307 09313 38626 38628 38627 38629 09450 09456 09451 09457 09378 09384 09379 09385

09606 09612 09607 09613 38640 38646 38641 38647 09750 09756 09751 09757 09678 09684 09679 09685

R = Threaded rear terminals S5L 400 F R In 320 A


S5L 400 F R In 400 A

RC = Rear terminals for cables S5L 400 F RC In 320 A


S5L 400 F RC In 400 A

7
7/34

* Cable section = 1 x 240 mm2 ** Cable section = 2 x 120 mm2

ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

P = PLUG-IN

Moving part S5N 400 Iu (40 C) = 400 A


Thermomagnetic release
S5N 400 P MP S5N 400 P MP
PSIS9613

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


43896 43897 43902 43903

R 320 R 400

3200A 4000A

Microprocessor-based release
S5N 400 P MP S5N 400 P MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


08462 08464 08463 08465 08486 08488 08487 08489

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


08466 08472 08467 08473 08490 08496 08491 08497

S5H 400
Thermomagnetic release
S5H 400 P MP S5H 400 P MP

Iu (40 C) =

400 A
43898 43899

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


43904 43905

R 320 R 400

3200A 4000A

Microprocessor-based release
S5H 400 P MP S5H 400 P MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


09110 09112 09111 09113 09134 09136 09135 09137

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


09114 09120 09115 09121 09138 09144 09139 09145

S5L 400
Thermomagnetic release
S5L 400 P MP S5L 400 P MP

Iu (40 C) =

400 A
43900 43901

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


43906 43907

R 320 R 400

3200A 4000A

Microprocessor-based release
S5L 400 P MP S5L 400 P MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


09758 09760 09759 09761 09782 09784 09783 09785

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


09762 09768 09763 09769 09786 09792 09787 09793

7
ABB SACE 7/35

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part S5N 400 Iu (40 C) = 400 A


Thermomagnetic release
S5N 400 W MP S5N 400 W MP
PSIS9613

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38414 38415 38416 38417

R 320 R 400

3200A 4000A

Microprocessor-based release
S5N 400 W MP S5N 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


08474 08476 08475 08477 08498 08500 08499 08501

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


08478 08484 08479 08485 08502 08508 08503 08509

S5H 400
S5H 400 W MP S5H 400 W MP

Iu (40 C) =

400 A Icu (415 V) = 65 kA


Im = 5...10 Ith

Thermomagnetic release
R 320 R 400

code 1SDA0 . . . . . R1 3 poles 4 poles


38490 38491 38492 38493

3200A 4000A

Microprocessor-based release
S5H 400 W MP S5H 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


09122 09124 09123 09125 09146 09148 09147 09149

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


09126 09132 09127 09133 09150 09156 09151 09157

S5L 400
S5L 400 W MP S5L 400 W MP

Iu (40 C) =

400 A Icu (415 V) = 100 kA


Im = 5...10 Ith

Thermomagnetic release
R 320 R 400

code 1SDA0 . . . . . R1 3 poles 4 poles


38574 38575 38576 38577

3200A 4000A

Microprocessor-based release
S5L 400 W MP S5L 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


09770 09772 09771 09773 09794 09796 09795 09797

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


09774 09780 09775 09781 09798 09804 09799 09805

7
7/36 ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part (1) S5N 400 Iu (40 C) = 400 A


Thermomagnetic release
S5N 400 W MP S5N 400 W MP
PSIS9613

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38426 38427 38436 38437

R 320 R 400

3200A 4000A

Microprocessor-based release
S5N 400 W MP S5N 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38418 38420 38419 38421 38428 38430 51608 38431

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38422 38424 38423 38425 38432 38434 38433 38435

S5H 400
Thermomagnetic release
S5H 400 W MP S5H 400 W MP

Iu (40 C) =

400 A
38506 38507

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38520 38521

R 320 R 400

3200A 4000A

Microprocessor-based release
S5H 400 W MP S5H 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38494 38496 38495 38497 38508 38510 38509 38511

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38498 38504 38499 38505 38512 38518 38513 38519

S5L 400
Thermomagnetic release
S5L 400 W MP S5L 400 W MP

Iu (40 C) =

400 A
38590 38591

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38604 38605

R 320 R 400

3200A 4000A

Microprocessor-based release
S5L 400 W MP S5L 400 W MP In 320 A In 400 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38578 38580 38579 38581 38592 38594 38593 38595

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38582 38588 38583 38589 38596 38602 38597 38603

(1) The S5 400 mobile parts indicated on this page can be used in conjunction with S5 630 W FP fixed parts. Two different fixed parts are available for circuit-breakers S5 400 and S5 630. Fixed circuit-breaker S5 400: converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 13718 R1 (three-pole), 1SDA0 13719 R1 (four-pole) can be used in conjunction with the fixed part for S5 400 (see codes on pages 7/81). converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 38778 R1 (three-pole), 1SDA0 38779 R1 (four-pole) can be used in conjunction with the fixed part for S5 630. This page shows the codes for the mobile parts of withdrawable circuit-breakers which have already been converted and can be used in conjunction with the fixed parts for S5 630. Circuit-breaker S5 630 can be converted into the mobile part of a withdrawable circuit-breaker using kit 1SDA0 38778 R1 (three-pole), 1SDA0 38779 R1 (four-pole) and used in conjunction exclusively with the fixed parts for S5 630 (see codes on page 7/81).

ABB SACE

7/37

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5N 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38678 38683

F = Front terminals S5N 630 F F R 500 ES = Spreaded extended front terminals S5N 630 F ES R 500 FC Cu = Front terminals for copper cables S5N 630 F FC Cu R 500 R = Threaded rear terminals S5N 630 F R R 500

5000A

5000A

38684

38685

PSIS9613

5000A 5000A

38686 38690

38687 38691

Microprocessor-based release
F = Front terminals S5N 630 F F
In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38674 38675 38679 38680

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38676 38677 38681 38682

LSI LSIG

ES = Spreaded extended front terminals S5N 630 F ES In 630 A FC Cu = Front terminals for copper cables S5N 630 F FC Cu In 630 A R = Threaded rear terminals S5N 630 F R In 630 A

I LI

14575 14576

14725 14726

LSI LSIG

14577 14580

14727 14730

I LI I LI

14611 14612 14719 14720

14761 14762 14869 14870

LSI LSIG LSI LSIG

14613 14616 14721 14724

14763 14766 14871 14874

S5H 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38708 38713

F = Front terminals S5H 630 F F R 500 ES = Spreaded extended front terminals S5H 630 F ES R 500 FC Cu = Front terminals for copper cables S5H 630 F FC Cu R 500 R = Threaded rear terminals S5H 630 F R R 500

5000A

5000A

38714

38715

5000A 5000A

38716 38720

38717 38721

Microprocessor-based release
F = Front terminals S5H 630 F F
In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38704 38705 38709 38710

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38706 38707 38711 38712

LSI LSIG

ES = Spreaded extended front terminals S5H 630 F ES In 630 A FC Cu = Front terminals for copper cables S5H 630 F FC Cu In 630 A R = Threaded rear terminals S5H 630 F R In 630 A

I LI

14899 14900

15049 15050

LSI LSIG

14901 14904

15051 15054

I LI I LI

14935 14936 15043 15044

15085 15086 15193 15194

LSI LSIG LSI LSIG

14937 14940 15045 15048

15087 15090 15195 15198

7
7/38 ABB SACE

Order codes
SACE Isomax S5 circuit-breaker

F = FIXED

S5L 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38740 38745

F = Front terminals S5L 630 F F R 500 ES = Spreaded extended front terminals S5L 630 F ES R 500 FC Cu = Front terminals for copper cables S5L 630 F FC Cu R 500 R = Threaded rear terminals S5L 630 F R R 500

5000A

5000A

38746

38747

PSIS9613

5000A 5000A

38748 38752

38749 38753

Microprocessor-based release
F = Front terminals S5L 630 F F
In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38736 38737 38741 38742

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38738 38739 38743 38744

LSI LSIG

ES = Spreaded extended front terminals S5L 630 F ES In 630 A FC Cu = Front terminals for copper cables S5L 630 F FC Cu In 630 A R = Threaded rear terminals S5L 630 F R In 630 A

I LI

15223 15224

15373 15374

LSI LSIG

47991 15228

43801 15378

I LI I LI

15259 15260 15367 15368

15409 15410 15517 15518

LSI LSIG LSI LSIG

43748 15264 43775 15372

43815 15414 43843 15522

7
ABB SACE 7/39

Order codes
SACE Isomax S5 circuit-breaker

W = WITHDRAWABLE Moving part S5N 630 Iu (40 C) = 630 A Icu (415 V) = 35 kA


Thermomagnetic release
S5N 630 W MP R 500
Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38666 38673

5000A

PSIS9613

Microprocessor-based release
S5N 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38660 38661 38667 38668

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38662 38665 38669 38672

S5H 630
Thermomagnetic release
S5H 630 W MP

Iu (40 C) =

630 A
38697

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38703

R 500

5000A

Microprocessor-based release
S5H 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38693 38694 38699 38700

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38695 38696 38701 38702

S5L 630
Thermomagnetic release
S5L 630 W MP

Iu (40 C) =

630 A
38729

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38754

R 500

5000A

Microprocessor-based release
S5L 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


38723 38724 38730 38731

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


38725 38728 38732 38734

7
7/40 ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6N 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38787 38789 38788 38790

F = Front terminals S6N 630 F F R 630 EF = Extended front terminals S6N 630 F EF R 630 FC CuAl = Front terminals for copper/aluminium cables S6N 630 F FC CuAl* R 630 R = Threaded rear terminals S6N 630 F R R 630 RC = Rear terminals for cables S6N 630 F RC R 630

6300A 6300A

PSIS9616

6300A 6300A 6300A

38791 38795 38793

38792 38796 38794

Microprocessor-based release
F = Front terminals S6N 630 F F
In 630 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18518 18519 09806 09807 18572 18573 09902 09903

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


18520 18523 09808 09811 18574 18577 09904 09907

EF = Extended front terminals S6N 630 F EF In 630 A FC CuAl = Front terminals for copper/aluminium cables S6N 630 F FC CuAl* In 630 A R = Threaded rear terminals S6N 630 F R In 630 A RC = Rear terminals for cables S6N 630 F RC In 630 A

I LI I LI I LI

09836 09837 09896 09897 09866 09867

09932 09933 09992 09993 09962 09963

LSI LSIG LSI LSIG LSI LSIG

09838 09841 09898 09901 09868 09871

09934 09937 09994 09997 09964 09967

S6S 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

50 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38799 38801 38800 38802

F = Front terminals S6S 630 F F R 630 EF = Extended front terminals S6S 630 F EF R 630 FC CuAl = Front terminals for copper/aluminium cables S6S 630 F FC CuAl* R 630 R = Threaded rear terminals S6S 630 F R R 630 RC = Rear terminals for cables S6S 630 F RC R 630

6300A 6300A

6300A 6300A 6300A

38817 38957 38819

38818 38959 38820

Microprocessor-based release
F = Front terminals S6S 630 F F
In 630 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18626 18627 10010 10011 18680 18681 10106 10107

PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18628 18631 10012 10015 18682 18685 10108 10111

LSI LSIG LSI LSIG

EF = Extended front terminals S6S 630 F EF In 630 A FC CuAl = Front terminals for copper/aluminium cables S6S 630 F FC CuAl* In 630 A R = Threaded rear terminals S6S 630 F R In 630 A RC = Rear terminals for cables S6S 630 F RC In 630 A

I LI I LI I LI

10040 10041 10100 10101 10070 10071

10136 10137 10196 10197 10166 10167

LSI LSIG LSI LSIG LSI LSIG

10042 10045 10102 10105 10072 10075

10138 10141 10198 10201 10168 10171

7
7/41

* Cable section = 1 x 240 mm2

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6H 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38823 38825 38824 38826

F = Front terminals S6H 630 F F R 630 EF = Extended front terminals S6H 630 F EF R 630 FC CuAl = Front terminals for copper/aluminium cables S6H 630 F FC CuAl* R 630 R = Threaded rear terminals S6H 630 F R R 630 RC = Rear terminals for cables S6H 630 F RC R 630

6300A 6300A

PSIS9616

6300A 6300A 6300A

38827 38958 38843

38835 38960 38844

Microprocessor-based release
F = Front terminals S6H 630 F F
In 630 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18734 18735 10214 10215 18788 18789 10310 10311

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


18736 18739 10216 10219 18790 18793 10312 10315

EF = Extended front terminals S6H 630 F EF In 630 A FC CuAl = Front terminals for copper/aluminium cables S6H 630 F FC CuAl* In 630 A R = Threaded rear terminals S6H 630 F R In 630 A RC = Rear terminals for cables S6H 630 F RC In 630 A

I LI I LI I LI

10244 10245 10304 10305 10274 10275

10340 10341 10400 10401 10370 10371

LSI LSIG LSI LSIG LSI LSIG

10246 10249 10306 10309 10276 10279

10342 10345 10402 10405 10372 10375

S6L 630
Thermomagnetic release

Iu (40 C) =

630 A

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38847 38849 38848 38850

F = Front terminals S6L 630 F F R 630 EF = Extended front terminals S6L 630 F EF R 630 FC CuAl = Front terminals for copper/aluminium cables S6L 630 F FC CuAl* R 630 R = Threaded rear terminals S6L 630 F R R 630 RC = Rear terminals for cables S6L 630 F RC R 630

6300A 6300A

6300A 6300A 6300A

38851 38961 38867

38859 38962 38868

Microprocessor-based release
F = Front terminals S6L 630 F F
In 630 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18842 18843 10418 10419 18896 18897 10514 10515

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


18844 18847 10420 10423 18898 18901 10516 10519

EF = Extended front terminals S6L 630 F EF In 630 A FC CuAl = Front terminals for copper/aluminium cables S6L 630 F FC CuAl* In 630 A R = Threaded rear terminals S6L 630 F R In 630 A RC = Rear terminals for cables S6L 630 F RC In 630 A

I LI I LI I LI

10448 10449 10508 10509 10478 10479

10544 10545 10604 10605 10574 10575

LSI LSIG LSI LSIG LSI LSIG

10450 10453 10510 10513 10480 10483

10546 10549 10606 10609 10576 10579

7
7/42

* Cable section = 2 x 240 mm2

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

W = WITHDRAWABLE Moving part S6N 630 Iu (40 C) = 630 A


Thermomagnetic release
S6N 630 W MP R 630
Im = 5...10 Ith

Icu (415 V) =

35 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


38785 38786

6300A

PSIS9616

Microprocessor-based release
S6N 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


09998 09999 10004 10005

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


10000 10003 10006 10009

S6S 630
Thermomagnetic release
S6S 630 W MP

Iu (40 C) =

630 A
38797

Icu (415 V) =

50 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38798

R 630

6300A

Microprocessor-based release
S6S 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


10202 10203 10208 10209

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


10204 10207 10210 10213

S6H 630
Thermomagnetic release
S6H 630 W MP

Iu (40 C) =

630 A
38821

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38822

R 630

6300A

Microprocessor-based release
S6H 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


10406 10407 10412 10413

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


10408 10411 10414 10417

S6L 630
Thermomagnetic release
S6L 630 W MP

Iu (40 C) =

630 A
38845

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38846

R 630

6300A

Microprocessor-based release
S6L 630 W MP In 630 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


10610 10611 10616 10617

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


10612 10615 10618 10621

7
ABB SACE 7/43

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6N 800
Thermomagnetic release

Iu (40 C) =

800 A

Icu (415 V) =

35 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38871 38873 38872 38874

F = Front terminals S6N 800 F F R 800 EF = Extended front terminals S6N 800 F EF R 800 FC CuAl = Front terminals for copper/aluminium cables S6N 800 F FC CuAl* R 800 R = Threaded rear terminals S6N 800 F R R 800 RC = Rear terminals for cables S6N 630 F RC R 800

8000A 8000A

PSIS9616

8000A 8000A 8000A

38875 38879 38877

38876 38880 38878

Microprocessor-based release
F = Front terminals S6N 800 F F
In 800 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


18950 18951 10622 10623 19004 19005 10718 10719

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


18952 18955 10624 10627 19006 19009 10720 10723

EF = Extended front terminals S6N 800 F EF In 800 A FC CuAl = Front terminals for copper/aluminium cables S6N 800 F FC CuAl* In 800 A R = Threaded rear terminals S6N 800 F R In 800 A RC = Rear terminals for cables S6N 800 F RC In 800 A

I LI I LI I LI

10652 10653 10712 10713 10682 10683

10748 10749 10808 10809 10778 10779

LSI LSIG LSI LSIG LSI LSIG

10654 10657 10714 10717 10684 10687

10750 10753 10810 10813 10780 10783

S6S 800
Thermomagnetic release

Iu (40 C) =

800 A

Icu (415 V) =

50 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38883 38885 38884 38886

F = Front terminals S6S 800 F F R 800 EF = Extended front terminals S6S 800 F EF R 800 FC CuAl = Front terminals for copper/aluminium cables S6S 800 F FC CuAl* R 800 R = Threaded rear terminals S6S 800 F R R 800 RC = Rear terminals for cables S6S 800 F RC R 800

8000A 8000A

8000A 8000A 8000A

38887 38963 38903

38895 38964 38904

Microprocessor-based release
F = Front terminals S6S 800 F F
In 800 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19058 19059 10826 10827 19112 19113 10922 10923

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


19060 19063 10828 10831 19114 19117 10924 10927

EF = Extended front terminals S6S 800 F EF In 800 A FC CuAl = Front terminals for copper/aluminium cables S6S 800 F FC CuAl* In 800 A

I LI I LI I LI

10856 10857 10916 10917 10886 10887

10952 10953 11006 11007 10976 10977

LSI LSIG LSI LSIG LSI LSIG

10858 10861 10918 10921 10888 10891

10954 10957 11008 11011 10978 10981

7
7/44

R = Threaded rear terminals S6S 800 F R In 800 A RC = Rear terminals for cables S6S 800 F RC In 800 A
* Cable section = 3 x 185 mm2

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

F = FIXED

S6H 800
Thermomagnetic release

Iu (40 C) =

800 A

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38907 38909 38908 38910

F = Front terminals S6H 800 F F R 800 EF = Extended front terminals S6H 800 F EF R 800 FC CuAl = Front terminals for copper/aluminium cables S6H 800 F FC CuAl* R 800 R = Threaded rear terminals S6H 800 F R R 800 RC = Rear terminals for cables S6H 800 F RC R 800

8000A 8000A

PSIS9616

8000A 8000A 8000A

38911 38965 38927

38919 38966 38928

Microprocessor-based release
F = Front terminals S6H 800 F F
In 800 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19166 19167 11024 11025 19220 19221 11120 11121

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


19168 19171 11026 11029 19222 19225 11122 11125

EF = Extended front terminals S6H 800 F EF In 800 A FC CuAl = Front terminals for copper/aluminium cables S6H 800 F FC CuAl* In 800 A R = Threaded rear terminals S6H 800 F R In 800 A RC = Rear terminals for cables S6H 800 F RC In 800 A

I LI I LI I LI

11054 11055 11114 11115 11084 11085

11150 11151 11210 11211 11180 11181

LSIG LSIG LSIG LSIG LSI LSIG

11056 11059 11116 11119 11086 11089

11152 11155 11212 11215 11182 11185

S6L 800
Thermomagnetic release

Iu (40 C) =

800 A

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38931 38933 38932 38934

F = Front terminals S6L 800 F F R 800 EF = Extended front terminals S6L 800 F EF R 800 FC CuAl = Front terminals for copper/aluminium cables S6L 800 F FC CuAl* R 800 R = Threaded rear terminals S6L 800 F R R 800 RC = Rear terminals for cables S6L 800 F RC R 800

8000A 8000A

8000A 8000A 8000A

38935 38973 38951

38943 38974 38952

Microprocessor-based release
F = Front terminals S6L 800 F F
In 800 A I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19274 19275 11228 11229 19328 19329 11324 11325

PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


19276 19279 11230 11233 19330 19333 11326 11329

EF = Extended front terminals S6L 800 F EF In 800 A FC CuAl = Front terminals for copper/aluminium cables S6L 800 F FC CuAl* In 800 A R = Threaded rear terminals S6L 800 F R In 800 A RC = Rear terminals for cables S6L 800 F RC In 800 A
* Cable section = 3 x 185 mm2

I LI I LI I LI

11258 11259 11318 11319 11288 11289

11354 11355 11414 11415 11384 11385

LSI LSIG LSI LSIG LSI LSIG

11260 11263 11320 11323 11290 11293

11356 11359 11416 11419 11386 11389

7
7/45

ABB SACE

Order codes
SACE Isomax S6 circuit-breaker

W = WITHDRAWABLE Moving part S6N 800 Iu (40 C) = 800 A


Thermomagnetic release
S6N 800 W MP R 800
Im = 5...10 Ith

Icu (415 V) =

35 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


38869 38870

8000A

PSIS9616

Microprocessor-based release
S6N 800 W MP In 800 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


10814 10815 10820 10821

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


10816 10819 10822 10825

S6S 800
Thermomagnetic release
S6S 800 W MP

Iu (40 C) =

800 A
38881

Icu (415 V) =

50 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38882

R 800

8000A

Microprocessor-based release
S6S 800 W MP In 800 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


11012 11013 11018 11019

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


11014 11017 11020 11023

S6H 800
Thermomagnetic release
S6H 800 W MP

Iu (40 C) =

800 A
38905

Icu (415 V) =

65 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38906

R 800

8000A

Microprocessor-based release
S6H 800 W MP In 800 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


11216 11217 11222 11223

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


11218 11221 11224 11227

S6L 800
Thermomagnetic release
S6L 800 W MP

Iu (40 C) =

800 A
38929

Icu (415 V) =

100 kA

Im = 5...10 Ith

code 1SDA0 . . . . . R1 3 poles 4 poles


38930

R 800

8000A

Microprocessor-based release
S6L 800 W MP In 800 A I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


11420 11421 11682 11683

PR212 P LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


11422 11425 11684 11687

7
7/46 ABB SACE

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7S 1250
Microprocessor-based release
F = Front terminals S7S 1250 F F

Iu (40 C) =

1250 A

Icu (415 V) =

50 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19382 19384 19383 19385 11432 11434 11433 11435 19490 19492 19491 19493 11624 11626 11625 11627

code 1SDA0 . . . . . R1 3 poles 4 poles


19386 19392 19387 19393 11436 11442 11437 11443 19494 19500 19495 19501 11628 11634 11629 11635

In 1000 A I LI S7S 1250 F F In 1250 A I LI EF = Extended front terminals S7S 1250 F EF In 1000 A I LI S7S 1250 F EF In 1250 A I LI FC CuAl = Front terminals for copper/aluminium cables S7S 1250 F FC CuAl In 1000 A I LI S7S 1250 F FC CuAl In 1250 A I LI VR = Vertical flat-bar rear terminals S7S 1250 F VR In 1000 A I LI S7S 1250 F VR In 1250 A I LI HR = Horizontal flat-bar rear terminals S7S 1250 F HR In 1000 A I LI S7S 1250 F HR In 1250 A I LI

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

11492 11494 11493 11495

11428 11430 11429 11431

LSI LSIG LSI LSIG

11496 11502 11497 11503

11688 11694 11689 11695

PSIS9620

11612 11614 11613 11615

11804 11806 11805 11807

LSI LSIG LSI LSIG

11616 11622 11617 11623

11808 11814 11809 11815

11552 11554 11553 11555

11744 11746 11745 11747

LSI LSIG LSI LSIG

11556 11562 11557 11563

11748 11754 11749 11755

S7H 1250
Microprocessor-based release
F = Front terminals S7H 1250 F F

Iu (40 C) =
PR211 P

1250 A

Icu (415 V) =

65 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19598 19600 19599 19601 11840 11842 11841 11843 19706 19708 19707 19709 12032 12034 12033 12035

code 1SDA0 . . . . . R1 3 poles 4 poles


19602 19608 19603 19609 11844 11850 11845 11851 19710 19716 19711 19717 12036 12042 12037 12043

In 1000 A I LI S7H 1250 F F In 1250 A I LI EF = Extended front terminals S7H 1250 F EF In 1000 A I LI S7H 1250 F EF In 1250 A I LI FC CuAl = Front terminals for copper/aluminium cables S7H 1250 F FC CuAl In 1000 A I LI S7H 1250 F FC CuAl In 1250 A I LI VR = Vertical flat-bar rear terminals S7H 1250 F VR In 1000 A I LI S7H 1250 F VR In 1250 A I LI HR = Horizontal flat-bar rear terminals S7H 1250 F HR In 1000 A I LI S7H 1250 F HR In 1250 A I LI

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

11900 11902 11901 11903

12092 12094 12093 12095

LSI LSIG LSI LSIG

11904 11910 11905 11911

12096 12102 12097 12103

12020 12022 12021 12023

12212 12214 12213 12215

LSI LSIG LSI LSIG

12024 12030 12025 12031

12216 12222 12217 12223

11960 11962 11961 11963

12152 12154 12153 12155

LSI LSIG LSI LSIG

11964 11970 11965 11971

12156 12162 12157 12163

7
7/47

ABB SACE

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7L 1250
Microprocessor-based release
F = Front terminals S7L 1250 F F

Iu (40 C) =

1250 A

Icu (415 V) =

100 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


19814 19816 19815 19817 12248 12250 12249 12251 19922 19924 19923 19925 12440 12442 12441 12443

code 1SDA0 . . . . . R1 3 poles 4 poles


19818 19824 19819 19825 12252 12258 12253 12259 19926 19932 19927 19933 12444 12450 12445 12451

In 1000 A I LI S7L 1250 F F In 1250 A I LI EF = Extended front terminals S7L 1250 F EF In 1000 A I LI S7L 1250 F EF In 1250 A I LI FC CuAl = Front terminals for copper/aluminium cables S7L 1250 F FC CuAl In 1000 A I LI S7L 1250 F FC CuAl In 1250 A I LI VR = Vertical flat-bar rear terminals S7L 1250 F VR In 1000 A I LI S7L 1250 F VR In 1250 A I LI HR = Horizontal flat-bar rear terminals S7L 1250 F HR In 1000 A I LI S7L 1250 F HR In 1250 A I LI

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

12308 12310 12309 12311

12500 12502 12501 12503

LSI LSIG LSI LSIG

12312 12318 12313 12319

12504 12510 12505 12511

PSIS9620

12428 12430 12429 12431

12620 12622 12621 12623

LSI LSIG LSI LSIG

12432 12438 12433 12439

12624 12630 12625 12631

12368 12370 12369 12371

12560 12562 12561 12563

LSI LSIG LSI LSIG

12372 12378 12373 12379

12564 12570 12565 12571

W = WITHDRAWABLE Moving part S7S 1250 Iu (40 C) = 1250 A


Microprocessor-based release
S7S 1250 W MP S7S 1250 W MP In 1000 A I LI In 1250 A I LI PR211 P 11816 11818 11817 11819

Icu (415 V) =

50 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


11828 11830 11829 11831

code 1SDA0 . . . . . R1 3 poles 4 poles


11820 11826 11821 11827 11832 11838 11833 11839

LSI LSIG LSI LSIG

S7H 1250
Microprocessor-based release
PSIS9620

Iu (40 C) =
PR211 P

1250 A
12224 12226 12225 12227

Icu (415 V) =

65 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


12236 12238 12237 12239

code 1SDA0 . . . . . R1 3 poles 4 poles


12228 12234 12229 12235 12240 12246 12241 12247

S7H 1250 W MP S7H 1250 W MP

In 1000 A I LI In 1250 A I LI

LSI LSIG LSI LSIG

S7L 1250
Microprocessor-based release
S7L 1250 W MP S7L 1250 W MP

Iu (40 C) =

1250 A
12632 12634 12633 12635

Icu (415 V) =

100 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


12644 12646 12645 12647

code 1SDA0 . . . . . R1 3 poles 4 poles


12636 12642 12637 12643 12648 12654 12649 12655

7
7/48

In 1000 A I LI In 1250 A I LI

LSI LSIG LSI LSIG

ABB SACE

Order codes
SACE Isomax S7 circuit-breaker

F = FIXED

S7S 1600
Microprocessor-based release
F = Front terminals S7S 1600 F F

Iu (40 C) =

1600 A

Icu (415 V) =

50 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


20030 20031 12656 12657 20072 20073 12710 12711

code 1SDA0 . . . . . R1 3 poles 4 poles


20032 20035 12658 12661 20074 20077 12712 12715

PSIS9620

In 1600 A I LI EF = Extended front terminals S7S 1600 F EF In 1600 A I LI VR = Vertical flat-bar rear terminals S7S 1600 F VR In 1600 A I LI HR = Horizontal flat-bar rear terminals S7S 1600 F HR In 1600 A I LI

LSI LSIG LSI LSIG

12704 12705

12758 12759

LSI LSIG

12706 12709

12760 12763

12680 12681

12734 12735

LSI LSIG

12682 12685

12736 12739

S7H 1600
Microprocessor-based release
F = Front terminals S7H 1600 F F

Iu (40 C) =

1600 A

Icu (415 V) =

65 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


20114 20115 12776 12777 20156 20157 12830 12831

code 1SDA0 . . . . . R1 3 poles 4 poles


20116 20119 12778 12781 20158 20161 12832 12835

In 1600 A I LI EF = Extended front terminals S7H 1600 F EF In 1600 A I LI VR = Vertical flat-bar rear terminals S7H 1600 F VR In 1600 A I LI HR = Horizontal flat-bar rear terminals S7H 1600 F HR In 1600 A I LI

LSI LSIG LSI LSIG

12824 12825

12878 12879

LSI LSIG

12826 12829

12880 12883

12800 12801

12854 12855

LSI LSIG

12802 12805

12856 12859

S7L 1600
Microprocessor-based release
F = Front terminals S7L 1600 F F

Iu (40 C) =

1600 A

Icu (415 V) =

100 kA
PR212 P LSI LSIG LSI LSIG

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


20198 20199 12896 12897 20240 20241 12962 12963

code 1SDA0 . . . . . R1 3 poles 4 poles


20200 20203 12898 12901 20242 20245 12964 12967

In 1600 A I LI EF = Extended front terminals S7L 1600 F EF In 1600 A I LI VR = Vertical flat-bar rear terminals S7L 1600 F VR In 1600 A I LI HR = Horizontal flat-bar rear terminals S7L 1600 F HR In 1600 A I LI

12956 12957

13010 13011

LSI LSIG

12958 12961

13012 13015

12932 12933

12986 12987

LSI LSIG

12934 12937

12988 12991

ABB SACE

7/49

Order codes
SACE Isomax S7 circuit-breaker

W = WITHDRAWABLE Moving part S7S 1600 Iu (40 C) = 1600 A


Microprocessor-based release
S7S 1600 W MP In 1600 A I LI PR211 P 12764 12765

Icu (415 V) =

50 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


12770 12771

code 1SDA0 . . . . . R1 3 poles 4 poles


12766 12769 12772 12775

LSI LSIG

S7H 1600
Microprocessor-based release
S7H 1600 W MP
PSIS9620

Iu (40 C) =

1600 A
12884 12885

Icu (415 V) =

65 kA
PR212 P

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


12890 12891

code 1SDA0 . . . . . R1 3 poles 4 poles


12886 12889 12892 12895

In 1600 A I LI

LSI LSIG

S7L 1600
Microprocessor-based release
S7L 1600 W MP

Iu (40 C) =

1600 A
13016 13017

Icu (415 V) =

100 kA
PR212 P LSI LSIG

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


13022 13023

code 1SDA0 . . . . . R1 3 poles 4 poles


13018 13021 13024 13027

In 1600 A I LI

7/50

ABB SACE

Order codes
SACE Isomax S8 circuit-breaker

F = FIXED

S8H 2000
Microprocessor-based release
F = Front terminals S8H 2000 F F
S8H 2000 F F

Iu (40 C) =

2000 A

Icu (415 V) =

85 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


44861 44863 44862 44864 44869 44871 44870 44872 44877 44879 44878 44880 44885 44887 44886 44888

In 1600 A In 2000 A

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

VR = Vertical flat-bar rear terminals S8H 2000 F VR In 1600 A


S8H 2000 F VR
GSIS9018

In 2000 A

S8V 2000
Microprocessor-based release
F = Front terminals S8V 2000 F F
S8V 2000 F F

Iu (40 C) =

2000 A

Icu (415 V) =

120 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


44918 44920 44919 44921 44926 44928 44927 44929 44934 44936 44935 44937 44942 44944 44943 44945

In 1600 A In 2000 A

LSI LSIG LSI LSIG LSI LSIG LSI LSIG

VR = Vertical flat-bar rear terminals S8V 2000 F VR In 1600 A


S8V 2000 F VR In 2000 A

S8H 2500
Microprocessor-based release
F = Front terminals S8H 2500 F F

Iu (40 C) =

2500 A

Icu (415 V) =

85 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


44891 44892 44895 44896 44899 44900 44903 44904

In 2500 A

LSI LSIG LSI LSIG

VR = Vertical flat-bar rear terminals S8H 2500 F VR In 2500 A

S8V 2500
Microprocessor-based release
F = Front terminals S8V 2500 F F

Iu (40 C) =

2500 A

Icu (415 V) =

120 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


44948 44949 44952 44953 44956 44957 44960 44961

In 2500 A

LSI LSIG LSI LSIG

VR = Vertical flat-bar rear terminals S8V 2500 F VR In 2500 A

S8H 3200
Microprocessor-based release

Iu (40 C) =

3200 A

Icu (415 V) =

85 kA
PR212 P

code 1SDA0 . . . . . R1 3 poles 4 poles


44908 44909 44912 44913

VR = Vertical flat-bar rear terminals S8H 3200 F VR In 3200 A

LSI LSIG

S8V 3200
Microprocessor-based release

Iu (40 C) =

3200 A

Icu (415 V) =

120 kA
PR212 P

7
44968 44969

code 1SDA0 . . . . . R1 3 poles 4 poles


44964 44965

VR = Vertical flat-bar rear terminals S8V 3200 F VR In 3200 A

LSI LSIG

ABB SACE

7/51

Order codes
SACE Isomax S2X 100 current-limiting circuit-breaker

F = FIXED

S2X 100
Thermomagnetic release

Iu (40 C) =

100 A

Icu (415 V) =

70 kA
Im

code 1SDA0 . . . . . R1 3 poles

FC Cu = Front terminals for copper cables S2X 100 F FC Cu R1 S2X 100 F FC Cu R 1.6 S2X 100 F FC Cu R 2.5 S2X 100 F FC Cu R4 S2X 100 F FC Cu R 6.3 S2X 100 F FC Cu R 10 S2X 100 F FC Cu R 12.5 S2X 100 F FC Cu R 16 S2X 100 F FC Cu R 20 S2X 100 F FC Cu R 25 S2X 100 F FC Cu R 32 S2X 100 F FC Cu R 40 S2X 100 F FC Cu R 50 S2X 100 F FC Cu R 63 S2X 100 F FC Cu R 80 S2X 100 F FC Cu R 100 R = Threaded rear terminals S2X 100 F R R1 S2X 100 F R R 1.6 S2X 100 F R R 2.5 S2X 100 F R R4 S2X 100 F R R 6.3 S2X 100 F R R 10 S2X 100 F R R 12.5 S2X 100 F R R 16 S2X 100 F R R 20 S2X 100 F R R 25 S2X 100 F R R 32 S2X 100 F R R 40 S2X 100 F R R 50 S2X 100 F R R 63 S2X 100 F R R 80 S2X 100 F R R 100

10A 16A 25A 40A 63A 100A 125A 160A 200A 250A 320A 400A 500A 630A 800A 1000A

50307 50308 50309 50310 50311 50312 50313 50314 50315 50316 50317 50318 50319 50320 50321 50322

GSIS9150

10A 16A 25A 40A 63A 100A 125A 160A 200A 250A 320A 400A 500A 630A 800A 1000A

50339 50340 50341 50342 50343 50344 50345 50346 50347 50348 50349 50350 50351 50352 50353 50354

P = PLUG-IN

Moving part S2X 100 Iu (40 C) = 100 A


Thermomagnetic release
S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP S2X 100 P MP R1 R 1.6 R 2.5 R4 R 6.3 R 10 R 12.5 R 16 R 20 R 25 R 32 R 40 R 50 R 63 R 80 R 100
GSIS9150

Icu (415 V) =

70 kA
Im 10A 16A 25A 40A 63A 100A 125A 160A 200A 250A 320A 400A 500A 630A 800A 1000A

code 1SDA0 . . . . . R1 3 poles


50371 50372 50373 50374 50375 50376 50377 50378 50379 50380 50381 50382 50383 50384 50385 50386

7/52

ABB SACE

Order codes
SACE Isomax S3X current-limiting circuit-breaker

F = FIXED

S3X 125
Thermomagnetic release

Iu (40 C) =

125 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles 4 poles


45197 45199 45201 45203 45205 45207 45209 45211 45213 45215

F = Front terminals S3X 125 F F R 32 S3X 125 F F R 50 S3X 125 F F R 80 S3X 125 F F R 100 S3X 125 F F R 125 EF = Extended front terminals S3X 125 F EF R 32 S3X 125 F EF R 50 S3X 125 F EF R 80 S3X 125 F EF R 100 S3X 125 F EF R 125 FC Cu = Front terminals for copper cables S3X 125 F FC Cu R 32 S3X 125 F FC Cu R 50 S3X 125 F FC Cu R 80 S3X 125 F FC Cu R 100 S3X 125 F FC Cu R 125 FC CuAl = Front terminals for copper/aluminium cables S3X 125 F FC CuAl R 32 S3X 125 F FC CuAl R 50 S3X 125 F FC CuAl R 80 S3X 125 F FC CuAl R 100 S3X 125 F FC CuAl R 125 R = Threaded rear terminals S3X 125 F R R 32 S3X 125 F R R 50 S3X 125 F R R 80 S3X 125 F R R 100 S3X 125 F R R 125 RC = Rear terminals for cables S3X 125 F RC R 32 S3X 125 F RC R 50 S3X 125 F RC R 80 S3X 125 F RC R 100 S3X 125 F RC R 125

500A 500A 800A 1000A 1250A

GSIS9151

500A 500A 800A 1000A 1250A

45217 45219 45221 45223 45225

45267 45269 45271 45273 45275

500A 500A 800A 1000A 1250A

45227 45229 45231 45233 45235

45277 45279 45281 45283 45285

500A 500A 800A 1000A 1250A

45237 45239 45241 45243 45245

45287 45289 45291 45293 45295

500A 500A 800A 1000A 1250A

45257 45259 45261 45263 45265

45307 45309 45311 45313 45315

500A 500A 800A 1000A 1250A

45247 45249 45251 45253 45255

45297 45299 45301 45303 45305

ABB SACE

7/53

Order codes
SACE Isomax S3X current-limiting circuit-breaker

F = FIXED

S3X 200
Thermomagnetic release

Iu (40 C) =

200 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles 4 poles


46039 46041 46043 46045 46047 46049

F = Front terminals S3X 200 F F S3X 200 F F S3X 200 F F EF = Extended front terminals S3X 200 F EF S3X 200 F EF S3X 200 F EF FC Cu = Front terminals for copper cables S3X 200 F FC Cu S3X 200 F FC Cu S3X 200 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S3X 200 F FC CuAl S3X 200 F FC CuAl S3X 200 F FC CuAl R = Threaded rear terminals S3X 200 F R S3X 200 F R S3X 200 F R RC = Rear terminals for cables S3X 200 F RC S3X 200 F RC S3X 200 F RC

R 125 R 160 R 200

1250A 1600A 2000A

R 125 R 160 R 200

1250A 1600A 2000A

46051 46053 46055

46081 46083 46085

GSIS9151

R 125 R 160 R 200

1250A 1600A 2000A

46057 46059 46061

46087 46089 46091

R 125 R 160 R 200

1250A 1600A 2000A

46063 46065 46067

46093 46095 46097

R 125 R 160 R 200

1250A 1600A 2000A

46075 46077 46079

46105 46107 46109

R 125 R 160 R 200

1250A 1600A 2000A

46069 46071 46073

46099 46101 46103

P = PLUG-IN

Moving part S3X 125 Iu (40 C) = 125 A


Thermomagnetic release
S3X 125 P MP S3X 125 P MP S3X 125 P MP S3X 125 P MP S3X 125 P MP R 32 R 50 R 80 R 100 R 125

Icu (415 V) =

200 kA
Im 500A 500A 800A 1000A 1250A

code 1SDA0 . . . . . R1 3 poles 4 poles


45317 45319 45321 45323 45325 45327 45329 45331 45333 45335

GSIS9151

S3X 200
Thermomagnetic release
S3X 200 P MP S3X 200 P MP S3X 200 P MP

Iu (40 C) =

200 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles 4 poles


46111 46113 46115 46117 46119 46121

R 125 R 160 R 200

1250A 1600A 2000A

7/54

ABB SACE

Order codes
SACE Isomax S3X current-limiting circuit-breaker

W = WITHDRAWABLE Moving part S3X 125 Iu (40 C) = 125 A


Thermomagnetic release
S3X 125 W MP S3X 125 W MP S3X 125 W MP S3X 125 W MP S3X 125 W MP R 32 R 50 R8 0 R 100 R 125

Icu (415 V) =

200 kA
Im 500A 500A 800A 1000A 1250A

code 1SDA0 . . . . . R1 3 poles 4 poles


45337 45339 45341 45343 45345 45347 45349 45351 45353 45355

GSIS9151

S3X 200
Thermomagnetic release
S3X 200 W MP S3X 200 W MP S3X 200 W MP

Iu (40 C) =

200 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles 4 poles


46123 46125 46127 46129 46131 46133

R 125 R 160 R 200

1250A 1600A 2000A

ABB SACE

7/55

Order codes
SACE Isomax S4X current-limiting circuit-breaker

F = FIXED

S4X 250
F = Front terminals S4X 250 F F
S4X 250 F F S4X 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

200 kA
PR212 P

Microprocessor-based release
In=100 In=160 In=250 I LI I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


46582 46584 46583 46585 46524 46525 46592 46594 46593 46595 46528 46529

code 1SDA0 . . . . . R1 3 poles 4 poles


46586 46588 46587 46589 46526 46527 46596 46598 46597 46599 46530 46531

LSI LSIG LSI LSIG LSI LSIG

GSIS9152

EF = Extended front terminals S4X 250 F EF


S4X 250 F EF S4X 250 F EF

In=100 In=160 In=250

I LI I LI I LI

46657 46660 46658 46661 46659 46662

46707 46710 46708 46711 46709 46712

LSI LSIG LSI LSIG LSI LSIG

46663 46668 46664 46669 46665 46670

46713 46716 46714 46717 46715 46718

FC Cu = Front terminals for copper cables S4X 250 F FC Cu In=100


S4X 250 F FC Cu S4X 250 F FC Cu In=160 In=250

I LI I LI I LI

46671 46674 46672 46675 46673 46676

46719 46722 46720 46723 46721 46724

LSI LSIG LSI LSIG LSI LSIG

46677 46680 46678 46681 46679 46682

46725 46728 46726 46729 46727 46730

FC CuAl = Front terminals for copper/aluminium cables S4X 250 F FC CuAl In=100
S4X 250 F FC CuAl S4X 250 F FC CuAl In=160 In=250

I LI I LI I LI

46830 46833 46831 46834 46832 46835

46842 46845 46843 46846 46844 46847

LSI LSIG LSI LSIG LSI LSIG

46836 46839 46837 46840 46838 46841

46848 46851 46849 46852 46850 46853

R = Threaded rear terminals S4X 250 F R


S4X 250 F R S4X 250 F R

In=100 In=160 In=250

I LI I LI I LI

46695 46698 46696 46699 46697 46700

46743 46746 46744 46747 46745 46748

LSI LSIG LSI LSIG LSI LSIG

46701 46704 46702 46705 46703 46706

46749 46752 46750 46753 46751 46754

RC = Rear terminals for cables S4X 250 F RC


S4X 250 F RC S4X 250 F RC

In=100 In=160 In=250

I LI I LI I LI

46683 46686 46684 46687 46685 46688

46731 46734 46732 46735 46733 46736

LSI LSIG LSI LSIG LSI LSIG

46689 46692 46690 46693 46691 46694

46737 46740 46738 46741 46739 46742

7/56

ABB SACE

Order codes
SACE Isomax S4X current-limiting circuit-breaker

P = PLUG-IN

Moving part S4X 250 Iu (40 C) = 250 A


Microprocessor-based release
S4X 250 P MP S4X 250 P MP S4X 250 P MP In=100 In=160 In=250 I LI I LI I LI PR211 P 46755 46758 46756 46759 46757 46760

Icu (415 V) =

200 kA
PR212 P LSI LSIG LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


46767 46770 46768 46771 46769 46772

code 1SDA0 . . . . . R1 3 poles 4 poles


46761 46764 46762 46765 46763 46766 46773 46776 46774 46777 46775 46778

W = WITHDRAWABLE Moving part S4X 250 Iu (40 C) = 250 A


Microprocessor-based release
S4X 250 W MP S4X 250 W MP S4X 250 W MP In=100 In=160 In=250 I LI I LI I LI PR211 P 46779 46782 46780 46783 46781 46784

GSIS9152

Icu (415 V) =

200 kA
PR212 P LSI LSIG LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


46791 46794 46792 46795 46793 46796

code 1SDA0 . . . . . R1 3 poles 4 poles


46785 46788 46786 46789 46787 46790 46797 46800 46798 46801 46799 46802

GSIS9152

ABB SACE

7/57

Order codes
SACE Isomax S6X current-limiting circuit-breaker

F = FIXED

S6X 400
F = Front terminals S6X 400 F F
S6X 400 F F

Iu (40 C) =

400 A

Icu (415 V) =

200 kA
PR212 P

Microprocessor-based release
In=320 In=400 I LI I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


47595 47596 46534 46535 47601 47602 46538 46539

code 1SDA0 . . . . . R1 3 poles 4 poles


47597 47598 46536 46537 47603 47604 46540 46541

LSI LSIG LSI LSIG

EF = Extended front terminals S6X 400 F EF


S6X 400 F EF
GSIS9153

In=320 In=400

I LI I LI

47661 47663 47660 47662

47693 47695 47692 47694

LSI LSIG LSI LSIG

47665 47667 47664 47666

47697 47699 47696 47698

FC CuAl = Front terminals for copper/aluminium cables S6X 400 F FC CuAl In=320
S6X 400 F FC CuAl In=400

I LI I LI

47669 47671 47668 47670

47701 47703 47700 47702

LSI LSIG LSI LSIG

47673 47675 47672 47674

47704 47707 47705 47706

R = Threaded rear terminals S6X 400 F R


S6X 400 F R

In=320 In=400

I LI I LI

47685 47687 47684 47686

47717 47719 47716 47718

LSI LSIG LSI LSIG

47689 47691 47688 47690

47721 47723 47720 47722

RC = Rear terminals for cables S6X 400 F RC


S6X 400 F RC

In=320 In=400

I LI I LI

47677 47679 47676 47678

47709 47711 47708 47710

LSI LSIG LSI LSIG

47681 47683 47680 47682

47713 47715 47712 47714

S6X 630
F = Front terminals S6X 630 F F EF = Extended front terminals S6X 630 F EF

Iu (40 C) =

630 A

Icu (415 V) =

200 kA
PR212 P

Microprocessor-based release
In=630 I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


46560 46561 46564 46565

code 1SDA0 . . . . . R1 3 poles 4 poles


46562 46563 46566 46567

LSI LSIG

In=630

I LI

47724 47725

47744 47745

LSI LSIG

47726 47727

47746 47747

FC CuAl = Front terminals for copper/aluminium cables S6X 630 F FC CuAl In=630 R = Threaded rear terminals S6X 630 F R RC = Rear terminals for cables S6X 630 F RC

I LI

47729 47730

47749 47750

LSI LSIG

47731 47732

47751 47752

In=630

I LI

47739 47740

47759 47760

LSI LSIG

47741 47742

47761 47762

In=630

I LI

47734 47735

47754 47755

LSI LSIG

47736 47737

47756 47757

7/58

ABB SACE

Order codes
SACE Isomax S6X current-limiting circuit-breaker

W = WITHDRAWABLE Moving part S6X 400 Iu (40 C) = 400 A


Microprocessor-based release
S6X 400 W MP S6X 400 W MP In=320 In=400 I LI I LI PR211 P 47633 47635 47632 47634

Icu (415 V) =

200 kA
PR212 P LSI LSIG LSI LSIG

code 1SDA0 . . . . . R1 3 poles 4 poles


47643 47645 47642 47644

code 1SDA0 . . . . . R1 3 poles 4 poles


47637 47641 47636 47640 47647 47649 47646 47648

S6X 630
GSIS9153

Iu (40 C) =

630 A
47650 47651

Icu (415 V) =

200 kA
PR212 P LSI LSIG

Microprocessor-based release
S6X 630 W MP In=630 I LI

PR211 P

code 1SDA0 . . . . . R1 3 poles 4 poles


47655 47656

code 1SDA0 . . . . . R1 3 poles 4 poles


47652 47653 47657 47658

ABB SACE

7/59

Order codes
SACE Isomax S2X 80 circuit-breaker for motor protection

F = FIXED

S2X 80
Magnetic only release

Iu (40 C) =

80 A

Icu (415 V) =

70 kA
Im

code 1SDA0 . . . . . R1 3 poles


50231 50232 50233 50234 50235 50236 50237 50238 50239 50240 50241 50242 50243 50244 50245 50246 50247 50248 50249 50250 50251 50252 50253 50254 50255 50256 50257 50258 50259 50260 50261 50262 50263 50264 50265 50266 50267 50268

FC Cu = Front terminals for copper cables S2X 80 F FC Cu R1 S2X 80 F FC Cu R 1.6 S2X 80 F FC Cu R2 S2X 80 F FC Cu R 2.5 S2X 80 F FC Cu R 3.2 S2X 80 F FC Cu R4 S2X 80 F FC Cu R5 S2X 80 F FC Cu R 6.5 S2X 80 F FC Cu R 8.5 S2X 80 F FC Cu R 11 S2X 80 F FC Cu R 12.5 S2X 80 F FC Cu R 16 S2X 80 F FC Cu R 20 S2X 80 F FC Cu R 25 S2X 80 F FC Cu R 32 S2X 80 F FC Cu R 42 S2X 80 F FC Cu R 52 S2X 80 F FC Cu R 63 S2X 80 F FC Cu R 80 R = Threaded rear terminals S2X 80 F R R1 S2X 80 F R R 1.6 S2X 80 F R R2 S2X 80 F R R 2.5 S2X 80 F R R 3.2 S2X 80 F R R4 S2X 80 F R R5 S2X 80 F R R 6.5 S2X 80 F R R 8.5 S2X 80 F R R 11 S2X 80 F R R 12.5 S2X 80 F R R 16 S2X 80 F R R 20 S2X 80 F R R 25 S2X 80 F R R 32 S2X 80 F R R 42 S2X 80 F R R 52 S2X 80 F R R 63 S2X 80 F R R 80

13A 21A 26A 32A 42A 52A 65A 84A 110A 145A 163A 210A 260A 325A 415A 545A 680A 820A 1040A 13A 21A 26A 32A 42A 52A 65A 84A 110A 145A 163A 210A 260A 325A 415A 545A 680A 820A 1040A

P = PLUG-IN

GSIS9154

Moving part S2X 80 Iu (40 C) = 80 A


Magnetic only release
S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP S2X 80 P MP R1 R 1.6 R2 R 2.5 R 3.2 R4 R5 R 6.5 R 8.5 R 11 R 12.5 R 16 R 20 R 25 R 32 R 42 R 52 R 63 R 80
GSIS9154

Icu (415 V) =

70 kA
Im 13A 21A 26A 32A 41A 52A 65A 84A 110A 145A 163A 210A 260A 325A 415A 545A 680A 820A 1040A

code 1SDA0 . . . . . R1 3 poles


50269 50270 50271 50272 50273 50274 50275 50276 50277 50278 50279 50280 50281 50282 50283 50284 50285 50286 50287

7/60

ABB SACE

Order codes
SACE Isomax S3 circuit-breaker for motor protection

F = FIXED

S3N 160
Magnetic only release
F = Front terminals S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F S3N 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

35 kA
Im

code 1SDA0 . . . . . R1 3 poles


47782 47783 47784 47785 47786 47787 47788 47789

R3 R5 R 10 R 25 R 50 R 100 R 125 R 160

12 ... 36A 20 ... 60A 40 ... 120A 100 ... 300A 200 ... 600A 400 ... 1200A 500 ... 1500A 640 ... 1600A

PSIS9607

S3H 160
Magnetic only release
F = Front terminals S3H 160 F F S3H 160 F F S3H 160 F F S3H 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

65 kA
Im

code 1SDA0 . . . . . R1 3 poles


45185 45186 45187 45188

R 50 R 100 R 125 R 160

200 ... 600A 400 ... 1200A 500 ... 1500A 640 ... 1600A

S3L 160
Magnetic only release
F = Front terminals S3L 160 F F S3L 160 F F S3L 160 F F S3L 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

85 kA
Im

code 1SDA0 . . . . . R1 3 poles


50544 50545 50546 50547

R 50 R 100 R 125 R 160

200 ... 600A 400 ... 1200A 500 ... 1500A 640 ... 1600A

S3N 250
Magnetic only release
F = Front terminals S3N 250 F F S3N 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

35 kA
Im

code 1SDA0 . . . . . R1 3 poles


48651 48654

R 160 R 200

640 ... 1920A 800 ... 2400A

S3H 250
Magnetic only release
F = Front terminals S3H 250 F F S3H 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

65 kA
Im

code 1SDA0 . . . . . R1 3 poles


48657 48658

R 160 R 200

640 ... 1920A 800 ... 2400A

S3L 250
Magnetic only release
F = Front terminals S3L 250 F F S3L 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

85 kA
Im

code 1SDA0 . . . . . R1 3 poles


50548 50549

R 160 R 200

640 ... 1920A 800 ... 2400A

Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80.

ABB SACE

7/61

Order codes
SACE Isomax S4 circuit-breaker for motor protection

F = FIXED

S4N 160
F = Front terminals S4N 160 F F S4N 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

35 kA
PR212 MP

Microprocessor-based release
In = 100A In = 160A

code 1SDA0 . . . . . R1 3 poles


50139 50140

LRIU LRIU

PSIS9610

S4H 160
F = Front terminals S4H 160 F F S4H 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

65 kA
PR212 MP

Microprocessor-based release
In = 100A In = 160A

code 1SDA0 . . . . . R1 3 poles


45049 45050

LRIU LRIU

S4L 160
F = Front terminals S4L 160 F F S4L 160 F F

Iu (40 C) =

160 A

Icu (415 V) =

100 kA
PR212 MP

Microprocessor-based release
In = 100A In = 160A

code 1SDA0 . . . . . R1 3 poles


50550 50551

LRIU LRIU

S4N 250
F = Front terminals S4N 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

35 kA
PR212 MP

Microprocessor-based release
In = 200A

code 1SDA0 . . . . . R1 3 poles


50141

LRIU

S4H 250
F = Front terminals S4H 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

65 kA
PR212 MP

Microprocessor-based release
In = 200A

code 1SDA0 . . . . . R1 3 poles


48662

LRIU

S4L 250
F = Front terminals S4L 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

100 kA
PR212 MP

Microprocessor-based release
In = 200A

code 1SDA0 . . . . . R1 3 poles


50552

LRIU

7
Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80.

7/62

ABB SACE

Order codes
SACE Isomax S5-S6-S7 circuit-breakers for motor protection

F = FIXED

S5N 400
F = Front terminals S5N 400 F F

Iu (40 C) =

400 A

Icu (415 V) =

35 kA
PR212 MP

Microprocessor-based release
In = 320A

code 1SDA0 . . . . . R1 3 poles


50142

LRIU

S5H 400
PSIS9613

Iu (40 C) =

400 A

Icu (415 V) =

65 kA
PR212 MP

Microprocessor-based release
F = Front terminals S5H 400 F F
In = 320A

code 1SDA0 . . . . . R1 3 poles


45051

LRIU

S5L 400
F = Front terminals S5L 400 F F

Iu (40 C) =

400 A

Icu (415 V) =

100 kA
PR212 MP

Microprocessor-based release
In = 320A

code 1SDA0 . . . . . R1 3 poles


50553

LRIU

S6N 800
F = Front terminals S6N 800 F F

Iu (40 C) =

800 A

Icu (415 V) =

35 kA
PR212 MP

Microprocessor-based release
In = 630A

code 1SDA0 . . . . . R1 3 poles


50143

LRIU

S6H 800
PSIS9616

Iu (40 C) =

800 A

Icu (415 V) =

65 kA
PR212 MP

Microprocessor-based release
F = Front terminals S6H 800 F F
In = 630A

code 1SDA0 . . . . . R1 3 poles


45052

LRIU

S6L 800
F = Front terminals S6L 800 F F

Iu (40 C) =

800 A

Icu (415 V) =

100 kA
PR212 MP

Microprocessor-based release
In = 630A

code 1SDA0 . . . . . R1 3 poles


50554

LRIU

S7S 1250
Microprocessor-based release
F = Front terminals S7S 1250 F F

Iu (40 C) =

1250 A

Icu (415 V) =

50 kA
PR212 MP

code 1SDA0 . . . . . R1 3 poles


50144

In = 1000A

LRIU

S7H 1250
Microprocessor-based release
F = Front terminals S7H 1250 F F
PSIS9620

Iu (40 C) =

1250 A

Icu (415 V) =

65 kA
PR212 MP

code 1SDA0 . . . . . R1 3 poles


45053

In = 1000A

LRIU

Note
Withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80.

ABB SACE

7/63

Order codes
SACE Isomax S3X-S4X-S6X current-limiting circuit-breakers for motor protection

F = FIXED

S3X 125
Magnetic only release
F = Front terminals S3X 125 F F S3X 125 F F S3X 125 F F S3X 125 F F
GSIS9151

Iu (40 C) =

125 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles


45387 45388 45389 45390

R 25 R 50 R 100 R 125

100 ... 300A 200 ... 600A 400 ... 1200A 500 ... 1500A

S3X 200
Magnetic only release
F = Front terminals S3X 200 F F S3X 200 F F S3X 200 F F

Iu (40 C) =

200 A

Icu (415 V) =

200 kA
Im

code 1SDA0 . . . . . R1 3 poles


46135 48659 48660

R 125 R 160 R 200

500 ... 1500A 640 ... 1920A 800 ... 2400A

S4X 250
F = Front terminals S4X 250 F F S4X 250 F F S4X 250 F F

Iu (40 C) =

250 A

Icu (415 V) =

200 kA
PR212 MP

Microprocessor-based release
In = 100A In = 160A In = 200A

code 1SDA0 . . . . . R1 3 poles


46590 46591 48661

LRIU LRIU LRIU

S6X 400
F = Front terminals S6X 400 F F

Iu (40 C) =

400 A

Icu (415 V) =

200 kA
PR212 MP

Microprocessor-based release
GSIS9152

code 1SDA0 . . . . . R1 3 poles


47780

In = 320A

LRIU

S6X 630
F = Front terminals S6X 630 F F S6X 630 F F

Iu (40 C) =

630 A

Icu (415 V) =

200 kA
PR212 MP

Microprocessor-based release
In = 400A In = 630A

code 1SDA0 . . . . . R1 3 poles


47781 48663

LRIU LRIU

7
Note
Plug-in and withdrawable version are taken from the corresponding fixed version by means of the conversion kits indicated on page 80.

7/64

GSIS9153

ABB SACE

Order codes
SACE Isomax S circuit-breakers for applications up to 1000V

F = FIXED

S3L 160
Thermomagnetic release
F = Front terminals S3L 160 F F S3L 160 F F S3L 160 F F S3L 160 F F S3L 160 F F S3L 160 F F

Iu (40 C) =

160 A

Icu (1000 V) =

6 kA
AC ~

code 1SDA0 . . . . . R1 3 poles


50436 50437 50438 50439 50441 50442

R 32 R 50 R 80 R 100 R 125 R 160

Im Im Im Im Im Im

500A 500A 800A 1000A 1250A 1600A

PSIS9607

S3L 160
Thermomagnetic release
F = Front terminals S3L 160 F F (N100%) S3L 160 F F (N100%) S3L 160 F F (N100%) S3L 160 F F (N100%) S3L 160 F F (N100%) S3L 160 F F (N100%)

Iu (40 C) =

160 A

Icu (1000 V) =

40 kA
DC

code 1SDA0 . . . . . R1 4 poles


50443 50444 50445 50446 50447 50448

R 32 R 50 R 80 R 100 R 125 R 160

Im Im Im Im Im Im

500A 500A 800A 1000A 1250A 1600A

S3L 250
Thermomagnetic release
F = Front terminals S3L 250 F F (N100%) S3L 250 F F (N100%)

Iu (40 C) =

250 A

Icu (1000 V) =

40 kA
DC

code 1SDA0 . . . . . R1 4 poles


50449 50450

R 200 R 250

Im 2000A Im 2500A

S3X 125
Thermomagnetic release
F = Front terminals S3X 125 F F S3X 160 F F S3X 160 F F S3X 160 F F S3X 160 F F

Iu (40 C) =

125 A

Icu (1000 V)=

30 kA
AC ~

code 1SDA0 . . . . . R1 3 poles


50451 50452 50453 50454 50455

R 32 R 50 R 80 R 100 R 125

Im Im Im Im Im

500A 500A 800A 1000A 1250A

S4L 160
F = Front terminals S4L 160 F F

Iu (40 C) =

160 A

Icu (1000 V) =

8 kA
PR212 P LSI LSIG

Microprocessor-based release
In 100 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles


50547

code 1SDA0 . . . . . R1 3 poles


50458 50459

PSIS9610

S4L 250
F = Front terminals S4L 250 F F

Iu (40 C) =

250 A

Icu (1000 V) =

8 kA
PR212 P LSI LSIG

Microprocessor-based release
In 250 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles


50460

code 1SDA0 . . . . . R1 3 poles


50461 50462

S4X 250
F = Front terminals S4X 250 F F

Iu (40 C) =

250 A

Icu (1000 V) =

30 kA
PR212 P LSI LSIG

7
code 1SDA0 . . . . . R1 3 poles
50464 50465

Microprocessor-based release
In 250 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles


50463

ABB SACE

7/65

Order codes
SACE Isomax S circuit-breakers for applications up to 1000V

F = FIXED

S5L 400
Thermomagnetic release
F = Front terminals S5L 400 F F (N100%)

Iu (40 C) =

400 A

Icu (1000 V) =

40 kA
DC

code 1SDA0 . . . . . R1 4 poles


50466

R 400

Im 4000A

S6L 630
PSIS9613

Iu (40 C) =

630 A

Icu (1000 V) =

40 kA
DC

Thermomagnetic release
F = Front terminals S6L 630 F F (N100%)
R 630

code 1SDA0 . . . . . R1 4 poles


50467

Im 6300A

S6L 800
Thermomagnetic release
F = Front terminals S6L 800 F F (N100%)

Iu (40 C) =

800 A

Icu (1000 V) =

50 kA
DC

code 1SDA0 . . . . . R1 4 poles


50468

R 800

Im 8000A

S5L 400
PSIS9616

Iu (40 C) =

400 A
50582

Icu (1000 V) =

8 kA
PR212 P LSI LSIG

Microprocessor-based release
S5L 400 F F In 400 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles

code 1SDA0 . . . . . R1 3 poles


50583 50584

S6L 630
S6L 630 F F

Iu (40 C) =

630 A
50469

Icu (1000 V) =

12 kA
PR212 P LSI LSIG

Microprocessor-based release
In 630 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles

code 1SDA0 . . . . . R1 3 poles


50470 50471

S6L 800
F = Front terminals S6L 800 F F
GSIS9153

Iu (40 C) =

800 A

Icu (1000 V) =

12 kA
PR212 P LSI LSIG

Microprocessor-based release
In 800 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles


50534

code 1SDA0 . . . . . R1 3 poles


50535 50536

S6X 630
F = Front terminals S4X 630 F F

Iu (40 C) =

630 A

Icu (1000 V) =

30 kA
PR212 P

Microprocessor-based release
In 630 A LI

PR211 P

code 1SDA0 . . . . . R1 3 poles


50472

code 1SDA0 . . . . . R1 3 poles


50473 50474

LSI LSIG

7
PSIS9155

S3D/S6D/S7D
Switch-disconnector
F = Front terminals S3D 320 F F S6D 800 F F S7D 1600 F F

Iu (40 C) =

320/800/1600 A
code 1SDA0 . . . . . R1 3 poles
50446 50475 50479

7/66

ABB SACE

Order codes
SACE Isomax S2D switch-disconnectors

F = FIXED

S2D 125
Switch-disconnector

Iu (40 C) =

125 A

Icw (1s) =

2.2 kA

Icm (415 V) =

3.1 kA

code 1SDA0 . . . . . R1 3 poles 4 poles

FC Cu = Front terminals for copper cables S2D 125 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S2D 125 F FC CuAl* S2D 125 F FC CuAl** EF = Extended front terminals S2D 125 F EF R = Threaded rear terminals S2D 125 F R

PSIS9604

45057

45063

45058 45059 45056 45060

45064 45065 45062 45066

S2D 160
Switch-disconnector

Iu (40 C) =

160 A

Icw (1s) =

2.2 kA

Icm (415 V) =

3.1 kA

code 1SDA0 . . . . . R1 3 poles 4 poles

FC Cu = Front terminals for copper cables S2D 160 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S2D 160 F FC CuAl* S2D 160 F FC CuAl** EF = Extended front terminals S2D 160 F EF R = Threaded rear terminals S2D 160 F R

20632

45071

45068 20633 20630 20634

45072 45074 45070 45073

P = PLUG-IN

Moving part S2D 125 Iu (40 C) = 125 A


Switch-disconnector
PSIS9604

Icw (1s) =

2.2 kA

Icm (415 V) =

3.1 kA
45067

code 1SDA0 . . . . . R1 3 poles 4 poles


45061

S2D 125 P MP

S2D 160
Switch-disconnector
S2D 160 P MP

Iu (40 C) =

160 A

Icw (1s) =

2.2 kA

Icm (415 V) =

3.1 kA
45075

code 1SDA0 . . . . . R1 3 poles 4 poles


45069

* Cable section = 1 x 2.5...50 mm2 ** Cable section = 1 x 35...95 mm2

ABB SACE

7/67

Order codes
SACE Isomax S3D switch-disconnectors

F = FIXED

S3D 100
Switch-disconnector

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20906 20329 20907 20354

F = Front terminals S3D 100 F F EF = Extended front terminals S3D 100 F EF FC Cu = Front terminals for copper cables S3D 100 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S3D 100 F FC CuAl R = Threaded rear terminals S3D 100 F R RC = Rear terminals for cables S3D 100 F RC

PSIS9607

20335

20360

20341 20353 20347

20366 20378 20372

S3D 160
Switch-disconnector

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20908 20383 20909 20408

F = Front terminals S3D 160 F F EF = Extended front terminals S3D 160 F EF FC Cu = Front terminals for copper cables S3D 160 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S3D 160 F FC CuAl R = Threaded rear terminals S3D 160 F R RC = Rear terminals for cables S3D 160 F RC

20389

20414

20395 20407 20401

20420 20432 20426

P = PLUG-IN

S3D 100
Switch-disconnector
S3D 100 P MP

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20381

code 1SDA0 . . . . . R1 3 poles 4 poles


20379

PSIS9607

S3D 160
Switch-disconnector
S3D 160 P MP

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20435

code 1SDA0 . . . . . R1 3 poles 4 poles


20433

W = WITHDRAWABLE S3D 100


Switch-disconnector
S3D 100 W MP

Iu (40 C) =

100 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20382

code 1SDA0 . . . . . R1 3 poles 4 poles


20380

PSIS9607

S3D 160
Switch-disconnector
S3D 160 W MP

Iu (40 C) =

160 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20436

code 1SDA0 . . . . . R1 3 poles 4 poles


20434

7/68

ABB SACE

Order codes
SACE Isomax S3D switch-disconnectors

F = FIXED

S3D 250
Switch-disconnector

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20910 20437 20911 20462

F = Front terminals S3D 250 F F EF = Extended front terminals S3D 250 F EF FC Cu = Front terminals for copper cables S3D 250 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S3D 250 F FC CuAl R = Threaded rear terminals S3D 250 F R RC = Rear terminals for cables S3D 250 F RC

PSIS9607

20443

20468

20449 20461 20455

20474 20486 20480

S3D 320
Switch-disconnector

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20912 20491 20913 20516

F = Front terminals S3D 320 F F EF = Extended front terminals S3D 320 F EF FC Cu = Front terminals for copper cables S3D 320 F FC Cu FC CuAl = Front terminals for copper/aluminium cables S3D 320 F FC CuAl R = Threaded rear terminals S3D 320 F R RC = Rear terminals for cables S3D 320 F RC

20497

20522

20503 20515 20509

20528 20540 20534

P = PLUG-IN

S3D 250
Switch-disconnector
S3D 250 P MP

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20489

code 1SDA0 . . . . . R1 3 poles 4 poles


20487

PSIS9607

S3D 320
Switch-disconnector
S3D 320 P MP

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20543

code 1SDA0 . . . . . R1 3 poles 4 poles


20541

W = WITHDRAWABLE S3D 250


Switch-disconnector
S3D 250 W MP

Iu (40 C) =

250 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20490

code 1SDA0 . . . . . R1 3 poles 4 poles


20488

PSIS9607

S3D 320
Switch-disconnector
S3D 320 W MP

Iu (40 C) =

320 A

Icw (1s) =

6.5 kA

Icm (415 V) =

10 kA
20544

code 1SDA0 . . . . . R1 3 poles 4 poles


20542

ABB SACE

7/69

Order codes
SACE Isomax S6D switch-disconnectors

F = FIXED

S6D 400
Switch-disconnector

Iu (40 C) =

400 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20545 20552 20581 20588

F = Front terminals S6D 400 F F EF = Extended front terminals S6D 400 F EF FC CuAl = Front terminals for copper/aluminium cables S6D 400 F FC CuAl R = Threaded rear terminals S6D 400 F R RC = Rear terminals for cables S6D 400 F RC

20566 20573 23326

20601 20608 23327

GSIS9156

S6D 630
Switch-disconnector

Iu (40 C) =

630 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20674 20680 20699 20705

F = Front terminals S6D 630 F F EF = Extended front terminals S6D 630 F EF FC CuAl = Front terminals for copper/aluminium cables S6D 630 F FC CuAl R = Threaded rear terminals S6D 630 F R RC = Rear terminals for cables S6D 630 F RC

20686 20698 20692

20711 20723 20717

S6D 800
Switch-disconnector

Iu (40 C) =

800 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20724 20730 20749 20755

F = Front terminals S6D 800 F F EF = Extended front terminals S6D 800 F EF FC CuAl = Front terminals for copper/aluminium cables S6D 800 F FC CuAl R = Threaded rear terminals S6D 800 F R RC = Rear terminals for cables S6D 800 F RC

20736 20748 20742

20761 20773 20767

W = WITHDRAWABLE S6D 400


Switch-disconnector
S6D 400 W MP

Iu (40 C) =

400 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA
20619

code 1SDA0 . . . . . R1 3 poles 4 poles


20617

S6D 630
Switch-disconnector
GSIS9156

Iu (40 C) =

630 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA
20919

code 1SDA0 . . . . . R1 3 poles 4 poles


20918

S6D 630 W MP

S6D 800
Switch-disconnector
S6D 800 W MP

Iu (40 C) =

800 A

Icw (1s) =

15 kA

Icm (415 V) =

30 kA
20921

code 1SDA0 . . . . . R1 3 poles 4 poles


20920

7/70

ABB SACE

Order codes
SACE Isomax S7D switch-disconnectors

F = FIXED

S7D 1000

Iu (40 C) =

1000 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA

Switch-disconnector
F = Front terminals S7D 1000 F F EF = Extended front terminals S7D 1000 F EF FC CuAl = Front terminals for copper/aluminium cables S7D 1000 F FC CuAl VR = Vertical flat-bar rear terminals S7D 1000 F VR HR = Horizontal flat-bar rear terminals S7D 1000 F HR
PSIS9625

code 1SDA0 . . . . . R1 3 poles 4 poles


20774 20780 20799 20805

20786 20798 20792

20811 20823 20817

S7D 1250
Switch-disconnector

Iu (40 C) =

1250 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20824 20830 20849 20855

F = Front terminals S7D 1250 F F EF = Extended front terminals S7D 1250 F EF FC CuAl = Front terminals for copper/aluminium cables S7D 1250 F FC CuAl VR = Vertical flat-bar rear terminals S7D 1250 F VR HR = Horizontal flat-bar rear terminals S7D 1250 F HR

20836 20848 20842

20861 20873 20867

S7D 1600
Switch-disconnector

Iu (40 C) =

1600 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


20874 20879 20889 20884 20900 20890 20895

F = Front terminals S7D 1600 F F EF = Extended front terminals S7D 1600 F EF VR = Vertical flat-bar rear terminals S7D 1600 F VR HR = Horizontal flat-bar rear terminals S7D 1600 F HR

W = WITHDRAWABLE S7D 1000


Switch-disconnector
S7D 1000 W MP

Iu (40 C) =

1000 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA
20923

code 1SDA0 . . . . . R1 3 poles 4 poles


20922

S7D 1250
Switch-disconnector
S7D 630 W MP

Iu (40 C) =

1250 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA
20925

code 1SDA0 . . . . . R1 3 poles 4 poles


20924

S7D 1600
PSIS9625

Iu (40 C) =

1600 A

Icw (1s) =

25 kA

Icm (415 V) =

52.5 kA
20927

Switch-disconnector
S7D 1600 W MP

code 1SDA0 . . . . . R1 3 poles 4 poles


20926

ABB SACE

7/71

Order codes
SACE Isomax S8D switch-disconnectors

F = FIXED

S8D 2000
Switch-disconnector

Iu (40 C) =

2000 A

Icw (1s) =

40 kA

Icm (415 V) =

85 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


45158 45160 45159 45161

F = Front terminals S8D 2000 F F VR = Vertical flat-bar rear terminals S8D 2000 F VR

S8D 2500
Switch-disconnector
GSIS9149

Iu (40 C) =

2500 A

Icw (1s) =

40 kA

Icm (415 V) =

85 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


45162 45164 45163 45165

F = Front terminals S8D 2500 F F VR = Vertical flat-bar rear terminals S8D 2500 F VR

S8D 3200
Switch-disconnector

Iu (40 C) =

3200 A

Icw (1s) =

40 kA

Icm (415 V) =

85 kA

code 1SDA0 . . . . . R1 3 poles 4 poles


45167 45166

VR = Vertical flat-bar rear terminals S8D 3200 F VR

7/72

ABB SACE

Order codes
SACE Isomax S accessories

Duty releases
Shunt opening releases
Type
24...30 V AC 48 V AC - 60 V DC 110...130 V AC 220...250 V AC 380...400 V AC 12 V DC 24 V DC 48 V DC 110 V DC 220 V DC 250 V DC 12 V DC 24 V AC / DC 48 V AC / DC 60 V AC / DC 60 V AC / 60 ... 72 V DC 110...120 V AC - 110...125 V DC 220...240 V AC - 220...250 V DC 380...400 V AC 480 V AC 24 V DC 30 V DC - 24 V AC 48 V AC / DC 60 V DC 100...127 V DC / AC 127...150 V AC 160 V DC / 150...180 V AC 200...250 V DC / 200...255 V AC 380...500 V AC

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


13311 13306 13312 13313 13314 50581 13304 13305 13307 13309 13310 23403 13781 13782 23405 13783 13785 13786 37512

S6-S7

S8

GSIS9001

23404 14136 14137 23406 14138 14140 14141 37514 50685 46602 46600 46603 47564 46605 47565 46607 46608

Shunt closing releases


Type
24 V AC 50 Hz 30 V AC 50 Hz 48 V AC 50 Hz 60 V AC 50 Hz 127 ...130 V AC 50 Hz 220 V AC 50 Hz 500 V AC 50 Hz 24 V AC 60 Hz 120 V AC 60 Hz 208 ...220 V AC 60 Hz 240 V AC 60 Hz 380 V AC 60 Hz 100 V AC 50 Hz - 110 ...115 V AC 60 Hz 110 ...115 V AC 50 Hz - 125 ...127 V AC 60 Hz 230 ...240 V AC 50 Hz - 277 V AC 60 Hz 380 ...400 V AC 50 Hz - 440 V AC 60 Hz 415 ...440 V AC 50 Hz - 480 V AC 60 Hz 24 V DC 30 V DC 48 V DC 60 V DC 110...125 V DC 220...250 V DC 310 V DC

code 1SDA0 . . . . . R1 S8
46636 46643 46637 46638 46646 46633 46644 46649 46647 46641 46648 46645 46639 46634 46640 46635 46642 46650 46655 46651 46656 46652 46653 46654

GSIS9003

7
7/73

ABB SACE

Order codes
SACE Isomax S accessories
Undervoltage releases
Type
24 V AC 50 Hz 30 V AC 50 Hz 48 V AC 50 Hz 60 V AC 50 Hz 110 V AC 50 Hz 127 ...130 V AC 50 Hz 220 V AC 50 Hz 500 V AC 50 Hz 100 V AC 50 Hz - 110 ...115 V AC 60 Hz 110 ...115 V AC 50 Hz - 125 ...127 V AC 60 Hz 230 ...240 V AC 50 Hz - 277 V AC 60 Hz 380 V AC 50 Hz - 380 ...440 V AC 60 Hz 380 ...400 V AC 50 Hz - 440 V AC 60 Hz 415 ...440 V AC 50 Hz - 480 V AC 60 Hz 24 V AC 48 V AC 60 V AC 110 V AC 60 Hz 110 ...127 V AC 120 V AC 60 Hz 208 ...220 V AC 60 Hz 220 ...250 V AC 240 V AC 60 Hz 380 V AC 60 Hz 380 ...440 V AC 480 V AC 24 V DC 30 V DC 48 V DC 60 V DC 110 V DC 110...125 V DC 220 V DC 220...250 V DC

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


23401 23402 13319 13320

S6-S7

S8
46613 46620 46614 46615 46623 46609 46621 46616 46611 46617 46612 46619

GSIS9002

13321

13842 13843 23346 45046 13844

14188 14189 23347 14190 46624 46618

13846

14192 46625 46622

13315 13316 45045 13317 13318

13847 37513 13833 13835 13836 13838 13839

14193 37515 14179 14181 14182 14184 14185

46626 46631 46627 46632 46628 46629

Undervoltage releases + time-lag device


Type
110 - 220 V AC 24 V AC/DC 30 V AC/DC 48 V AC/DC 60 V AC/DC 110/125 V AC/DC 220/250 V AC/DC

code 1SDA0 . . . . . R1 S3-S4-S5


13840

S6-S7
14186

S8
50737 50738 50739 50740 50741 50742

GSIS9042

Connectors for duty releases


Type
for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for plug-in or withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=2m flying 9-pole socket-plug - L=0,6m extension for testing auxiliary circuits with the circuit-breaker racked out

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5-S6 S7


13865 37523 14209 44752 13866 14210 48949 13333 25552 25552

7
7/74

GSIS9013

ABB SACE

Order codes
SACE Isomax S accessories

Electrical signalling
Auxiliary contacts
Type
2 open/closed change-over contacts 1 open/closed change-over contacts and 1 release tripped signal 1 NO, 1 NC and 1 release not tripped signal 1 NO, 1 NC and 1 release tripped signal 3 open/closed change-over contacts
GSIS9004

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


13328 13327 13856 13575

S6-S7
23366 23332 25773 48956

S8

47563

Auxiliary contacts for digital signals


Type
2 open/closed change-over contacts 1 open/closed change-over contacts and 1 release tripped signal 1 NO, 1 NC and 1 release not tripped signal

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


25544 25545

S6-S7
25774 25775 25776

S8

Early making contacts and connectors


Type
early making contact and connector for undervoltage release

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5-S6 S7


25551 48106

S8

Connectors for auxiliary contacts


Type
for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for plug-in or withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=2m flying 9-pole socket-plug - L=0,6m extension for testing auxiliary circuits with the circuit-breaker racked out

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5-S6 S7


13863 37522 14207 44751 13864 14208 48947 13329 25553 25553

S8

GSIS9015

Signally contacts
Type
contact for signalling closing springs charged

code 1SDA0 . . . . . R1 S8
47562

7
ABB SACE 7/75

Order codes
SACE Isomax S accessories

Motor operating mechanisms


Solenoid operator
Type
at the side of the circuit-breaker 48 V DC 60 V DC - 110 V AC 110 V DC - 220...230 V AC 220 V DC on the front of the circuit-breaker 48 V DC 60 V DC - 110 V AC 110 V DC - 220...230 V AC 220 V DC
GSIS9023

code 1SDA0 . . . . . R1 S1-S2


48025 48026 48027 48028 48015 48016 48017 48018

GSIS9022

Direct action motor operating mechanism


Type
24 V DC 48...60 V DC 100...127 V AC - 100...125 V DC 220...240 V AC - 220...250 V DC 380 V AC 440 V AC
GSIS9021

code 1SDA0 . . . . . R1 S3-S4-S5


13873 13874 13875 13876 13877 14545

Stored energy motor operating mechanism


Type
24 V DC 48 V DC 60 V DC 110 V AC / DC 120...127 V AC / DC 220...250 V AC / DC 380 V AC

code 1SDA0 . . . . . R1 S6
14029 14030 23348 23349 14031 14032 14033

S7
14214 14215 23350 23351 14216 14217 14218

GSIS9020

Geared motor for automatic charging of closing springs


Type
24/30 V DC 48/60 V DC 100...130 V DC 220...250 V DC

code 1SDA0 . . . . . R1 S8
47558 47559 47560 47561

GSIS9007

Connectors for motor operating mechanism and auxiliary contacts


Type
for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for fixed circuit-breakers - L=1m for fixed circuit-breakers - L=2m for plug-in or withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=1m for withdrawable circuit-breakers - L=2m flying 9-pole socket-plug - L=0,6m extension for testing auxiliary circuits with the circuit-breaker racked out

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5-S6 S7


13857 37524 14203 44850 13858 14204 48950 13329 25554 25554

7
7/76

GSIS9014

ABB SACE

Order codes
SACE Isomax S accessories

Operating mechanism and locks


Direct-mounted rotary handle operating mechanism
Type
GSIS9025

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


13867 13868 13870

S6
14026 14027 46568

S7
14211 14212 46570

for fixed/plug-in circuit breakers for withdrawable circuit breakers emergency for fixed or plug-in circuit-breakers

Rotary handle operating mechanism with transmission rod


Type
GSIS9024

code 1SDA0 . . . . . R1 S1-S2 S3-S4-S5


13326 13869 50714

S6

S7

compartment door, fixed depth for fixed or plug-in circuit-breakers (L= 119,5 mm) compartment door, adjustable depth (Lmax=300 mm) for fixed or plug-in compartment door, adjustable depth (Lmax=300 mm) for withdrawable compartment door, adjustable depth (Lmax=500 mm) for fixed compartment door, adjustable depth (Lmax=500 mm) for withdrawable compartment door, emergency, fixed depth for fixed or plug-in circuit-breakers (Lmax= 119.5 mm) compartment door, emergency, adjustable depth for fixed or plug-in circuit-breakers (Lmax= 300 mm) compartment door, emergency, adjustable depth for fixed circuit-breakers (Lmax= 500 mm) remote transmission rod with adj. depth (Lmax= 180 mm) remote transmission rod with adj. depth (Lmax= 500 mm)

14028 50715 45054 13871 46569 25436 45055 25427

14213 50716

46572

Front flange
Type
front flange for operating lever mechanism for fixed or plug-in front flange for operating lever mechanism for withdrawable flange for compartment door

code 1SDA0 . . . . . R1 S3...S5 S6


13889 13890 14035 14036

S7
14227 14228

S8

GSIS9026

45023

Key lock for open position


Type
for motor operating mechanism - a different key for each cb. for motor operating mechanism - the same key for sets of cbs for motor operating mechanism against manual operation the same key for each circuit-breaker for front flange / rotary handle a different key for each circuit-breaker for front flange / rotary handle the same key for sets of circuit-breakers for front flange key lock type RONIS

code 1SDA0 . . . . . R1 S3...S5 S6-S7


13883 13884 13885 13886 36245 13881 13882 43514 13881 13882

S8

GSIS9008

45024 43514

Locks
GSIS9010

Type
compartment door lock for front flange for locks /crank handle operating mechanism padlock device for operating lever padlock device on the front of the circuit-breaker tamper-proof lock for thermal release tamper-proof lock for thermal release

Size

code 1SDA0 . . . . . R1
13880 13332 45025 36196 25548

ABB SACE

GSIS9035

S3-S4-S5-S6-S7 S1-S2 S8 S2 S3

7
7/77

Order codes
SACE Isomax S accessories
Mechanical interlock across two circuit-breakers
Type
S3 S3X S4 S4X S5400/630 S6 S7 S3-S4-S5-S6-S7 (circuit-breaker/fixed part for interlocking)

code 1SDA0 . . . . . R1 horizontal


23330 50524 13690 50525 43453 14024 14205 50093

vertical
23331 13691 43454 14025 14206 50093

PSIS9640

Connection terminals
Type
EF=Extended front terminals S2 S3-S4 S5 400 S6 630 S6 800 S7 ES=Spreaded extended front terminals S3-S4 S5 S6 (1/2 upper kit) S6 (1/2 lower kit) S6 S7 (1/2 upper kit) S7 (1/2 lowerkit) S7 FC Cu=Front terminals for copper cables S3-S4 S5 400 S5 630 FC CuAl=Front terminals for copper/aluminium cables S2 (2,5-50 mm2) (*) S2 (35-95 mm2) (*) S3D 100 S3 160 - S4 160 (1x95 mm2) S3 250 - S4 250 (1x150 mm2) S5 400 (2x120 mm2) S5 400 (1x240 mm2) S6 630 (2x240 mm2) S6 800 (3x185 mm2) S7 1250 (4x240 mm2) R=Threaded rear terminals S1 S2 S3-S4 S5 400 S5 630 S6 R Res.Cur.=Threaded rear terminals for reasidual current-release mounted below S3 HR/VR=Horizontal or vertical flat-bar rear terminals S7 S8 RC = Rear terminals for copper/aluminium cables S3-S4 (1x120 mm2) S5 400 (1x240 mm2) S6 630 (2x150 mm2) S6 800 (3x240 mm2) (*) Order also the relevant EF extended front terminals

code 1SDA0 . . . . . R1 3 pieces 4 pieces 6 pieces


25797 13596 13706 13920 13954 14079 46515 47549 50688 50690 13598 13708 38767 36194 25801 13600 13602 20293 23295 13710 13922 13956 14081 13268 13294 13606 13714 38968 13960

8 pieces
25798 13597 13707 13921 13955 14080 46516 47550 50689 50691 13599 13709 38768 36195 25802 13601 13603 20294 23296 13711 13923 13957 14082 13269 13295 13607 13715 38775 13961

23353 23367 23379 23383 23399 46517 47551 50692 50704 50694 50705 23354 23368 38769 50526 50527 23355 23356 23357 25766 23370 23380 23384 23387

23359 23373 23389 23393 23396 46518 47552 50693 50695 23360 23374 38770 50528 50530 23361 23362 23363 25765 23376 23390 23394 23397

PSIS9642 PSIS9643

PSIS9641

PSIS9663

23352 23372 38776 23382

23365 23378 38777 23392

25543 23400 23398 14083 46578 13604 13712 13924 13958 14084 46579 13605 13713 13925 13959

7
7/78

23358 23371 23381 23385

23364 23377 23391 23395

ABB SACE

Order codes
SACE Isomax S accessories
Insulating terminal covers
Type
PSIS9644

code 1SDA0 . . . . . R1 3 poles 4 poles


13291 13341 13696 13898 14041 13293 13343 13694 13896 14039 23325

high for fixed S1 13290 S2 13340 S3-S4 13695 S5 13897 S6 14040 low for fixed and for moving part of plug-in or withdrawable circuit-breakers S1 13292 S2 13342 S3-S4 13693 S5 13895 S6 14038 S7 23324

PSIS9638

Screws for sealing terminal covers


Type
S1-S2 S3-S4-S5-S6-S7

code 1SDA0 . . . . . R1
13344 13699

Accessories for electronic releases


Type
GSIS9041

Model
S4-S5-S6-S7 S8 S4-S5-S6-S7 S4-S5-S6-S7 S4-S5-S6-S7 S4-S5-S6-S7 S8 S4-S5-S6-S7 S4-S5-S6-S7 S4-S5-S6-S7 S4 100 S4 160 S4 250 S5 320 S5 400 S5 630 S6 630 S6 800 S7 1000 S7 1250 S7 1600 S8 1600 S8 2000 S8 2500 S8 3200 S4-S5-S6-S7 S4-S5-S6-S7 S4-S5-S6-S7 S4-S5-S6-S7 S8

code 1SDA0 . . . . . R1
48965 45021 50718 50719 50720 50721 45020 37121 48964 50708 37114 37115 37117 37118 37119 37120 25777 25778 25779 25780 25781 45015 45016 45017 45018 13702 13704 13703 13705 46581

Signalling unit SACE PR010/K Signalling unit SACE PR212/K Dialogue unit SACE PR212/D-M Modbus + actuator unit SACE PR212/T for SACE PR212/P (LSI - LSIG) Dialogue unit SACE PR212/D-M Modbus + actuator unit SACE PR212/T for SACE PR212/MP (LRIU) Dialogue unit SACE PR212/D-L Lon + actuator unit SACE PR212/T for SACE PR212/P (LSI - LSIG) Dialogue unit SACE PR212/D-L Lon + actuator unit SACE PR212/T for SACE PR212/MP (LRIU) Dialogue unit SACE PR212/D + Actuator unit SACE PR212/T Test unit SACE TT1 Test and configuration unit SACE PR010/T SACE PR212/CI contactor operating unit (with PR212/MP) Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker Current transformer for neutral conductor outside circuit-breaker X3 connector for relay tripped signal and neutral protection for fixed circuit-breaker with PR211/P, PR212/P - LSI X3, X4 connectors for relay tripped signal and neutral protection for fixed circuit-breaker with PR212/P - LSIG X3 connector for relay tripped signal and neutral protection for plug-in or withdrawable circuit-breaker with PR211/P, PR212/P - LSI X3, X4 connectors for relay tripped signal and neutral protection for plug-in or withdrawable circuit-breaker with PR212/P - LSIG electrical/mechanical signalling and lock for PR212/P tripped

GSIS9043 GSIS9045 GSIS9005

ABB SACE

GSIS9031

7
7/79

Order codes
SACE Isomax S accessories

Conversion kits
from fixed circuit-breaker to moving part of plug-in circuit-breaker
Type
S1 S2 S3-S4 S3X S4X S5 400

code 1SDA0 . . . . . R1 3 poles 4 poles


13270 13296 13608 46519 46511 13716 13271 13297 13609 46520 46512 13717

GSIS9036

from fixed circuit-breaker to moving part of withdrawable circuitbreaker


Type
S3-S4 S3X S4X S5 400 S5 630 S6 630 / 800 S6X S7

code 1SDA0 . . . . . R1 3 poles 4 poles


13610 46521 46514 13718 38778 13962 47619 23299 13611 46522 46513 13719 38779 13963 47620 14087

GSIS9037

from plug-in circuit-breaker to withdrawable circuit-breaker


Type
Guide for preparing the fixed part of a plug-in circuit-breaker for use as the fixed part of a withdrawable circuit-breaker Guide for preparing the fixed part of a plug-in circuit-breaker for use as the fixed part of a withdrawable circuit-breaker
GSIS9047

Size

code 1SDA0 . . . . . R1
13692 13892

S3-S4 S5

7
7/80 ABB SACE

Order codes
SACE Isomax S accessories

Fixed parts
Plug-in circuit-breaker
Type
EF = Extended front terminals S3 P FP EF S4 P FP EF S5 400 P FP EF FC = Front terminals for copper cables S1 P FP FC S2 P FP FC S3 P FP FC S4 P FP FC S5 400 P FP FC R = Threaded rear terminals S1 P FP R S2 P FP R S3 P FP R S4 P FP R S5 400 P FP R

code 1SDA0 . . . . . R1 3 poles 4 poles


13539 13612 13720 13272 13298 13543 13616 13724 13273 13299 13547 13620 13728 13548 13621 13729 13274 13300 13550 13625 13733 13275 13540 13554 13629 13737

GSIS9123

Withdrawable circuit-breaker
Type
EF = Extended front terminals S3 W FP EF S4 W FP EF S5 400 W FP EF S6 W FP EF S7 W FP EF ES = Spreaded extended front terminals S5 630 W FP ES FC = Front terminals for copper cables S3 W FP FC S4 W FP FC S5 400 W FP FC R = Threaded rear terminals S3 W FP R S4 W FP R S5 400 W FP R S5 630 W FP R VR = Vertical flat-bar rear terminals S5 630 W FP VR S6 W FP VR S7 W FP VR HR = Horizontal flat-bar rear terminals S6 W FP HR S7 W FP HR

code 1SDA0 . . . . . R1 3 poles 4 poles


13555 13630 13738 13964 48951 38761 13559 13634 13742 13563 13638 13746 38763 38971 13972 14096 13968 14092 13564 13639 13747 13973 14097 38762 13568 13643 13751 13572 13647 13755 38970 38972 13981 14105 13977 14101

GSIS9124

7
ABB SACE 7/81

Order codes
SACE Isomax S accessories

Accessories for fixed part of plug-in or withdrawable circuit-breakers


Terminals for the fixed parts of plug-in or withdrawable circuit-breakers
PSIS9653

Type
EF = Extended front terminals S3-S4 S5 400 S5 630 S6 (with terminals mounted below for S6X) S7 FC Cu/Al = Front terminals for copper / aluminium cables S3-S4 S5 400 R = Threaded rear terminals S3-S4 S5 400 S5 630 HR = Horizontal flat-bar rear terminals S6 S7 VR = Vertical flat-bar rear terminals S5 630 S6 S7

code 1SDA0 . . . . . R1 3 poles 4 poles


13650 13759 38780 13984 14108 13652 13761 13654 13763 38969 13986 14110 38763 13988 14112 13651 13760 38781 13985 14109 13653 13762 13655 13764 38782 13987 14111 38784 13989 14113

PSIS9655

PSIS9654

PSIS9646

Insulating covers for fixed parts


Type
S3-S4 S5 400

code 1SDA0 . . . . . R1 3 poles 4 poles


13697 13899 13698 13900

Position contacts
Type
GSIS9006

Model
S3-S4-S5-S6-S7 S3-S4-S5-S6-S7 S3-S4-S5-S6-S7 S3-S4-S5-S6-S7

code 1SDA0 . . . . . R1
13859 25546 13860 25547

contacts for signalling circuit-breaker racked out contacts for signalling circuit-breaker racked out for digital signals contacts for signalling circuit-breaker racked in contacts for signalling circuit-breaker racked in for digital signals

Lock for fixed part of withdrawable circuit-breakers


Type
GSIS9009

Model
S3-S4-S5-S6-S7 S3-S4-S5-S6-S7 S3-S4-S5-S6-S7

code 1SDA0 . . . . . R1
25434 25435 13872

key lock for locking in racked in / out position - different key for each cb. key lock for locking in racked in / out position - same key for sets of cb. padlock device

7
7/82 ABB SACE

Order codes
SACE Isomax S accessories

Installation accessories
Bracket for mounting on DIN rail
Type
DIN EN 50022 DIN EN 50022 DIN EN 50022 (for solenoid operator) DIN EN 50022 (for solenoid operator) DIN EN 50023 (complete with DIN front flange H=45 mm) DIN EN 50023 (complete with DIN front flange H=45 mm) DIN EN 50023 (complete with DIN front flange H=45 mm) DIN EN 50023 (complete with DIN front flange H=45 mm) DIN EN 50023 (complete with DIN front flange H=45 mm) DIN EN 50023 (complete with DIN front flange H=45 mm)

Model
S1 S2 S1 S2 S3 - 3 poles S3 - 4 poles S4 - 3 poles S4 - 4 poles S5 - 3 poles S5 - 4 poles

code 1SDA0 . . . . . R1
23328 23329 48523 48524 13576 13577 13700 13701 13901 13902

GSIS9011

IP54 protection
Type
PSIS9657

Model
S1-S2 S3-S4-S5-S6-S7

code 1SDA0 . . . . . R1
13339 13891

for fixed-depth rotary handle operating mechanism on door for adjustable-depth rotary handle operating mechanism on door

Residual-current releases
SACE RC210, RC211, SACE RC212
Type
RC210/1 for S1 (In=63 A - IDn=0,3 A) RC210/1 for S1 (In=63 A - IDn=0,5 A) RC210/1 for S1 (In=63 A - IDn=0,3 A) RC210/1 for S1 (In=63 A - IDn=0,5 A) RC211/1 for S1 RC211/2 for S2 RC211/3 for S3 RC212/1 for S1 RC212/2 for S2 RC212/3 for S3
PSIS9665 GSIS9027

code 1SDA0 . . . . . R1 side by side below


45076 45077 45079 45080 13282 13222 20288 13284 13324 20290 13283 13323 20289 13285 13325 20291

SACE RCQ
Type
release and closed toroid - diameter 60 mm release and closed toroid - diameter 110 mm release and closed toroid - diameter 185 mm release and opening toroid - diameter 110 mm release and opening toroid - diameter 180 mm release and opening toroid - diameter 230 mm release only closed toroid only - diameter 60 mm closed toroid only - diameter 110 mm closed toroid only - diameter 185 mm opening toroid only - diameter 110 mm opening toroid only - diameter 180 mm opening toroid only - diameter 230 mm

code 1SDA0 . . . . . R1
37388 37389 50542 37390 37391 37392 37393 37394 37395 50543 37396 37397 37398

GSIS9046

7
7/83

ABB SACE

Due to possible developments of standards as well as of materials, the characteristics and dimensions specified in the present catalogue may only be considered binding after confirmation by ABB SACE.

ABB SACE S.p.A. L.V. Breakers Division Via Baioni, 35 24123 Bergamo - Italy Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433
http://www.abb.com

604050/012 en Printed in Italy Tipografia