Sei sulla pagina 1di 1

CalculationofMakeupWater Circulatingwaterquantity Temperaturedrop Latentheatofwater Sp.

Heatofwater Cycleofconcentration R
3 200 m /h O

T 10 C HL 2260 kJ/kg C 4200 kJ/kgK 8 A. Eveporationloss,E= = B. Windageloss,W= = RHL/CT


3 10.76 m /h

0.2%ofR
3 0.40 m /h

C. Blowdownwaterquantity,B = [E/(COC1)]W 3 = 1.14 m /h

Makeupofwater= E+W+B = 12.30 m3/h


SomakeupwaterprovidedbySINOMAisok