Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Large capacity range up to 1000kW (341103BTU/h) Maintenance-friendly thanks to modular design Robust burner design Safe ame control thanks to ionization electrode and reliable electrical ignition Length increments enable individual adjustment either to new systems or when modernizing existing systems Low polluting level thanks to optimized combustion For installation as ceiling or side-wall burners Can be combined with different combustion chamber shapes Air preheating up to 500C (932F) BIOW, ZIOW: housing with internal insulation to reduce the surface temperature
Table of contents
Burners for gas BIO, BIOA, BIOW, ZIO, ZIOW . . . . . . . . . . . . 1 Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Examples of application . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.4.1 Burners with burner quarl . . . . . . . . . . . . . . . . . . . . . . . . . . 19 5.4.2 Burners with burner attachment tube . . . . . . . . . . . . . . . . 21
1.1.1 Modulating control with pneumatic ratio control system . . . 6 1.1.2 Modulating control with pneumatic ratio control system and lance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1.3 Cascade control for extended control range . . . . . . . . . . . . 7 1.1.4 Staged control with pneumatic ratio control system and ON/OFF cyclical control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.1.5 Staged control with pneumatic ratio control system and ON/OFF cyclical control with a defined pilot rate . . . . . . . . . . . . . 8 1.1.6 Staged control with pneumatic ratio control system and LOW/HIGH cyclical control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Project planning information . . . . . . . . . . . . . . . . . . . . . 25 6.1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.2 Flat flame burner spacing . . . . . . . . . . . . . . . . . . . . . . 25 6.3 Recommended ignition transformer . . . . . . . . . . . . . 25 6.4 Non-return gas valve . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.5 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 6.6 Hot air compensation . . . . . . . . . . . . . . . . . . . . . . . . . 26 6.7 Purging air/cooling air . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.7.1 Electrodes with air connection . . . . . . . . . . . . . . . . . . . . . . 27
6.8 Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 6.9 Gas line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.10 Air line connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.11 Condition on delivery . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.12 Special applications . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.13 Build up of noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 7 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 7.1 Adapter set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.1.1 Nozzle set 80-140 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Burners with ignition lance . . . . . . . . . . . . . . . . . . . . . . . 5 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 Burner type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Burner size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Burner head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13 14 15 15 15 16
8.1.1 BIO, BIOA [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 8.1.2 BIO [inch] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 8.1.3 ZIO [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 8.1.4 ZIO [inch] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 8.1.5 BIOW [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 8.1.6 BIOW [inch] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 8.1.7 ZIOW [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
= To be continued
8.3 Electrodes with air connection . . . . . . . . . . . . . . . . . . 44 9 Maintenance cycles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 10 Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
= To be continued
1 Application
BIO
BIOA
BIOW
ZIO
For industrial furnaces and ring systems in the iron and steel industries in the precious, non-ferrous and light metal sector, as well as in the plastics, bre and paper industries. Other elds of application are thermal incineration installations, as well as driers and hot air generators. The burners are used in combination with a burner quarl made from refractory concrete. Different ame shapes can be achieved by using burner quarls with different geometries. The burner may be adapted to the system requirements using different burner lengths. A high temperature version of the burner is available for high temperature applications (e.g. forging furnaces). For low temperature applications (e.g. for radiant tube heating or hot air generation), the burners are equipped with a heat-resistant steel attachment tube.
Application
Application
AKT
VAS
VAG
Threepoint step
M
IC 20 + BVA BVA
EKO
AKT
VAS
VAG
1.1.2 Modulating control with pneumatic ratio control system and lance The burners exibility is increased thanks to an ignition lance. This type of control is used in heat treatment furnaces in the iron and non-ferrous metal industries and in heating furnaces in the steel industry, for example.
60DJZ
VG 8 GEH
60DJLZ
GEH
M
IC 20..E + BVA BVA
EKO
1.1.3 Cascade control for extended control range The burner is adjusted near-stoichiometrically to a low-re rate of 10% using a pneumatic ratio control system. Smaller capacities can be adjusted with the IC20 at a constant low-re air ow rate by restricting the gas ow. With cascade control, control ranges of 1:45 can be achieved with excess air.
VMV EKO
AKT
VAS
VAG
ZIO, BIO
M
IC 20 + BVA BVA
AKT
VAS
VAG
EKO
LEH
1.1.4 Staged control with pneumatic ratio control system and ON/OFF cyclical control With ON/OFF cyclical control, the capacity supplied to the process is controlled by means of a variable ratio of the operating time to the pause time. The burner is ignited while the air valve is opening slowly. The pneumatic ratio control system controls the gas volume and ensures a constant mixture of gas and air in the burner. In accordance with EN746-2, this type of control can only be used for burner capacities of up to 360kW (1229103BTU/h). While the burner is switched off and depending on the furnace temperature, there must be a certain air ow, see page27 (Purging air/cooling air).
VR..L
Application
1.1.5 Staged control with pneumatic ratio control system and ON/OFF cyclical control with a dened pilot rate With this kind of cyclical control, the capacity supplied to the process is controlled by means of a variable ratio of the operating time to the pause time (ON/OFF). Here, the burner is ignited at a dened pilot rate via a bypass valve (PILOT RATE/HIGH/OFF burner control). This burner system can thus be used regardless of the burner capacity. A 2-stage air control valve allows the volume of air inltrating when the burners are switched off to be minimized. Alternatively, a single-stage air control valve with bypass for the pilot rate can be used if the volume of air inltrating into the process is non-critical.
AKT
VAS
VAG VMV
M
IC 40 + BV BVA
EKO
AKT
VAS
VAS GIKB
EKO
1.1.6 Staged control with pneumatic ratio control system and LOW/HIGH cyclical control The burner is ignited at a dened pilot rate. In the gas circuit, the pilot rate is achieved via a bypass nozzle in the GIKB and in the air circuit, via a hole in the air valve, for example. This burner system can thus be used regardless of the burner capacity. The burner capacity is switched cyclically between HIGH re and LOW re by opening and closing the air valve. The air control valve should open and close slowly. For other burner systems see www.system-technik.info
LEH
VR..R
2 Certication
Approval for Russia
Certied by Gosstandart under Technical Regulations. Approved by Rostekhnadzor (RTN). Declaration of Incorporation pursuant to the Machinery Directive Burners BIO, BIOA, ZIO, BIOW and ZIOW comply with the requirements of EN 746-2 and the Machinery Directive 2006/42/EC. This is conrmed by the manufacturers Declaration of Incorporation.
3 Mechanical construction
The burners are composed of three modules: burner housing, burner insert and burner tube. This structure allows the burners to be easily adapted to the respective process or to be integrated into existing systems. Maintenance and repair times are reduced, and existing furnace installations can easily be converted.
The burner is secured to the furnace by the burner housing. The burner housing accommodates the burner insert and the burner tube, and routes the combustion air. The combustion air pressure can be measured using an air pressure test nipple.
10
Mechanical construction
The combustion gas is supplied to the burner head via the gas connection and the gas pipe. The gas connection ange assembly includes the sight glass, ground screw and spark plugs with angle plugs. As of construction stage E, a measuring orice and ow adjustment are integrated in the connection ange to allow the gas ow rate to be easily measured and adjusted. The ignition and ionization electrodes are screwed into the connection ange and can be replaced without removing the burner insert. Burners BIO, BIOA, BIOW, ZIO and ZIOW are nozzle-mixing burners. Gas and air are mixed only once they are in the burner head. This prevents explosive gases from being generated in the pipeline. There are various burner head versions for different uses and gas types.
A complete pilot burner with separate gas and air connection is integrated on burners with integrated ignition lance instead of the ignition electrode. 3.2.2 High temperature version
A high temperature version is available for burners with preheated combustion air and minimum cooling air. This version is characterized by a burner head made of heatresistant steel and electrodes with an air connection. For use in forging furnaces, where at ame burners are used predominantly, the heat-resistant burner head is also equipped with a partly ceramic gas nozzle.
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13. 11
Mechanical construction
Different overall lengths enable adjustment to the furnace wall thickness of the system. 3.3.1 Burner tube in burner quarl The burner head is positioned inside the burner tube. The burner quarl accommodates the burner tube and simultaneously acts as the combustion chamber for the complete combustion of the ame. The burner quarls are components of the refractory lining of the furnace and are usually supplied by the furnace manufacturer. 3.3.2 Burner tube with attachment tube The burner head is positioned inside the burner tube. An attachment tube made of heat-resistant steel acts as the combustion chamber for the complete combustion of the ame for low- and medium-temperature applications.
12
4 Function
Burner housing Burner insert Burner head
Gas
Air
Burner tube
Burner insert
Gas
Burner tube
ZIO, ZIOW
Air
The burner control unit opens the gas and air control valves. Gas ows through the gas connection ange and air ows through the burner housing as far as the nozzle-mixing burner head. The combustible gas/air mixture is produced downstream of the burner head. Slots and holes in the air disc vary the angle of twist of the combustion air and determine the ame geometry. Depending on the gas type, the geometry of the gas nozzle varies. The gas/air mixture is electrically ignited directly by an ignition electrode or an ignition lance. A ame forms which is monitored using an ionization electrode or optionally using the UV sensor. The choice of the respective combustion chamber material and geometry is primarily determined by the process. Using burner quarls, almost any ame shape and outlet velocity can be achieved. For low temperature applications, a combustion chamber made of heat-resistant steel can be used. The ame burns inside the metal burner attachment tube.
Gas nozzle
13
Function
Gas
In the case of ignition with an ignition lance, the pilot burner is supplied with gas and air before the main burner starts. The gas/air mixture is electrically ignited directly by the ignition lance electrode and is then monitored by this electrode using ionization control. Once the ignition lance has been successfully ignited, the main burner is ignited via the ignition lance.
Air
Ignition lance
BIO, BIOW
Burner insert
Ignition lance
Burner head
ZIO, ZIOW
14
5 Selection
5.1 Burner type
Type BIO BIOA ZIO BIOW ZIOW Housing Cast steel AlSi St St with internal insulation St with internal insulation Air temperature C F up to 450 up to 842 up to 200 up to 392 up to 450 up to 842 up to 500 up to 932 up to 500 up to 932 Furnace temperature C F up to 1600 up to 2912 up to 1400 up to 2552 up to 1600 up to 2912 up to 1600 up to 2912 up to 1600 up to 2912
Burner capacity 103 BTU/h2) kW1) 40 151 90 340 150 567 230 870 320 1210 450 1702 630 2382 1000 3782
in kW refer to the lower caloric valueHu. in BTU/h refer to the upper caloric valueHo.
15
Selection
F continuous staged up to 2012 1:10 1:10 up to 2552 1:10 1:10 up to 2912* 1:10 1:10 up to 2012 1:2.5 1:10 up to 2462 ON/OFF
16
Calorific value range kWh/m3(n)4) BTU/scf5) 812 8101215 2535 25603474 2535 25603474 45 421503 1.72)3 161290 4.56.5 457658
Density kg/m3 lb/scf 0.70.9 0.0410.053 2.02.7 0.1180.159 2.02.7 0.1180.159 0.40.6 0.0240.035 0.91.15 0.0530.068 1.41.16 0.0830.069
burner head for composition of the fuel gas CH4 = 45% 65%, remaining components CO2 or N2. Suitable burner sizes on request. 4) Caloric value ranges in kWh/m3 refer to the lower caloric valueH . u 5) Caloric value ranges in BTU/scf refer to the upper caloric valueH . o
Low caloric value gas In the case of low caloric value gas, the composition of the fuel gas is required to select the burner. Recommended with burner quarl type (C) for an outlet velocity of approximately 80m/s. Burner BIO 65HLR BIO 80HLR BIO 100HLR BIO 125HLR BIO 140HLR
1) Capacities 2) Capacities
Burner quarl outlet diameter mm inch 33 1.3 40 1.57 50 1.97 66 2.6 70 2.76
17
Code letter L R
in kW refer to the lower caloric valueHu. in BTU/h refer to the upper caloric valueHo.
18
Field of application
chamIllustration Combustion ber E Burner with attachment tube and purging air bore holes Burner with attachment tube and purging air bore holes, B protective ame tube FPT
Control
Burner head H
Remarks Note the capacity of the radiant tube in accordance with the manufacturers specications. A draught blocker must be tted on the ue gas side. Only with cold air and where the furnace temperature is <850C. Protection of the ame from cooling is enL10 L10 sured by using a protective ame tubeFPT at ow velocities of >15m/s). Only with D cold air and where the furnace temperature is <600C.
ON/OFF
L10
Hot-air generation
100%
For further information on burner quarl dimensions see the burner quarl tables at www.docuthek.com.
19
L2 LF
L10
Legend L1 = burner tube length L2 = position of burner head LF = furnace wall thickness L10 = length of combustion chamber
Calculation example L2 should be appropriately selected, so that the burner head extends into the burner quarl. The following lengths are available for L2: 35, 135, 235, 335 mm, etc. The burner chamber length L10 for ensuring optimum ame formation and stable burner operation must be observed see burner quarl (Kind of document: General info) at www.docuthek.com. To determine L2: L2=LF - L10 The burner tube length (L1) is predened, depending on the burner head R, K orH: R, K burner head: L1 = L2 + 15 mm (L1 = L2 + 0.591 inches) H burner head: L1 = L2 + 65 mm (L1 = L2 + 2.56 inches) Example Desired burner quarl type=B, desired burner head=R (coldair). Selected burner with 90kW capacity= BIO65, suitable for a burner chamber length(L10)= 115 to 265mm. Furnace wall thickness LF = 340mm. Calculate shortest length for L2: Select maximum burner chamber length: L10 = 265 mm. L2 = LF - L10 = 340 mm - 265 mm = 75 mm. Compare L2 (here 75 mm) with standard lengths (35, 135, 235, 335 mm, etc.). Select next longest standard length L2: L2 = 135 mm. Test whether the burner chamber length L10 ts: LF - L2 = L10 340 mm - 135 mm = 205 mm. 205 mm falls into the burner chamber length range for burners BIO65: 115to265mm see burner quarl (Kind of document: General info) at www.docuthek.com.
20
open combustion chambers Forging furnaces, Selection > Field open combustion chambers
K K(...E)
100% 100%
range (40%) Hot air, only staged control possible (min. capacity = 50% of the rated capacity)
Remarks Note the capacity of the radiant tube in accordance with the manufacturers specications. A draught blocker must be tted on the ue gas side. Only with cold air and where the furnace temperature is <850C. Protection of the ame from cooling is ensured by using a protective ame tubeFPT at ow velocities of >15m/s). Only with cold air and where the furnace temperature is <600C.
ON/OFF
Hot-air generation
100%
Radiant tube heating When using the burner in radiant tubes or protective ame tubes, the extended burner tube (attachment tube) acts as the combustion chamber. Burners for this eld of application are supplied with purging air bore holes for optimal ame stability. The burner with attachment tube is only suitable for cold air applications. Maximum furnace temperature approx. 850C (1562F). The outlet diameter of the radiant tube must be reduced to the point where a pressure loss of approx. 10mbar (3.94"WC) occurs at the burners rated capacity.
Hot air generation To generate hot air at a furnace temperature of <600C (<1112F), burners with an attachment tube and purging air bore holes are used. The burner with attachment tube is only suitable for cold air applications. At ow velocities of > 15 m/s, the protective ame tube FPT is used to protect the ame from being cooled. At ow velocities of < 15 m/s, the protective ame tube FPT is not needed.
FPT FPT
F E
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13. 21
Selection > Field of application > Burners with burner attachment tube
Calculation example Attachment tube lengths (L1-2):
L1 Burner head
LF L2 L1-2
Legend L1 = burner tube length L2 = position of burner head LF = furnace wall thickness L1-2 = attachment tube length (distance of burner head to burner tube end)
H burner head mm inch 115 4.53 115 4.53 165 6.5 165 6.5 215 8.46 265 10.4 265 10.4 315 12.4
R burner head mm inch 115 4.53 115 4.53 165 6.5 165 6.5 215 8.46 265 10.4 165 6.5 215 8.46
L2 should be appropriately selected, so that the burner head is positioned near the interior furnace wall: L2 = LF 50 mm (L2 = LF 1.97 inches) The burner tube length (L1) is calculated by adding L2 to the attachment tube length (L1-2): L1 = L2 + L1-2 Example Burner head = H see page 19 (Field of application). Selected burner with 90 kW capacity = BIO 65, attachment tube length (L1-2) = 115 mm. Furnace wall thickness LF = 300 mm. Calculate the shortest distance for L2: L2 = LF - 50 mm = 300 - 50 mm = 250 mm. Compare L2 (here 75 mm) with standard lengths (35, 135, 235, 335 mm, etc.). Select next longest standard length L2: L2 = 335 mm. Calculate the related burner tube length (L1): L1 = L2 + L1-2 = 335 mm + 115 mm = 450 mm.
22
Selection
b = standard, = available
23
Description Burner for gas Burner for gas with aluminium housing Burner for gas with internal insulation Burner for gas Burner for gas with internal insulation Burner size Use: cold air hot air at ame Gas type: natural gas propane, propane/butane, butane low caloric value gas coke oven gas, town gas biologically produced methane Variants: with ignition lance with reduced max. connection rating
Position of burner head (L2) [mm] Burner head identier High temperature version Construction stage With purging air bore holes
For < 0.9 or when using the BIO50. R, K burner head H burner head
24
25
110
100
50 100 150 200 250 300 350 400 450 Hot air [C]
26
6.7.1 Electrodes with air connection In order to reduce the cooling air volume via the burner air connection, electrodes with an air connection can be installed. A purging air volume of approx. 1.5 to 2m3/h per electrode is recommended. This corresponds to a pressure of 10 to 15mbar (3.94 to 5.91WC).
Pressures for purges electrodes
p [mbar] 40 30 20
10 0
* The cooling air volumes measured in standard cubic metres are converted into percentage values.
27
6.8 Emissions
Emissions for cold air operating mode do not exceed the limits stipulated by the German Clean Air Directive. NOxvalues depend on the temperature, burner head, combustion chamber, furnace chamber, value and capacity (NOxvalues on request). If operated with LPG, NOx values are approx.25% higher.
NOX [mg/m3] 5 % O2 600 500 400 300 200 K (450 C) H (450 C)
CO values depend on the temperature, burner head, combustion chamber, furnace chamber, value and capacity (COvalues on request).
CO [mg/m] ref. 5% O2
4000
R, K
3000 2000 1000 0
100
200
300
400
500
600
100 70 50
10
50
28
29
7 Accessories
7.1 Adapter set
7.3 UV sensor
BIO 50 100
BIOA 65
For connecting BIO and BIOAburners to NPT/ANSIconnections. Gas Adapter set connection BIO 50 BR 50 NPT NPT BIO 65 BR 65 NPT NPT BIOA 65* NPT BIO 80 BR 80 NPT NPT BIO 100 BR 100 NPT NPT 1 BIO 125 BR 125 NPT NPT 1 BIO 140 BR 140 NPT NPT 1 Burner Air connection NPT 1 NPT 1 1.89" NPT 2 NPT 2 2.94" 3.57" Order No. 74922630 74922631 75456281 74922632 74922633 74922634 74922635
UVS 10
UVD
* An NPT thread adapter is required for connection to the gas circuit only.
Adapter set for BIOW and ZIOW on request. 7.1.1 Nozzle set 80-140 The nozzle set with NPT thread is required for integrated ignition lances. Gas type Natural gas LPG Order No. 74922638 74922639
For monitoring gas burners in conjunction with ame detectors or automatic burner control units. An installation set is required for installation on a burner BIO, BIOA orZIO. For burner BIO50, UV control using UVS10 plus a lens is only possible using the sight glass thread. UVS 10: with quartz glass heat guard, UVD: for continuous operation, in aluminium housing with socket, 24 V supply voltage. UV sensor and installation set supplied on request.
30
8 Technical data
Gas supply pressure and air supply pressure each depend on the use and gas type (gas and air pressures: see burner diagrams at www.docuthek.com). Burner length increments: 100 mm (3.94). Gas types: natural gas, LPG (gaseous), coke oven gas and biologically produced methane; other types of gas on request. Control type: staged: ON/OFF, LOW/HIGH, modulating: constant value. Most of the burner components are made of corrosionresistant stainless steel. Housing: BIO: cast steel, BIOA: AlSi, ZIO: St, BIOW: St + internal insulation, ZIOW: St + internal insulation. Flame control: with ionization electrode (UV sensor as an option). Ignition: direct spark ignition; lance as an option. Maximum furnace temperature: BIO/ZIO in burner quarl: up to 1600C (up to 2912F), BIO/ZIO with burner attachment tube: up to 600C (up to 1112F).
Maximum air temperature: BIO, ZIO: up to 450C (842F), BIOA: up to 200C (392F), BIOW, ZIOW: up to 500C (932F). REACH Regulation applies to BIOW and ZIOW only. Information pursuant to REACH Regulation No. 1907/2006, Article 33. Insulation contains refractory ceramic bres (RCF)/aluminium silicate wool (ASW). RCF/ASW are listed in the Candidate List of the European REACH Regulation No.1907/2006.
31
Technical data
Burner BIO 50 BIO 50 BIO 50 BIO 50 BIO(A) 65 BIO(A) 65 BIO(A) 65 BIO(A) 65 BIO 80 BIO 80 BIO 80 BIO 80 BIO 100 BIO 100 BIO 100 BIO 100 BIO 125 BIO 125 BIO 125 BIO 125 BIO 140 BIO 140 BIO 140 BIO 140
1) Rated
Rated capacity1) kW 40 40 40 40 90 90 90 90 150 150 150 150 230 230 230 230 320 320 320 320 450 450 450 450 103 BTU/h 151 151 151 151 340 340 340 340 567 567 567 567 870 870 870 870 1210 1210 1210 1210 1702 1702 1702 1702
Flame length2) cm 25 30 50 40 50 60 45 60 70 55 70 80 60 100 115 80 120 140 inch 9.84 11.8 19.7 15.7 19.7 23.6 17.7 23.6 27.6 21.7 27.6 31.5 23.6 39.4 45.3 31.5 47.2 55.1
Flame outlet velocity3) m/s 15 55 50 20 70 65 20 75 70 20 75 70 20 65 60 20 75 70 ft/s 49.2 180 164 65.6 230 213 65.6 246 230 65.6 246 230 65.6 213 197 65.5 246 230
capacity for cold air. Higher capacities are are possible either on request or see burner diagrams at www.docuthek.com. Capacities in kW refer to the lower caloric valueHu and capacities in BTU/h refer to the upper caloric valueHo. 2) Measured in the burner quarl from the front edge of the burner quarl. The ame diameter is approx. one to two times that of the burner tube or burner quarl outlet. 3) Based on the rated capacity for cold air, with a flame temperature of 1600C for Rburner head and 1500C for Hburner head. The flow velocity is increased when the outlet diameter of the burner quarl is reduced. The rated capacity must then be adjusted to the outlet diameter.
32
Technical data
Burner ZIO 165 ZIO 165 ZIO 165 ZIO 165 ZIO 200 ZIO 200 ZIO 200 ZIO 200
1) Rated
Rated capacity1) kW 630 630 630 630 1000 1000 1000 1000 103 BTU/h 2382 2382 2382 2382 3782 3782 3782 3782
Flame length2) cm 90 110 160 100 130 200 inch 35.4 43.3 63 39.4 51.2 78.7
Flame outlet velocity3) m/s 20 75 70 25 85 80 ft/s 65.6 246 230 82 279 262
capacity for cold air. Higher capacities are are possible either on request or see burner diagrams at www.docuthek.com. Capacities in kW refer to the lower caloric valueHu and capacities in BTU/h refer to the upper caloric valueHo. 2) Measured in the burner quarl from the front edge of the burner quarl. The ame diameter is approx. one to two times that of the burner tube or burner quarl outlet. 3) Based on the rated capacity for cold air, with a flame temperature of 1600C for Rburner head and 1500C for Hburner head. The flow velocity is increased when the outlet diameter of the burner quarl is reduced. The rated capacity must then be adjusted to the outlet diameter.
33
8.1 Dimensions
8.1.1 BIO, BIOA [mm]
d3 n3 k3 D3 L5 LA L3 F S H d2 n2 H LA L5 L3 S d2 F n2
GA L6 L4 L2 L1 k2 D2
GA L6 L4 L2 L1 k2 D2
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example)) BIO BIOA
Burner BIO 50 BIO 65 BIOA 65 BIO 80 BIO 100 BIO 125 BIO 140
Connections GA Rp 1/2 Rp 3/4 Rp 1/2 Rp 3/4 Rp 1 Rp 11/2 Rp 11/2 LA Rp 11/2 Rp 11/2 48 Rp 2 Rp 2 DN65 DN80 D** 50 65 65 82 100 127 140 H 50 62 110 112 100 135 150 h 38 48 44 55 60 73 80 S 12 12 16 14 16 16 18
Gas connection L3 73 73 95 90 103 120 130 L4 149 156 170 172 185 254 271 L5 240 246 261 272 285 350 381 L6 127 127 149 140 153 212 232 D2 151 165 165 210 200 240 265 k2 151 165 165 210 200 240 265 d2 12 12 13 14 14 14 14 F 75 95 88 110 120 145 160
No. of Weight Air connection drillings D3 k3 d3 n2 n3 [kg] 4 5.4 4 7.2 4 3.6 4 11.2 4 12.6 185 145 18 4 4 21.7 200 160 18 4 8 29
* Cold air connection, open ame, = 1.1. Capacities in kW refer to the lower caloric value Hu. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13. 34
L6 L4
L2 L1
k2 D2
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Burner BIO 50 BIO 65 BIO 80 BIO 100 BIO 125 BIO 140
Rated capacity* [103 BTU/h] 151 340 567 870 1210 1702
Connections GA
1/ 3/ 3/ 2 NPT 4 NPT
Gas connection D** 1.97 2.56 3.23 3.94 5 5.51 H 1.97 2.44 4.41 3.94 5.31 5.91 h 1.5 1.89 2.17 2.36 2.87 3.15 S 0.472 0.472 0.551 0.63 0.63 0.709 L3 2.87 2.87 3.54 4.06 4.72 5.12 L4 5.87 6.14 6.77 7.28 10 10.7 L5 9.45 9.69 10.7 11.2 13.8 15 L6 5 5 5.51 6.02 8.35 9.13 D2 7.13 7.68 9.45 9.45 10.6 11.8 k2 5.94 6.5 8.27 7.87 9.45 10.4 d2 0.47 0.47 0.55 0.55 0.55 0.55 F 2.95 3.74 4.33 4.72 5.71 6.3
No. of Weight Air connection drillings D3 D4 d3 n2 n3 [lbs] 4 11.9 4 15.8 4 24.6 4 27.7 7.28 2.94 0.709 4 4 47.7 7.87 3.57 0.709 4 8 63.8
* Cold air connection, open ame, = 1.1. Capacities in BTU/h refer to the upper caloric value Ho. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
35
LA L3 L4 d3 D3 k3 L2 L1
k2 D2
n3
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Rated Burner capacity* Connections Gas connection [kW] GA LA D** H h S L3 L4 L5 L6 D2 k2 d2 F ZIO 165 630 R 11/2 DN100 165 213 20 150 359 230 285 240 14 220 ZIO 200 1000 R 2 DN150 194 220 20 220 469 340 330 295 22 255
No. of Weight Air connection drillings D3 k3 d3 n2 n3 [kg] 220 180 18 4 8 26 285 240 22 8 8 37
* Cold air connection, open ame, = 1.1. Capacities in kW refer to the lower caloric value Hu. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
36
LA L3 L4 d3 D3 D4 L2 L1
k2 D2
n3
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Rated Gas connection Air connection capacity* Connections 3 [10 BTU/h] GA LA D** H h S L3 L4 L5 L6 D2 k2 d2 F D3 D4 d3 ZIO 165 2382 11/2 NPT DN100 6.5 8.39 0.787 5.91 14.1 9.06 11.2 9.45 0.55 8.66 8.66 4.57 0.709 ZIO 200 3782 2 NPT DN150 7.64 8.66 0.787 8.66 18.5 13.4 13 11.6 0.87 10 11.2 6.72 0.866 Burner
* Cold air connection, open ame, = 1.1. Capacities in BTU/h refer to the upper caloric value Ho. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
No. of drillings n2 n3 4 8 8 8
37
GA L6 L4 L2 L1 k2 D2
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Connections GA Rp 3/4 Rp 3/4 Rp 1 Rp 11/2 Rp 11/2 LA DN65 DN80 DN80 DN100 DN125 D** 65 82 100 127 140 H 142 152 152 182 195 h 47 54 59 72 79 S 22 22 22 22 22
Gas connection L3 121.5 139 139 170 180 L4 256 272 285 351 371 L5 344 368 381 450 480 L6 216 229 242 299 319 D2 195 240 240 270 300 k2 165 210 200 240 265 d2 12 14 14 14 14 F 138 156 172 200 215
Air connection D3 185 200 200 220 250 k3 145 160 160 180 210 d3 18 18 18 18 18
* Cold air connection, open ame, = 1.1. Capacities in kW refer to the lower caloric value Hu. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13. 38
GA L6 L4 L2 L1 k2 D2
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Connections GA 3/4 NPT 3/4 NPT 1 NPT 11/2 NPT 11/2 NPT
Gas connection
Air connection
LA D** H h S L3 L4 DN65 2.56 5.59 1.85 0.866 4.78 10.1 DN80 3.23 5.98 2.13 0.866 5.47 10.7 DN80 3.94 5.98 2.32 0.866 5.47 11.2 DN100 5 7.17 2.83 0.866 6.69 13.8 DN125 5.51 7.68 3.11 0.866 7.09 14.6
L5 L6 D2 k2 d2 F D3 D4 d3 I3 13.5 8.5 7.68 6.5 0.47 5.43 7.28 2.94 0.709 58 14.5 9.02 9.45 8.27 0.55 6.14 7.87 3.57 0.709 70 15 9.53 9.45 7.87 0.55 6.77 7.87 3.57 0.709 70 17.7 11.8 10.6 9.45 0.55 7.87 8.66 4.57 0.709 83 18.9 12.6 11.8 10.4 0.55 8.46 9.84 5.65 0.709 106
* Cold air connection, open ame, = 1.1. Capacities in BTU/h refer to the upper caloric value Ho. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13. 39
n2 d2
LA L3 L4 D3 k3 I3 L2 L1
k2 D2
d3
n3
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Burner
Rated capacity* Connections [kW] GA LA D** H h ZIOW 165 630 R 11/2 DN150 165 213
No. of drillings Weight S L3 L4 L5 L6 D2 k2 d2 F D3 k3 d3 I3 n2 n3 [kg] 20 187 460 320 285 240 14 264 285 240 22 130 4 8 32 Gas connection Air connection
* Cold air connection, open ame, = 1.1. Capacities in kW refer to the lower caloric value Hu. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
40
n2 d2
LA L3 L4 D3 D4 I3 L2 L1
k2 D2
d3
n3
L1 (burner tube length) and L2 (position of burner head) are variable (see page 20 (Calculation example))
Burner
Rated No. of Gas connection Air connection capacity* Connections drillings LA D** H h S L3 L4 L5 L6 D2 k2 d2 F D3 D4 d3 I3 n2 n3 [103 BTU/h] GA 8 ZIOW 165 2382 11/2 NPT DN150 6.89 8.39 0.787 7.36 18.1 12.6 11.2 9.45 0.55 10.4 11.2 6.72 0.866 5.12 4
* Cold air connection, open ame, = 1.1. Capacities in BTU/h refer to the upper caloric value Ho. ** Approx. 10 cm larger in the case of a deviation from the standard length, as a weld seam is applied.
41
Technical data
B
E1
Gas
I Z
W1
W2
Air
Burner
Dimensions E1 mm 7 7 8 16 inch 0.276 0.276 0.315 0.669 mm 10 10 8 18 E2 inch 0.394 0.394 0.315 0.709 mm 177 190 261 276 L7 inch 6.97 7.48 10.3 10.9 W1 36 36 30 42 W2 45 45 30 45
E2
42
Air
C E1
I I
Gas
Burner
43
Technical data
W1
Burner B BIO 80 BIO 100 BIO 125 BIO 140 BIOW 80 BIOW 100 BIOW 125 BIOW 140 mm 57 57 69 63 57 57 69 63 inch 2.24 2.24 2.72 2.48 2.24 2.24 2.72 2.48
Dimensions E1 L7 mm inch mm inch 7 0.276 177 6.97 7 0.276 190 7.48 8 0.315 261 10.3 16 0.63 276 10.9 7 0.276 277 10.9 7 0.276 290 11.4 8 0.315 361 14.2 16 0.63 376 14.8
Burner W1 36 36 30 42 36 36 30 42 ZIO 165 ZIO 200 ZIOW 165 L7 mm 259 369 359 inch 10.2 14.5 14.1
44
9 Maintenance cycles
Twice per year, but if the media are highly contaminated, this interval should be reduced.
45
10 Legend
Manual valve Gas solenoid valve Air/gas ratio control with solenoid valve Flow adjusting cock
M
Buttery valve with actuator Buttery valve with manual adjustment Solenoid valve for gas, slow opening Air/gas ratio control with bypass nozzle
46
Finally, we are offering you the opportunity to assess this Technical Information (TI) and to give us your opinion, so that we can improve our documents further and suit them to your needs. Clarity Found information quickly Searched for a long time Didnt find information What is missing? No answer Use To get to know the product To choose a product Planning To look for information Remarks Comprehension Coherent Too complicated No answer Scope Too little Sufficient Too wide No answer My scope of functions Technical department Sales No answer
Feedback
Contact
Elster GmbH Postfach 2809 49018 Osnabrck Strotheweg 1 49504 Lotte (Bren) Germany T +49 541 1214-0 F +49 541 1214-370 info@kromschroeder.com www.kromschroeder.com
BIO, BIOA, BIOW, ZIO, ZIOW Edition 10.13.
The current addresses of our international agents are available on the Internet: www.kromschroeder.de/index.php?id=718&L=1 We reserve the right to make technical modications in the interests of progress. Copyright 2013 Elster GmbH All rights reserved.
03250786