Features
4 channels for -20...+20 mA, 0...20 mA, 4...20 mA, -10...+10 V, 0...10 V, 2...10 V, -5...+5 V, 0...5 V, 1...5 V d.c. bipolar differential inputs. One group of 4 channels isolated from ground. Configurable on a per channel basis. 14 Bit resolution plus sign. Input shunt resistors protected to 30 V d.c. EMC protection. DIN rail mounting. The input withstand HART communication.
F R W 1
Description
The AI820 Analog Input Module has 4 differential, bipolar current/voltage inputs. Each channel can be either a voltage or current input.
AI820
20 mA, 10 V Diff The current inputs can withstand an accidental maximum normal mode 30 V d.c. connection. To protect the current input circuit against dangerous input levels, that is, by accidentally connecting a 24 V source, the resistor rating of the 250 current sense resistors is about 5 Watts. This is intended only to temporarily protect one channel at a time.
The module distributes the external transmitter supply to each channel. This adds a simple connection (with extended MTUs) to distribute the supply to external 2 wire transmitters. There is no current limiting on the transmitter power terminals. All 4 channels are isolated from the ModuleBus in one group. Power to the input stages is converted from the 24 V on the ModuleBus.
3BSE020924R5021
87
AI820 Differential Analog Input Module, +/- 20 mA, +/- 10 V, +/- 5 V (4...20 mA, 2...10 V, 1...5 V)
Three LEDs indicate module status Fault (Red), Run (Green) and Warning (Yellow). The RUN LED indicates normal operation and the WARNING LED indicates if any diagnostic condition is active. The FAULT LED indicates that the module is in Init state or Not configured state. In Not Configured state the FAULT LED is turned off after the first valid access to the module. The reset circuitry gives a reset signal when the module is inserted until the BLOCK signal is inactive and the POWOK signal is active. The BLOCK signal is deactivated when the module lock mechanism is in the locked position. The POWOK comes from the ModuleBus master after power is applied. Four different types of MTUs can be used. The TU830 Extended MTU enables three wire connection to the devices without additional terminals. The TU810 (or TU814) Compact MTU has terminals for 24 V process voltage inputs, but requires external terminals for distribution of 24 V power supply to the field devices. The TU812 Compact MTU has a D-Sub 25 pin (male) connector for connection to the process.
88
3BSE020924R5021
Appendix A Specifications
Technical Data
Bipolar differential -20...+20 mA, 0...20 mA, 4...20 mA (1), -10...+10 V, 0...10 V, 2...10 V (1), -5...+5 V, 0...5 V, 1...5 V (1) d.c. 15% 200k + / 25% Common mode 800k + / 25% Normal mode 250 600 meters, (656 yd.) 30 V 50 V d.c. 80 dB (>60 dB d.c.) 33 dB Max. 0,1% 14 bit plus sign Max.50 ppm/ C Max.70 ppm/ C <26 ms 70 mA 80 mA 1.7W
Over/under range Input impedance (at voltage input) Input impedance (at current input) Maximum field cable length Max. Differential d.c. input (Fault) Common mode voltage input CMRR, 50 Hz, 60 Hz NMRR, 50 Hz, 60 Hz Error Resolution Temperature drift, Current Temperature drift, Voltage Update cycle time (all four channels) Current consumption 24 V Current consumption 5 V Power dissipation
3BSE020924R5021
89
AI820 Differential Analog Input Module, +/- 20 mA, +/- 10 V, +/- 5 V (4...20 mA, 2...10 V, 1...5 V)
Table 15. AI820 Differential Analog Input Module Specifications at 25C (Continued)
Feature Maximum ambient temperature Voltage supervision Input filter (rise time) Fusing of transmitter supply Isolation Module termination units MTU keying code Equipment class Protection rating Rated insulation voltage Dielectric test voltage Width Depth Height Weight 55/40C (131/104F)(2) Internal process supply 40 ms on Extended MTU Groupwise isolated from ground (RIV=50 V) TU810, TU812, TU814 or TU830 BB Class I according to IEC 61140; (earth protected) IP20 according to IEC 60529 50 V 500 V a.c. 45 mm (1.77) 97 mm (3.8), 106 mm (4.2) including connector 119 mm (4.7) 0.2 kg (0.44 lbs.) AI820 Analog Input Module
(1) Handled by the FCI or controller. (2) 40C (104F) applies to compact MTUs with I/O-modules or S800L-modules mounted on vertical DIN rail.
90
3BSE020924R5021
Appendix A Specifications
L1+ L1L1+ L1I1U+ I1IB I1I+ I1L1+ L1I2U+ I2IB I2I+ I2I3U+ I3IB I3I+ I3L2+ L2I4U+ I4IB I4I+ I4L2+ L2L2+ L2AMP + LPF AMP + LPF Mux PGA G=1/2 # MBI-2
Pos
AMP + LPF
+UPInt ZP -UPInt
+24 V +0 V 24
AMP + LPF
ZP
EM
3BSE020924R5021
91
AI820 Differential Analog Input Module, +/- 20 mA, +/- 10 V, +/- 5 V (4...20 mA, 2...10 V, 1...5 V)
Process Connections
Process Connection +24 V d.c. 0 V d.c. (ZP) Ch1, L1+ Ch1V, Voltage Input + Ch1IB
(2)
Ch1, L1Ch 1, L1+ Ch 1I, Current Input + Ch 1-, Return Ch 1, L1Ch 2, L1+
(2)
B3 A3 C4 B4 A4 -
92
3BSE020924R5021
Appendix A Specifications
Process Connection Ch 3IB (2) Ch 3, L2Ch 3, L2+ Ch 3I, Current Input + Ch 3-, Return - (2) Ch 3, L2Ch 4, L2+
Ch 4V, Voltage Input + C7 Ch 4IB (2) Ch 4, L2Ch 4, L2+ Ch 4I, Current Input + Ch 4-, Return - (2) Ch 4, L2+24 V d.c. 0 V d.c. (ZP) B7 A7 C8 B8 A8 L2+ L2-
(1) Pin 13 connected to connector body for EM. (2) When connect current signal current bridge must be connected to the voltage Input. If 2-wire transmitter also connect Return- to L1- or L2-.
3BSE020924R5021
93
AI820 Differential Analog Input Module, +/- 20 mA, +/- 10 V, +/- 5 V (4...20 mA, 2...10 V, 1...5 V)
Figure 26 shows the process connections for the Differential Analog Input Module AI820 when installed on a TU830 Extended MTU.
Process Pwr. Source 0 - 10V Ch1 V 4 Wire XTMR 4 - 20mA 2 Wire XTMR Ch1 L1+ Ch2V Ch2IB Ch2 I Ch2L1Ch3V Ch3IB 0 - 20mA Ch3 I Ch3 4 Wire XTMR CH4 V 0 - 10V 3 Wire XTMR L2+ L2+24v Chx V = Voltage Input Chx I = Current Input 0v
TU830/TU833 6.3A L1+ L1+ Fuse L1L1B1,B2 C1 C2 A1,A2 B3,B4 C3 C4 A3,A4 B5,B6 C5 C6 A5,A6 B7,B8 C7 C8 A7,A8 B9,B10 C9 C10 A9,A10 B11,B12 C11 C12 A11,A12 B13,B14 C13 C14 A13,A14 B15,B16 C15 C16 A15,A16 L2+ L2+ L2L26.3A Fuse
AI820
+24v 0v
L1+ L1L1+ I1U+ I1IB L1L1+ I1I+ I1L1L1+ I2U+ I2IB L1L1+ I2I+ I2L1L2+ I3U+ I3IB L2L2+ I3I+ I3L2L2+ I4U+ I4IB L2L2+ I4I+ I4L2L2+ L2-
Compensation
250W
Compensation
Pwr. Source
250W
Compensation
250W
Compensation
94
3BSE020924R5021
Appendix A Specifications
Figure 27 shows the process connections for the AI820 when installed on a TU810 or TU814 Compact MTU.
+24V 0V
AI820
L1+ L1L1+ I1U+ I1IB L1L1+ I1I+ I1L1L1+ I2U+ I2IB L1L1+ I2I+ I2L1L2+ I3U+ I3IB L2L2+ I3I+ I3L2L2+ I4U+ I4IB L2L2+ I4I+ I4L2L2+ L2-
4 Wire XTMR Ch1 4 - 20mA 2 Wire XTMR Ch2V Ch2IB Ch2 I Ch2 L1Ch3V Ch3IB 0 - 20mA Ch3 I Ch3 4 Wire XTMR CH4 V 0 - 10V 3 Wire XTMR Ch4 -
Compensation
250W
Compensation
Pwr. Source
250W
Compensation
Compensation
+24v 0v
Figure 27. AI820 with TU810 or TU814 Compact MTU Process Connections
3BSE020924R5021
95
AI820 Differential Analog Input Module, +/- 20 mA, +/- 10 V, +/- 5 V (4...20 mA, 2...10 V, 1...5 V)
Figure 28 shows the process connections for the AI820 when installed on a TU812.
TU812 1 14 2 15 3 16 4 17 5 18 Process Connection 6 19 7 20 8 21 9 22 10 23 11 24 12 25 13 1 UP1 +24V 14 UP1 2 ZP1 0V 15 ZP1 3 S1 16 S2 4 S3 17 S4 5 S5 18 S6 6 S7 19 S8 7 S9 Ch1 V Ch1 IB Ch1 I Ch1 R Ch2 V Ch2 IB Ch2 I Ch2 R Ch3 V
AI820
L1+ L1L1+ I1U+ I1IB L1L1+ I1I+ I1L1L1+ I2U+ I2IB L1L1+ I2I+ I2L1L2+ I3U+ I3IB L2L2+ I3I+ I3L2L2+ I4U+ I4IB L2L2+ I4I+ I4L2L2+ L2-
Compensation
250W
Compensation
20 S10 Ch3 IB 8 S11 Ch3 I 21 S12 Ch3 R 9 S13 Ch4 V 22 S14 Ch4 IB 10 S15 Ch4 I 23 S16 Ch4 R 11 UP2 +24V 24 UP2 12 ZP2 0V 25 ZP2 13 EM
250W
Compensation
250W
Compensation
96
3BSE020924R5021
Appendix A Specifications
4 channels individually galvanic isolated inputs for +20 mA, 0...20 mA, 4...20 mA, +10 V, 0...10 V, 2...10 V. 14 Bit resolution plus sign. Input shunt resistors protected to 30 V d.c. EMC protection. DIN rail mounting. The input withstands HART communication.
Description
The AI825 Analog Input Module has 4 individually galvanic isolated, bipolar current/voltage inputs. Each channel can be either a voltage or current input. The module has a direct current input that withstand up to 6.3 V and a over voltage protected current input that withstand up to +30 V d.c. The current is limited by a PTC resistor. Power to the input stages is converted from the 24 V on the ModuleBus. Three LEDs indicate module status Fault (Red), Run (Green) and Warning (Yellow). The RUN LED indicates normal operation and the WARNING LED indicates if any diagnostic condition is active. The FAULT LED indicates that the module is in Init state or Not configured state. In Not Configured state the FAULT LED is turned off after the first valid access to the module. The reset circuitry gives a reset signal when the module is inserted until the BLOCK signal is inactive and the POWOK signal is active. The BLOCK signal is deactivated when the module lock mechanism is in the locked position. The POWOK comes from the ModuleBus master after power is applied.
3BSE020924R5021
97
Appendix A Specifications
Three different types of MTUs can be used; TU831 Extended MTU, TU811 or TU813 Compact MTU. The TU813 Compact MTU has crimped snap-in connectors for connection to the process.
Technical Data
-20...+20 mA, 0...20 mA, 4...20 mA, -10...+10 V, 0...10 V, 2...10 V d.c. 15% 10 M 50 50 + 125 600 meters, (656 yd.) 30 V 30 V 6.3 V 120 dB >40 dB at 50 Hz, >55 dB at 60 Hz
Over/under range Input impedance at voltage input (I x U) Input impedance at current input (I x I) Over voltage protected current input (I x IP) Maximum field cable length Max. Differential d.c. input (Fault) Voltage input Over voltage protected current input Current input CMRR, 50 Hz, 60 Hz NMRR
98
3BSE020924R5021