Sei sulla pagina 1di 13

Atlas Copco

Refrigerant Air Dryers FD series (6-4000 l/s, 13-8480 cfm)

Why dry your compressed air?


Compressed air is used in a wide variety of industrial applications. Wherever it is used, compressed air must be clean and dry. Containing solid, liquid and gaseous contaminants, untreated compressed air poses a substantial risk as it can damage your air system and end product. Moisture, one of the main components of untreated air can cause corrosion in pipe work, premature failure of pneumatic equipment, product spoilage and more. An air dryer is therefore essential to protect your systems and processes.

Limit the risks of moisture


When the air that surrounds us is compressed, its water vapor and particle concentration increases dramatically. For example, compressing ambient room air to 7 bar(e)/100 psig increases the vapor content or humidity by a factor of around 8, and subsequent cooling forms liquid water. The amount of water depends on the specic application. Compressed air can actually contain three forms of water: liquid water, aerosol (mist) and vapor (gas). An efcient means of removing water from compressed air is therefore vital.

compression

Moisture in the air can be particularly problematic, causing: Corrosion of compressed air piping. Damages & malfunction of air powered equipment. Compressed air leakages due to corroded pipes. Poor paint quality, deterioration of electrostatic painting processes. Deteriorated end product quality.


ISO quality air standard (ISO 8573-1:2010)


The quality of compressed air used in industrial processes is specied in the international standard ISO 8573-1. Untreated compressed air typically contains 3 types of contaminants: dirt, water and oil. The Quality Classes specify the maximum allowed limits.

Dirt ISO 8573-1:2010 Maximum number of particles per m 0.1 - 0.5 micron 0 1 2 3 4 5 6 7 8 9 X 20000 400000 -

Water

Oil

FD series

Mass Total oil Vapor pressure concentration Liquid g/m (aerosol liquid and vapor) dewpoint 0.5 - 1 1-5 mg/m mg/m micron micron As specied by the equipment user or supplier and more stringent than Class 1 400 10 -70C/-94F 0.01 6000 100 -40C/-40F 0.1 90000 1000 -20C/-4F 1 10000 +3C/+37 .4F 5 100000 +7C/+44.6F 5 +10C/+50F 5 - 10 0.5 0.5 - 5 5 - 10 > 10 > 10 > 10

What is a refrigerant dryer?


A refrigerant dryer uses a refrigerant circuit and heat exchanger(s) to pre-cool air, refrigerate it to condense out moisture vapor, and then re-heat the air to prevent pipe sweating downstream. Refrigerant dryers can lead to a pressure dewpoint (PDP) as low as +3C/+37.4F for many applications where there is a need for dry air. They can be used at different pressures and consume no processed compressed air. Main types of refrigerant dryers on the market Direct expansion dryers - Fixed speed non-cycling dryers run continuously irrespective of varying load conditions. - Fixed speed cycling dryers shut down at lower loads to save energy and restart when required. - Variable speed dryers are on the cutting edge of energy efciency. They automatically change the speed of the refrigerant compressor to adapt to varying loads.
 

Thermal mass dryers have a heat exchanger which typically contains a liquid thermal mass to store cold energy. Thermal mass dryers shut down when there is no or little air, or at low loads to save energy.


Digital scroll dryers have a refrigerant compressor that loads/unloads according to the demand.

Typical working principle of direct expansion dryers


Air circuit
Hot wet air

Refrigerant circuit

4
Outgoing dry air

9
Cool wet air Refrigerant gas/liquid

Refrigerant gas Hot refrigerant gas

Cold refrigerant liquid Expanded refrigerant liquid

8 2 7

Air circuit
1 Air-to-air heat exchanger: Incoming air is cooled down by the outgoing dry cold air. 2 Air-to-refrigerant heat exchanger: The air is cooled to the required dewpoint by the refrigerant circuit.

The water vapor condenses into water droplets.


3 Integrated water separator: The moisture is collected and evacuated by the electronic drain.

Refrigerant circuit
The refrigerant removes the heat from the compressed air and cools down to the desired dewpoint.
4 Refrigerant compressor: Compresses the gaseous refrigerant to a higher pressure. 5 Regulation device: The hot gas bypass valve regulates the dryer to prevent freezing at lower load conditions. 6 Refrigerant condenser: Cools the refrigerant so that it changes from a gas to a liquid. 7 Refrigerant lter: Protects the expansion device from harmful particles.

9 Liquid separator: Ensures that only refrigerant gas enters the compressor.

FD series

8 Thermostatic expansion valve: The expansion process reduces the pressure and cools the refrigerant further.

Atlas Copcos FD refrigerant dryers


Based on years of experience in the industry, Atlas Copco has chosen to incorporate direct expansion technology with cycling, non-cycling and Variable Speed variants in its range.

Direct expansion dryers without Saver Cycle Control (non-cycling)


FLOW

Applications: stable dewpoint, full load applications. Key advantage: xed speed dryers run continuously to ensure a stable dewpoint by design (irrespective of varying load conditions). Range: FD 5-2000.

time

Direct expansion dryers with Saver Cycle Control (cycling)


flow

Applications: varying temperatures, varying ows. Key advantage: cycling dryers shut down the refrigerant compressor at lower load conditions which leads to signicant energy savings. Range: FD 5-1010.

time

Variable speed dryers (VSD = Variable Speed Drive)


flow

Applications: varying temperatures, varying ows. Key advantage: VSD dryers match the energy consumed to the actual compressed air used. This ensures supreme energy savings as well as a stable dewpoint across the whole spectrum of temperature and ow. FD 760-4000 VSD.

time

FD series

Protecting your reputation and production


Compressed air entering the air net is always 100% saturated. When it cools, this moisture will condense, causing damage to your air system and nished products. Removing moisture from compressed air with a dewpoint as low as +3C/+37.4F, Atlas Copcos FD refrigerant dryers provide the clean, dry air you need to expand the life of your equipment and ensure the quality of your end product. In addition, FD dryers comply with the most stringent environmental regulations.

Keeping your production up and running


Atlas Copcos FD refrigerant dryers are designed in-house, tested using the most stringent methods (at ambient temperatures up to 50C/122F) and manufactured on a very advanced production line. Separate components undergo severe endurance tests while the unique design of the heat exchanger signicantly improves the dryer lifetime. Advanced control functions ensure dry air at all conditions and prevent freezing at low loads. FD dryers meet or exceed the international standards for compressed air purity and are tested according to ISO 7183:2007.

Driving down energy costs


Atlas Copcos refrigerant dryers incorporate a range of energy-saving features that will cut your carbon footprint and reduce costs. Incorporating unique heat exchanger technology and Saver Cycle Control, the FD ensures a low pressure drop of typically below 0.2 bar/2.9 psi and minimal energy consumption. The integrated Variable Speed Drive (VSD) technology offers extra energy savings by automatically tuning the energy input to the precise demand. All this ensures a low lifecycle cost.

Easy installation and long maintenance intervals


FD dryers have a small footprint thanks to an innovative all-in-one design. Delivered ready for use, installation is straightforward, minimizing costly production downtime. FD dryers come as all-in-one packages including an electronic no-loss drain, integrated OSD condensate treatment (optional) and spin-on DD/PD lters (optional). For easy installation against the wall, the in- and outlet connections on some models are positioned on top of the unit.

Assuring your peace of mind


Through continuous investment in our competent, committed and efcient service organization, Atlas Copco ensures superior customer value by maximizing productivity. With a presence in over 170 countries, we offer professional and timely service through interaction and involvement. Uptime is ensured by dedicated technicians and 24/7 availability.

Low environmental impact


Fully compliant with ISO 14001 standards and Montreal Protocol regulations, FD dryers use CFC-free refrigerants (R134a, R410a, R404a) to prevent any damage to the earths ozone layer. FD dryers have an ozone depletion potential (ODP) of zero and are enclosed in a sound suppression canopy to reduce the noise levels, making FD dryers among the most environmentally friendly and quietest in their class. FD series

FD 5-95 & FD 120-285: Superior productivity


6 Optimum performance and safety in all conditions

Hot gas bypass valve prevents freezing at lower loads. R134a piston compressor with high coefcient of performance (FD 5-95) or extremely reliable R410a rotary compressor (FD 120-285) provide the best performance for each size while having minimum environmental impact. Capillary tubes cope with all conditions no moving parts for extra reliability. FD 120-285 also offer condenser with louvered n technology for improved performance in dusty environments.

1 Electronic no-loss condensate drain


Level sensor senses the level of the condensate and opens the drain, preventing any loss of compressed air when condensate is drained. Equipped with backup manual drain as standard and drain alarm (FD 120-285).

* Only for FD 120-285.

5 Advanced control and monitoring system


The controller displays the pressure dewpoint (PDP) and relative humidity. Setting allows dryer to cycle or not (Saver Cycle Control algorithm) and restart or not after power failure. Remote alarm through voltage-free contact. The controller offers additional features such as energy-saving ow switch algorithm, alarm history, standard remote visualization (Ethernet plug) and communication extension possibility (FD 120-285).

2 High-efciency heat exchanger


Counter-ow compact brazed plate (FD 5-50) or aluminum (FD 60-285) heat exchanger, with air-to-air side for optimum cooling efciency.

3 Fan switch


Robust and compact design

Reduces energy consumption and optimizes the pressure dewpoint at very low temperatures.

Forklift opening for easy transport. Inlet and outlet located at the top (can be optional) for easy installation. Easily removed front and side panels for full access.

FD series

FD series

Optional: IP54, DD/PD lters (with pressure drop monitoring for FD 120-285) and OSD (FD 60-285 only) integrated condensate treatment.

FD 310-4000: Superior productivity


1

7 User-friendly state-of-the-art Elektronikon controller


Monitoring of all parameters to ensure maximum reliability for your installation. Fitted inside a real IP54 cubicle for easy cabling and safety.

High-efciency heat exchanger

Counter-ow on both air-to-air and air-to-refrigerant sides for efcient heat transfer. As the outgoing air is reheated, it protects the outlet piping against pipe sweating. Unlike some other dryer designs, a separate pre-lter is not required. This results in a low pressure drop. The design ensures a smooth air ow which makes the dryer less sensitive to contamination.
* The type of controller may vary depending on the model.

2 Integrated water separator


Low velocity condensate separator with high separation efciency even in low ow conditions. Reliable and effective condensate evacuation from the separation chamber via the no-loss condensate drain.

Outgoing dry air Incoming wet air

6 Filters

For processes requiring higher levels of ltration, Atlas Copco offers integrated DD and PD lters (optional on FD 310-510).

5 Hot gas bypass valve


Prevents freezing at lower loads.

3 Electronic no-loss condensate drain


4 Refrigerant circuit

Level sensor senses the level of the condensate and opens the drain, preventing any loss of compressed air when condensate is drained, which is the case with timer-based drains.

Designed to perform reliably under extreme conditions of 50C/122F ambient temperatures and 60C/140F inlet temperatures*. This is due to the sizing of key components such as the heat exchanger, refrigerant compressor, valves etc.

* Some models might require ow correction.

FD series

FD series

Supreme energy efciency


When purchasing a refrigerant dryer, the main focus is usually on the initial cost. What is mostly overseen is that this only represents approximately 10% of the lifecycle cost, the rest being taken up by energy, maintenance and installations costs. Of these, direct and indirect energy costs (pressure drop) are the most important.

Direct energy costs


Direct energy costs are related to the power that the dryer consumes. Atlas Copco's FD dryers incorporate a variety of state-of-the-art technologies such as Saver Cycle Control and Variable Speed Drive. These features result in further savings on energy costs, depending on your air consumption prole.

Lifecycle cost
Indirect energy costs (on average 38%) Direct energy costs (on average 43%)

Saver Cycle Control


To help you save energy, Atlas Copco FD dryers are able to adapt their working cycle to the real load by continuously monitoring and comparing the ambient temperature and the pressure dewpoint. When there is less heat load, the refrigerant compressor stops and power consumption is signicantly reduced.

Variable Speed Drive (VSD)


The VSD controller incorporated in certain FD refrigerant dryers matches the energy consumed to the actual compressed air used. This signicantly reduces energy consumption by as much as 70% compared to conventional dryers. It works by varying the speed of the compressor and ensuring a stable dewpoint. In this way the speed of the refrigeration compressor can be matched to inlet conditions, resulting in lower energy consumption at reduced loads.

Flow switch
If the compressor is unloaded for some time, the ow switch shuts down the refrigerant compressor automatically, typically after ten minutes, saving energy. Investment Installation Maintenance

Indirect energy costs


Indirect energy costs are related to the extra energy your air compressor will consume to overcome the pressure drop of the air dryer. By design, Atlas Copco FD refrigerant dryers offer a low pressure drop and efcient heat transfer both of which contribute to a reduction of the indirect energy costs.

Reduce your total lifecycle cost by up to 50% with Atlas Copcos FD dryers
Up to 50% savings on Indirect energy costs Up to 70% savings on Direct energy costs

Low pressure drops


If a refrigerant dryer has a high internal pressure drop, the compressor needs to run at a higher pressure. As illustrated in the example, this wastes energy and increases operating costs. Atlas Copco has therefore put considerable efforts into minimizing pressure drops in its dryers. A low pressure drop of typically below 0.2 bar/2.9 psi at full ow is ensured by the heat exchanger technology, an integrated low velocity water separator, and generously sized components.
Annual energy cost

Example of the costs related to high pressure drop

0.1/1.4

0.2/2.9

0.3/4.3

0.4/5.8

0.5/7.2

Pressure drop (bar/psi)

Efcient heat transfer through unique heat exchanger technology


The FD dryer uses a counter ow heat exchanger on both the air-to-air and air-to-refrigerant side. Compared to a cross ow heat exchanger, the counter ow design results in a more efcient heat transfer and stable temperatures. This signicantly lowers energy consumption.

Hot wet air (50C) Reheated dry air (45C)

FD series

Cold wet air (30C)

FD series

Low temperature dry air (3C)

A step ahead in control and monitoring


Atlas Copco's Elektronikon controls and monitors your FD refrigerant dryers to ensure optimal productivity and efciency at your site.

User-friendly interface
Available in 32 languages, this graphical 3.5-inch high-denition color display with pictograms and LED indicators for key events is easy to use. The keyboard is durable to resist tough treatment in demanding environments.

Comprehensive maintenance display


Valuable items of information displayed include the ServicePlan indicator and preventive maintenance warnings.

Control and monitoring

Internet-based visualization*
The Elektronikon system monitors and displays key parameters such as dewpoint and inlet temperature, etc. Internet-based visualization of your dryer is possible by using a simple Ethernet connection.

AIRConnect*
AIRConnect is an optional advanced remote monitoring package that offers complete analysis and accurate management. It is fully customizable to meet specic customer needs, from simple alarm notication via email or SMS to visualization via eldbus, LAN or internet, including advanced reporting services.

FD series

* Not applicable for the lower range controllers.

Optimize your system


With the FD, Atlas Copco provides an all-in-one standard package incorporating the latest technology in a built-to-last design. To further optimize your FDs performance or to simply tailor it to your specic production environment, optional features are available.

Scope of supply
Cooling circuit

Electrical components

Mechanical components

Integrated electronic no-loss drain

Elektronikon control

Counter-ow air-to-air heat exchanger Counter-ow air-to-refrigerant heat exchanger

Voltage-free contacts for remote alarm signal Digital pressure dewpoint readout

Additional features & options


Options
GENERAL High efciency coalescing lters General purpose coalescing lters Integrated OSD oil/water condensate separator Anchor pads MOTOR VSD control Saver Cycle Control Control panel protection to IP23 Control panel protection to IP54 OTHER OPTIONS Flow switch Smart pressure dewpoint alarm Automatic hot gas bypass valve Electronic hot gas bypass valve Automatic expansion valve

FD 5-95

FD 120-285

FD 310-510

FD 610

FD 760-1010

FD 1250-2000

FD 2400-4000

(1) (1) - Not available

(2) (2)

(3) (3)

Standard

Optional

(1) FD 5-50: spin-on lters - FD 60-95: integrated lters (2) Integrated lters (3) Spin-on lters

FD series

Technical specications
50 Hz versions
Model Maximum inlet conditions at full ow (ambient/inlet) C AIR-COOLED VERSIONS FD 5 FD 10 FD 15 FD 20 FD 25 FD 30 FD 40 FD 50 FD 60 FD 70 FD 95 FD 120 FD 150 FD 185 FD 220 FD 245 FD 285 FD 310 FD 310 FD 310 FD 410 FD 410 FD 410 FD 510 FD 510 FD 510 FD 610 FD 760 FD 760 VSD FD 870 FD 870 VSD FD 1010 FD 1010 VSD FD 1250 FD 1250 VSD FD 1400 FD 1400 VSD FD 1600 FD 1600 VSD FD 2000 FD 2000 VSD
Inlet ow with a pressure dewpoint (PDP) of 3C/37.4F

Pressure drop at full ow bar psi

Power consumption kW hp

Maximum working pressure bar psi

Compressed air connections mm

Dimensions L in mm W in mm H in kg

Weight

l/s

cfm

lb

50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 40/50 46/56 50/60 40/50 46/56 50/60 40/50 46/56 50/60 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50 40/50

6 10 15 20 25 30 40 50 60 70 95 120 150 185 220 245 285 310 310 310 410 410 410 510 510 510 610 760 760 870 870 1010 1010 1250 1250 1400 1400 1600 1600 2000 2000 310 410 510 610 760 760 870 870 1010 1010 1250 1250 1400 1400 1600 1600 2000 2000 2400 4000

13 21 32 42 53 64 85 106 127 148 201 254 318 392 466 519 604 657 657 657 869 869 869 1081 1081 1081 1293 1611 1611 1844 1844 2141 2141 2650 2650 2968 2968 3392 3392 4240 4240 657 869 1081 1293 1611 1611 1844 1844 2141 2141 2650 2650 2968 2968 3392 3392 4240 4240 5088 8480

0.07 0.11 0.12 0.12 0.17 0.25 0.2 0.2 0.22 0.22 0.22 0.11 0.15 0.22 0.12 0.18 0.22 0.23 0.23 0.23 0.21 0.21 0.21 0.20 0.20 0.20 0.17 0.17 0.17 0.14 0.14 0.17 0.17 0.24 0.24 0.24 0.24 0.13 0.13 0.22 0.22 0.23 0.21 0.2 0.17 0.17 0.09 0.14 0.12 0.17 0.17 0.24 0.24 0.24 0.24 0.13 0.13 0.22 0.22 0.23 0.22

1.02 1.6 1.75 1.75 2.47 3.64 2.91 2.91 3.2 3.2 3.2 1.6 2.18 3.19 1.74 2.61 3.19 3.3 3.3 3.3 3 3 3 2.9 2.9 2.9 2.47 2.47 2.47 2.03 2.03 2.47 2.47 3.5 3.5 3.5 3.5 1.9 1.9 3.2 3.2 3.3 3 2.9 2.47 2.47 1.31 2.03 1.74 2.47 2.47 3.5 3.5 3.5 3.5 1.9 1.9 3.2 3.2 3.3 3.2

0.2 0.2 0.33 0.41 0.41 0.41 0.57 0.54 0.63 0.87 1.18 1 1 1.4 1.9 2.1 2.2 2.8 2.8 2.9 3 4.6 4.8 4.5 6.4 6.9 4.8 5.3 5.3 6.6 5.8 7.4 6.6 8.3 10 8.5 9.3 13.6 13.3 20 19.5 2 2.4 4.1 3.1 3.6 3.3 4.5 4.2 5.1 5.6 8.1 9.7 7.3 8.5 11.8 9.3 17 13.5 18.3 27.9

0.27 0.27 0.45 0.56 0.56 0.56 0.76 0.72 0.84 1.17 1.58 1.3 1.3 1.9 2.5 2.8 2.9 3.75 3.75 3.89 4.02 6.17 6.44 6.03 8.58 9.25 6.4 7.1 7.1 8.8 7.8 9.9 8.8 11.13 13.41 11.4 12.47 18.24 17.84 26.82 26.15 2.68 3.22 5.5 4.2 4.8 4.4 6 5.6 6.8 7.5 10.86 13.01 9.79 11.4 15.82 12.47 22.8 18.1 24.54 37.41

16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 13 13 13 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 13 13 13 13 13 13 13 13 14 14 14 14 14 14 14 14 14 14 13 13 13 13 13 13 13 13 13 13

233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 189 189 189 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 189 189 189 189 189 189 189 189 203 203 203 203 203 203 203 203 203 203 189 189 189 189 189 189 189 189 189 189

R 3/4 R 3/4 R 3/4 R 3/4 R 3/4 R 3/4 R1 R1 R1 R1 R1 1 1/2 1 1/2 2 1/2 2 1/2 2 1/2 2 1/2 G3 G3 G3 G3 G3 G3 G3 G3 G3 DIN100 DIN100 DIN100 DIN150 DIN150 DIN150 DIN150 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 G3 G3 G3 DIN100 DIN100 DIN100 DIN150 DIN150 DIN150 DIN150 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN200 DIN250

525.5 525.5 525.5 525.5 525.5 525.5 716 716 795 795 795 1015 1015 1024 1024 1024 1024 986 986 986 986 1250 1525 1250 1525 1525 1040 1245 1245 1245 1245 1580 1580 1640 1640 1640 1640 2660 2660 2660 2660 986 1250 1250 1245 1245 1580 1245 1580 1245 1580 1300 1300 1300 1300 2120 2120 2120 2120 2000 2200

20.7 20.7 20.7 20.7 20.7 20.7 28.2 28.2 28.2 28.2 28.2 40 40 40.3 40.3 40.3 40.3 38.8 38.8 38.8 38.8 49.2 60 49.2 60 60 40.9 49 49 49 49 62.2 62.2 64.6 64.6 64.6 64.6 104.7 104.7 104.7 104.7 38.8 49.2 49.2 49 49 62.2 49 62.2 49 62.2 51.2 51.2 51.2 51.2 83.5 83.5 83.5 83.5 78.7 86.6

390 390 390 390 390 390 389 389 482 482 482 675 675 816 816 816 816 850 850 850 850 850 850 850 850 850 1060 1060 1060 1060 1060 1060 1060 1350 1350 1350 1350 1350 1350 1350 1350 850 850 850 1060 1060 1060 1060 1060 1060 1060 1350 1350 1350 1350 1350 1350 1350 1350 1350 2300

15.4 15.4 15.4 15.4 15.4 15.4 15.3 15.3 19.0 19.0 19.0 26.6 26.6 32.1 32.1 32.1 32.1 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 41.7 41.7 41.7 41.7 41.7 41.7 41.7 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 33.5 33.5 33.5 41.7 41.7 41.7 41.7 41.7 41.7 41.7 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 90.6

530 530 530 530 530 530 679 679 804 804 804 881 881 943 943 943 943 1190 1190 1190 1375 1375 1375 1375 1375 1375 1580 1580 1580 1580 1580 1580 1580 1880 1880 1880 1880 1880 1880 1880 1880 1190 1375 1375 1580 1580 1580 1580 1580 1580 1580 1880 1880 1880 1880 1880 1880 1880 1880 1880 1910

20.9 20.9 20.9 20.9 20.9 20.9 26.8 26.8 31.7 31.7 31.7 34.7 34.7 37.1 37.1 37.1 37.1 46.9 46.9 46.9 54.1 54.1 54.1 54.1 54.1 54.1 62.2 62.2 62.2 62.2 62.2 62.2 62.2 74 74 74 74 74 74 74 74 46,9 54,1 54,1 62.2 62.2 62.2 62.2 62.2 62.2 62.2 74 74 74 74 74 74 74 74 74 75.2

27 27 32 34 34 34 57 58 80 81 87 170 170 185 197 197 197 198 200 202 220 240 290 260 310 315 320 380 380 400 400 460 460 860 860 940 940 1280 1300 1345 1325 180 240 260 350 360 410 370 410 380 410 750 750 820 820 1090 1110 1155 1135 1155 2010

60 60 70 75 75 75 125 128 176 178 192 375 375 408 434 434 434 437 441 445 485 529 639 573 683 694 705 838 838 882 882 1014 1014 1896 1896 2072 2072 2822 2866 2965 2921 397 529 573 772 794 904 816 904 838 904 1653 1653 1808 1808 2403 2447 2546 2502 2546 4431

Water-cooled versions FD 310 50/60 FD 410 50/60 FD 510 50/60 FD 610 40/50 FD 760 40/50 FD 760 VSD 40/50 FD 870 40/50 FD 870 VSD 40/50 FD 1010 40/50 FD 1010 VSD 40/50 FD 1250 40/50 FD 1250 VSD 40/50 FD 1400 40/50 FD 1400 VSD 40/50 FD 1600 40/50 FD 1600 VSD 40/50 FD 2000 40/50 FD 2000 VSD 40/50 FD 2400 VSD 40/50 FD 4000 VSD 40/50

(1) 20 bar(g)/290 psi(g) variant available Reference conditions: Performance data per ISO 7183:2007 Ambient temperature: 25C, 77F Inlet compressed air temperature: 35C, 95F Inlet pressure: 7 bar(e)/102 psig Refrigerant types: FD 5-95: R134a FD 120-1010: R410a FD 1250-4000: R404a
L W

FD series

60 Hz versions
Model Maximum inlet conditions at full ow (ambient/inlet)
Inlet ow with a pressure dewpoint (PDP) of 3C/37.4

Pressure drop at full ow bar psi

Power consumption kW hp

Maximum working pressure bar psi

Compressed air connections mm

Dimensions L in mm W in mm H in kg

Weight lb

l/s AIR-COOLED VERSIONS FD 5 FD 10 FD15 FD 20 FD 25 FD 30 FD 40 FD 50 FD 60 FD 70 FD 95 FD 120 FD 150 FD 185 FD 220 FD 245 FD 285 FD 310 (1) FD 310 (1) FD 310 (1) FD 410 (1) FD 410 (1) FD 410 (1) FD 510 (1) FD 510 (1) FD 510 (1) FD 610 FD 760 FD 760 VSD FD 870 FD 870 VSD FD 1010 FD 1010 VSD FD 1250 FD 1250 VSD FD 1400 FD 1400 VSD FD 1600 FD 1600 VSD FD 2000 FD 2000 VSD

cfm

122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 122/140 104/122 115/133 122/140 104/122 115/133 122/140 104/122 115/133 122/140 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122 104/122

6 10 15 20 25 30 40 50 60 70 95 120 140 170 220 230 285 310 310 310 410 410 410 510 510 510 610 760 760 870 870 1010 1010 1250 1250 1400 1400 1600 1600 2000 2000 310 410 510 610 760 760 870 870 1010 1010 1250 1250 1400 1400 1600 1600 2000 2000 2400 4000

13 21 32 42 53 64 85 106 127 148 201 254.4 296.8 360.4 466.4 487.6 604.2 657 657 657 869 869 869 1081 1081 1081 1293 1611 1611 1844 1844 2141 2141 2650 2650 2968 2968 3392 3392 4240 4240 657 869 1081 1293 1611 1611 1844 1844 2141 2141 2650 2650 2968 2968 3392 3392 4240 4240 5088 8480

0.07 0.11 0.12 0.12 0.17 0.25 0.2 0.2 0.22 0.22 0.22 0.11 0.14 0.22 0.12 0.18 0.22 0.23 0.23 0.23 0.21 0.21 0.21 0.2 0.2 0.2 0.17 0.17 0.17 0.14 0.14 0.17 0.17 0.24 0.24 0.24 0.24 0.13 0.13 0.22 0.22 0.23 0.21 0.20 0.17 0.17 0.09 0.14 0.12 0.17 0.17 0.24 0.24 0.24 0.24 0.13 0.13 0.22 0.22 0.23 0.22

1.02 1.6 1.75 1.75 2.47 3.64 2.91 2.91 3.2 3.2 3.2 1.6 2.03 3.19 1.74 2.61 3.19 3.3 3.3 3.3 3 3 3 2.9 2.9 2.9 2.47 2.47 2.47 2.03 2.03 2.47 2.47 3.5 3.5 3.5 3.5 1.9 1.9 3.2 3.2 3.3 3.0 2.9 2.47 2.47 1.31 2.03 1.74 2.47 2.47 3.5 3.5 3.5 3.5 1.9 1.9 3.2 3.2 3.3 3.2

0.23 0.23 0.34 0.53 0.53 0.53 0.73 0.79 0.63 0.87 1.18 1.73 2.35 2.32 2.58 2.85 3.09 4.3 4.6 4.6 4.5 6.1 7.3 7.3 9.1 10.4 7.6 8.1 9.1 10.2 11.1 11.9 11.4 13.6 8.5 14.1 8.6 18.4 16.1 26 24.9 2.5 3.2 5.0 3.9 4.5 4.3 5.8 5.6 6.2 6.1 9.8 5 9.5 5.1 12 8.1 19 12.9 9.8 13.2

0.31 0.31 0.46 0.71 0.71 0.71 0.98 1.06 0.84 1.17 1.58 2.3 3.2 3.1 3.5 3.8 4.1 5.77 6.17 6.17 6.03 8.18 9.79 9.79 12.2 13.95 10.2 10.9 12.2 13.7 14.9 16 15.3 18.24 11.4 18.91 11.53 24.67 21.59 34.87 33.39 3.35 4.29 6.71 5.2 6 5.8 7.8 7.5 8.3 8.2 13.14 6.71 12.74 6.84 16.09 10.86 25.48 17.3 13.14 17.7

16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 16 (1) 13 13 13 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 13 13 13 13 13 13 13 13 14 14 14 14 14 14 14 14 14 14 13 13 13 13 13 13 13 13 13 13

233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 233 (1) 189 189 189 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 203 189 189 189 189 189 189 189 189 203 203 203 203 203 203 203 203 203 203 189 189 189 189 189 189 189 189 189 189

NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 1/2 NPT 1 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 2 1/2 NPT 3 NPT 3 NPT 3 NPT 3 NPT 3 NPT 3 NPT 3 NPT 3 NPT 3 ANSI 4 ANSI 4 ANSI 4 ANSI 6 ANSI 6 ANSI 6 ANSI 6 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 NPT 3 NPT 3 NPT 3 ANSI 4 ANSI 4 ANSI 4 ANSI 6 ANSI 6 ANSI 6 ANSI 6 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 8 ANSI 10

496 496 496 496 496 496 688 689 726 726 726 836 836 1024 1024 1024 1024 986 986 986 986 1250 1525 1250 1525 1525 1040 1245 1245 1245 1580 1580 1580 1640 1640 1640 1640 2660 2660 2660 2660 986 1525 1525 1245 1245 1580 1245 1580 1245 1580 1300 1300 1300 1300 2120 2120 2120 2120 2000 2200

19.5 19.5 19.5 19.5 19.5 19.5 27.1 27.1 28.6 28.6 28.6 32.9 32.9 40.3 40.3 40.3 40.3 38.8 38.8 38.8 38.8 49.2 60 49.2 60 60 40.9 49 49 49 62.2 62.2 62.2 64.6 64.6 64.6 64.6 104.7 104.7 104.7 104.7 38.8 60.0 60.0 49 49 62.2 49 62.2 49 62.2 51.2 51.2 51.2 51.2 83.5 83.5 83.5 83.5 78.7 86.6

377 377 377 377 377 377 389 389 482 482 482 661 661 816 816 816 816 850 850 850 850 850 850 850 850 850 1060 1060 1060 1060 1060 1060 1060 1350 1350 1350 1350 1350 1350 1350 1350 850 850 850 1060 1060 1060 1060 1060 1060 1060 1350 1350 1350 1350 1350 1350 1350 1350 1350 2300

14.8 14.8 14.8 14.8 14.8 14.8 15.3 15.3 19.0 19.0 19.0 26.0 26.0 32.1 32.1 32.1 32.1 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 41.7 41.7 41.7 41.7 41.7 41.7 41.7 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 33.5 33.5 33.5 41.7 41.7 41.7 41.7 41.7 41.7 41.7 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 53.1 90.6

461 461 461 461 461 461 604 604 804 804 804 802 802 943 943 943 943 1190 1190 1190 1375 1375 1375 1375 1375 1375 1580 1580 1580 1580 1580 1580 1580 1880 1880 1880 1880 1880 1880 1880 1880 1190 1375 1375 1580 1580 1580 1580 1580 1580 1580 1880 1880 1880 1880 1880 1880 1880 1880 1880 1910

18.1 18.1 18.1 18.1 18.1 18.1 23.8 23.8 31.7 31.7 31.7 31.6 31.6 37.1 37.1 37.1 37.1 46.9 46.9 46.9 54.1 54.1 54.1 54.1 54.1 54.1 62.2 62.2 62.2 62.2 62.2 62.2 62.2 74 74 74 74 74 74 74 74 46.9 54.1 54.1 62.2 62.2 62.2 62.2 62.2 62.2 62.2 74 74 74 74 74 74 74 74 74 75.2

27 27 32 34 34 34 57 58 80 81 87 170 170 185 197 197 197 198 200 202 220 240 290 260 310 315 320 380 380 400 450 460 460 750 750 940 940 1280 1300 1345 1325 180 240 260 350 360 410 370 410 380 410 750 750 820 820 1100 1110 1155 1155 1180 2010

60 60 70 75 75 75 125 128 176 178 192 375 375 408 434 434 434 437 441 445 485 529 639 573 683 694 705 838 838 882 992 1014 1014 1653 1653 2072 2072 2822 2866 2965 2921 397 529 573 772 794 904 816 904 838 904 1653 1653 1808 1808 2425 2447 2546 2546 2601 4431

Water-cooled versions FD 310 122/140 FD 410 122/140 FD 510 122/140 FD 610 104/122 FD 760 104/122 FD 760 VSD 104/122 FD 870 104/122 FD 870 VSD 104/122 FD 1010 104/122 FD 1010 VSD 104/122 FD 1250 104/122 FD 1250 VSD 104/122 FD 1400 104/122 FD 1400 VSD 104/122 FD 1600 104/122 FD 1600 VSD 104/122 FD 2000 104/122 FD 2000 VSD 104/122 FD 2400 VSD 104/122 FD 4000 VSD 104/122 (1) 20 bar(g)/290 psi(g) variant available Reference conditions:

Refrigerant types: FD 5-95: R134a FD 120-1010: R410a FD 1250-4000: R404a


L

FD series

Ambient temperature: 38C, 100F Inlet compressed air temperature: 38C, 100F Inlet pressure: 7 bar(e)/102 psig

Driven by innovation With more than 135 years of innovation and experience, Atlas Copco will deliver the products and services to help maximize your companys efciency and productivity. As an industry leader, we are dedicated to offering high air quality at the lowest your bottom line and bring you peace of mind. Building on interaction As part of our long-term relationship with our customers, we have accumulated extensive knowledge of a wide diversity of processes, needs and objectives. This gives us the exibility to adapt and efciently produce customized compressed air solutions that meet and exceed your expectations. A committed business partner With a presence in over 170 countries, we will deliver high-quality customer service anywhere, anytime. Our highly skilled technicians are available 24/7 and are supported by an efcient logistics organization, ensuring fast delivery of genuine spare parts when you need them. We are committed to providing the best possible know-how and technology to help your company produce, grow, and succeed. With Atlas Copco you can rest assured that your superior productivity is our rst concern!
2935 0582 10 Printed in Belgium Subject to alteration without prior notice. Never use compressed air as breathing air without prior purication in accordance with local legislation and standards.

possible cost of ownership. Through continuous innovation, we strive to safeguard

www.atlascopco.com

Potrebbero piacerti anche