Dimensioning menu Calculation modules With these modules you can evaluate specic application cases from an engineering standpoint and select and order the products suitable for your application case via product group selections. You are also provided with additional information on the application cases, the products and the technical background of evaluation, calculation and planning from an engineering standpoint. Industries menu Anchor technology application selection The main applications for your industry Heating, plumbing, air-conditioning, ventilation Wood processing and wood working Metal processing and metal working Construction /Expansion Electrical/communication engineering Industry, public authorities are recorded and assigned here. The usable systems are suggested to you. Also use the practical keyword search to nd our products quickly.

Design details menu Do you require design details of individual anchor products for integration in CAD drawings? Download them onto your computer here. Product index menu Anchor product specications You know what you need simply click on the desired products on the left to receive detailed information, e.g. Product information Serial number, designation, image Version Approvals (download possible) Area of use, advantages, features Setting instructions Performance data Characteristic values Dimensions Demand assessment Ordering data Downloading of entire product specications (incl. installation instructions)

ANCHOR TECHNOLOGY DIMENSIONING SOFTWARE


The Wrth Dimensioning Software designed for intuitive use and proven in practice, enables you to individually evaluate and realistically dimension safe, economical attachments. The following modules are available for measuring:

You can order the software on CD-ROM (Art. No. 0990 903 002) at www.wuerth.de/duebeltechnik. Wrth anchor dimensioning software of an early version which is already installed can be updated and supplemented with missing modules at any time with Internet updates. Of course, you can always use the software directly on our homepage.

General anchor dimensioning Railings Facades Awnings Sub-structures for awnings Suspended ceilings
MWF - 11/11 - 09041 -

Brackets and bracket supports REBAR Fire protection Set pins VARIFIX Wood construction Light metal construction Art. No. 0990 903 002

PERFORMANCE OVERVIEW OF ANCHOR TECHNOLOGY


General construction permit 1) Attachment of facade coverings 2) Multiple attachment of non-load-bearing systems European Technical Approval Fire resistance (TR020) Fire resistance in acc. with VdS Directives Test report available available

Included in approval Included in approval

02.1 02.2 02.3

Included in approval Included in approval Included in approval

02.5 02.6 02.7 02.8

03 06

/ / /

07.1 11.1 11.2 13.1 13.2 13.3 15.1 16 31

32 34.1 34.2 34.3 SZ 1.1

Cracked Uncracked concrete concrete (tensile zone)

Lightweight concrete

Aerated concrete

Solid stone masonry

Perforated stone masonry 21.1 21.2 21.3 22 23.1 23.2 23.3 23.4

KR - 11/11 - 10757 -

23.5

can be loaded immediately

Test report

Cotter pin mounting

Cracked Uncracked concrete concrete (tensile zone) (pressure zone)

Suspended ceiling

Multiple attachment

Aerated concrete

Solid stone masonry

Product Specication No. Throughbolt mounting

Surface

Installation

PERFORMANCE OVERVIEW OF ANCHOR TECHNOLOGY

Anchor type

Anchor Illustrations

Galvanized steel

Hot galvanized

W-SA Screw Anchor W-SA Screw Anchor W-SA TC Screw Anchor Timber Connect W-FAZ / Fixing Anchor W-FAZ-IG / Fixing Anchor Inner Thread W-HAZ High-Performance Anchor W-PA Aerated Concrete Anchor W-HD Hollow-Ceiling Anchor W-FA / Fixing Anchor W-ED / Drive-In Anchor W-ED M12 Drive-In Anchor W-ED DW15 Drive-In Anchor W-TM Heavy Duty Anchor W-SA Screw Anchor W-DS Quick-Action Ceiling Anchor W-ZS 6-5 Quick-Action Anchor W-SD Impact Anchor W-PN Power Nail

7.5 - 20 7.5 7.5/10/12 M8 - M24 M6 - M12 M6 - M20 M6 - M12 M6 - M12 M6 - M20 M5 - M20 M12/DW15 M6 - M12 5. 6. 7.5 8 6 6. 8 4.5

W-VD / Shear Anchor W-VD-IG / ... Shear-Anchor Female Thread W-VHP Shear Anchor Hammer Cartridge W-VIZ / Injection System a) W-VI / Injection System b)
KR - 11/11 - 10758 -

M8 - M24 M8 - M16 10 - 16 M8 - M24 M8 - M30 M8 - M24

WIT-C 100 Injection System

a)

WIT-VM 100 Mortar compound

b)

WIT-VM 200 Mortar compound

HCR steel 1.4529

A2 Stainless steel A4 Stainless steel

Thread size or dia. of anchor in mm

Available versions

Outer thread

Inner thread

PERFORMANCE OVERVIEW OF ANCHOR TECHNOLOGY


General construction permit Attachment of facade coverings 2) Multiple attachment of non-load-bearing systems
1)

European Technical Approval Test report available available Fire resistance in acc. with VdS Directives Product Specication No.

Surface
Cracked Uncracked concrete concrete (tensile zone) Lightweight concrete Aerated concrete Solid stone masonry Perforated stone masonry

Installation
Throughbolt mounting
can be loaded immediately

Test report

23.6 23.7 23.8 23.9 24.1 24.2 25 26.1 28.1


c) c)

29.1 Aerated concrete Solid stone masonry


1)

Concrete

Lightweight concrete

Perforated stone masonry

Plate materials/ hollow walls 41

1)

1) 2) 2)

1) 2) 2)

1) 2)

1) 2)

1) 2)

42.1 42.2 42.3

2)

2)

2)

2)

42.5 43.1 44 51 52 53 55.1 55.2 55.3 61 62

KR - 11/11 - 10759 -

63 63.2
c)

Reinforcement attachment

Cotter pin mounting

PERFORMANCE OVERVIEW OF ANCHOR TECHNOLOGY


Test report available Available Fire resistance

in accordance with VdS Directives

Product Specication No. Throughbolt mounting 64 71 73 74 74.1 75 81 82 83 91 92 92.1 93 94 95 96 97 99 99.1 110 111

Substrate
Concrete Lightweight concrete Aerated concrete Solid stone masonry Perforated stone masonry Plate materials/ hollow walls

Montageart
Cotter-pin mounting can be loaded immediately

KR - 11/11 - 10892 -

Test report

PERFORMANCE OVERVIEW FOR ANCHOR TECHNOLOGY

Anchor type

Anchor illustrations

Galvanized steel

Hot galvanized

W-KH Plastic Hollow-Wall Anchor W-MG Metal Multi-Purpose Anchor W-GS Gypsum Plasterboard Anchor W-KL Light Construction Anchor W-ID Insulating Anchor W-GB Aerated Concrete Anchor W-DSD Insulation Anchor with expansion nail W-IN Insulation Nail W-MID Insulation Bolt and Insulation Disk Nylon anchor ZEBRA Shark W-ZX ZEBRA Shark Anchors W-ZND Nail Anchor Securing sleeve Hammer rivet Brass anchor W-SSD Sound Protection Anchor AMO -Max AMO light Screw High-Performance Stud Thrust Device DIVA 1 Premium High-Performance Fuel Unit DIGA CS-1

Dia. 10 Dia. 5 - 10 Dia. 18 Dia. 18 + 30 Dia. 10 - 14 Dia. 10 Dia. 8 Dia. 8 Dia. 4 - 20 Dia. 5 - 14 Dia. 5 - 14 Dia. 5 - 10 6 - 8 mm dia. Dia. 4.8 - 6.4 M4 - M16 Dia. 10 - 18 Dia. 40 Dia. 10

MWF - 11/11 - 10893 -

HCR steel 1.4529

Stainless steel A2

Stainless steel A4

Thread size or dia. of anchor thread in mm

Available versions

Female thread

Male thread

W-FAZ/S FIXING ANCHOR

02.5
Individual attachment: Cracked and uncracked concrete

W-FAZ/S, galvanized steel

W-FAZ/S, galvanized steel with large washer

For W-FAZ/A4 Fixing Anchor, see 02.6 For W-FAZ/HCR Fixing Anchor, see 02.6

Proof of performance Approvals European Technical Approval


Option 1 for cracked and uncracked concrete

Test reports Fire resistance Direct ame eect

2. Advantages
High loads, small axle bases and edge clearances Time-saving through-bolt mounting Can be loaded immediately no waiting times The fixing anchor cone with patented plastic coating enables safe subsequent expansion in cracked concrete Reliable mounting thanks to the application of the prescribed torque when anchoring

Fire resistance
Technical Report TR 020 R30-R120

Machine Setting Tool for xing anchors (W-FA & W-FAZ) M8 M16

Art. No. 0904 908 016 For details, see separate product information

1. Applications
Can be used for medium to heavy loads Suitable for fastening: Metal structures, metal profiles, brackets, foot plates, supports, cable conduits, piping, railings, wooden structures, beams etc. With European Technical Approval, the anchor may be used in reinforced or unreinforced standard concrete of a strength class of at least C20/25 and at most C50/60 in accordance with EN 206:2000-12 For use in concrete < C20/25 and pressure-resistant natural stone (without approval) The anchor may be used for anchoring under primarily static loads or quasi-static loads Individual fastening: Anchoring with European Technical Approval in cracked concrete (concrete tensile zone) and in uncracked concrete (concrete pressure zone) W-FAZ/S may only be used under the conditions of dry interior rooms

3. Properties
Force-controlled/torque-controlled spreading anchor made of electrogalvanized steel in sizes M8, M10, M12, M16, M20 and M24 Approval: ETA-99/0011 for individual fastening Option 1, cracked and uncracked concrete, galvanized steel M8 M24; dimensioned in accordance with the "European Technical Approval Guideline (ETAG) of Metal Anchors for Use in Concrete" Appendix C, Measurement Process A Fire resistance: W-FAZ/S (M8 M16) F30, F60, F90 and F120; fire load according to DIN 4102-02:1977-09 (ETK Einheits-Temperaturzeitkurve (standard temperature time curve)) Fire resistance: W-FAZ/S (M8 M24) R30, R60, R90, R120; Technical Report TR020 (contained in ETA-99/0011)

Setting instructions

MWF - 04/11 - 04256 -

Drill hole

Clean drilled hole

Knock in anchor with mason's mallet or machine setting tool

Mount component

Apply torque

W-FAZ/S FIXING ANCHOR


Performance data
Anchor diameter [in mm] M8 M10 Tensile zone (cracked concrete C20/252), 2.4 4.3 Permissible tensile load1) s 3 hef, c 1.5 hef) N perm. [kN] = C20/252) on a single anchor Pressure zone without edge influence (uncracked concrete C20/252) ) 5.7 7.6 (scr,sp 3 hef, ccr,sp 1.5 hef) Tensile zone (cracked concrete C20/252), 8.6 12.6 Permissible transverse c 10 hef) 1) load Vperm. [kN] = C20/252) on a single anchor Pressure zone without edge influence (uncracked concrete C20/252), 8.6 12.6 c 10 hef) Permissible bending torque M perm. [Nm] 13.1 26.9 Permissible load under fire load (R30, R60, R90, R120) see European Technical Approval ETA-99/0011 F30 [in kN] 2.0 5.6 F60 [in kN] 1.0 2.2 Fire resistance duration F90 [in kN] 0.65 1.3 F120 [in kN] 0.5 0.8 M12 7.6 11.9 17.1 17.1 46.9 9.0 3.5 2.0 1.3

02.5

M16 11.9 16.7 26.9 34.3 119.4 16.0 7.0 4.3 3.0

M20 17.1 24.0 34.3 37.1 195.0

M24 21.1 29.6 42.3 59.2 513.1

Characteristic values
Axial spacing Edge spacing Standard minimum component thickness Minimum axial spacing Cracked concrete Uncracked concrete Minimum edge spacing Cracked concrete Uncracked concrete Reduced minimum component thickness Minimum axial spacing Cracked concrete Uncracked concrete Minimum edge spacing Cracked concrete Uncracked concrete Effective anchoring depth Nom. drill dia. Drill cutting dia. Drill hole depth Through-hole in the component being connected Torque while installing anchor scr,N [in mm] ccr,N [in mm] hstd [in mm] s min [in mm] for c [mm] c min [in mm] for s [in mm] h min [mm] s min [in mm] for c [mm] c min [in mm] for s [in mm] hef [in mm] d 0 [in mm] dcut [in mm] h1 [in mm] d f [in mm] T inst [Nm] 138 69 100 40 70 40 80 80 40 70 40 80 46 8 8.45 60 9 20 180 90 120 45 70 45 90 100 45 90 50 115 60 10 10.45 75 12 25 210 105 140 60 100 60 140 120 60 100 60 140 70 12 12.5 90 14 45 255 127.5 170 60 100 60 180 140 70 160 80 180 85 16 16.5 110 18 90 300 150 200 95 150 95 200 100 20 20.55 125 22 160 345 172.5 230 100 180 100 220 115 24 24.55 145 26 200

40 80 50 100 40 80 50 100

45 70 50 100 60 140 90 140

60 120 75 150 60 120 75 150

65 120 80 150 80 180 90 200

90 180 130 240

100 180 100 220

Anchor dimensions
Anchor diameter Total length Max. attachment height [in mm] l [in mm] t fix [in mm] M8 M10 M12 M16 M20 M24 75 95 115 165 95 110 130 110 125 145 160 180 200 220 240 255 285 325 145 170 220 260 300 165 195 265 285 190 220 235 100 100 100 50 50 50 50 25 25 25 25 25 25 25 20 20 20 20 20 20 10 10 10 10 10 5 5 10 10 5
1) 2)

Designation

W-FAZ/S Fixing Anchor Galvanized steel

Art. No.

W-FAZ/S Fixing Anchor Galvanized steel with large washer Packing unit Can be stored in ORSY
MWF - 06/11 - 04257 -

Art. No.

P. Qty.

Wrth system components


The part safety coe cients of the resistances regulated in the approval and a part safety coe cient of the e ects of F = 1.4 have been taken into account. For the combination of tensile and transverse loads, for edge inuence and anchor groups, please refer to the Directive for European Technical Approval (ETAG) Appendix C. The concrete has normal reinforcement. Higher values are possible for higher concrete strengths.

0904 531 211 0904 531 212 0904 531 213 0904 531 214 0904 531 215 0904 531 216

0904 520 801 0904 520 802 0904 520 803 0904 520 804 0904 521 001 0904 521 002 0904 521 003 0904 521 211 0904 521 212 0904 521 213 0904 521 214 0904 521 215 0904 521 216 0904 521 217 0904 521 218 0904 521 219 0904 521 601 0904 521 602 0904 521 603 0904 521 604 0904 521 605 0904 522 001 0904 522 002 0904 522 003 0904 522 004 0904 522 401 0904 522 402 0904 522 403

W-FAZ/S M8-10/75 W-FAZ/S M8-30/95 W-FAZ/S M8-50/115 W-FAZ/S M8-100/165 W-FAZ/S M10-15/95 W-FAZ/S M10-30/110 W-FAZ/S M10-50/130 W-FAZ/S M12-15/110 W-FAZ/S M12-30/125 W-FAZ/S M12-50/145 W-FAZ/S M12-65/160 W-FAZ/S M12-85/180 W-FAZ/S M12-105/200 W-FAZ/S M12-125/220 W-FAZ/S M12-145/240 W-FAZ/S M12-160/255 W-FAZ/S M12-190/285 W-FAZ/S M12-230/325 W-FAZ/S M16-25/145 W-FAZ/S M16-50/170 W-FAZ/S M16-100/220 W-FAZ/S M16-140/260 W-FAZ/S M16-180/300 W-FAZ/S M20-30/165 W-FAZ/S M20-60/195 W-FAZ/S M20-130/265 W-FAZ/S M20-150/285 W-FAZ/S M20-30/190 W-FAZ/S M20-60/220 W-FAZ/S M20-75/235

10 30 50 100 15 30 50 15 30 50 65 85 105 125 145 160 190 230 25 50 100 140 180 30 60 130 150 30 60 75

W-FAZ/A4 W-FAZ/HCR FIXING ANCHORS

02.6
Individual attachment: Cracked and uncracked concrete

W-FAZ/A4, Stainless steel A4

W-FAZ/HCR (via special order) Highly corrosion-resistant steel (1.4529) For W-FAZ/S Fixing Anchor, see 02.5

Proof of performance Approvals European Technical Approval


Option 1 for cracked and uncracked concrete

Test reports Fire resistance Direct ame eect

2. Advantages

Fire resistance
Technical Report TR 020 R30 - R120

High loads, small axle bases and edge clearances Time-saving through-bolt mounting Can be loaded immediately no waiting times The fixed anchor cone with patented plastic coating facilitates reliable later expansion Reliable mounting thanks to the application of the prescribed torque when anchoring

Machine Setting Tool for xing anchors (W-FA & W-FAZ) M8 M16

3. Properties
Can be used for medium to heavy loads Suitable for fastening: Metal structures, metal profiles, brackets, foot plates, supports, cable conduits, piping, railings, wooden structures, beams etc. With European Technical Approval, the anchor may be used in reinforced or unreinforced standard concrete of a strength class of at least C20/25 and at most C50/60 in accordance with EN 206:2000-12 For use in concrete < C20/25 and pressure-resistant natural stone (without approval) The anchor may be used for anchoring under primarily static loads or quasi-static loads Individual fastening: Anchoring with European Technical Approval in cracked concrete (concrete tensile zone) and in uncracked concrete (concrete pressure zone) W-FAZ/A4 (stainless steel A4) may be used in dry indoor rooms, outdoors (including industrial atmospheres and near the sea) or in humid rooms if no especially aggressive conditions exist W-FAZ/HCR (highly corrosion-resistant steel HCR) may be used in areas with a very high corrosion potential e.g. indoor pool atmosphere, road tunnels, poorly ventilated parking garages and parts in seawater and in a marine atmosphere).

1. Applications

Force-controlled/torque-controlled spreading anchor made of stainless steel A4 and highly corrosion-resistant steel HCR in the sizes M8, M10, M12, M16 and M20 Approvals: ETA-99/0011 for individual attachment Option 1, cracked and uncracked concrete, stainless steel A4 and HCR highly corrosionresistant steel; dimensioned in accordance with the "Guideline for European Technical Approval (ETAG) of Metal Anchors for Use in Concrete", Appendix C, Measurement Process A Fire resistance: W-FAZ/A4, W-FAZ/HCR (M8 M16) R30, R60, R90, R120 Technical Report TR020 (contained in ETA-99/0011) Fire resistance: W-FAZ/A4, W-FAZ/HCR (M8 M16) F30, F60, F90 and F120 Fire load according to DIN 4102-02:1977-09 (ETK Einheits-Temperaturzeitkurve (standard temperature time curve)) Fire resistance: W-FAZ/HCR (M8 M16) Fire load according to the ZTV tunnel fire compartment curve

Art. No. 0904 908 016 For details, see separate product information

Setting instructions

MWF - 06/11 - 04381 -

Drill hole

Clean drilled hole

Knock in anchor with mason's mallet or machine setting tool

Mount component

Apply torque

W-FAZ/A4 W-FAZ/HCR FIXING ANCHORS


Performance data
Perm. centered tensile load1) on a single anchor without edge influence Anchor diameter [in mm] M8 M10 Tensile zone 2.4 4.3 (cracked concrete C20/252), s 3 hef, c 1.5 hef) N perm. [kN] = C20/252) Pressure zone (uncracked concrete 5.7 7.6 C20/252),scr,sp and ccr,sp see approval Tensile zone Perm. 7.4 11.4 (uncracked concrete C20/252), transverse c 10 hef) load1) Vperm. [kN] = C20/252) on a single Pressure zone anchorwithout (uncracked concrete C20/252), 7.4 11.4 edge influence c 10 hef) Permissible bending torque M perm [Nm] 14.9 29.7 Permissible load under fire load (R30, R60, R90, R120) see European Technical Approval ETA-99/0011 F30 [in kN] 9.0 15.0 F60 [in kN] 5.0 9.0 Fire resistance duration (anchoring base: concrete C20/25) F90 [in kN] 1.8 4.0 F120 [in kN] 1.0 2.0

02.6

M12 7.6 11.9 17.1 17.1 52.6 19.0 12.0 5.0 3.0

M16 11.9 16.7 26.9 31.4 133.1 30.0 15.0 7.5 6.0

M20 17.1 24.0 34.3 43.9 231.6

Characteristic values
Standard minimum component thickness Minimum axial spacing Cracked concrete Uncracked concrete Minimum edge spacing Cracked concrete Uncracked concrete Reduced minimum component thickness Minimum axial spacing Cracked concrete Uncracked concrete Minimum edge spacing Cracked concrete Uncracked concrete Axial spacing Edge spacing Effective anchoring depth Nom. drill dia. Drill cutting dia. Drill hole depth Through-hole in the component being connected Torque while installing anchor hstd [in mm] s min [in mm] for c [in mm] c min [in mm] for s [in mm] h min [in mm] s min [in mm] for c [in mm] c min [in mm] for s [in mm] scr,N [in mm] ccr,N [in mm] hef [in mm] d 0 [in mm] dcut [in mm] h1 [in mm] d f [in mm] T inst = [in Nm] 100 40 70 40 80 80 40 70 40 80 138 69 46 8 8.45 60 9 20 40 80 50 100 40 80 50 100 120 50 75 55 90 100 45 90 50 115 180 90 60 10 10.45 75 12 35 50 75 60 120 60 140 90 140 140 60 100 60 140 120 60 100 60 140 210 105 70 12 12.5 90 14 50 60 120 75 150 60 120 75 150 160 60 100 60 180 140 70 160 80 180 255 127.5 85 16 16.5 110 18 110 65 120 80 150 80 180 90 200 200 95 150 95 200 300 150 100 20 20.55 125 22 200 90 180 130 240

Anchor dimensions (W-FAZ/HCR available via special order)


W-FAZ/A4 Total length Max. attachment height l [in mm] t fix [in mm] M8 M10 M12 M16 M20 75 80 95 115 165 90 95 110 130 180 110 115 125 145 180 220 255 275 300 325 145 170 220 280 300 325 340 165 195 265 285 100 100 100 100 50 50 50 50 50 50 25 25 25 25 25 25 20 20 20 20 20 20 10 10 10 10 10 10 10 5 5
1) 2)

Designation

W-FAZ/A4 Fixing Anchor Stainless steel A4

Art. No.

Packing unit

P. Qty.

MWF - 06/11 - 04382 -

Wrth system components


The part-safety coe cients of the resistances regulated in the approval and a part-safety coe cient ofthe e ects of F = 1.4 have been taken into account. For the combination of tensile and transverse loads, for edge in uence and anchor groups, please refer to the Guideline for European Technical Approval (ETAG), Appendix C. The concrete has normal reinforcement. Higher values are possible for higher concrete strengths.

0904 608 10 0904 608 15 0904 608 30 0904 608 50 0904 608 100 0904 610 10 0904 610 15 0904 610 30 0904 610 50 0904 610 100 0904 621 201 0904 621 202 0904 621 203 0904 621 204 0904 621 205 0904 621 206 0904 621 207 0904 621 208 0904 621 210 0904 621 211 0904 616 25 0904 616 50 0904 616 100 0904 616 160 0904 616 180 0904 616 205 0904 616 220 0904 620 30 0904 620 60 0904 620 130 0904 620 150

W-FAZ/A4 M8-10/75 W-FAZ/A4 M8-15/80 W-FAZ/A4 M8-30/95 W-FAZ/A4 M8-50/115 W-FAZ/A4 M8-100/165 W-FAZ/A4 M10-10/90 W-FAZ/A4 M10-15/95 W-FAZ/A4 M10-30/110 W-FAZ/A4 M10-50/130 W-FAZ/A4 M10-100/180 W-FAZ/A4 M12-15/110 W-FAZ/A4 M12-20/115 W-FAZ/A4 M12-30/125 W-FAZ/A4 M12-50/145 W-FAZ/A4 M12-85/180 W-FAZ/A4 M12-125/220 W-FAZ/A4 M12-160/255 W-FAZ/A4 M12-180/275 W-FAZ/A4 M12-205/300 W-FAZ/A4 M12-230/325 W-FAZ/A4 M16-25/145 W-FAZ/A4 M16-50/170 W-FAZ/A4 M16-100/220 W-FAZ/A4 M16-160/280 W-FAZ/A4 M16-180/300 W-FAZ/A4 M16-205/325 W-FAZ/A4 M16-220/340 W-FAZ/A4 M20-30/165 W-FAZ/A4 M20-60/195 W-FAZ/A4 M20-130/265 W-FAZ/A4 M20-150/285

10 15 30 50 100 10 15 30 50 100 15 20 30 50 85 125 160 180 205 230 25 50 100 160 180 205 220 30 60 130 150

W-FA/S, W-FA/F FIXING ANCHORS

11.1
Individual fastening: Uncracked concrete

W-FA/S, Galvanized steel with large washer

W-FA/S, Galvanized steel

W-FA/F, Hot galvanized steel W-FA/A4 Fixing Anchor, see 11.2 W-FA/HCR M6 Fixing Anchor, see 11.2 Proof of performance Approvals European Technical Approval
Option 7 for uncracked concrete

Test reports Fire resistance Direct eect of ames

Two anchoring depths:

Machine Setting Tool for xing anchors (W-FA / W-FAZ) M8 M16

Art. No. 0904 908 016 For details, see separate product info 1. Areas of Application
Can be used for medium to heavy loads Suitable for fastening: Metal structures, metal profiles, brackets, foot plates, supports, cable conduits, piping, wooden structures, beams, purlins, etc. With European Technical Approval, the anchor may be used in reinforced or nonreinforced standard concrete of a strength class of at least C20/25 and at most C50/60 in accordance with EN 206-1:2000-12 Can be used in < C20/25 concrete and pressure-resistant natural stone (without approval) The anchor may only be used for anchoring under a predominantly static or quasi-static (e. g. facade, railing) load Individual fastening: Anchoring with European Technical Approval in uncracked concrete (concrete pressure zone) W-FA/S and W-FA/F may only be used under the conditions of dry inside rooms applications Can be loaded immediately No wait times Mounting reliability ensured through the application of the prescribed torques when anchoring

3. Properties
Force-controlled/torque-controlled spreading anchor made of electrogalvanized and hot galvanized steel in sizes M6, M8, M10, M12, M16 and M20 Approvals: ETA-02/0001 for individual fastening Option 7, uncracked concrete, galvanized steel (M6 M20) and hot galvanized (M8 M20); Measured as per the "European Technical Approval Guideline (ETAG) of Metal Anchors for Use in Concrete", Appendix C, measuring procedure A Fire resistance: W-FA/S (M6 M20) F30, F60, F90 and F120 Fire load in accordance with DIN 4102-02: 1977-09 (Standard temperature-time curve)

2. Advantages
High load-bearing capacities, small axial and edge spacing Time-saving pass-through mounting Two anchoring depths Versatile in use for medium- and heavy-load

Setting instructions

MWF - 04/11 - 04266 -

Drill hole

Clean drilled hole

Knock in anchor with mason's mallet or machine setting tool

Set anchor in place

Apply torque

W-FA/S, W-FA/F FIXING ANCHORS


Performance data
Anchor diameter [in mm] Standard anchoring depth/ Reduced anchoring depth Perm. centered tensile load1)
on a single anchor without edge in uenc

11.1

M6 hef/hef,red [in mm] 40 30

M8 44 35

M10 48 42

M12 65 50

M16 82 64

M20 100 78

Pressure zone (uncracked concrete C20/252), s 3 hef, c 1.5 hef)

Nperm. [kN] = C20/252)

4.1

2.9

5.7

5.0

7.6

6.5

12.6

8.5

17.8

12.3

24

16.5

on a single anchor without edge in uence

Perm. transverse load1)

Pressure zone (uncracked concrete C20/252), c 10 hef)

Vperm. [kN] = C20/252)

2.9

2.9

6.3

5.0

8.0

6.5

14.3

8.5

23.6

23.6

37.1

33.1

Permissible bending torque Fire resistance duration (W-FA/S)

Mperm. [Nm] F30 [in kN] F60 [in kN] F90 [in kN] F120 [in kN]

5.1 0.9 0.5 0.3 0.25

5.1

13.1 1.4 0.8 0.5 0.4

13.1

25.7 2.2 1.2 0.8 0.6

25.7

44.6 3.2 1.8 1.2 0.9

44.6

99.9 6.0 3.4 2.2 1.7

99.9

195 10.0 5.25 3.6 2.75

195

Characteristic values
Setting depth Nom. drill dia. Drill cutting dia. Drill hole depth hnom/hnom,red [in mm] d 0 [in mm] dcut [in mm] h1/h1,red [in mm] 49 6 6.4 55 7 8 39 6 6.4 45 7 8 56 8 8.45 65 9 15 47 8 8.45 55 9 15 62 10 10.45 70 12 30 56 10 10.45 65 12 30 82 12 12.5 90 14 50 67 12 12.5 75 14 50 102 16 16.5 110 18 100 84 16 16.5 95 18 100 121 20 20.55 130 22 200 99 20 20.55 110 22 200

Through-hole in the component d f [in mm] being connected Torque while installing anchor Tinst = [Nm] (W-FA/S, galvanized steel)

Individual attachment: Uncracked concrete, Option 7 (ETA-02/0001 Galvanized steel and hot galvanized steel)
Axial spacing Edge spacing Minimum axial spacing Minimum edge spacing Minimum component thickness scr,N [in mm] ccr,N [in mm] smin [in mm] c min [in mm] hmin [in mm] 120 60 35 40 100 90 45 35 40 80 132 66 40 45 100 105 53 40 45 80 144 72 55 65 100 126 63 55 65 100 195 98 75 90 130 150 75 100 100 100 246 123 90 105 170 192 96 100 100 130 300 150 105 125 200 234 117 140 140 160

Please continue on next page

MWF - 04/11 - 04267 -

Wrth system components


1)

2)

The part safety coe cients of the resistances regulated in the approval and a part safety coe cient of the e ects of F = 1.4 have been taken into account. For the combination of tensile and transverse loads, for edge inuence and anchor groups, please refer to the Directive for European Technical Approval (ETAG) Appendix C. The concrete has normal reinforcement. Higher values are possible for higher concrete strengths.

W-FA/S, W-FA/F FIXING ANCHORS

11.1
Individual fastening (M6 - M20): Uncracked concrete (ETA-02/0001)

W-FA/S Fixing Anchor, galvanized steel (with small washer)


Anchor dia. [in mm] M6 M6 M6 M6 M8 M8 M8 M8 M8 M8 M8 M10 M10 M10 M10 M10 M10 M10 M10 M10 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12 M12 M16 M16 M16 M16 M16 M16 M16 M16 M16 M16 M20 M20 M20
MWF - 04/11 - 10456 -

Designation

Fastening height t fix / t fix,red [in mm] 5 10 / 20 25 / 35 40 / 50 5 10 / 19 15 / 24 25 / 34 30 / 39 45 / 54 55 / 64 10 10 / 16 15 / 21 20 / 26 30 / 36 45 / 51 70 / 76 100 / 106 140 / 146 5 10 / 25 15 / 30 20 / 35 30 / 45 50 / 65 65 / 80 85 / 100 105 / 120 125 / 140 145 / 160 160 / 175 13 10 / 28 30 / 48 60 / 78 80 / 98 100 / 118 130 / 148 165 / 183 200 / 218 220 / 238 5 / 27 35 / 57 60 / 82 95 / 117

Total length l [in mm] 40 67 82 97 50 75 80 90 95 110 120 60 85 90 95 105 120 145 175 215 75 105 110 115 125 145 160 180 200 220 240 255 115 130 150 180 200 220 250 285 320 340 150 180 205 240

Effective anchoring depthh ef/hef,red [in mm] 18 40 / 30 40 / 30 40 / 30 24 44 / 35 44 / 35 44 / 35 44 / 35 44 / 35 44 / 35 23 48 / 42 48 / 42 48 / 42 48 / 42 48 / 42 48 / 42 48 / 42 48 / 42 40 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 64 82 / 64 82 / 64 82 / 64 82 / 64 82 / 64 82 / 64 82 / 64 82 / 64 82 / 64 100 / 78 100 / 78 100 / 78 100 / 78

Thread [dia. x length]

Approval ETA Option 7 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001

Art. No.

P. Qty.

W-FA/S M6-5/40 W-FA/S M6-10-20/67 W-FA/S M6-25-35/82 W-FA/S M6-40-50/97 W-FA/S M8-5/50 W-FA/S M8-10-19/75 W-FA/S M8-15-24/80 W-FA/S M8-25-34/90 W-FA/S M8-30-39/95 W-FA/S M8-45-54/110 W-FA/S M8-55-64/120 W-FA/S M10-10/60 W-FA/S M10-10-16/85 W-FA/S M10-15-21/90 W-FA/S M10-20-26/95 W-FA/S M10-30-36/105 W-FA/S M10-45-51/120 W-FA/S M10-70-76/145 W-FA/S M10-100-106/175 W-FA/S M10-140-146/215 W-FA/S M12-5/75 W-FA/S M12-10-25/105 W-FA/S M12-15-30/110 W-FA/S M12-20-35/115 W-FA/S M12-30-45/125 W-FA/S M12-50-65/145 W-FA/S M12-65-80/160 W-FA/S M12-85-100/180 W-FA/S M12-105-120/200 W-FA/S M12-125-140/220 W-FA/S M12-145-160/240 W-FA/S M12-160-175/255 W-FA/S M16-13/115 W-FA/S M16-10-28/130 W-FA/S M16-30-48/150 W-FA/S M16-60-78/180 W-FA/S M16-80-98/200 W-FA/S M16-100-118/220 W-FA/S M16-130-148/250 W-FA/S M16-165-183/285 W-FA/S M16-200-218/320 W-FA/S M16-220-238/340 W-FA/S M20-5-27/150 W-FA/S M20-35-57/180 W-FA/S M20-60-82/205 W-FA/S M20-95-117/240

M6 x 16 M6 x 30 M6 x 35 M6 x 35 M8 x 22 M8 x 40 M8 x 45 M8 x 55 M8 x 60 M8 x 75 M8 x 85 M10 x 25 M10 x 40 M10 x 45 M10 x 50 M10 x 60 M10 x 75 M10 x 80 M10 x 80 M10 x 80 M12 x 30 M12 x 60 M12 x 65 M12 x 70 M12 x 80 M12 x 100 M12 x 100 M12 x 100 M12 x 100 M12 x 80 M12 x 80 M12 x 80 M16 x 60 M16 x 70 M16 x 90 M16 x 110 M16 x 110 M16 x 80 M16 x 80 M16 x 80 M16 x 80 M16 x 80 M20 x 70 M20 x 70 M20 x 70 M20 x 70

5932 006 040 5932 006 067 5932 006 082 5932 006 097 5932 008 050 5932 008 075 5932 008 080 5932 008 090 5932 008 095 5932 008 110 5932 008 120 5932 010 060 5932 010 085 5932 010 090 5932 010 095 5932 010 105 5932 010 120 5932 010 145 5932 010 175 5932 010 215 5932 012 075 5932 012 105 5932 012 110 5932 012 115 5932 012 125 5932 012 145 5932 012 160 5932 012 180 5932 012 200 5932 012 220 5932 012 240 5932 012 255 5932 016 115 5932 016 130 5932 016 150 5932 016 180 5932 016 200 5932 016 220 5932 016 250 5932 016 285 5932 016 320 5932 016 340 5932 020 150 5932 020 180 5932 020 205 5932 020 240

100 100 100 100 100 100 100 100 100 100 100 50 50 50 50 50 50 50 50 25 25 25 25 25 25 25 25 25 25 25 20 20 20 20 20 20 10 10 10 10 10 10 10 10 10 10

M20

Please continue on next page

W-FA/S, W-FA/F FIXING ANCHORS

11.1
Individual fastening (M12 - M16): Uncracked concrete (ETA-02/0001)

W-FA/S Fixing Anchor, galvanized steel (with large washer)


Anchor dia. [in mm] M12 M12 M12 M12 M12 M12 M12 M12 M12 M16 M16 M16 M16 Designation Fastening height t fix / t fix,red [in mm] 65 / 80 85 / 100 105 / 120 125 / 140 145 / 160 160 / 175 190 / 205 230 / 245 260 / 275 100 / 118 130 / 148 165 / 183 200 / 218 Total length l [in mm] 160 180 200 220 240 255 285 325 355 220 250 285 320 Effective anchoring depth hef/hef,red [in mm] 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 65 / 50 82 / 64 82 / 64 82 / 64 82 / 64 Thread [dia. x length] Approval ETA Option 7 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 Art. No. P. Qty.

W-FA/S M12-65-80/160 W-FA/S M12-85-100/180 W-FA/S M12-105-120/200 W-FA/S M12-125-140/220 W-FA/S M12-145-160/240 W-FA/S M12-160-175/255 W-FA/S M12-190-205/285 W-FA/S M12-230-245/325 W-FA/S M12-260-275/355 W-FA/S M16-100-118/220 W-FA/S M16-130-148/250 W-FA/S M16-165-183/285 W-FA/S M16-200-218/320

M12 x 100 M12 x 100 M12 x 100 M12 x 80 M12 x 80 M12 x 80 M12 x 80 M12 x 80 M12 x 80 M16 x 80 M16 x 80 M16 x 80 M16 x 80

5932 112 160 5932 112 180 5932 112 200 5932 112 220 5932 112 240 5932 112 255 5932 112 285 5932 112 325 5932 112 355 5932 116 220 5932 116 250 5932 116 285 5932 116 320

25 25 25 25 20 20 20 20 10 10 10 10 10

Individual fastening (M6 - M20): Uncracked concrete (ETA-02/0001) W-FA/F Fixing Anchor, hot galvanized steel ( 40 m)
Anchor dia. [in mm] M6 M8 M8 M8 M10 M10 M10 M12 M12 M12 M12 M16 Designation Fastening height t fix / t fix,red [in mm] 5 15 / 24 30 / 39 55 / 64 15 / 21 30 / 36 45 / 51 15 / 30 30 / 45 50 / 65 85 / 100 30 / 48 Total length l [in mm] 40 80 95 120 90 105 120 110 125 145 180 150 Effective anchoring depth hef/hef,red [in mm] / 18 44 / 35 44 / 35 44 / 35 48 / 42 48 / 42 48 / 42 65 / 50 65 / 50 65 / 50 65 / 50 82 / 64 Thread [dia. x length] Approval ETA Option 7 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 ETA-02/0001 Art. No. P. Qty.

W-FA/F M6-5/40 W-FA/F M8-15-24/80 W-FA/F M8-30-39/95 W-FA/F M8-55-64/120 W-FA/F M10-15-21/90 W-FA/F M10-30-36/105 W-FA/F M10-45-51/120 W-FA/F M12-15-30/110 W-FA/F M12-30-45/125 W-FA/F M12-50-65/145 W-FA/F M12-85-100/180 W-FA/F M16-30-48/150

M6 x 16 M8 x 45 M8 x 60 M8 x 85 M10 x 45 M10 x 60 M10 x 75 M12 x 65 M12 x 80 M12 x 100 M12 x 100 M16 x 90

5932 906 040 5932 908 080 5932 908 095 5932 908 120 5932 910 090 5932 910 105 5932 910 120 5932 912 110 5932 912 125 5932 912 145 5932 912 180 5932 916 150

100 100 100 100 50 50 50 25 25 25 25 20

MWF - 04/11 - 10457 -

11.2 W-FA/A4 W-FA/HCR M6


Fixing Anchor
Individual attachment: Uncracked concrete Multiple attachment: Anchoring of light ceiling coverings and joist constructions, cracked and uncracked concrete W-FA/A4, Stainless steel A4 W-FA/HCR M6 (via special order) Highly corrosion-resistant steel (1.4529) For W-FA/S Fixing Anchor, see
11.1

For W-FA/hot-galvanized Fixing Anchor, see 11.1

Proof of Performance
Approvals
European Technical Approval
Option 7 for uncracked concrete

Test Reports
Fireresistance
Technical Report TR 020 R30-R120

2 anchoring depths:

European Technical Approval


Multiple attachment of non load-bearing systems in concrete

Machine Setting Tool for Fixing Anchor (W-FA/W-FAZ) M8 M16

Ceiling
Suspended ceiling and statically comparable attachments

Fireresistance
Direct effect of flames

Z-21.1-1598

Art. No. 0904 908 016 For details, see separate product information

1. Applications
Can be used for medium to heavy loads Suitable for fastening: Metal structures, metal profiles, brackets, foot plates, supports, cable conduits, piping, wooden structures, beams, purlins, etc. With European Technical Approval, the anchor can be used in reinforced or nonreinforced standard concrete of a strength class of at least C20/25 and at most C50/60. Can be used in concrete <C20/25 and pressure-resistant natural stone (without approval) The anchor may be used for anchorage with primarily static loads or quasi-static loads Individual attachment: Anchoring with European Technical Approval in uncracked concrete (concrete pressure zone) Multiple attachment: Anchoring of non-load-bearing systems with European technical Approval in cracked and uncracked concrete Suspended ceiling: Anchoring with general construction permit for suspended ceilings and statically comparable attachments (up to a maximum of 1 kN/m2) W-FA/A4 (stainless steel A4) may be used in dry indoor rooms, outdoors (including industrial atmosphere and near the sea) or in humid rooms if no especially aggressive conditions exist W-FA/HCR M6 (HCR highly corrosion-resistant steel) may be used in areas with extremely high corrosion loading (e.g. indoor pool atmosphere, street tunnels, poorly ventilated car parcs or parts in seawater and in marine atmosphere).

2. Advantages
High loads, small axle bases and edge clearances Time-saving through-bolt mounting Two anchoring depths Flexible use for medium and heavy loads Can be loaded immediately no waiting times Reliable installation due to application of prescribed torque during anchoring

3. Features
Force-controlled/torque-controlled spreading anchor made of stainless steel A4 and HCR highly corrosion-resistant steel Approvals: ETA-05/0019 for individual attachment Option 7, uncracked concrete; stainless steel A4: M6 M20 ETA-06/0162 for multiple attachment of non-load-bearing systems Uncracked or cracked concrete; stainless steel A4: M6; fire resistance in accordance with TR 020 R30 R120 ETA-06/0235 for multiple attachment of non-load-bearing systems Uncracked or cracked concrete; HCR highly corrosion-resistant steel (1.4529/1.4565): M6; fire resistance in accordance with TR 020 R30 R120 Z-21.1-1598 for suspended ceilings Uncracked or cracked concrete; stainless steel A4: M6 M10 Fire resistance: W-FA/A4, W-FA/HCR (M6 M20) F30, F60, F90, F120; fire stress according to DIN 4102-02:1977-09 (ETK Einheits-Temperaturzeitkurve (standard temperature-time curve)) Fire resistance: W-FA/HCR (M6) fire stress in accordance with ZTV-ING Part 5 (ETK-Tunnel-Brandraumkurve (Tunnel Fire Compartment Curve))

Setting instructions

MWF - 01/10 - 09507 -

Drill hole

Clean drilled hole

Knock in anchor with masons mallet or machine setting tool

Set anchor in place

Apply torque

W-ED 13.1 W-ED/S Drive-In Anchor


W-ED/S Galvanized steel, M6 M20 W-ED Galvanized steel, M5, w/o approval Marking-spreading tool with hand guard ( visual setting check) Spreading tool ( no visual setting check) W-ED/A4 Drive-In Anchor, see 13.2 W-ED M12 Drive-In Anchor (for core drills), see 13.3 W-ED DW15 Drive-In Anchor, see 13.3 Evidence of Performance Approvals Test Reports

European Technical Approval


Option 7 for uncracked concrete

European Technical Approval


Multiple attachment of non-load-bearing systems in concrete

Fire Resistance
Direct flame effect

2. Advantages
l l l l l l

Shallow drilled hole depth High load-bearing capacities Easy installation due to low knock-in energy Visual setting check and hand guard when installing with markingspreading tool Can be loaded immediately no waiting time Attachment can easily be detached again at any time

3. Properties
l

1. Applications
l l l l

l l

l l

Can be used for medium to heavy loads W-ED/S and W-ED M5 may only be used in dry interior rooms Suitable for attaching threaded rods, metal structures, metal profiles, grids, cable conduits, pipes, mounting rails etc. With European Technical Approval, the anchor can be used in reinforced or non-reinforced standard concrete of a strength class of at least C20/25 and at most C50/60 in accordance with EN 206-1:2000-12 For use in concrete < C20/25 and pressure-resistant natural stone (without approval) The anchor may only be used for anchorage with primarily static loads (e.g. own weight, installations, support materials) or quasi-static loads (e.g. faades, railings) Individual attachment: Anchorage with European Technical Approval in uncracked concrete (concrete pressure zone) Multiple attachment: Anchoring of light ceiling coverings and joist constructions in accordance with DIN 18168 and for comparable static anchoring up to 1.0 kN/m2 with general construction permit

l l

Distance-controlled spreading anchor of galvanized steel in the sizes M5, M6, M8, M10, M12, M16 and M20 The add-on piece can be attached with a securing screw or a threaded rod Approvals: ETA-02/0044 for individual attachment Option 7, uncracked concrete, galvanized steel M6 M20; dimensioned in accordance with the European Technical Approval Guideline (ETAG) for Metal Anchors for Anchoring in Concrete Appendix C, Dimensioning Method A ETA-05/0120 for multiple attachment of non-load-bearing systems in concrete Uncracked or cracked concrete, galvanized steel M6 M12; dimensioned in accordance with the European Technical Approval Guideline (ETAG) for Metal Anchors for Anchoring in Concrete, Appendix C, Dimensioning Method B Fire resistance: R30, R60, R90, R120: Technical Report TR 020 Assessment of anchoring in concrete with regard to the fire resistance (included in ETA-05/0120); F30, F60, F90, F120: Fire stress in accordance with DIN 4102-02: 1977-09 (uniform temperature curve)

Setting Instructions

MWF - 10/09 - 04270 -

Drill hole

Clean drilled hole

Knock in anchor until flush

Anchor with spreading tool

Secure component Apply torque

W-ED/S/W-ED Drive-In Anchor 13.1


Performance data
Anchor diameter [in mm] Perm.centr. Pressure zone tensile force 1) (uncracked concrete of an indiv. C20/252), s 3 hef, anchor w/o edge c 1.5 h ) ef influence Perm. transv. Pressure zone load 1) (uncracked concrete of an individual C20/252), anchor w/o edge c 10 hef) influence Multiple attachment of non load-bearing systems in concrete4) Permissible bending torque 4)
uncracked concrete/multiple attachment Nperm [kN] = C 20/25 2)

M58) Frec 1.4

M6 3.3 2.8

M8 3.6

M10 5.1

M12 7.1

M16 10.5

M20 14.3

Vperm [kN] = C 20/25 2)3)

Frec 1.5 Frec 0.3

2.1 1.2 2.7/3.3 0.8 0.8 0.4 0.2 1.7 0.7 0.4 0.3

3.9 1.7

3.9 2.0

4.1 2.0 15.8/15.8 1.5 1.5 1.5 1.0 4.7 2.4 1.3 1.0

9.0 2.4 27.8/27.8 1.5 1.5 1.5 1.2 6.9 3.5 1.8 1.4

16.8 71.0 12.5 5.6 3.5 2.5

26.2 138.6 18.0 8.5 5.5 4.4

Fperm [kN] C 20/25 Mperm [Nm] R30; Fperm [kN] R60; Fperm [kN] R90; Fperm [kN] R120; Fperm [kN] F 30 [kN] F 60 [kN] F 90 [kN] F120 [kN]

8.1/8.1 0.9 0.9 0.9 0.4 1.7 0.7 0.4 0.3 3.0 1.5 0.8 0.6

Perm. load under fire stress4) (Technical Report TR 020)


For unc axial and edge distances, see European Technical Approval ETA-05/0120

Fire-resistance time )

Characteristic values
Minimum axial spacing Axial spacing7)
uncracked concrete/multiple attachment

smin [mm] scr,N / scr [mm] cmin [mm] ccr,N / ccr [mm] hmin [mm] h ef [mm] d0 [mm] dcut [mm] h0 = [mm] df [mm] Tinst = [Nm]

60 75 95 37.5 100 25 8 8.45 25 6 3

55 90 / 130 95 45 / 65 100 30 8 8.45 30 7 4

60 90/ 180 95 45/ 90 100 30

80 120/ 210 60/ 105 40

100 120/170 135 60/85 120 40 12 12.5 40 12 15

120 150/170 165 75/85 130 50 15 15.5 50 14 35

150 195 200 97.5 160 65 20 20.55 65 18 60

160 240 260 120 200 80 25 25.55 80 22 120

Minimum edge spacing Edge spacing7)


uncracked concrete/multiple attachment

Minimum component thickness Effective anchoring depth Nom. drill dia. Drill cutting dia. Drill hole depth Through-hole in the comp. to be connected Torque during anchoring

10 10.45 30 9 8 40

Anchor dimensions
Total length Thread depth (max. screw-in depth) Minimum screw-in depth LH [mm] Lth [mm] Lsdmin [mm] 25 10 6 W-ED M5 x 25 30 13 7 0904 010 06 W-ED/S M6 x 30 30 13 9 0904 010 08 W-ED/S M8 x 30 0904 010 081 W-ED/S M8 x 40 40 20 40 15 11 0904 010 10 W-ED/S M10 x 40 50 18 13 0904 010 12 W-ED/S M12 x 50 65 23 18 0904 010 16 W-ED/S M16 x 65 80 34 22 0904 010 20 W-ED/S M20 x 80 25 0904 020 20 0904 022 20

Designation

Art. No. Packing unit Marking-Spreading Tool with hand guard ( visual setting check) Art. No. P. Qty. = 1 Spreading Tool ( no visual setting check) Art. No. P. Qty. = 1
MWF - 10/09 - 04271 -

P. Qty.

100

0904 58)

100

100 0904 020 08 0904 022 08

100 0904 020 081 0904 022 081

50 0904 020 10 0904 022 10

50 0904 020 12 0904 022 12

25 0904 020 16 0904 022 16

Wrth System Components

0904 020 06
1

0904 058)

) The approval takes account of the part-safety coefficients of the resistances and a part-safety coefficient of the effects of F = 1.4. For the combination of tensile and transverse loads, for edge influence and dowel groups, please refer to the guideline for European Technical Approval (ETAG) Appendix C. 2 ) The concrete has normal reinforcement. Higher values are possible for higher concrete strengths. 3 ) Steel quality 5.6. With a higher steel quality, higher transverse load values apply. 4 ) The permissible loads were determined without axial and edge influence. 5 ) Steel quality 5.6. With a higher steel quality, higher permissible bending moments apply. 6 ) Fire resistance duration: Drive-in anchor W-ED/S in conjunction with screws of the strength classes 5.6. 7 ) The minimum axial spacing and the minimum edge spacing must be complied with! 8 ) Without approval

13.2 Drive-In Anchor W-ED/A4 W-ED/HCR

Individual fastening: Uncracked concrete Multiple attachment: Cracked and uncracked concrete W-ED/A4 Stainless steel A4 W-ED/HCR Highly corrosion-resistant steel (material number 1.4529)
Available on special order

Marking-spreading tool with hand protection ( visual setting check) Spreading tool ( no visual setting check Drive-in anchor W-ED/S see 13.1

Proof of performance Approvals


A4: M6-M20 HCR: M6-M10 A4: M6-M12 HCR: M6-M10

Test Reports

European Technical Approval


Option 7 for uncracked concrete

European Technical Approval


Multiple attachment of non load-bearing systems in concrete

Fire resistance
Technical Report TR 020 R30 - R120

Fire resistance
Direct flame effect

2. Advantages
l l l l l l

Shallow drilled hole depth High load-bearing capacities Easy installation due to low knock-in energy Visual setting check and hand protection when installing with the marking-spreading tool Can be loaded immediately no waiting time Attachment can easily be detached again at any time

1. Applications
l Can be used for medium to heavy loads l With European Technical Approval, the anchor may be used in

3. Properties
l l l

l l

l l l l

reinforced or non-reinforced standard concrete of a strength class of at least C20/25 and at most C50/60 in accordance with EN 206-1:2000-12 Individual attachment: Anchorage with European Technical Approval in uncracked concrete (concrete pressure zone) Multiple attachment of non load-bearing systems: Anchoring with European technical approval in cracked concrete (concrete tensile zone) and in uncracked concrete (concrete pressure zone) The anchor may only be used in anchorages primarily subject to resting or quasi-resting loads For use in concrete < C20/25 and pressure-resistant natural stone (without approval) W-ED/A4 (stainless steel A4) may be used in dry interior rooms, outdoors (including industrial atmospheres and near the sea) or in damp rooms W-ED/HCR (highly corrosion-resistant steel HCR) may be used in areas with very high corrosion stress (e.g. indoor pool atmosphere, street tunnels, poorly ventilated car parks or also parts in seawater and in a marine atmosphere) Suitable for attaching threaded rods, metal structures, metal profiles, grids, cable conduits, pipes, mounting rails etc.

Distance-controlled spreading anchor of stainless steel in the sizes M6, M8, M10, M12, M16 and M20 The add-on piece can be attached with a securing screw or a threaded rod Approvals: Uncracked concrete, Option 7: Stainless steel A4 M6-M20 and highly corrosion-resistant steel HCR M6M10; European Technical Approval ETA-03/0051 Multiple attachment of non load-bearing systems in concrete: Stainless steel A4 M6-M12 and highly corrosion-resistant steel HCR M6M10; European Technical Approval ETA-05/0121 Fire resistance: R30, R60, R90, R120: Technical Report TR 020 Evaluation of Anchorages in Concrete with Regard to Fire Resistance (contained in ETA-05/0121); F30, F60, F90, F120: Fire load in accordance with DIN 4102-02: 197709 (ETK)

Setting instructions

MWF - 10/09 - 04358 -

Drill hole

Clean drilled hole

Drive in anchor until flush

Anchor with spreading tool

Fit component, apply torque

Drive-In Anchor W-ED/A4 / W-ED/HCR 13.2


Performance data
Anchor diameter [mm] Pressure zone (uncracked concrete Nperm. [kN] = C 20/25 2) C20/252), s 3 hef, c 1,5 hef) Pressure zone (uncracked concrete Vperm. [kN] = C 20/25 2) C20/252), c 10 hef) Multiple attachment of non load-bearing systems in concrete 3) Fperm [kN] C 20/25 Mperm (A4-70) [Nm] Permissible bending moment Mperm (A4-80) [Nm] Perm. load under fire stress 3) R30; Fperm [kN] (Technical Report TR 020) R60; Fperm [kN] For axial and edge spacings, see European R90; Fperm [kN] Technical Approval ETA-05/0121 R120; Fperm [kN] F 30 [kN] Fire-resistance time 4) F 60 [kN] F 90 [kN] F120 [kN] M6 3,3 3,3 M8 3,6 M10 6,1 M12 8,5 M16 12,6 M20 17,2
Perm. Perm. centr. transverse tensile load 1) load1) of a of a single single anchor anchor without edge without edge influence influence

3,2 1.2 5,0 6,4 0,8 0,8 0,4 0,2 1,7 0,7 0,4 0,3 1,7

4,6 2,0 11,9 16,1 0,9 0,9 0,9 0,4 1,7 0,7 0,4 0,3 3,0 1,5 0,8 0,6

6,0 2,0 23,8 32,2 1,5 1,5 1,5 1,0 4,7 2,4 1,3 1,0

11,9 2,4 42,1 56,4 1,5 1,5 1,5 1,2 6,9 3,5 1,8 1,4

19,2 106,7 142,9 12,5 5,6 3,5 2,5

30,7 207,9 278,7 18,0 8,5 5,5 4,4

Characteristic Values
Minimum axial spacing uncracked concrete / multiple attachment Axial spacing 5) uncracked concrete / multiple attachment Minimum edge clearance uncracked concrete / multiple attachment Edge clearance 5) uncracked concrete / multiple attachment Minimum component thickness uncracked concrete / multiple attachment Effective anchoring depth Nom. drill dia. Drill cutting dia. Drill hole depth Through-hole in the component to be connected Torque while installing anchor smin [mm] scr,N / scr [mm] cmin [mm] scr,N / scr [mm] hmin [mm] hef [mm] d0 [mm] dcut [mm] h0 = [mm] df [mm] Tinst = [Nm] LH [mm] Lth [mm] Lsdmin [mm] 50 / 55 90 / 130 80 / 95 45 / 65 100 / 100 30 8 8,45 30 7 4 30 13 7 0904 030 06 W-ED/A4 M6 x 30 30 13 9 0904 030 08 W-ED/A4 M8 x 30 0904 030 081 W-ED/A4 M8 x 40 60 / 60 90 / 180 95 / 95 45 / 90 80 / 80 120 / 210 95 / 95 60 / 105 100 / 100 120 / 170 135 / 135 60 / 85 130 / 120 40 12 12,5 40 12 15 40 20 40 15 11 0904 030 10 W-ED/A4 M10 x 40 120 / 120 150 / 170 165 / 165 75 / 85 140 / 130 50 15 15,5 50 14 35 50 18 13 0904 030 12 W-ED/A4 M12 x 50 150 195 200 100 160 65 20 20,55 65 18 60 65 23 18 0904 030 16 W-ED/A4 M16 x 65 16 240 260 120 250 80 25 25,55 80 22 120 80 34 22 W-ED/A4 M20 x 80
Available on Available on special order special order Available on special order

100 / 100 100 / 100 30 10 10,45 30 9 8 40 40

Anchor Dimensions
Total length Thread depth (max. screw-in depth) Minimum screw-in depth

Designation

Drive-in anchor W-ED/A4 Stainless steel A4 Packing unit Marking-spreading tool with hand protection ( visual setting check)

Art. No. P. Qty. Art. No. P. Qty = 1

100

100 0904 020 08 0904 022 08

100 0904 020 081 0904 022 081

50 0904 020 10 0904 022 10

50 0904 020 12 0904 022 12

25 0904 020 16 0904 022 16

25

Spreading tool ( no visual setting check)


MWF - 10/09 - 04359 -

Art. No. P. Qty. = 1

Wrth system components

0904 020 06

) The part safety coefficients of the resistances regulated in the approval and a part safety coefficient of the effects of ? F = 1.4 have been taken into account. For the combination of tensile and transverse loads, for edge influence and anchor groups, please refer to the Guideline for European Technical Approval (ETAG), Appendix C. 2 ) The concrete has normal reinforcement. Higher values are possible for higher concrete strengths. 3) The permissible loads were determined without axial and edge influence. 4 ) Fire resistance duration: Drive-in anchor W-ED /A4 in conjunction with screws of stainless steel A4. 5) The minimum axle base and the minimum edge clearance must be complied with!
1

21.1

W-VD/S Shear-Anchor Cartridge System


Individual attachment: Uncracked concrete Galvanized steel W-VD/A4 Shear-anchor cartridge system see 21.2 W-VD/HCR Shear-anchor cartridge system see 21.2

Evidence of performance
Approvals Test reports Drill hole cleaning Cleaning the drill hole: 1x blow-out, 1x brush-out, 1x blow-out, 1x brush-out Installation instructions Set anchor bar rotating and + impacting with hammer drill or percussion drill.
l

European Technical Approval


Option 8 for uncracked concrete

Fire Resistance

Suitable for fastening metal constructions, metal profiles, brackets, foot plates, supports, wood structures, beams etc.

1. Applications
l l

2. Advantages
l l l

l l

l l l l

Can be used for medium to heavy loads With European Technical Approval, the anchor can be used in reinforced or non-reinforced standard concrete with a strength class of at least C 20/25 and at most C 50/60 in accordance with EN 206:2000-12 Anchorage with European Technical Approval in uncracked concrete (concrete pressure zone) The anchor may be used for anchorage with primarily static loads (e.g. own weight, installations, support materials) or quasi-static loads Installation in dry or wet concrete The temperature in the mortar area may not exceed +50C and briefly +80C For use in concrete < C 20/25 and pressure-resistant natural stone (without approval) W-VD/S (galvanized steel) can be used in dry interior rooms

Heavy loads, small axial and edge distances Hardened composite mortar largely seals off the drill hole Attachment with low expansion pressure allows small edge and axial clearances

3. Properties
l

l l

Anchoring through bond between mortar, anchor bar and anchoring base. Galvanized anchor bar in the sizes M8, M10, M12, M16, M20 and M24 Galvanized steel: European Technical Approval ETA-06/0074 Dimensioned in accordance with the Guideline for European Technical Approval (ETAG) of Metal Anchors for Use in Concrete, Annex C, dimensioning method A Fire resistance: F30, F60, F90, F120: One-sided fire stress according to DIN EN 1363-1:1999-10

Setting instructions

MWF - 04/08 - 04276 -

Drill hole

1x blow-out, 1x brush-out, 1x blow-out, 1x brush-out

Resin must flow like honey when cartridge is hand-warm

Push in cartridge

Set threaded rod rotating/ impacting

Visual check of mortar filling quantity

Observe the hardening time

Mount component, apply torque

W-VD/S Shear-Anchor Cartridge System


Performance data
Anchor diameter
Perm. transv. Perm. centered load1) tensile load1) of a single anchor of a single anchor w/o edge influence w/o edge influence

21.1

M8 Nperm [kN] = C20/25 50C 2)/80C 3)

M 10

M 12

M 16

M20

M24

Pressure zone (uncracked concrete C 20/25 M8: s 3 hef, c 1.5 hef M10-M24: s 2 hef, c 1 hef)

7.9

11.9

15.9

19.8

29.8

35.7

Pressure zone (uncracked concrete C 20/25, Vperm [kN] = C20/25 c 10 hef) Mperm [Nm] F30 [kN] F60 [kN] F90 [kN] F120 [kN]

5.1 10.9 2.3 1.29 0.79 0.53

8.0 21.1 3.64 2.04 1.3 1.0

12.0 37.1 5.26 3.07 2.0 1.5

22.3 94.9 9.79 5.72 3.68 2.67

34.9 185.7 15.28 8.93 5.75 4.16

50.3 320.6 22.01 12.86 8.28 6.0

Permissible bending torque Fire resistance time Fire resistance duration

Characteristic values
Minimum axial spacing Axial spacing Minimum edge spacing Edge spacing Minimum component thickness Effective anchoring depth Nom. drill dia. Drill cutting dia. Drilled hole depth Through-hole in component to be connected Torque during anchoring Cleaning brush dia. smin [mm] scr,N [mm] cmin [mm] ccr,N [mm] hmin [mm] hef [mm] d0 [mm] dcut [mm] h0 [mm] df [mm] Tinst = [Nm] D [mm] 40 240 40 120 110 80 10 10.5 80 9 10 10.8 45 180 45 90 120 90 12 12.5 90 12 20 13 55 220 55 110 140 110 14 14.5 110 14 40 15 65 250 65 125 160 125 18 18.5 125 18 80 19 85 340 85 170 220 170 25 25.5 170 22 120 27 105 420 105 210 260 210 28 28.5 210 26 180 29

Drill hole cleaning


Cleaning brush (steel) Machine mounting Extension Brush template Blow-out pump Art. No. Art. No. Art. No. Art. No. Art. No. P. Qty. = 1 P. Qty. = 1 P. Qty. = 1 P. Qty. = 1 P. Qty. = 1

M8 M24: 1x blow-out, 1x brush-out, 1x blow-out, 1x brush-out 0905 499 001 0905 499 002 0905 499 003 0905 499 004 0905 499 006 0905 499 0084) Hexagon: Art. No. 0905 499 101 SDS plus: Art. No. 0905 499 102 0905 499 111 0905 499 099 Blow-out pump: Art. No. 0903 990 001

Anchor dimensions
20 110 60 150 15 115 30 130 65 165 90 190 10 135 35 160 85 210 10 5915 012 095 W-VD M12 10 5915 112 250 W-VD-A/S M12-125/250 125 250 10 5915 012 095 W-VD M12 10 5915 112 300 W-VD-A/S M12-175/300 175 300 20 165 45 190 85 230 10 5915 016 095 W-VD M16 10 5915 116 250 W-VD-A/S M16-105/250 105 250 10 5915 016 095 W-VD M16 10 5915 116 300 W-VD-A/S M16-155/300 155 300 20 220 60 260 10 5915 020 175 W-VD M20 10 5915 120 300 W-VD-A/S M20-100/300 100 300 15 260 5 5915 124 260 W-VD-A/S M24-15/260 5 5915 024 210 W-VD M24

l [mm] tfix [mm]

max. mounting height

10 5915 010 080 W-VD M10 10 5915 110 115 W-VD-A/S M10-15/115

10 5915 010 080 W-VD M10 10 5915 110 130 W-VD-A/S M10-30/130

10 5915 010 080 W-VD M10 10 5915 110 165 W-VD-A/S M10-65/165

10 5915 010 080 W-VD M10 10 5915 110 190 W-VD-A/S M10-90/190

10 5915 012 095 W-VD M12 10 5915 112 135 W-VD-A/S M12-10/135

10 5915 012 095 W-VD M12 10 5915 112 160 W-VD-A/S M12-35/160

10 5915 012 095 W-VD M12 10 5915 112 210 W-VD-A/S M12-85/210

10 5915 016 095 W-VD M16 10 5915 116 165 W-VD-A/S M16-20/165

10 5915 016 095 W-VD M16 10 5915 116 190 W-VD-A/S M16-45/190

10 5915 016 095 W-VD M16 10 5915 116 230 W-VD-A/S M16-85/230

10 5915 020 175 W-VD M20 10 5915 120 220 W-VD-A/S M20-20/220

10 5915 020 175 W-VD M20 10 5915 120 260 W-VD-A/S M20-60/260

10 5915 108 110 W-VD-A/S M8-20/110

Designation Anchor bar

W-VD-A/S Anchor Bar, galvanized steel Packing unit Designation Shear-anchor mortar cartridge

Art. No. P. Qty.

10 5915 108 150 W-VD-A/S M8-60/150

10 5915 008 080 W-VD M8

W-VD shear-anchor mortar cartridge Packing unit


MWF - 04/08 - 04277 -

Art. No. P. Qty. [pieces]

10 5915 008 080 W-VD M8

Wrth System Components

1)

2) 3) 4)

The part safety coefficients of the resistances and a part safety coefficient of the effects of F = 1.4 have been taken into account. For the combination of tensile and transverse loads, for edge influence and dowel groups, please refer to the Directive for European Technical Approval (ETAG) Appendix C. Maximum long-term temperature. Maximum short-term temperature. Cleaning brush without M6 connecting thread.

5 5915 024 210 W-VD M24

5 5915 124 300 W-VD-A/S M24-55/300

55 300

Anchor diameter Total length

M8

M 10

M 12

M 16

M20

M24

WIT-PE 500
Performance data Injection mortar Reinforcement rod diameter [mm] W-ZA Stay Nominal drill-bit diameter WIT-PE 500 Mortar Cartridge Static Mixer Drill hole cleaning

29.1
8 d0 [in mm] Art. No. Art. No. 12 14 16 20 25 28 M12 M16 M20 12 14 16 18 20 25 32 35 (incl.1static mixer) 385 mL: 0903 480 001, P. Qty. = 1/12 1,400 ml: 0903 480 002, P. Qty. = 1/5 0903 488 101 P. Qty. = 10 Blow out at least four times with compressed air (> 6 bar) Blow out at least four times with compressed air (> 6 bar) Break out drill core; rinse with tap water (until clear water comes out), brush out mechanically at least twice, rinse with tap water (until clear water comes out), blow out at least twice with compressed air (> 6 bar); brush out mechanically at least twice; blow out at least twice with compressed air (> 6 bar) 10 12 14 16 20 25 28 M12 M16 M20 0903 489 227 P. Qty. = 1 dia. 27 mm WIT-DD 25-28 0699 903 13 P. Qty. = 1 dia. 20 mm WIT-SDD 25-28 0903 489 292 P. Qty. = 1 0903 489 020 P. Qty. = 1 Color green dia. 27 mm 0903 489 025 P. Qty. = 1 Color brown dia. 34 mm 0903 489 028 P. Qty. = 1 Color red dia. 37 mm 28 0903 489 217 P. Qty. = 1 dia. 17 mm WIT-DD 16-20 0903 489 016 P. Qty. = 1 Color gray dia. 22 mm 0903 489 214 P. Qty. = 1 dia. 14 mm WIT-DD 12-14 0903 489 012 P. Qty. = 1 Color blue dia. 17,5 mm 0903 489 014 P. Qty. = 1 Color black dia. 19,5 mm 14 10

Hammer drilling procedure: Compressed-air procedure: Diamond drilling procedure:

Compressed-Air Hose, WIT-SDD (pre-mounted) Compr.-Air Nozzle Thread Conn. Hand Slide Valve (pre-mounted) Cleaning Brush

0903 489 008 P. Qty. = 1 Color white dia. 13 mm

Brush Template Cleaning Brush Extension SDS plus Machine Holder

Art. No. Art. No. Art. No. 8 10

0903 489 010 P. Qty. = 1 Color yellow dia. 15,5 mm

Art. No. Outer dia. Designation Art. No. Art. No. Art. No. Color Outer dia.

0903 489 210 P. Qty. = 1 dia. 10 mm WIT-DD 8-10

Reinforcement rod diameter [mm] W-ZA Stay Compressed-Air Nozzle, WIT-DD

8 Art. No. Outer dia. Designation

0699 903 7 P. Qty. = 1 dia. 10 mm WIT-SDD 8-20 0903 489 291 P. Qty. = 1 0699 903 38 P. Qty. = 1

0903 489 099 P. Qty. = 1 0903 489 111 P. Qty. = 2 0903 489 101 P. Qty. = 1 12 M12 0891 009 0891 017 0891 015 0903 488 121 P. Qty. = 20 dia. 10 mm, L = 2 m WIT-MV 8-12 WIT-MV 14-28 0903 488 123 P. Qty. = 10 dia. 10 mm, L = 2 m 16 20 25 M16 M20 P. Qty. = 1 uses 385 mL cartridge P. Qty. = 1 uses 385 mL cartridge P. Qty. = 1 uses 1,400 mL cartridge 0903 488 122 P. Qty. = 20 dia. 16 mm, L = 2 m (L= 2.80 m as special order)

Injection accessories Reinforcement rod diameter [in mm] W-ZA Stay Manual Application Gun Art. No. Pneumatic Extrusion Device Art. No. Mixer Extension, WIT-MV Mixer Extension, WIT-MV exible Injection Adapter, WIT-IA Art. No. Outer dia. Designation Art. No. Outer dia. Art. No. Color Outer dia. Designation

WIT-REBAR System Case

for rod diameter 8 mm through 28 mm Art. No. 0964 903 480 P. Qty. = 1

Case contents Drilling: Drilling aid 17 mm combination wrench Drill hole cleaning accessories: Compressed-air nozzle hose (pre-mounted) for rod diameter 8 - 20 mm Compressed-air nozzle hose (pre-mounted) for rod diameter 25 and 28 mm Compressed-air nozzle dia. 10 mm, dia. 14 mm, dia. 17mm, dia. 27mm Hand slide valve (pre-mounted)

MWF - 08/11 - 11111 -

WIT-REBAR System Case accessories Foam Parts Art. No. for WIT-REBAR System Case Drilling aid Art. No.

Wrth System Components

0903 488 008 P. Qty. = 20 Color white dia. 11 mm WIT-IA 8 0903 488 010 P. Qty. = 20 Color yellow dia. 13 mm WIT-IA10 0903 488 012 P. Qty. = 20 Color blue dia. 15 mm WIT-IA 12 0903 488 014 P. Qty. = 20 Color black dia. 17 mm WIT-IA 14 0903 488 016 P. Qty. = 20 Color gray dia. 19 mm WIT-IA 16 0903 488 020 P. Qty. = 10 Color green dia. 24 mm WIT-IA 20 0903 488 025 P. Qty. = 10 Color brown dia. 31 mm WIT-IA 25 0903 488 028 P. Qty. = 10 Color red dia. 34 mm WIT-IA 28
Cleaning brushes dia. 13 mm, dia. 15.5 mm, dia. 17.5 mm, dia. 19.5 mm, dia. 22 mm, dia. 27 mm, dia. 34 mm, dia. 37mm Brush template Cleaning brush extension SDS plus machine holder Injection accessories: Manual application gun Static mixer Injection adapter dia. 11mm, dia. 13 mm, dia. 5 mm, dia. 17mm, dia. 19 mm, dia. 24 mm, dia. 31mm, dia. 34 mm Bow saw Miscellaneous: Mounting log Mounting instructions Adhesive tape Safety goggles Measuring tape Temperature measurement device Fine-dust mask

Top layer: Bottom layer: 0955 903 480 P. Qty. = 1 0955 903 481 P. Qty. = 1 0903 489 401 P. Qty. = 1

PLASTIC FRAME-FIXING ANCHOR W-UR8

42.1

Multiple attachment of non load-bearing systems: Concrete, solid and perforated bricks and aerated concrete

W-UR 8 with countersunk screw Galvanized steel Stainless steel A4 W-UR F 8 with hexagon screw + pressed-on washer Galvanized steel Stainless steel A4 W-UR F 8 with panhead screw Galvanized steel Stainless steel A4 W-UR F 8 with connecting thread M6 + M8 Galvanized steel Stainless steel A4 Evidence of Performance Approvals
European Technical Approval Multiple attachment of non load-bearing systems in concrete and masonry W-UR (F) 8

Test Reports Facade Covering W-UR 8, W-UR F 8


Z-21.2-1838

Fire Resistance Concrete and masonry

Good to know: Drill perforated and hollow blocks in rotating gear (without impact mechanism). For anchoring in solid brick and solid sand-lime brick, we recommend that you perform pull-out tests due to the dierences in brick manufacturing. Drilling dust is to be removed from the drill hole. Minimal insertion torque of the anchor screw Slight spreading of the anchor, almost no turning of the anchor sleeve 2 setting depths (hnom = 50 + 70 mm): Concrete C12/15; Solid brick Mz 10 ( NF); Vertically perforated brick HLz 8 ( 2DF); Solid sand-lime brick KS 10 ( NF); Perforated sand-lime brick KS L 6 ( 2DF); Perforated sand-lime brick KS L 6 ( 12DF); Normal concrete solid bricks Vbn 10 ( NF); Lightweight concrete solid bricks V 2 ( NF) Spreading in four directions High loads Improved power transmission: Even, continuous load distribution across the entire spreading area Universal frame- xing anchor (concrete, masonry of perforated and solid brick, aerated concrete) The knock-in lock prevents premature spreading of the anchor during installation The anchor sleeve and special screw are pre-mounted Less mounting eort Anchor type W-UR F means an additional washer is not required and prevents contact corrosion Improved transmission of force in solid and hollow construction materials

The anchor may be used with a European technical approval for the multiple attachment of non-load-bearing systems (e.g. facade, suspended ceiling, etc.) W-UR, W-UR F may be anchored in the following anchoring bases: normal concrete masonry walls (solid bricks, solid sand-lime bricks, vertically perforated bricks, perforated sand-lime bricks, hollow blocks made of lightweight concrete, solid stones and solid blocks of lightweight concrete, masonry stones made of concrete) Brick ceilings, hollow pre-stressed concrete panels, reinforced concrete, gypsum wall panels Installation temperatures: Temperature in anchoring base: 40C Temperature of anchor sleeve: 0C The stainless-steel screw may be used outdoors and in industrial atmospheres and near the sea The galvanized screw may be used outdoors or in damp rooms (careful installation) if the area near the screw head is protected against moisture or driving rain so that penetration of moisture into the anchor shaft is not possible (suitable paint). Suitable for the attachment of facade, ceiling, or roof substructures (made of wood or steel), wood beams, wood laths, metal brackets, metal rails, suspended ceilings, cable routes, angle brackets, proles, wall-mounted cabinets, shelf units, etc.

1. Applications

3. Properties

2. Advantages

Through-bolt mounting Can be loaded immediately no waiting time

Anchoring via friction engaging between anchor sleeve and anchor surface W-UR 8, W-UR F 8 (galvanized steel, stainless steel): General construction permit Z-21.2-1838 W-UR 8 and W-UR F 8 (galvanized steel, stainless steel): European Technical Approval ETA-08/0190 The anchor sleeve is made of high-quality polyamide Fire resistance W-UR 8: Concrete: Tensile and transverse load, R30, R60, R90, R120 (based on Technical Report TR 020) Masonry: Tensile load: F30 (solid sand-lime bricks, solid bricks, perforated sand-lime bricks) Transverse load: F30, F60, F90, F120 (vertically perforated bricks, perforated sand-lime bricks, solid bricks, aerated concrete)

Setting Instructions I

Setting Instructions II

MWF - 11/10 - 10843 -

Drill hole

Clean drilled hole

Set anchor and screw

Screw in screw

Screw in screw until ush

Drill hole

Clean drilled hole

Set anchor and screw

Screw in screw

Screw in screw until ush

PLASTIC FRAME-FIXING ANCHOR W-UR 8


Mounting characteristic values for concrete and masonry
Anchor diameter [mm] Nom. drill dia. Drill cutting dia. Drill hole depth Setting depth of the anchor sleeve Through-hole in attachment part d 0 [mm] dcut [mm] h1 [mm] h nom [mm] d f [mm] W-UR 8 8 8.45 607) 507) 8.5

42.1

80 70

Concrete: ETA-08/0190, Multiple attachment of non-load-bearing systems


Anchor diameter [mm] Central tensile load1) for single anchor or anchor group Transverse load1) Galvanized steel Stainless steel A4 for single anchor or anchor group N perm = C12/15 [kN] N perm C16/20 [kN] Vperm C12/15 [kN] 30C 2)/50C 3) 50C 2)/80C 3) 30C 2)/50C 3) 50C 2)/80C 3) W-UR 8 1.2 1.0 1.8 1.4 3.37 3.16 1.6 1.4 2.4 2.0 3,37 3,16

Masonry4): ETA-08/0190, Multiple attachment of non-load-bearing systems (temperature range: 50C2)/80C3)) Other brick types, raw densities, minimum compressive strengths or temperature ranges can be found in the ETA-08/0190 approval.
Brick format [mm] Clay brick Mz, EN 771-1, DIN 105 Solid sand-lime brick KS, EN 771-2, DIN 106 Solid normal concrete brick Vbn, EN 771-3, DIN 18152 Vertically perforated brick HLz 6), EN 771-1, DIN 105-1 e.g. Wienerberger, Schlagmann Vertically perforated brick POROTON S11-36.56), EN 771-1, Z-17.1-812 Wienerberger, Schlagmann Vertically perforated brick UNIPOR WS14, UNIPOR WS12 CORISO EN 771-1, Z-17.1-883 Unipor-Ziegel Marketing GmbH NF ( 240 x 115 x 71) NF ( 240 x 115 x 71) Raw density class [kg/dm 3] 1.8 2.0 Minimum compressive strength [N/mm2] 28 36 10 20 28 10 20 28 8 12 20 6 10 0.8 12 10 12 16 10 12 16 2 4 6 2 4 2 7 Fperm [kN]5) (for single anchors or anchor groups) W-UR 8 hef= 50 to 69 mm/h ef= 70 mm 0.71 0.86 1.0 1.14 0.43 0.43 0.57 0.71 0.86 1.0 0.43 0.43 0.71 0.71 1.0 1.0 0.14 0.21 0.21 0.26 0.34 0.43 0.26 0.26 0.34 0.57 0.17 0.21 0.57 0.71 0.71 0.26 0.34 0.43 0.11 0.26 0.34 0.17 0.34 0.14 0.85

NF ( 240 x 115 x 71)

2.0

2DF ( 240 x 115 x 113)

1.2

248 x 365 x 249 10DF ( 247 x 300 x 249)

0.9

Perforated sand-lime brick EN 771-2, DIN 106-1 e.g. Xella

KSL 6),

2DF ( 240 x 115 x 113)

1.6

8DF ( 249 x 240 x 238)

1.4

Lightweight concrete hollow block 3K Hbl, EN 771-3, DIN 181516) e.g. Liapor Lightweight concrete hollow block Liapor-Super-K6), EN 771-3, Z-17.1-501 Aerated concrete AAC

16DF ( 498 x 240 x 238) 16DF ( 495 x 240 x 238)

0.7 0.8

Anchor dimensions
Anchor diameter Total length Max. attachment height, h nom = 50 mm7) / 70 mm Plastic Frame-Fixing Anchor W-UR 8 with countersunk screw, galvanized steel Plastic Frame-Fixing Anchor W-UR 8 A4 with countersunk screw, stainless steel A4 Plastic Frame-Fixing Anchor W-UR F 8 with countersunk screw and pressed-on washer, galvanized steel Plastic Frame-Fixing Anchor W-UR F 8 A4 with countersunk screw and pressed-on washer, stainless steel A4 Plastic Frame-Fixing Anchor W-UR F 8 with pan head screw, galvanized steel Plastic Frame-Fixing Anchor W-UR F 8 with pan head screw, stainless steel A4 Plastic Frame-Fixing Anchor W-UR F 8 with M6 stud screw, galvanized steel Plastic Frame-Fixing Anchor W-UR F 8 with M6 stud screw, stainless steel A4 Plastic Frame-Fixing Anchor W-UR F 8 with M8 stud screw, galvanized steel Packing unit
1)

[mm] l [mm] t fix [mm] Art. No. Drive AW 30 Art. No. Drive AW 30 Art. No. Drive AW 25, 10 mm Art. No. 10 mm Art. No. Drive AW 30 Art. No. Drive AW 30 Art. No. 10 mm Art. No. 10 mm Art. No. 10 mm P. Qty. [pieces]

W-UR 8 60 107) / 0912 808 402 0912 808 502 0912 808 602 0912 808 702 0912 808 802 0912 808 902 0912 808 202 0912 808 302 0912 808 252 50

80 307) / 10 0912 808 403 0912 808 503 0912 808 603 0912 808 703 0912 808 803 0912 808 903 0912 808 203 0912 808 303 0912 808 253 50
5)

100 507) / 30 0912 808 404 Available via S-Procurement 0912 808 604 Available via S-Procurement 50

120 707) / 50 0912 808 405 Available via S-Procurement 0912 808 605 Available via S-Procurement 50

140 907) / 70 0912 808 406 50

160 1107) / 90 0912 808 407 50

MWF - 10/10 - 10844 -

The part safety coecients of the resistances regulated in the approval and a part safety coe cient of the e ects of F = 1.4 have been taken into account. In case of a combination of tensile and transverse loads, please observe ETAG 020 Appendix C. 2) Maximum long-term temperature. 3) Maximum short-term temperature. 4) Other brick types, raw densities, minimum compressive strengths and temperature ranges can be found in the ETA-08/0190 approval.

The brick geometry should be compared with the ETA-08/0190 approval. 6) If the drill hole is created through impacting or hammering, the permissible load is to be determined via tests on the building. 7 ) 2. Setting depth applies for the following anchoring bases: Concrete C12/15; Solid brick Mz 10 ( NF); Vertically perforated brick HLz 8 ( 2DF); Solid sand-lime brick KS 10 ( NF); Solid sand-lime brick KS L 6 ( 2DF); Perforated sand-lime brick KS L 6 ( 12DF); Solid normal concrete brick Vbn 10 ( NF); Solid lightweight concrete brick V 2 ( NF).

Can be stored in ORSY System

91 Nylon Anchor
Polyamide (nylon) dia. 5-8 Polyamide (nylon) dia. 10-20 Installation Impact Tool dia. 6, 8, 10 mm Used for creation of the drill hole in aerated concrete ( PB4, install in stages: pound in, release, etc.)

Art. No. 0906 100 001

Proof of performance
Assortment Case
Nylon Anchor Assortment Contents: 5 x 25 = 200 pc. 6 x 30 = 300 pc. 8 x 40 = 150 pc. 10 x 50 = 100 pc. 12 x 60 = 30 pc. 14 x 75 = 20 pc. = 800 pieces Art. No. 0964 903 001 P. Qty. 1

Important information for experts: Drill aerated concrete and perforated bricks in rotating gear (without impact mechanism). Drilling dust must be removed from the drill hole. Screw length = attached part thickness (+ plaster/insulation thickness) + anchor length + screw dia.

1. Applications
Plastic anchors for lower load range (secondary fastening) Can be used in concrete, solid brick, solid sand-lime brick, aerated concrete and pressure-resistant natural stone. Suitable for securing curtain rails, wall shelves, light hanging cupboards, picture frames, cable ducts, cable clamps, electrical switches, hand towel rails, signs, motion detectors, hanging baskets, etc. For the attachment of components in conjunction with a wood or particle board screw (no drill bit, counter thread or ring thread) Can be used outside or in rooms subject to moisture in conjunction with a stainless-steel screw

2. Advantages
The knock-in lock prevents premature spreading during through-bolt mounting The twist lock prevents turning in the drilled hole Spreading-pressure-free dowel neck prevents damage to plaster and tiles Through-bolt and cotter-pin mounting

3. Features
High-quality polyamide (nylon) Halogen- and silicone-free Temperature-resistant from 40C to +80C

Setting instructions

MWF - 01/10 - 04336 -

Drill hole

Clean drilled hole

Set anchor in place

Watch spreading part position in edge area

Secure component

Nylon Anchor
Performance Data
Anchor diameter [mm] Recommended load 1)
Concrete B25; C20/25 Solid brick Mz12 Solid sand-lime brick KS12 Aerated concrete PP4, PB4

91

4 0.15 Frec. [kN] 0.14 0.14

5 0.25 0.25 0.25 0.03

6 0.38 0.3 0.3 0.06

8 0.6 0.5 0.5 0.1

10 0.9 0.15

12 1.4 0.2

14 1.9

16 2.3

20 3.0

Characteristic Values
Axial spacing Edge clearance Drill hole depth Setting depth Nominal drill dia. Wood screw dia. Particle board screw dia. Screw length a

[mm]

40 20 30 20 4 23 3.5

50 25 35 25 5 2.5 4 4.5

60 30 40 30 6 3.5 5 5

80 40 50 40 8 4.5 6 6

100 50 65 50 10 68

120 60 75 60 12 8 10

140 70 85 75 14 10 12

160 80 95 80 16 12 14

200 100 105 90 20 16

ar [mm] t [mm] hS [mm] ddrl [mm] dscr.wood [mm] dscr.particle [mm] lS [mm]

Attached part thickness (+ plaster/insulation thickness) + anchor length + screw dia.

Anchor Dimensions
Anchor diameter Total length Max. mounting height Designation Nylon Anchor l [mm] da [mm]
4 x 20 5 x 25 6 x 30

4
20

5
25

6
30

8
40

10
50

12
60

14
75

16
80

20
90

Depends on screw length


8 x 40/M6 10 x 50 12 x 60 14 x 75 16 x 80 20 x 90 8 x 40

0903 14 75

0903 10 50

0903 12 60

0903 8 406 P. Qty. = 100

Nylon anchor with M 6 metric thread, white (for screwing in threaded rods, screws, bolts) Art. No. Packing unit in ORSY ORSY cartons in cartons + outer carton bulk packed... pieces each) P. Qty.

0903 16 80

0903 5 25*

0903 6 30*

0903 4 20

0903 8 40

Art. No. Nylon Anchor

200

100/1000

100/500

100/300

50/200

25

20 480/20 ea.

10

5400/100 ea. 4000/500 ea. 2400/300 ea. 1200/50 ea. 600/25 ea. 8000/1000 ea.4800/100 ea. 2300/100 ea. 1600/200 ea.

Wrth System Components