MAKING MODERN LIVING POSSIBLE

Optyma Condensing Unit Right Choice for Each Application

TM

Multi-refrigerant capability

Dual Technology

Option of complete range between Scroll and Reciprocating compressor technology

Units with MLZ suitable for R404A/R507/R134a/R407c & R22

O P T Y M AT M
www.danfoss.com/drives
DANFOSS CONDENSING UNITS

Low Temperature Application


60 50 Amb Temp 40 30 20 10 0 -45 -40 -35 -30 -25 20 -15 -10 -5 0

Evap Temp

R404A/R507 - Evaporating temperature range -40 to -10 C


Condensing Unit Model OP- LGHE068 OP- LGHE068 OP- LCHE096 OP- LGHE108 OP- LGHE136 OP- LGHE215 OP- LGHE271 Code 114X8000 114X8001 114X8002 114X8003 114X8004 114X8005 114X8006
Compressor

Model NTZ068 NTZ068 NTZ096 NTZ108 NTZ136 NTZ215 NTZ271

Nominal Electrical phases HP 2 2 3 3 4 7 8 1 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph

Cooling capacity W 1560 1560 1726 2096 2786 3690 5493 Btu/hr 5323 5323 5892 7153 9508 12593 18747

Power i/p kW 1.88 1.88 2.02 2.43 3.47 4.83 6.82

Dimensions (mm) Height 655 655 655 655 725 725 725 Width 760 760 760 760 800 800 800 Length 700 700 700 700 1210 1210 1210

Weight Kg 56 56 71 73 97 141 144

Ambient temp 46C

No added subcooling

Evaporating temp -30C

Superheat 10K All dimensions and weight are for bare unit design A02.

1 ph 220V / 1~ / 50Hz & 3 ph 400V / 3~ / 50Hz

Designation system for Optyma Condensing Unit program


1. Application 2. Platform / design 3. Refrigerant 4. Condenser option 5. Compressor displacement 6. Compressor platform 7. Level of equipment 8. Electrical version
1 2 3 4 5 6 7 8

OP - MCME 060 MT A06 G

1.

L - Low (LBP) M - Medium (MBP) U - Low / Medium / High (Universal) C - Air cooled condensing unit with 1 fan G - Air cooled condensing unit with 2 fan P - MCHE Condenser with 1 fan Z - R404A/R507/R407C/R134a M - R22 U - R404A/R507/R407C/R134a/R22 H - R404A/R507 C - Standard condenser E - Oversized condenser for Higher ambient and / or higher efficiency

5.

Compressor displacement in cc/rev

2.

6.

Compressor platform - ML, MT, NT, SM, SZ

3.

7.

A02 - With receiver, stop valves, pressure switch and electrical box A06 - A02 + filter drier, sight glass, solenoid valve, weather proof canopy W02 - Standard Unit Slimpack version W04 - W02 + Fully equipped Electrical box G - Compressor 220V/1~/50 Hz Fan 220V/1~/50 Hz D - Compressor 400V/3~/50 Hz Fan 400V/3~/50 Hz E - Compressor 400V/3~/50 Hz Fan 220V/1~/50 Hz

4.

8.

If the condensing unit you are looking for is not mentioned in this leaflet or if you have special requirments, Danfoss partner wholesalers or local Danfoss teams can offer you help and guidance and will do their utmost to fulfil your needs.

60 50 Amb Temp 40 30 20 10 0 -25 -20 -15 -10 -5 Evap Temp 0 5 0 15

R22 - Evaporating temperature range -20 to +10 C


Condensing Unit Model OP- MCUE034 OP- MCUE046 OP- MCUE046 OP- MGUE069 OP- MGUE080 OP- MGUE107 OP- MGUE126 OP- MGUE148 OP- MGUE162 OP- MGME217 OP- MCME038 OP- MCME048 OP- MCME060 OP- MCME060 OP- MGME086 OP- MGME108 OP- MGME121 OP- MGME136 OP- MGME171 OP- MGME215 OP- MGME242 OP- MGME271 Code
Compressor

Nominal Electrical HP 2 3 3 4 5 6 7 8 10 13 1 2 3 3 4 5 6 6 8 10 12 13 phases 3 Ph 1 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 1 Ph 3 Ph 1 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph

Cooling capacity W 3567 4876 4876 7404 8485 11366 13618 15773 17859 20543 2835 3975 5073 5073 6344 8138 9518 11214 12810 16417 18018 20109 Btu/hr 12174 16642 16642 25269 28960 38791 46477 53834 60952 70113 9675 13565 17315 17315 21653 27774 32485 38272 43721 56032 61496 68630

Power i/p kW 1.92 2.61 2.61 3.80 4.69 5.80 6.44 7.41 9.03 9.94 1.52 2.16 2.86 2.86 3.57 4.82 5.10 5.97 6.75 9.05 10.22 11.46

Dimensions (mm) Height 655 655 655 725 725 725 1005 1005 1005 1005 655 655 655 655 725 725 725 725 1005 1005 1005 1005 Width 760 760 760 800 800 800 875 875 875 875 760 760 760 760 800 800 800 800 875 875 875 875 Length 700 700 700 1210 1210 1210 1510 1510 1510 1510 700 700 700 700 1210 1210 1210 1210 1510 1510 1510 1510

Weight Kg 62 73 73 99 99 99 201 201 201 249 57 61 72 72 102 118 125 128 208 220 223 228

Model

114X8044 MLZ015 114X8315 MLZ021 114X8316 MLZ021 114X8319 MLZ030 114X8321 MLZ038 114X8325 MLZ048 114X8045 MLZ058 114X8046 MLZ066 114X8047 MLZ076 114X8660 SM160-4 114X8017 MT22 114X8018 MT28 114X8111 MT36 114X8112 MT36 114X8120 MT50 114X8022 MT64 114X8024 MT73 114X8026 MT80 114X8028 MT100 114X8029 MT125 114X8030 MT144 114X8031 MT160

Ambient temp 46 C

1 ph 220V / 1~ / 50Hz & 3 ph 400V / 3~ / 50Hz

No added subcooling

Evaporating temp - 5C

Superheat 10K All dimensions and weight are for bare unit design A02.

Medium Temperature Application

R404A/R507 - Evaporating temperature range -20 to + 10 C


Condensing Unit Model Code
Compressor

Nominal Electrical HP 2 3 3 4 5 6 7 8 10 13 1 2 3 4 5 6 8 10 12 13 phases 3 Ph 1 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 1 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph 3 Ph

Cooling capacity W 3118 4497 4497 6644 7546 10536 12633 14873 15423 20266 2789 3435 4568 6089 7457 10428 12916 15602 17460 19265 Btu/hr 10643 15349 15349 22674 25754 35960 43116 50763 52640 69167 9518 11725 15590 20782 25451 35592 44081 53249 59591 65750

Power i/p kW 2.24 2.94 2.94 4.33 5.39 6.70 7.60 8.70 10.06 11.55 1.74 2.34 3.10 4.24 5.48 6.70 7.88 10.05 11.69 13.32

Dimensions (mm) Height 655 655 655 725 725 725 1005 1005 1005 1005 655 655 655 725 725 725 1005 1005 1005 1005 Width 760 760 760 800 800 800 875 875 875 875 760 760 760 800 800 800 875 875 875 875 Length 700 700 700 1210 1210 1210 1510 1510 1510 1510 700 700 700 1210 1210 1210 1510 1510 1510 1510

Weight Kg 62 73 73 99 99 99 201 201 201 249 57 61 72 102 118 128 208 220 223 228

Model

OP- MCUE034 114X8044 MLZ015 OP- MCUE046 114X8315 MLZ021 OP- MCUE046 114X8316 MLZ021 OP- MGUE069 114X8319 MLZ030 OP- MGUE080 114X8321 MLZ038 OP- MGUE107 114X8325 MLZ048 OP- MGUE126 114X8045 MLZ058 OP- MGUE148 114X8046 MLZ066 OP- MGUE162 114X8047 MLZ076 OP- MGZE217 114X8760 SZ160-4 OP- MCZE038 OP- MCZE048 OP- MCZE060 114X8007 MTZ22 114X8008 MTZ28 114X8009 MTZ36

OP- MGZE086 114X8010 MTZ50 OP- MGZE108 114X8011 MTZ64 OP- MGZE136 114X8012 MTZ80 OP- MGZE171 114X8013 MTZ100 OP- MGZE215 114X8014 MTZ125 OP- MGZE242 114X8015 MTZ144 OP- MGZE271 114X8016 MTZ160
Ambient temp 46 C

No added subcooling

Evaporating temp - 5C

Superheat 10K All dimensions and weight are for bare unit design A02.

1 ph 220V / 1~ / 50Hz & 3 ph 400V / 3~ / 50Hz

60 50 Amb Temp 40 30 20 10 0 -25 -20 -15 -10 -5 0 5 0 15

Evap Temp

SLIM PACK Condensing units


R404A Electrical Nominal Compressor phases Capacity Power HP W W R22 Capacity W Power W R134a Capacity W Power W Height mm Dimensions Width mm Length mm Weight Kg

Model

MPUE034 MPUE046 MPUE068 MPUE080 MPUE093 MPUE107 MPME048 MPME060

MLZ015 MLZ021 MLZ030 MLZ038 MLZ045 MLZ048 MT28 MT36

2 3 4 5 6 6 2 3

1 & 3 Ph 1 & 3 Ph 1 & 3 Ph 1 & 3 Ph 3 Ph 3 Ph 1 & 3 Ph 1 & 3 Ph

3340 4533 7699 8927 10332 11054

2193 3077 3925 4831 6097 6724

3591 4730 7822 9085 10180 11291 4006 4857

1897 2737 3506 4252 5224 5853 2156 2907

2320 3072 4825 5602 6804 7167

1262 1699 2393 2913 3409 3699

695 695 830 830 830 830 695 695

464 464 464 464 464 464 464 464

1106 1106 1106 1106 1106 1106 1106 1106

74 74 96 96 96 96 66 68

Ambient temp 46 C

No added subcooling

Evaporating temp - 5C

Superheat 10K

1 ph 220V / 1~ / 50Hz & 3 ph 400V / 3~ / 50Hz

The design which makes a difference:


1. Heat exchanger and housing resistant to corrosion prolongs the lifetime of the unit. 2. Microchannel heat exchanger enhances units performance and saves on energy. 3. Accessible fan and condenser for easy maintenance. 4. Accessible pre-wired electrical junction panel enables easy servicing. 5. Solenoid valve protects compressor from liquid flood back. 6. Safety cartridge pressure swicthes HP & LP. 7. Filter drier protects from moisture, acids and solid particles. 8. Receiver with service valve makes service easier. 9. Crankcase heater protects compressor against liquid migration. 10. Quick connections accelerate installation. 11. Accessible service ports. 12. Option to have fully equipped Electrical box for Quick installation.

w Ne
1 2 4 3 5 6 12

8 7 10 11 9

Notes

Reduce your customers' running costs:


OptymaTM with scroll & reciprocating technology is very energyefficient solution for your application. Due to the large heat transfer area and high COP of our condensers you are going to reduce the energy consumption significantly and therefore cut the energy bill.

Optimise your stock and logistics:


OptymaTM range is available for use with R404A/ R507/R134A as well as R22. Multifunctional condensing unit is perfect for a wide variety of applications. It will reduce your stock and improve your logistics.

Installation just got easier:


OptymaTM save costs for service and maintenance. The high robustness and easy access to all components, reduces cost of installation even in very harsh environments.

No compromise on quality:
We at Danfoss do not accept any compromise regarding quality & reliability for our products. With OptymaTM we provide 100% factory tested units to our customers with a premium Quality.

Complete range of refrigeration products

Electronic thermostat Solenoid valve Thermostatic Expansion valve Temperature sensor

Sight glass

Ball valve

Filter drier

Ball valve

OptymaTM

OptymaTM Slimpack

OptymaTM Plus

Danfoss Commercial Compressors is a worldwide manufacturer of compressors and condensing units for refrigeration and HVAC applications. With a wide range of high quality and innovative products we help your company to nd the best possible energy ecient solution that respects the environment and reduces total life cycle costs. We have 40 years of experience within the development of hermeting compressors and today we operate engineering and manufacturing facilities spread across three continents.

Performer Variable Speed scroll compressors

Performer Air Conditioning scroll compressors

Performer Heat Pump scroll compressors

Maneurop Variable Speed reciprocating compressors

Performer Refrigeration scroll compressors

Maneurop Reciprocating Compressors

Optyma Plus Condensing Units

Optyma Condensing Units

Our products can be found in a variety of applications such as rooftops, chillers, residential air conditioners, heatpumps, coldrooms, supermarkets, milk tank cooling and industrial cooling processes.

member of:

www.asercom.org
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

INCC.PB.028.A1.02 - Replaces INCC.PK.028 September 2011