Author Lutz Hulka | lutz.hulka@omicron.at Markus Ptter | markus.puetter@omicron.at Date Dec 15, 2010 Related OMICRON Product CPC 100 Application Area Instrument Transformer Testing, Power Transformer Diagnosis, Rotating Machines Diagnosis, Grounding System Analysis Version v1.1 Document ID ANP_10021_ENU

OMICRON

Page 1 of 24

Contents
1 Using This Document ............................................................................................................................3 1.1 Conventions and Symbols Used ....................................................................................................3 1.2 Related Documents ........................................................................................................................3 CPC 100 Start Page ...............................................................................................................................4 2.1 General Settings .............................................................................................................................4
2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.1.7 Language .......................................................................................................................................... 4 Web Links ......................................................................................................................................... 4 Device Settings ................................................................................................................................. 5 Manuals .......................................................................................................................................... 12 Application Notes ............................................................................................................................ 12 Show News ..................................................................................................................................... 13 Application Videos .......................................................................................................................... 13 Template Filter ................................................................................................................................ 14 Transferring One or More Test Templates ...................................................................................... 14 Transferring All Test Templates to the CPC 100 ............................................................................ 20 Show Template Usage.................................................................................................................... 20 Types of OMICRON Test Templates .............................................................................................. 21 Tools ............................................................................................................................................... 23

2.2

OMICRON Test Templates.......................................................................................................... 13


2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6

Please use this note only in combination with the related product manual which contains several important safety instructions. The user is responsible for every application that makes use of an OMICRON product.

OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON. OMICRON 2010. All rights reserved. This application note is a publication of OMICRON. All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted. The product information, specifications, and technical data embodied in this application note represent the technical status at the time of writing and are subject to change without prior notice. We have done our best to ensure that the information given in this application note is useful, accurate and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present. OMICRON translates this application note from the source language English into a number of other languages. Any translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern.

OMICRON 2010

Page 2 of 24

Using This Document

This Application Note describes how to use the OMICRON CPC 100 Start Page and the OMICRON Test Templates.

1.1

Conventions and Symbols Used


In this document, the following symbols indicate paragraphs with special safety relevant meaning:

Symbol

Description Equipment damage or loss of data possible.

Personal injury or severe damage to objects possible.

1.2

Related Documents
The following document completes the information covered in this Application Note.

Title CPC 100 Reference Manual

Description Provides detailed hardware and software information on the CPC 100 test system including relevant safety instructions.

OMICRON 2010

Page 3 of 24

CPC 100 Start Page


Open the OMICRON CPC 100 Start Page with the shortcut on your desktop. The OMICRON CPC 100 Start Page will open.

2.1
2.1.1

General Settings
Language The OMICRON CPC 100 Start Page is available in different languages. Choose the language next to the header by clicking the drop-down list box. The build number of the CPC 100 Start Page is also shown on the top.

The following User Interface (UI) languages are available: English German French Spanish Simplified Chinese Traditional Chinese Japanese Russian (further languages might be available in the future) 2.1.2 Web Links

OMICRON 2010

Page 4 of 24

Visit the OMICRON electronics website directly from the CPC 100 Start Page to get more information about OMICRON electronics and the latest products.

2.1.3

Device Settings Device List Choose the device by clicking the drop-down combo box. If your device is not displayed, try the Refresh button.

Choose the device Refresh button

The CPC 100 Start Page also provides information about the current software version of the selected device. The number in brackets (for example, 660) indicates the corresponding build number.

Firmware Upgrade of the CPC 100 First, connect the CPC 100 with a computer or laptop, which are in the same network.
1.

To upgrade the CPC 100 click the Manage drop-down list box and select Upgrade device....

2.

The following window will be displayed. Confirm this window by clicking OK to continue the upgrade procedure.

OMICRON 2010

Page 5 of 24

3.

Select the right upgrade package for your device.

Check on your CPC 100 nameplate if you have a: V0 device V1 device and select the upgrade package accordingly. Note: The files UpgradeV1_CHS_nnn.upg and UpgradeV1_CHT_nnn.upg are Chinese language packs. Detailed information about upgrading the CPC 100 is available.
4.

The next window asks you to start the upgrade process.

The upgrade procedure takes about one minute. A message box will inform you if the update has been successful. Do not interrupt the upgrade process and keep your CPC 100 running.

Limited Functionality

OMICRON 2010

Page 6 of 24

Device names written in red color indicate that the device is in a restricted mode and permits only firmware upgrades. All the other device management actions, such as file and test template transfer etc., are disabled.

IP Configuration (Device Network Settings)


1.

To configure the IP address of the CPC 100 click the Manage drop-down list box and select IP configuration....

2.

Select either DHCP/Auto IP or Static IP.

Caution: Be careful when using this option. Your device might get inaccessible with the wrong IP settings.

View Logfile (CPC 100 Logfile Viewer)

OMICRON 2010

Page 7 of 24

The logfile contains information about internal operations of the device. If the device behaves unexpectedly, the logfile will help the OMICRON electronics Technical Support Team to help you on the issue. The file contains history records of events on the device.
1.

To view the logfile click the Manage drop-down list box and select View log file....

2.

The window CPC 100 Logfile Viewer (device number in brackets) opens. It takes a moment until the logfile is loaded and displayed.

3.

The log records are displayed in the following window.

4.

To refresh the logfile click the Refresh logfile button.

OMICRON 2010

Page 8 of 24

5.

Save the logfile on your local disk by clicking the Save as... button.

The following window will appear.

Predefined Phrases (CPC 100 Phrase Editor) As of version 1.43 a feature is offered which allows you to alter the default phrases of the String Editor of the CPC 100. There are two categories of phrases: Comment card phrases and File name and test card phrases. These phrases facilitate the entry of frequently used texts or file names. To open this feature click the Manage drop-down list box and select Predefined phrases....

The following window will appear.

OMICRON 2010

Page 9 of 24

Editing Phrases The current phrases of the selected device are displayed. Phrase Category Comment card phrases File name and test card phrases Allowed Characters A - Z, a - z, 0 - 9, _ ! ? . , : ; ( ){ A - Z, a - z, 0 - 9, blank, _

}[]%$

The following operations are possible for a selected phrase. Symbol Operation Move the phrase to the other panel. The phrase is removed from the current panel. Copy the phrase to the other panel. Add a line to enter a new phrase. Delete the selected phrase. Copy the selected phrase to the clipboard. Insert text from the clipboard. Move the phrase to the top. Move the phrase one position up. Move the phrase one position down. Move the phrase to the bottom. Edit the selected phrase. The phrases can be edited as follows: Via quick buttons: Mark the text and choose the symbols above or between the text fields.

OMICRON 2010

Page 10 of 24

Via context menu: Mark the text. Right-click on the marked text and choose Edit.

Via keyboard shortcuts: o Edit: space or F2 o Add: Enter or + o Delete: Del or o Insert from clipboard: Ins

Importing Phrases from a File It is possible to import phrases from a text file. The file has to be coded in ASCII characters and the phrases separated by carriage returns.

1.

Write some frequently used texts in a *.txt file and store it on your local disk.

2. 3.

On the CPC 100 Phrase Editor click the button. Choose to which category of phrases the phrases in the file shall be imported.

4.

Browse the stored *.txt file and open it. The text is shown in the corresponding text field.

OMICRON 2010

Page 11 of 24

1. 2.

Click the

button.

Choose which phrase category to export.

3.

Save the file as *.txt file on your local disk.

Transferring the Phrases to the Device After entering your individual texts, transfer phrases back to the CPC 100 by clicking the button. 2.1.4 Manuals The Manuals on the CPC 100 and its accessories can be viewed under Manuals. Manuals describe general functions of the CPC 100 hardware and software.

The following manuals are currently available: CPC 100 User Manual CPC 100 Reference Manual PTM User Manual CP TD1 manuals: o CP CAL1 User Manual o CP CR500 User Manual o CP TC12 Reference Manual o CP TD1 Reference Manual CP CU1 manuals: o CP AL1 User Manual o CP CU1Reference Manual CP SB1 User Manual (more Manuals may be available in the future) 2.1.5 Application Notes The Application Notes on the CPC 100 can be viewed under Application Notes. Application Notes describe particular test cases.

The following Application Notes are currently available:

OMICRON 2010

Page 12 of 24

AN CP0801 Mutual Coupling Measurements AN CP0502 Touch Voltage AN CP0902 VT Ratio Measurement with 12 kV AN CP0901 Power Transformer Short-Circuit Impedance (more Application Notes may be available in the future)

2.1.6

Show News To view the latest news on OMICRON electronics click Show news....

2.1.7

Application Videos The OMICRON CPC 100 Start Page offers Application Videos for a variety of tests and user interface simulation. To view the videos click Application Videos.

2.2

OMICRON Test Templates


OMICRON electronics offers predefined test templates for numerous applications. The test templates always consist of file pairs for the CPC 100 and Microsoft Excel and include an example file for loading into the Excel file. More information about the applications can be found in the CPC 100 User Manuals or Application Notes. All Microsoft Excel templates are available in several languages.

A test always consists of a pair of: 1. CPC 100 test template (*.xmt file): Contains predefined empty test cards. After conducting the test with the CPC 100, it contains the measured results. 2. Microsoft Excel sheet for evaluation and reporting (*.xlt file): To import the measurement results from the test template and for the presentation of results.

The CPC 100 test template (*.xmt file) and the Microsoft Excel sheet (*.xlt file) is a pair which belongs together. You will automatically get a report (for example, the Auto-TR Dissp. Factor test).

OMICRON 2010

Page 13 of 24

The following figures show how to open the test templates in the CPC Editor and CPC Excel File Loader.

CPC Editor:

CPC Excel File Loader:

The following figures show how the test templates (*.xml file) can be displayed in a folder (for example, Auto_TR_C-DF_wRes.xml).

2.2.1

Template Filter

Caution: Before using the test templates make sure that the right frequency is set. You can choose between 50 Hz and 60 Hz templates. To change the frequency click Applied filter: 50 Hz.

2.2.2

Transferring One or More Test Templates The following description explains how to transfer one or more templates to the CPC 100 a local disk a mass storage device like a USB stick. There are two ways to select the required test templates.

Template Transfer Wizard

OMICRON 2010

Page 14 of 24

1.

Click the Transfer wizard... symbol.

2.

Select the test templates of your choice using the check boxes.

Selecting Test Cases

1.

Open a test template (for example, Power transformers).

2.

Click Add to transfer selection or double-click the green square.

The green square is now marked.

3.

If you want to transfer a second test template or more, open again a test template and click Add to transfer selection or double-click the green square. The green square is now marked.

OMICRON 2010

Page 15 of 24

4.

To delete a test template from the transfer selection click Remove from transfer selection.

5.

Once you have selected all required templates, click the Transfer wizard... symbol.

6.

The Select templates for transfer window opens. The selected test templates are checked in the check box. However, selections can still be changed.

To open the Application Note of a test template click the

symbol.

Transfer to the CPC 100 Once you have finished your individual settings, click .

Select Transfer Location

OMICRON 2010

Page 16 of 24

1.

Location

It is possible to transfer the test templates to the CPC 100 or a local folder. For transferring the test templates to the CPC 100 click CPC 100 in the group box.

Select the device in the combo box. If the device is not displayed in the combo box, click the button. You can name the Target folder as you wish. However, valid paths must not begin with / and can only contain alphanumerical characters (A - Z, a - z, 0 - 9) and forward slashes (/) but not two or more successive forward slashes. Only a maximum of 255 characters are allowed. For transferring the test templates to a local folder or to a mass storage device (for example, USB stick) click Local folder in the group box.

Choose a folder or enter the target directory to which the test templates should be transferred into the text field. Browse the folder by clicking Change...

2.

Options

There are two options for transferring the test templates:

Retain folder structure on transfer:

OMICRON 2010

Page 17 of 24

This option allows to transfer the test templates of different devices (for example, Power Transformers, Rotating Machines, Other, Instrument Transformers, Grounding Systems or Cables & Transmission Lines) in the same logical folder structure.

The subfolders are created automatically. When transferring all test templates at once, this is the default setting. Keep templates selected after transfer: Templates remain selected after the file transfer. This is comfortable, for example, if you have more than one device to which you want to transfer the same test templates, or you like to remember which templates you have transferred.

3.

Transferring of test templates

OMICRON 2010

Page 18 of 24

Click to start the transfer of the test templates to your CPC 100 or your local folder. At the end of the transfer procedure a message that reads Transfer completed will be displayed.

Click again to continue. Now the Open corresponding Excel templates dialog is shown. It lists the corresponding Excel templates to the matching CPC 100 templates just transferred. Templates which could not be transferred are shown in red color. Templates which you have chosen not to overwrite if they already existed are shown in blue color. Click an item in the list to open the CPC Excel File Loader Template.

With the Load XML-File button, the results can be directly loaded from the CPC 100.

OMICRON 2010

Page 19 of 24

2.2.3

Transferring All Test Templates to the CPC 100 The CPC 100 Start Page allows you to transfer all templates at once. There are two ways to transfer all test templates. Template Transfer Wizard Click the All check box to select all available test templates.

Test Cases Click, for example, the Power transformers symbol to select all test templates for this category. To transfer the test templates click the Transfer wizard... symbol.

2.2.4

Show Template Usage The current Application Note is available under Show template usage...

OMICRON 2010

Page 20 of 24

2.2.5

Types of OMICRON Test Templates Templates for Power Transformers Transformer Ratio The Transformer Ratio templates facilitate the examination of the transformer ratio of power transformers with tap changers. The no-load current is also measured and displayed. Transformer Short Circuit Impedance - Leakage Reactance Using this template, you can quickly measure the short-circuit impedance and hence also the leakage inductance or leakage reactance of power transformers. Graphical display provides a wellarranged overview of the measured values. Transformer Tap Changer The graphical display of the phase switch tests quickly shows whether the tap changers need to be checked. Displaying the upward and downward tap changer movement in the same diagram supports the power transformer diagnosis. Both static DC resistance and dynamic switchover behavior between two taps are measured and displayed. TR_2-WIND This template is available for both the power factor and dissipation factor measurements between the windings and against the tank of two-winding power transformers. TR_3-WIND This template is available for both the power factor and dissipation factor measurements between the windings and against the tank of three-winding power transformers. Auto-TR This template is available for both the power factor and dissipation factor measurements between the winding and the tank of auto-transformers. Bushing This template is available for both the power factor and dissipation factor measurements. The template for transformer bushing displays the results graphically and in tabulated format. Displaying the measurements against voltage and frequency supports the fault diagnosis. Templates for Instrument Transformers CT Accuracy Limiting Factor You can use this template to approximate the accuracy limiting factor of a current transformer from three individual measurements (CT burden, winding resistance, magnetization curve). You can toggle between nominal and actual burden. Comprehensive CT Test Report This template demonstrates how to display a report for three current transformers including transformation measurement, winding resistance measurement, magnetization curve etc. on one page. CT This template is available for both the power factor and dissipation factor measurements on current transformers.

OMICRON 2010

Page 21 of 24

CVT This template is available for both the power factor and dissipation factor measurements on capacitive voltage transformers. Templates for Cables and Transmission Lines Line Impedance Using this template, you can measure the positive and zero-sequence impedance of three-phase overhead wires or underground cables. The k factors in different formats and k factors for the individual phases are calculated. Mutual Coupling Using this template, you can calculate the mutual coupling impedance as well as the mutual coupling factor for different relays from measurements on overhead lines.

Line Impedance 16.7 Hz Templates for 16.7 Hz systems, both dual and single-phase, are available for railway applications. Coupling into Signal Cables This template supports coupling measurements of overhead wires or underground cables to signal cables. Lightning Arrestor This template is available for both the power factor and dissipation factor measurements on surge arrestors. Reactor This template is available for both the power factor and dissipation factor measurements on reactor coils.

OMICRON 2010

Page 22 of 24

Templates for Rotating Machines Generator Testing This template is available for both the power factor and dissipation factor measurements of largescale generators with the CPC 100, CP TD1 and one or several CP CR500 resonance reactors. Templates for Grounding Systems Ground Impedance The ground resistance measurement template facilitates assessing the quality of grounding systems. It displays the results in relation to the distance from the grounding system graphically. If appropriate measuring points are selected, statements can also be made on the step voltage. Touch Voltage You can use this template for measurements with the CPC 100 alone. A wired connection from the location of the test back to the CPC 100 is needed. The touch voltage template can also be used for measuring the step voltage. The AN CP0502 Application Note explains the details of the measuring procedure. Step & Touch Voltage You can use this template for measurements with the CPC 100 together with the CP AL1 FFT voltmeter. No connection from the location of the test to the CPC 100 is needed. The AN CP0502 Application Note explains the details of the measuring procedure.

2.2.6

Tools The CPC 100 Start Page is directly linked to the OMICRON Tools.

CPC Editor It is used for offline test preparation, for example, setup of single test cards and/or entire tests with all of their test-specific settings on a PC, independent from the availability of a CPC 100. CPC Editor is only available in the CPC 100 Advanced Toolset distribution. CPC Excel File Loader CPC 100 Excel File Loader allows loading XML files generated with the CPC 100 into Microsoft Excel templates for post-processing. OMICRON Device Browser OMICRON devices such as the CPC 100 and their file systems are accessible like any other directory through the Windows Explorer. It is an application embedded in the Windows operating system.

OMICRON 2010

Page 23 of 24

OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products provides users with the highest level of confidence in the condition assessment of primary and secondary equipment on their systems. Services offered in the area of consulting, commissioning, testing, diagnosis, and training make the product range complete. Customers in more than 130 countries rely on the company's ability to supply leading edge technology of excellent quality. Broad application knowledge and extraordinary customer support provided by offices in North America, Europe, South and East Asia, and the Middle East, together with a worldwide network of distributors and representatives, make the company a market leader in its sector.

Americas OMICRON electronics Corp. USA 12 Greenway Plaza, Suite 1510 Houston, TX 77046, USA Phone: +1 713 830-4660 +1 800-OMICRON Fax: +1 713 830-4661 info@omicronusa.com

Asia-Pacific OMICRON electronics Asia Limited Suite 2006, 20/F, Tower 2 The Gateway, Harbour City Kowloon, Hong Kong S.A.R. Phone: +852 2634 0377 Fax: +852 2634 0390 info@asia.omicron.at

Europe, Middle East, Africa OMICRON electronics GmbH Oberes Ried 1 6833 Klaus, Austria Phone: +43 5523 507-0 Fax: +43 5523 507-999 info@omicron.at