Sei sulla pagina 1di 30

FACILITIES ALARM MONITORING SYSTEM, FMS

RECTIFIER ALARM MONITORING SYSTEM

DISTRIBUTION FRAME, DF

DXU MODULE

RBS 2202 CABINET


GENSET ALARM MONITORING SYSTEM

NOTE:
~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8001 Uen)

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

1 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL BTS - CHANGEOUT SITES (VISMIN) BTS SITE 16 External Alarms

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

DESIGNATION Illegal Entry ACU Alarm High Temp. Alarm Water Alarm Fire Alarm AC Mains Failure Battery Low Rectifier Failure Rectifier MCB Alarm Rectifier High Temp. LVDS Alarm Obstruction Light Failure Battery Charger Fail Day/Bulk Tank Fuel Low Load on Genset
Generator Alarm System Rectifier Cabinet Cabin Alarm System

ID NO. 0 1 2 3 4 5 6 7 8 9 A B C D E F

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking/Closing Breaking Breaking Breaking Breaking

SEVERIT Y LEVEL 1 1 1 1 1 2 1 1 1 1 1 2 1 1 2 2

Genset Fault

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

2 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL BTS - NEW SITES (VISMIN) BTS SITE 16 External Alarms

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

DESIGNATION
Cabin Alarm System

ID NO. 0 1 2 3 4 5 6 7 8 9
Generator Alarm System

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking/Closing Breaking Breaking Breaking Breaking Breaking

SEVERITY LEVEL 1 1 1 1 1 1 1 2 2 2 1 1 2 2 2

Illegal Entry ACU Alarm High Temp. Alarm Water Alarm Fire Alarm Rectifier A1 Alarm Rectifier A2 Alarm Rectifier O1 Alarm AC Mains Failure Obstruction Light Failure Genset Fault Battery Charger Fail Day Tank Fuel Low Bulk Tank Fuel Low Load on Genset SPARE

Rectifier Cabinet

A B C D E F

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

FACILITIES ALARM MONITORING SYSTEM, FMS

RECTIFIER ALARM MONITORING SYSTEM

SUB DISTRIBUTION FRAME, SDF

ALARM BOARD

NERA SDH CABINET


GENSET ALARM MONITORING SYSTEM

NOTE:
~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8003 Uen)

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

3 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL REPEATER CHANGEOUT SITES (VISMIN) REPEATER SITE 16 External Alarm s (SDH TRANSMISSION ONLY)

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

DESIGNATION Illegal Entry ACU Alarm High Temp. Alarm Water Alarm Fire Alarm AC Mains Failure Battery Low Rectifier Failure Rectifier MCB Alarm Rectifier High Temp. LVDS Alarm Obstruction Light Failure Battery Charger Fail Day/Bulk Tank Fuel Low Load on Genset
Generator Alarm System Rectifier Cabinet Cabin Alarm System

ID NO. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking/Closing Breaking Breaking Breaking Breaking

SEVERITY LEVEL 1 1 1 1 1 2 1 1 1 1 1 2 1 1 2 2

Genset Fault

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

4 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL REPEATER NEW SITES (VISMIN) REPEATER SITE 16 External Alarms (SDH TRANSMISSION ONLY)

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16

DESIGNATION
Cabin Alarm System

ID NO. 01 02 03 04 05 06 07 08 09 10
Generator Alarm System

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking/Closing Breaking Breaking Breaking Breaking Breaking

SEVERITY LEVEL 1 1 1 1 1 1 1 2 2 2 1 1 2 2 2

Illegal Entry ACU Alarm High Temp. Alarm Water Alarm Fire Alarm Rectifier A1 Alarm Rectifier A2 Alarm Rectifier O1 Alarm AC Mains Failure Obstruction Light Failure Genset Fault Battery Charger Fail Day Tank Fuel Low Bulk Tank Fuel Low Load on Genset SPARE

Rectifier Cabinet

11 12 13 14 15 16

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Priority alarm indicates 1 Non-priority alarm indicates 2

FACILITIES ALARM MONITORING SYSTEM, FMS

SUB DISTRIBUTION FRAME, SDF

RECTIFIER ALARM MONITORING SYSTEM SAU EXPANSION 2 MODULE

USER I/O (D-SUB 25)

GENSET ALARM MONITORING SYSTEM TMR 9202 CABINET, AMM01

NOTE:
~ See Cable Distribution Diagram for Sub-Distribution Frame, (2/193 18 - IPA 8002 Uen) ~ See Pin Configuration Diagram for USER I/O External Connector, (4-114, EN/LZT 110 2014 R6D)

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

5 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL REPEATER CHANGEOUT SITES (VISMIN) REPEATER SITE 12 External Alarms (PDH TRANSMISSION ONLY)

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12

DESIGNATION
Cabin Alarm System

USER I/O 1 2 3 4 5 6 7 8 9 10 11 12

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking

SEVERITY LEVEL 1 1 1 2 2 1 1 1 1 1 1 2

Illegal Entry Water Alarms High Temp./Fire Alarms AC Mains Failure Obstruction Light Failure Battery Low Rectifier Failure Rectifier MCB Alarm Rectifier High Temp. Genset Fault Battery Charge Fail Load on Genset

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Critical Alarm requires immediate action/response, whatever the time of day or night. Major Alarm requires immediate action/response, if it occurs during working-hours, otherwise as soon as
the working-hours commence. Minor Alarm requires non-immediate action/response that could be attended within the day. Warning Alarm is an observation alarm that indicates a temporary state of operation and does not normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.

Generator Alarm System

Rectifier Cabinet

EXTERNAL ALARM ALLOCATION REQUIREMENTS SPEC.


Prepared (also subject responsible if other) No.

6 (6)

OC/ENP/SO/D/S Alec Atienza


Approved Checked

DIG01.0004.045.149
Date Rev

Uen
Reference

OC/ENP/SO/D/SC Khairy Hassan

4/18/2005

PROJECT:DMPI Ph 4A BASE TRANSCEIVER STATION (GSM1800, RBS2206, TMR9202) SITE EQUIPMENT TYPE : : ALL REPEATER NEW SITES (VISMIN) REPEATER SITE 12 External Alarms (PDH TRANSMISSION ONLY)

ALARM NO. 01 02 03 04 05 06 07 08 09 10 11 12

DESIGNATION Illegal Entry Water Alarms High Temp./Fire Alarms Obstruction Light Failure Rectifier A2 Alarm Rectifier O1 Alarm AC Mains Failure Genset Fault Battery Charge Fail Day/Bulk Tank Fuel Low Load on Genset
Rectifier Cabinet

USER I/O
Cabin Alarm System

TYPE Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking Breaking

SEVERITY LEVEL 1 1 1 2 1 1 2 2 1 1 2 2

1 2 3 4 5 6 7 8 9 10 11 12

Rectifier A1 Alarm

Type Indicates the condition for the contact of the each individual alarm. Normally Closed (N.C.) Contacts indicates - Breaking Normally Open (N.O.) Contacts indicates - Closing Severity Level Indicates the severity of the alarm. Critical Alarm requires immediate action/response, whatever the time of day or night. Major Alarm requires immediate action/response, if it occurs during working-hours, otherwise as soon as
the working-hours commence. Minor Alarm requires non-immediate action/response that could be attended within the day. Warning Alarm is an observation alarm that indicates a temporary state of operation and does not normally require any action. However, if the alarm persists more than 20 hours, it must be investigated.

Generator Alarm System

MAINTENANCE INSTRUCTIONS

POWER SUPPLY SYSTEM ACTURA FLEX 48300 WITH SUPERVISION UNIT BMP 903 042/1 OR /2 Actions in case of alarm

EEmerson Energy Systems AB - All Rights Reserved -Interleaf-

1541-BMP 903 042/x Uen Rev A 2003-05-23

1(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

The contents of this document are subject to revision without notice due to continued progress in methodology, design, and manufacturing.

N.B.
Before starting any kind of work involving the power supply system, the safety document RULES 1550-1004 Uen must be read.

ACTURA is a registered trademark of Emerson Energy Systems AB

Emerson Energy Systems AB SE141 82 Stockholm Sweden

Tel: +46 8 721 60 00


1541-BMP 903 042/x Uen Rev A 2003-05-23

Fax:+ 46 8 721 71 77

www.emersonenergy.com

2(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

Contents
Item
1
1.1

Heading
General
Authorization

Page
5
5

2 3
3.1

Alarm Categories Procedure in Case of Alarm


Exchanging Units or Parts

6 6
6

4
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 4.18 4.19 4.20 4.21 4.22 4.23 4.24 4.25 4.26

Actions in Case of Alarm in the System 7


No. 1 No. 2 No. 5 No. 10 No. 11 No. 12 No. 21 No. 22 No. 23 No. 31 No. 32 No. 33 No. 34 No. 41 No. 42 No. 43 No. 51 No. 52 No. 53 No. 54 No. 55 No. 56 No. 58 No. 62 No. 63 No. 64 7 7 7 7 7 7 8 8 8 8 8 9 9 9 10 10 10 11 11 11 11 11 11 12 12 12
1541-Bmp 903 042/x Uen Rev A 2003-05-23

3(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x


4.27 4.28 4.29 4.30 4.31 4.32 4.33 4.34 4.35 4.36 4.37 4.38 4.39 4.40 4.41 4.42 4.43 4.44 No. 65 No. 66 No. 67 No. 68 No. 69 No. 72 No. 73 No. 74 No. 75 No. 76 No. 82 No. 83 No. 84 No. 105 No. 152 No. 153 No. 161 No. 162 12 13 13 13 13 13 14 14 14 14 14 14 14 15 15 15 15 15

1541-BMP 903 042/x Uen Rev A 2003-05-23

4(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

General
These instructions concern actions to be taken in case of alarm, and preventive maintenance of power supply system ACTURA Flex 48300, using supervision unit BMP 903 042/1 or BMP 903 042/2. Adequate knowledge of the power supply system is required. Refer to the system description and installation instructions for the system. N.B. These maintenance instructions, document SAFETY RULES 1550-1004 and local safety rules shall be followed when doing maintenance work in the power supply equipment. Measures that require work inside the cabinets or intervention in a unit shall always be carried out by adequately trained personnel with adequate knowled ge of the power supply system. When in doubt about an action or how to carry it out, always call for adequately trained personnel.

1.1
1.1.1

Authorization
Adequately Trained User
A user who has received adequate training for the power supply system in question is authorized to take responsibility for the equipment and to perform tests, fault tracing and exchange of units.

1.1.2

Other Users
Users with basic training for the power supply system in question are authorized to handle the equipment during normal operation only, and to take those actions in case of alarm which are included in these instructions and which do not involve work inside the cabinets.

1541-Bmp 903 042/x Uen Rev A 2003-05-23

5(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

Alarm Categories
The different alarm categories used in the power supply system are A1, A2, O1 and None. An alarm of category A1 requires immediate action, whatever the time of day or night. An alarm of category A2 requires immediate action if it occurs during workinghours, otherwise as soon as the workinghours commence. An alarm of category O1 is an observation alarm that indicates a temporary state of operation and does not normally require any action. However, if the alarm persists for more than 20 hours, it must be investigated. If an alarm has category None it means that the alarm is deactivated and will not be shown in the display of the PCU or in the Active Alarm" page of the web interface. At delivery, each alarm belongs to one of the alarm categories above. We normally recommend the factory setting to be retained, but if required, each alarm can be ranged under any alarm category except alarm No. 10 (always O1).

Procedure in Case of Alarm


These instructions follow the alarm numbers and not the alarm names. The alarm names may differ depending on the language used in the system. The alarm numbers are always the same. Enter in the log book of the power supply system all observations made at the mo ment of failure, such as date, time, system voltage and rectifier load. Enter also what alarm(s) are shown and any external disturbance such as thunderstorm or mains failure. Trace activated alarms by means of the alarm survey of the respective unit and the item which describes what actions to take on the respective alarm.

3.1

Exchanging Units or Parts


See document INSTALLATION INSTRUCTIONS for the power system regarding how to exchange units or parts.

1541-BMP 903 042/x Uen Rev A 2003-05-23

6(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4
4.1

Actions in Case of Alarm in the System


No. 1
The PCU has lost contact with all units because of a failure in the CAN communica tion. Check that the communication contact is properly installed on the PCU and that the communication cable is not damaged. If this is ok, exchang the PCU.

4.2

No. 2
The alarm is not used in this system.

4.3

No. 5
The PCU has lost communication with a certain unit. Check that the unit is properly installed, that the communication contact is properly connected to the unit and that the communication cable is not damaged. If all this is ok, exchange the unit.

4.4

No. 10
This alarm indicates that the alarms from the PCU are disabled.

4.5

No. 11
All rectifiers are reporting input failure at the same time, because of mains failure.

4.6

No. 12
One rectifier is reporting input failure. Check the feeding voltage for the rectifier.

1541-Bmp 903 042/x Uen Rev A 2003-05-23

7(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.7

No. 21
Indicates that the ambient temperature is too high. S S Check the sensor for the ambient temperature. Check the temperature. If it is too high, try to eliminate the reason for it.

4.8

No. 22
Indicates that the ambient temperature is too low. S S Check the sensor for the ambient temperature. Check the temperature. If it is too low, try to eliminate the reason for it.

4.9

No. 23
This alarm indicates that the temperature sensor for the ambient temperature has a fault. S S Check the sensor connection to the PCU. Exchange the temperature sensor.

4.10 No. 31
The measured temperature has risen above the preset high battery temperature level. S Check the battery temperature. If it is too high, try to eliminate the reason for it.

4.11 No. 32
Indicates that the battery temperature is too high. S S Check the battery temperature sensor. Check the temperature. If it is too high, try to eliminate the reason for it.

1541-BMP 903 042/x Uen Rev A 2003-05-23

8(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.12 No. 33
Indicates that the battery temperature is too low. S S Check the battery temperature sensor. Check the temperature. If it is too low, try to eliminate the reason for it.

4.13 No. 34
This alarm indicates that the battery temperature sensor has a fault. S S S Check the sensor connection to the PCU. Check that the sensor is properly installed on the battery. Exchange the temperature sensor.

4.14 No. 41
The alarm indicates that one or more of the rectifiers has supplied more output volta ge than what has been set on the PCU. This alarm is generated if the system volta ge exceeds a/the preset level. S Check the set battery voltage and the overvoltage; if the limits are incorrect, find out why they have changed and correct them.

1541-Bmp 903 042/x Uen Rev A 2003-05-23

9(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.15 No. 42
Shows that the distribution voltage has dropped below the preset alarm level, usually initiated because of mains failure. If the undervoltage is caused by a mains failure, check with the exchange manager whether some load could be switched off in order to prolong the operating time of the plant. If there is no mains failure, the reason for the low voltage is that the load is supplied entirely or to a large extent by the batteries because of rectifier failure or too high system load related to the rectifier capacity. If the undervoltage is caused by a rectifier failure, find out what rectifier alarms are active and follow the instructions concerning them. If all the rectifiers are in operation and take full load, the undervoltage may be due to recharge of the batteries after a mains failure or the rectifier capacity being too small. If the batteries are being recharged, the alarm will cease by itself when the battery voltage has increased over the undervoltage limit. Compare the distribution current with the rectifier current by using the following for mula: (number of rectifiers x 1500)/Usyst > 0.8 x (IB + IL) The distribution current must not exceed 80 % of the total rectifier current at floating voltage. If the distribution current is higher than the rectifier capacity, some load must be dis connected in order to secure the operation of the plant. Add more rectifiers so that they cover the need for the distribution current plus at least one redundant rectifier.

4.16 No. 43
See instructions for alarm No. 42, item 4.15.

4.17 No. 51
Indicates an internal rectifier defect. S Change the faulty rectifier.

1541-BMP 903 042/x Uen Rev A 2003-05-23

10(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.18 No. 52
A failure reported from two or more rectifiers. See item 4.17.

4.19 No. 53
The system load is higher than the rectifier capacity. One or more of the rectifiers may be out of order. Exchange the rectifiers. If the rectifiers are working, the problem is that the system load is higher than the rectifier capacity. Reduce the system load to ensure proper function of the system, or install more rectifiers.

4.20 No. 54
Indicates that the rectifier's internal temperature is too high and therefore the rectifier is reducing its output current in order to reduce the temperature. S Make sure that there is nothing obstructing the inflow of cooling air through the rectifier front. S Make sure that there is nothing obstructing the outflow of heated air through the cabinet. Change the faulty rectifier.

4.21 No. 55
Indicates that the feeding voltage to the rectifier is out of range.

4.22 No. 56
Indicates that a rectifier has a faulty fan that needs to be changed.

4.23 No. 58
Indicates an internal rectifier defect. S Change the faulty rectifier.

1541-Bmp 903 042/x Uen Rev A 2003-05-23

11(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.24 No. 62
The contactor for the normal load is open because the battery voltage is too low. If the rectifiers are working, the problem may be that the system load is higher than the rectifier capacity, causing the batteries to discharge. If the rectifiers are working and the system load is lower than the rectifier capacity, check the measuring cables to the contactor. They may be broken or have come loose. If the rectifiers are not working (e.g. mains failure), the batteries will be disconnected at a preset level, in order to protect the batteries from overdischarging.

4.25 No. 63
The contactor for the prioritized load is open because the battery voltage is too low. If the rectifiers are working, the problem may be that the system load is higher than the rectifier capacity, causing the batteries to discharge. If the rectifiers are working and the system load is lower than the rectifier capacity, check the measuring cables to the contactor. They may be broken or have come loose. If the rectifiers are not working (e.g. mains failure), the batteries will be disconnected at a preset level, in order to protect the batteries from overdischarging.

4.26 No. 64
This alarm indicates that the contactor for the normal load is not working. S S Check that the connections to the contactor are correct. Exchange the distribution unit with the contactor.

4.27 No. 65
This alarm indicates that the contactor for the prioritized load is not working. S S Check that the connections to the contactor are correct. Exchange the distribution unit with the contactor.

1541-BMP 903 042/x Uen Rev A 2003-05-23

12(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.28 No. 66
Indicates that one or more battery fuses/circuit breakers have blown/tripped or been removed. If a battery fuse/circuit breaker has been removed/tripped manually, check with the person that removed/tripped it before reinserting/resetting it. Ensure that there is no fault before doing that. The battery fuse shall be reinserted by adequately trained personnel. If the battery fuse/circuit breaker is blown/tripped, the reason for the failure probably is overload or short circuit. Find out and eliminate the reason for the blown/tripped fuse/circuit breaker before swapping/resetting it. The battery fuses shall be changed by adequately trained personnel.

4.29 No. 67
This alarm indicates that the PCU has an internal fault and needs to be exchanged.

4.30 No. 68
This alarm indicates that the PCU has an internal fault and needs to be exchanged.

4.31 No. 69
Indicates that the LCU is not configured to slave mode when a system with a PCU is interconnected with a system with an LCU. Configure the LCU to slave mode and press the reconfigure button on the PCU.

4.32 No. 72
This alarm indicates that battery end voltage is reached before end of test time dur ing a battery test. S S S Check the float charging level. Check that the load is lower than or equal to the capacity of the rectifiers. Check the battery according to the recommendations of the supplier.

1541-Bmp 903 042/x Uen Rev A 2003-05-23

13(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.33 No. 73
The PCU did not manage to start a battery test. The reason is that the battery discharge current did not exceed 3 A after one minute. S S S Check the current load. Check that the battery is connected. Check the battery according to the recommendations of the supplier.

4.34 No. 74
The battery test function has been activated (manually).

4.35 No. 75
The battery test function has been activated (cyclically).

4.36 No. 76
The battery test function has been activated (automatically) because of a mains fai lure.

4.37 No. 82
The boost charging function has been activated (manually).

4.38 No. 83
The boost charging function has been activated (cyclically).

4.39 No. 84
The boost charging function has been activated (automatically), for example after a mains failure.

1541-BMP 903 042/x Uen Rev A 2003-05-23

14(15)

MAINTENANCE INSTRUCTIONS - BMP 903 042/x

4.40 No. 105


In some system configurations (made in factory), one of the digital inputs, when acti vated will activate this alarm.

4.41 No. 152


Indicates that one or more distribution circuitbreakers for the normal load have trip ped. The reason for the tripping is probably overload of the circuit breaker, unless a short circuit has occurred. S Find out and eliminate the reason for the tripped circuit breaker before resetting it.

4.42 No. 153


Indicates that one or more distribution circuitbreakers for the prioritized load have tripped. The reason for the tripping is probably overload of the circuit breaker, unless a short circuit has occurred. S Find out and eliminate the reason for the tripped circuit breaker before resetting it.

4.43 No. 161


This alarm indicates that the battery current limitation is active.

4.44 No. 162


Indicates that the battery is being charged and that the current exceeds the set bat tery current limit. The system will automatically lower the system voltage to decrease the charging below the current limit.
1

1541-Bmp 903 042/x Uen Rev A 2003-05-23

15(15)

Potrebbero piacerti anche