Sei sulla pagina 1di 7

21, rue d'Artois, F-75008 Paris http://www.cigre.

org

B2-202

Session 2004
CIGR

THE INFLUENCE OF CONDUCTOR SAG ON SPATIAL DISTRIBUTION OF TRANSMISSION LINE MAGNETIC FIELD

M. P. ARABANI *
Moshanir, Power Engineering Consultants, Tehran, Iran

B. PORKAR
Sharif University of Technology, Tehran, Iran

S. PORKAR
Amir Kabir University of Technology, Tehran, Iran

KEYWORDS
Magnetic fields - transmission lines - sag conductor

1. INTRODUCTION
The calculation and measurement of fields generated by high voltage power transmission lines has been a major concern in the past years. Of the possible health implications and environmental impact caused by electric and magnetic fields of high voltage electric power lines, the most difficult issue to face will often be public perceptions of the possible health hazard, specifically an increased risk of contracting cancer, caused by the magnetic field of the power line [1-7]. Also utilities are challenged by the need to expand transmission system capacity to meet growing customer requirements. The acquisition of new transmission Right-of-Way (ROW) is very difficult, expensive and time consuming due to land use public concerns. Standardization of right-of-way distances for power lines sometimes include consideration of expected magnetic fields [8]. Other research has centered upon the design of power line proximity detectors, instrumentation and measurements equipment, and new line configuration. The ability to calculate magnetic fields levels that corrective with measurement data is important in all of this investigation [8]. Several publications have been made to calculate and measure the electric and magnetic fields created by power transmission lines. Most assume lines parallel to a flat ground, and the sag due to the line weight is neglected [9]. One publication [8] calculated the magnetic field of a catenary line in state of single phase. In this paper presented method in [8], was extended not only to 3-Phase transmission lines but also to those that have a change in direction.

1. CATENARY GEOMETRY
Figure 1 depicts the basic catenary geometry for a single-conductor line, where H is the maximum height on the extremes of the line where it is anchored, h is the minimum height at mid-span (hence the sag is S=H-h) and L is the span length between adjacent towers. * Email: mp.arabani@moshanir.com

A concise analytical method for calculation of magnetic field in the direct vicinity of power lines has been developed

and implemented for three-dimensional field modeling in [8]. In [8] the expression for the total field has been presented:

Figure 1: Basic catenary geometry

= 0 B 0 4

(J
M N L 2 i =1 k = N L 2

a x + J y a y + J z a z )dx

(1)

Where the parameter M represents the number of individual conductors on the support structures. Also the number of spans to the right and to left the generic one is represented by N in (1). And
z sinh (a x ) sinh (a x ) I i 0 i i 4 d i d i z 1 I 1 Jy = i 0 4 d i d i Jx =
cosh(ai x ) ( y0 ydi ) ai di ( x x + kL ) sin(a x ) 0 i di I i Jz = 4 cosh(ai x ) ( y0 2 ydi ) ai + d i ( x x0 + kL ) sin(ai x ) di
2 ( x x0 + kL )2 + z 0 + 2 2 d i = cosh(a x ) i y y di 0 ai
2 ( x x0 + kL )2 + z0 2 + 2 di = cosh(a x ) i ( y0 2 ydi ) ai

(2)

(3)

(4)

(5)
3

(6)

Also the complex depth of each element of image current can be found as given in [10,11]:

= 2 g e
g = 503

The parameter g in (7) is the skin depth of the earth represented by


g
f

(7)

Where g is the resistivity of earth and f is frequency of the source current.

3. EXAMPLES OF CALCULATIONS
A computer program is developed based on mentioned equations. In proof of the correctness of the developed computer program, example in [8] is solved again by the developed computer program. The distance L between the poles is 100m, the sag is 2m, and the height of suspension is 13m. A current of 100A is assumed to by flowing through the conductor. The effect of six neighboring spans (N=3) is taken into account. Figures 3, 4 and 5 present spatial distribution of mentioned power line magnetic field.

Figure 2: Field distribution on the ground level under the power line (H=13m, h=11m, Sag =2m)

Figure 3: Field distribution on the ground level under the power line (H=13m, h=9m, Sag = 4m)

These profiles are similar to the ones in [8]. From Figures 3 and 4, it is evident that with increasing sag conductor, magnetic field especially in mid-span will increase.

Figure 4: Distribution of magnetic field, below the catenary.

4. THE EFFECT OF NEIGHBORING SPANS


In this section, we evaluate the effect of neighboring spans on spatial distribution of mentioned power line magnetic field. The parameter N in (1) represents the number of spans to the right and the left from the generic one. One important question will be that how many is the parameter N? Figure 5 presents the difference of the mentioned power line magnetic field between two status, with considering N=2 and N=3 in other that profile 5 presents: (Magnetic field with N=3) - (magnetic field with N=2). From this plot, it is evident that:

Figure 5: the spatial distribution of the power line magnetic field difference with N=2 and N=3.

In mid-span, the spans of the right and the left from the generic one are far from points and their effects on spatial distribution in these points is negligible, but with approach the towers, the their influences will be considerable, and in these points the amount of the difference increased. Therefore, selection the parameter N depends on the amount of the difference in the location towers. Figure 6, 7 present the spatial distribution of the differences from (N=3&4, N=4,5). These plots illustrate that N=3 are the best options. Because with N=4, the most increasing of magnetic field will be smaller than 0.006 mG in location of towers. Also with selection N>3, the execution time of calculation will increase.

Figure 6: the spatial distribution of the power line magnetic field difference with N=3 and N=4.

Figure 6: the spatial distribution of the power line magnetic field difference with N=4 and N=5.

5. SPATIAL DISTRIBUTION OF 3-PHASE POWER LINES MAGNETIC FIELD THAT HAS A CHANGE IN DIRECTION
Figure 8 illustrates the spatial distribution on 3-phase power lines magnetic field that have a change in direction. The specifications of the 3-phase transmission lines are: Flat configuration, the phase distance is 20m, the distance L between the towers is 50m, the sag is 2m, the suspension is 10m, the change of direction is 10.8 deg., the resistivity of earth is 100 ohm.m, the frequency of the source current is 60Hz, the phase current is 100 A and N=3. Also the mentioned software was developed for calculation spatial distribution of the magnetic field of real transmission lines. In this status, the height of the conductors in the location of towers is different from a common surface. Figure 9 presents the mentioned status.

Figure 8: The spatial distribution of a 3-phase power lines magnetic field that has a change in direction.

Figure 9: The layout of a real transmission line.

6. CONCLUSIONS In this paper, calculation of magnetic fields in the direct vicinity of 3-Phase power lines that have a change in direction has been developed and implemented for three-dimensioned field modeling. The method takes into account the sag of the conductors of power lines. Also the effect neighboring spans on spatial distribution of power line magnetic field was evaluated and discussed.

7. REFERENCES
[1] M. Darveniza, D. Mackerras, Electric and Magnetic Field Effects From Power Lines: Review of Possible Health Effects, Lightning and Transient Protection PTY. LTD, 1 November 2002. [2] http://www.esaa.com.org.au [3] http://www.nrpb.org.uk [4] http://www.electricity.org.uk [5] http://www.iee.org.uk [6] http://www.enertech.net [7] http://www.niehs.nih.gov/emfrapid [8] A.V.Mamishev, R.D.Nevels, B.D.Russel, Effects of Conductor Sag on Spatial Distribution of Power Line Magnetic Field, IEEE Trans. On Power Delivery, Vol 11, No. 3, July 1996, pp. 1571-1576. [9] Transmission Line Reference Book, 345 kV and Above, Second Edition, EPRI Report EL-2500, EPRI, Palo Alto, CA, 1982. [10] J.R.Wait, K.P.Spies, On the Image Representation of the Quasi-Static Fields of a Line Current Source Above the Ground, Canadian Journal of Physics, Vol.47, 1969, pp.2731-2733. [11] R.G.Olsen, T.A.Pankaskie, On the Exact, Carson and Image Theories for Wires at or Above the Earths Interface, IEEE Trans. on Power Apparatus and System, Vol.102, No.3, March 1983, pp.769774.