Leading the Future in Refrigeration Technology

EMERSON
ZB Scroll Compressor

Product Manual

ZB Series
Index

General Information

Description of Features

Nomenclature & BOM

Application Envelope

4-5

R22

R404A/R507 & R134a

Application Guide
1. Scroll Compression process

6-6

2. Compressor Internal Protections

7-8

3. Compressor Information

8-10

Dimensions

46-65

Brazing Connection

46-49

ZB15~ZB29
ZB38~ZB48

(BOM 524)

46

(BOM 524)

47

ZB58

(BOM 524)

48

ZB66~ZB88
Rotalock Connection

(BOM 524)

49

ZB15~ZB29
ZB38~ZB48

(BOM 523)

50

(BOM 523)

51

ZB58

(BOM 523)

52

ZB66~ZB88
Brazing & Sight Glass

(BOM 523)

ZB15~ZB29
ZB38~ZB48

(BOM 558)

54

(BOM 558)

55
56-59

50-53

53
54-55

4. System Protection Guidelines

10-11

Brazing, Sight Glass & Oil Schrader Valve

5. Testing Guidelines

11-13

ZB58

(BOM 550)

6. Field & Installation Guidelines

13-14

ZB66~ZB88
ZB95~ZB114 TFD

(BOM 550)

57

(BOM 550)

58

ZB95~ZB114 TW7/TW5 (BOM 550)


Rotalock & Sight Glass

60-61

Performance Data
R22

15-43
50Hz

1-Phase

15-16

56

59

R22

50Hz

3-Phase

17-21

R404A/R507

50Hz

1-Phase

22

R404A/R507

50Hz

3-Phase

23-25

Rotalock, Sight Glass & Oil Schrader Valve

R134a

50Hz

1 & 3-Phase

26-28

ZB58

(BOM 551)

R22

60Hz

1-Phase

29-30

63

60Hz

3-Phase

31-35

ZB66~ZB88
ZB95~ZB114 TFD

(BOM 551)

R22

(BOM 551)

64

R404A/R507

60Hz

1-Phase

36-37

ZB95~ZB114 TW7/TW5 (BOM 551)

65

R404A/R507

60Hz

3-Phase

38-40

R134a

60Hz

1 & 3-Phase

41-43

Technical Data

44-45

ZB15~ZB29
ZB38~ZB48

(BOM 559)

60

(BOM 559)

61

Electrical Wiring Diagram

62-65
62

66-67

ZB15-ZB114

66

ZB15-ZB114 Control Circuit

67

ZB Series
General Information

ZB Scroll Compressors For Refrigeration And Process Cooling:


In the years since Emerson Climate Technologies Introduced ZB scroll compressors for medium-high temperature refrigeration and process cooling
applications, it has been well received by our customers. ZB scroll compressors are revolutionizing this segment of the industry by the providing
following benefits to our customers.

* Complete range between 2-15 HP


* Proven reliability
* Superior efficiency
* Low sound levels
* Availability for HFC and HCFC refrigerants
* All voltage offering
* Oil sight glass & Rotalock features
Customers can be confident that ZB scroll compressors are coming from Emerson Climate Technologies experience of over 80 million scroll
compressors. ZB scroll compressors are manufactured in our scroll factories in Suzhou, China and Rayong, Thailand. To our customers, this gives
additional value by lower inventory and reduced shipping cost.

ZB Model Line Up

16

14

12

Nominal HP

10

ZB15

ZB19

ZB21

ZB26

ZB29

ZB38

ZB45

ZB48
ZB58
ZB Models

ZB66

ZB76

ZB88

ZB95

ZB114

ZB Series
Description of Features

Dual Compliance

Unloaded Start

Compliance means sealing between the orbiting and fixed scroll

The scroll sets separate at the instant of compressor shutdown. This

involutes. Dual compliance means the sealing is on both the axial and

allows the scroll set internal pressures to equalize on compressor

radial directions. This prevents refrigerant leak back across successive

stops. In addition to this, the scroll sets are not engaged at the instant

scroll pressure pockets. Compliance design also allows the scroll

of starting. Scroll sets engage only after few milliseconds of startup.

involutes to separate in both the radial and axial directions. This allows

This allows easier startup of ZB scroll compressors. Due to this design

debris or liquid refrigerant to pass through the scroll involutes without

feature, typically a start assist kit is not required even on single phase

damaging the compressor. Benefits of Dual Compliance are:

compressors.

* Increased efficiency
* Better liquid handling capability

DU bearings

* Better handling of debris

A space age bearing material comprising of porous bronze with


PTFE-lead overlay. These bearings are used in ZB scroll compressors in
the scroll drive and main bearings. DU bearings work with exceptionally

Discharge
Fixed scroll
Suction

Orbiting
scroll

Axial compliance

low friction between the load bearing surfaces. In addition, DU bearings


can operate safely for a short time with loss of lubrication. This situations
could happen on compressor applications due to oil pump out during a
flooded start or heavy oil dilution after a defrost cycle.

Radial compliance

Figure 1
Crankshaft
Scroll Wear In
The scroll involutes of Copeland scroll compressor wear in, rather than
wear out. So unlike in other compressor technologies among similar
categories, there is no constant degradation of performance with
Figure 2

time due to wear out.

Lower sound, vibration and pulsation

All specifications in this catalogue are subject to change without

The compression process in a scroll set is symmetrical and continuous.

notice.

This inherently reduces the sound, vibration and pulsation. This


eliminates the need for use of vibration absorbers and suction or
discharge mufflers in most of the applications. In further, ZB scroll
compressors are engineered to produce smooth sound spectrum
which improves the quality of sound.

ZB Series
Nomenclature & BOM

Lubricant
Blank: Mineral Oil
E: Ester Oil

Compressor
Family

Compressor Motor Protection


Description
Inherent internal line break motor
protector
W:
Electronic motor protection with
themistors and control module in
the terminal box

Code
F:

Generation

Bill of Material

ZB 76 K Q E - T F D - XXX
High/Medium Temp
Refrigeration

Compressor Motor
Code
Description
P:
Single-phase
T:
Three-phase

Capacity @ 60Hz
(Medium Temperature
Condition: Btu/h)

J
V
D

Base Capacity
K x 1000
M x 10000

5
7

Motor voltages
V
Ph
220-240
1
265
1
200
1
208-230
1
380-420
3
460
3
200-220
3
200-230
3
380
3

Bill of Material (BOM)


Compressor
Model

BOM
Number

Suction & Discharge


Brazing Connection

Suction & Discharge


Rotalock Connection

523
ZB15-ZB48

ZB58-ZB114

Oil Sight
Glass

Schrader
Valve

524

558

559

523*

524*

550

551

*Not applicable for ZB95/114 models.

Hz
50
60
50
60
50
60
50
60
60

ZB Series
Application Envelope
R22

ZB95/ZB114 (TFD Motor Only)

70

70

60

60

Condensing Temp.oC

Condensing Temp.oC

ZB15~ZB88

50

40

30

40

30

20

20

10

10
-15

-10

-5

10

15

-15

Evaporating Temp. oC

60

50

40

30

20

10
-15

-10

-5

-5

10

15

Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only

ZB95/ZB114 (TW7, TW5 Motors)

70

-10

Evaporating Temp. oC

Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only

Condensing Temp.oC

50

10

15

Evaporating Temp. oC
Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only
3. TW5-R22 approved only at 60Hz.

ZB Series
Application Envelope
R404A/R507 & R134a

ZB95/ZB114
R404A/R507

ZB15~ZB88
R404A/R507
70

Condensing Temp.oC

Condensing Temp.oC

70
60
50
40
30

50
40
30

20

20

10

10
-20

-15

-10

-5

10

15

-20

Evaporating Temp. oC

80
70
60
50
40
30
20
10
-15

-10

-5

-10

-5

10

15

Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only

ZB15~ZB76
R134a

-20

-15

Evaporating Temp. oC

Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only

Condensing Temp.oC

60

10

15

Evaporating Temp. oC
Note:
1. Envelope In Non Shaded Region, max return gas temperature of 18.3C
2. Envelope In Shaded Region, Max superheat of 11K only

ZB Series
Application Guide

1. Scroll Compression process

Compression in the scroll is created by


the interaction of an orbiting spiral and
a stationary spiral. Gas enters the outer
openings as one of the spirals orbits.

The open passages are sealed off


as gas is drawn into the spiral.

By the time the gas arrives at the


center port, discharge pressure has
been reached.

As the spiral continues to orbit,


the gas is compressed into two
increasingly smaller pockets.

Actually, during operation, all six


gas passages are in various stages
of compression at all times,
resulting in nearly continuous
suction and discharge.

The scroll is a simple compression concept first patented in 1905. A scroll is an involute spiral which, when matched with a mating scroll form as shown
above, generates a series of crescent-shaped gas pockets between the two members. During compression, one scroll remains stationary (fixed scroll)
while the other form (orbiting scroll) is allowed to orbit (but not rotate) around the first form. As this motion occurs, the pockets between the two
forms are slowly pushed to the center of the two scrolls while simultaneously being reduced in volume. When the pocket reaches the center of the
scroll form, the gas, which is now at a hige pressure, is discharged out of a port located at the center. During compression, several pockets are being
compressed simultaneouly, resulting in a very smooth process. Both the suction process (outer portion of the scroll members) and the discharge
process (inner portion) are continuous.

ZB Series
Application Guide

2. Compressor Internal Protections

2.2 Internal Scroll Temperature Protection

2.1 Internal Pressure Relief Valve:

Events such as loss of charge, condenser fan failure, or low side charging

Models ZB15- ZB48 has internal pressure relief valve, which open at a

with inadequate pressure will cause the discharge gas to quickly rise.

discharge to suction differential pressure of 375 to 450 psi. This action

Excessively high discharge gas temperatures would affect the scroll

will trip the motor protector and remove the motor from the line.

compressor reliability. To prevent damage to scroll compressors ZBKQ/E


scroll compressors are built- in with internal scroll temperature protection.

Models ZB58 - ZB114 do not have internal pressure relief valves. To ensure
Compressor models ZB15-ZB48 incorporate a thermo disc which is a

safe operation, a high pressure control must be used in all applications.

temperature-sensitive snap disc device located at the scroll discharge


The high pressure control should have a manual reset feature for the

port. It is designed to open and route hot discharge gas back to the motor

highest level of system protection. Maximum cut out settings are listed

protector thus removing the compressor from the line.

in Table 1 If the compressor is fitted with a Rotalock valve the high


Compressor models ZB58-ZB114 models incorporate ASTP feature

pressure switch MUST be connected on the compressor side of the valve.

(Advanced Scroll Temperature Protection). ASTP feature will cause the


Compressors require a low pressure control for loss of charge protection.

scrolls to separate and stop pumping but allow the motor to continue to

If allowed to go undetected, loss of system charge will result in

run. After the compressor runs for some time without pumping gas, the

overheating and damage to the scrolls and floating seal. Prolonged

motor protector will open.

operation with low charge will result in decomposition of the oil that
might require complete system replacement. Minimum cut out settings

Depending on the heat build up in the compressor, it may take up to two

are listed in Table 1. The low pressure cut-out, if installed in the suction

hours for the motor protector to reset.

line to the compressor, can provide additional protection against a TXV


failed in the closed position, a closed liquid line service valve, or a blocked

2.3 Motor Protection

liquid line screen, filter, orifice, or TXV. All of these can starve the

For the models with a motor protection code F, an internal line break

compressor for refrigerant and result in compressor failure. The low

motor protector is located in the center of the Y of the motor windings.

pressure cut-out should have a manual reset feature for the highest level

This protector disconnects all three phases in case of an overload or

of system protection. If a compressor is allowed to cycle after a fault is

over-temperature condition. The protector reacts to a combination of

detected, there is a high probability that the compressor will be damaged

motor current and motor winding temperature. The internal protector

and the system contaminated with debris from the failed compressor and

protects against single phasing. Time must be allowed for the motor to

decomposed oil. If the compressor is fitted with a Rotalock valve the low

cool down before the protector will reset. If current monitoring to the

pressure switch MUST be connected on the compressor side of the valve.

compressor is available, the system controller can take advantage of the


compressor internal protector operation. The controller can lock out the
compressor if current draw is not coincident with contactor energizing,

Table 1
Pressure Setting Recommendations
Model

Control Type

implying that the compressor has shut off on its internal protector. This
R404A/R507

R22
2

1.2Kg/cm

R134a
0.3Kg/cm

will prevent unnecessary compressor cycling on a fault condition until


2

ZB15-ZB48

Low

1.3Kg/cm

ZB58-ZB114

High

28.7Kg/cm2

31.88Kg/cm2

23.9Kg/cm2

Low

1.3Kg/cm2

1.2Kg/cm2

0.3Kg/cm2

corrective action can be taken.

ZB Series
Application Guide

Models ZB95KQ/E and ZB114KQ/E with motor protection code W use

3.2 Rotation Direction of Three Phase Scroll Compressors

a combination of sensors and an electronic module (INT69SU) for motor

Scroll compressors will only compress in one rotational direction.

protection. For the INT69SU, there are four PTC (positive temperature

Direction of rotation is not an issue with single phase compressors since

coefficient) internal thermisters connected in series that react with

they will always start and run in the proper direction. Three phase

avalanche resistance in the event of high temperatures. All four are used

compressors will rotate in either direction depending upon phasing of

to sense motor temperature. The thermister circuit is connected to the

the power. Since there is a 50-50 chance of connecting power in such a

protector module terminals S1 and S2. When any thermister reaches a

way as to cause rotation in the reverse direction, it is important to include

limiting value, the module interrupts the control circuit and shuts off the

notices and instructions in appropriate locations on the equipment to

compressor. After the thermister has cooled sufficiently, the resistance

ensure proper rotation direction when the system is installed and

will decrease, thus allowing the module to reset. However, the module

operated. Verification of proper rotation direction is made by observing

has a 30-minute time delay before reset after a thermister trip. If the

that suction pressure drops and discharge pressure rises when the

INT69SU module is applied in conjunction with a Programmable Logic

compressor is energized. Reverse rotation of a scroll compressor also

Controller, it is important that a minimum load is carried through the

results in substantially reduced current draw compared to specification

M1-M2 control circuit contacts. The minimum required current through

sheet values. Suction temperature will be high, discharge temperature

the module relay contacts needs to be greater than 100 milliamps but

will be low and the compressor may be abnormally noisy There is no

not to exceed 5 amps. If this minimum current is not maintained, this has

negative impact on durability caused by operating three phase Copeland

a detrimental effect upon the long-term contact resistance of the relay

Scroll compressors in the reversed direction for a short period of time

and may result in false compressor trips. PLC operated control circuits may

(under one hour), In models ZB58 - ZB114 oil may be lost. This oil loss

not always provide this minimum current. In these cases modifications to

can be prevented during reverse rotation if the suction tubing is routed

the PLC control circuit are required. Consult your application engineering

at least six inches (15 cm) above the compressor. After several minutes of
operation in reverse, the compressor's motor protection system will trip the

department for details.

compressor off. If allowed to repeatedly restart and run in reverse without

3. Compressor Information

correcting the situation, the compressor will be permanently damaged.

3.1 Fusite (Terminal)


Fusite (Terminal) pin orientation for single-phase and three phase

All three phase scroll compressors are identically wired internally. As a

refrigeration scroll compressors are shown in Figure 1 and inside the

result, once the correct phasing is determined for a specific system or

terminal box.

installation, connecting properly phased power leads to the same


terminals will maintain proper rotation direction.
T1
T2
C
T3
S
R

Motor Terminal (Fusite) Connections for


Single Phase and Three Phase Scrolls
Figure 1

ZB Series
Application Guide

Brief Power Interruptions

The scroll compressor can be used to pump-down refrigerant in a unit

Brief power interruptions (less than second) may result in powered

as long as the pressures remain within the operating envelope. Low

reverse rotation of single-phase refrigeration scroll compressors.

suction pressures will result in overheating of the scrolls and permanent

High-pressure discharge gas expands backward through the scrolls at

damage to the compressor drive bearing or cause the scroll temperature

power interruption causing the scroll to orbit in the reverse direction. If

protection to activate.

power is reapplied while this reversal is occurring, the compressor may


continue to run noisily in the reverse direction for several minutes until

3.5 Shell Temperature

the compressor internal protector trips. This has no negative effect on

Certain types of system failures, such as condenser or evaporator fan

durability. When the protector resets, the compressor will start and

blockage or loss of charge, may cause the top shell and discharge line to

run normally.

briefly but repeatedly reach temperatures above 350F (177C) as the


compressor cycles on its internal protection devices. Care must be taken

No time delay is required on three phase models to prevent reverse

to ensure that wiring or other materials, which could be damaged by these

rotation due to power interruptions.

temperatures, do not come in contact with these potentially hot areas.

3.3 Oil Types

3.6 Suction and Discharge Fittings

In HCFC R-22 applications, mineral oil is used in the compressor. Polyol

Scroll compressors are available with stub tube or Rotalock connections.

ester lubricants must be used with HFC refrigerants (R404A, R507 and

The stub tube version has copper plated steel suction and discharge

134a).Compressors using polyol ester oil are identified with an "E" in

fittings. These fittings are far more rugged than copper fittings used on

the model number. A separate form may be requested (Form 93-11)

other compressors. Due to the different thermal properties of steel

which lists Emerson approved lubricants that may be used to recharge

and copper, brazing procedures may have to be changed from those

these compressors or if the addition of oil is required. See compressor

commonly used. Assembly and brazing procedures are explained in

nameplate for original oil charge. A complete recharge should be four

the later part of application guide.

ounces (118 ml) less than the original oil charge. If the oil level is above
the sight glass, it may lead to oil circulation rates higher than 1.5% which

3.7 Starting Characteristics Of Single-Phase Compressors

may lead to decreased capacity as the oil coats the evaporator coils.

Single-phase scroll compressors are designed with PSC type motors and
therefore will start without the need of start assist devices in most

3.4 Deep Vacuum Operation

applications. However, if low voltage conditions exist at start up, protector

WARNING: DO NOT RUN A REFRIGERATION SCROLL COMPRESSOR IN A

trips can result. Therefore, start assist devices (start capacitors and relays)

VACUUM. FAILURE TO HEED THIS ADVICE CAN RESULT IN PERMANENT

are available to maximize starting characteristics under abnormal

DAMAGE TO THE COMPRESSOR.

conditions.

A low-pressure control is required for protection against vacuum


operation. See the section on pressure controls for the proper set
points. (See Table 1)

Scrolls compressors (as with any refrigeration compressor) should never


be used to evacuate refrigeration or air conditioning systems.

ZB Series
Application Guide

3.8 Special handling consideration for ZB58-ZB114

Three-phase models

ZB58- ZB114 model compressors have the suction fitting located low on

ZB15ZB48- outdoor only

the shell. Due to this, its recommended to leave the suction connection

Crankcase heaters are required on three phase compressors where the

plug in place until the compressor is set into the unit. The discharge

system charge exceeds 4.5 Kgs. Table 3 lists the specification of applicable

connection plug should be removed first before pulling the suction

crankcase heaters.

connection plug to allow the dry air pressure inside the compressor to
escape. Pulling the plugs in this sequence prevents oil mist from coating

ZB58-ZB114

the suction tube making the brazing difficult.. The copper coated steel

Crankcase heaters are required where the system charge exceeds 7

suction tube should be cleaned before brazing. No object (example a

Kgs. The crankcase heater must be located below the suction inlet.

swaging tool) should be inserted deeper than 50mm into the suction

Table 3 lists the specification of applicable crankcase heaters

tube or it might damage the suction screen and motor.

Table 3
Crankcase Heater

4. System Protection Guidelines


4.1 Accumulator Requirement:
Due to the scrolls inherent ability to handle liquid refrigerant in flooded

Model

Part No

Volts

Watts

Length

ZB15-ZB48

018-0072-04

240

70

48" (122 mm)

ZB58-ZB114

018-0067-01

240

90

48" (122 mm)

start and defrost cycle operation conditions, accumulators may not be


required. An accumulator is required on single compressor systems when

The listed crankcase heaters are intended for use only when there is limited

the charge limitations exceed those values listed in Table 2. On systems

access (Table 3). The heaters are not equipped for use with electrical

with defrost schemes or transient operations that allow prolonged

conduit. Where applicable, electrical safety codes require lead protection,

uncontrolled liquid return to the compressor, an accumulator is required.

a crankcase heater terminal box should be used. Recommended


crankcase heater terminal box and cover part kit numbers are available
with Copeland Application Engineering Department.

Excessive liquid flood back or repeated flooded starts will dilute the oil
in the compressor causing inadequate lubrication and bearing wear.

The crankcase heater must remain energized during the compressor off cycles.

Proper system design will minimize liquid flood back, thereby ensuring
maximum compressor life.

The initial start in the field is a very critical period for any compressor
because all load bearing surfaces are new and require a short break-in

Table 2
Charge Limitations

period to carry high loads under adverse conditions. The crankcase

Models

Charge Limits

heater must be turned on a minimum of 12 hours prior to starting

ZB15- ZB48

4.5 Kgs

the compressor. This will prevent oil dilution and bearing stress on initial

ZB58-ZB114

7 Kgs

start up. If it is not feasible to turn on the crankcase heater 12 hours in


advance of starting the compressor, then use one of the techniques listed
below to prevent possible flooded start damage to the compressor: 1)

4.2 Crankcase Heaters Requirement

Direct a 500 watt heat lamp or other safe heat source at the lower shell

Single-phase models

of the compressor for approximately 30 minutes to boil off any liquid

No crankcase heaters are required on single-phase scroll compressors.

refrigerant prior to starting; or 2) Bump start the compressor by manually


energizing the compressor contactor for about one second. Wait five
seconds and again manually energize compressor for one second. Repeat
this cycle several times until the liquid in the shell has been boiled off and
the compressor can be safely started and run continuously.

10

ZB Series
Application Guide

4.3 Pump-Down Cycle

4.4 Filter Screens In System

A pump-down cycle for control of refrigerant migration may be used

The use of screens finer than 30 x 30 mesh (0.6 mm openings) anywhere

instead of, or in conjunction with, a crankcase heater when the

in the system is not recommended. Field experience has shown that finer

compressor is located so that cold air blowing over the compressor

mesh screens used to protect thermal expansion valves, capillary tubes,

makes the crankcase heater ineffective. A separate external check

or accumulators can become temporarily or permanently plugged with

valve must be added to the discharge line if pump-down is used.

normal system debris and block the flow of either oil or refrigerant to the

The built-in scroll discharge check valve is designed to stop extended

compressor. Such blockage can result in compressor failure.

reverse rotation and prevent high pressure gas from leaking rapidly
into the low side after shut off. High side leak-back through the check

5. Testing Guidelines

valve may exceed amounts typically found in reciprocating compressors

5.1 Compressor Hi-Pot Testing

with reed valves. This can cause the compressor to recycle more frequently.

Refrigeration scroll compressors are configured with the motor in the

Repeated short-cycling of this nature can result in low compressor oil

bottom of the shell. Unlike most other hermetic compressors, the motor

and consequent damage to the compressor. The recommended external

of a scroll compressor can be immersed in refrigerant when liquid is

check valve will prevent the frequent recycling due to leak-back. The low

present in the shell. Hi- Pot tests with liquid refrigerant in the shell can

pressure control cut-in and cut-out settings have to be reviewed since

show higher levels of current leakage due to the higher electrical

a relatively large volume of gas will re-expand from the high side of the

conductivity of liquid refrigerant vs. refrigerant vapor and oil. This

compressor into the low side on shut down. Emerson recommends that

phenomenon can occur with any compressor when the motor is

the cut out setting of the pump-down pressure control be set no more

immersed in refrigerant and does not present any safety issue. To lower

than a few degrees of equivalent saturated pressure below the lowest

the current leakage reading, operate the system for a brief period of time

expected normal operating pressure. It is not necessary to pump-down

redistributing the refrigerant to a more normal configuration and test

into nearly a vacuum to remove all liquid refrigerant for the low side.

again. Under no circumstances should the Hipot test be performed while

To achieve a fairly wide control differential the cut in setting should be

the compressor is in vacuum.

set a few degrees of equivalent saturated pressure below the lowest


expected temperature of the medium that is cooled. Copeland Scroll

5.2 Scroll Compressor Functional Check

compressors trap a considerable volume of high pressure gas between

A functional compressor test with the suction service valve closed to

the muffler plate and the top cap. When the compressor shuts down the

check how low the compressor will pull suction pressure is not a good

trapped gas will expand back into the suction side of the system. This

indication of how well a compressor is performing. Such a test will

frequently causes a pulse of pressure to propagate down the suction

almost certainly damage a scroll compressor. The following diagnostic

line and can cause the low pressure switch to reset. The compressor

procedure should be used to evaluate whether a Copeland Scroll

must not be allowed to short cycle which may result in oil pump out.

compressor is working properly.

The electrical circuitry should be arranged so that compressor restart


1. Proper voltage to the unit should be verified.

is triggered by demand from the thermostat rather than a reset low


pressure switch. Setting a wider differential between the cutout and cut
in pressures of a low pressure switch may solve the short cycling problem

2. The normal checks of motor winding continuity and short to ground

but may also result in unacceptable temperature swings in the cooled

should be made to determine if the inherent overload motor

space. If short cycling cannot be avoided, using a 3 minute time delay

protector has opened or if an internal motor short or ground fault

will limit the cycling of the compressor to an acceptable level.

has developed. If the protector has opened, the compressor must


be allowed to cool sufficiently to allow it to reset.

11

ZB Series
Application Guide

3.

Proper indoor and outdoor blower/fan operation should be verified.

Determine the control voltage by using a voltmeter and then measure


the voltage across the M1-M2 contacts:

4.

With service gauges connected to suction and discharge pressure

a. If the measured voltage is equal to the control volts then the


M1-M2 contacts are open.

fittings, turn on the compressor. If suction pressure falls below


normal levels, the system is either low on charge or there is a flow

5.

blockage in the system.

b. If the measurement is less than 1 volt and the compressor is not


running, then the problem is external to the INT69SU module.

In single Phase Compressors, if suction pressure does not drop and

c. If the voltage is greater than 1 volt but less than the control voltage,
the module is faulty and should be replaced.

discharge pressure does not rise to normal levels the compressor


is faulty. But in Three Phase compressors, reverse any two of the
Sensor Troubleshooting

compressor power leads and reapply power to make sure compressor

Remove the leads from S1-S2, and then by using an ohmmeter

was not wired to run in reverse direction.

measure the resistance of the incoming leads.


6.

CAUTION: Use an Ohmmeter with a maximum of 9 VDC for checking do

Before replacing, be certain that the compressor is actually defective.

not attempt to check continuity through the sensors with any other type of

As a minimum, recheck a compressor returned from the field in the

instrument. Any external voltage or current may cause damage requiring

shop or depot for Hipot, winding resistance, and ability to start.

compressor replacement.

Experience shows that more than one third of compressors are

a. During normal operation, this resistance value should read less


than 4500 ohms 20%.

determined to have nothing found wrong. They were mis-diagnosed


in the field as being defective. Replacing working compressors
unnecessarily costs everyone.

7.

b. If the M1-M2 contacts are open, the measured S1-S2 value is


above 2750 ohms 20% and the compressor has been tripped
less then 30 minutes then the module is functioning properly.

NEVER test a scroll compressor by closing the suction valve or the


liquid feed to the evaporator and pumping the compressor into a

If the S1-S2 wire leads read less than 2750 ohms 20% and the M1-M2

vacuum.

contacts are open, reset the module by removing the power to T1-T2
for a minimum of 5 seconds.

5.3 Electronic Motor Protection Module and Sensor Functional Check


The following field troubleshooting procedure can be used to evaluate

Replace all wire leads and use a voltmeter to verify the M1-M2 contacts

the solid state control circuit: Refer to Table 4 for a technical data

are closed.

summary.

If the M1-M2 contacts remain open and S1-S2 are less than 2500 ohms,

Module Voltage Supply Troubleshooting

remove leads from the M1-M2 contacts and jumper together;

Verify that all wire connectors are maintaining a good mechanical

CAUTION: Compressor should start at this time. HOWEVER DO NOT LEAVE

connection. Replace any connectors that are loose.

JUMPER IN PLACE FOR NORMAL SYSTEM OPERATIONS. THE JUMPER IS USED


FOR DIAGNOSTIC PURPOSES ONLY.

Measure the voltage across T1-T2 to ensure proper supply voltage.

Go to Compressor Supply Voltage Troubleshooting.

12

ZB Series
Application Guide

Compressor Supply Voltage Troubleshooting

6. Field & Installation Guidelines

Remove phase sensing leads from the module from L1/L2/L3.

6.1 Assembly Line And Field Brazing


ZB Scroll compressors are available with stub tube and Rotalock

Use a voltmeter to measure the incoming 3 phase voltage on L1/L2/L3.

connections. The stub tube version has copper plated steel suction and

WARNING: L1/L2/L3 could be at a potential up to 600VAC.

discharge fittings. Due to the different thermal properties of steel and


copper, brazing procedures may have to be changed from those commonly

Ensure proper voltage on each phase.

used The guidelines below gives a description for assembly line and field
brazing procedures.

Remove power to the module for a minimum of 5 seconds to reset and

replace all wire leads. Reenergize the module. If the M1-M2 contacts
are open with proper voltage to T1-T2, L1/L2/L3 and proper resistance
to S1-S2 then the module is faulty and should be replaced.
Figure 2

Table 4
Technical Data Summary Of Module
Emerson P/N

071-0641-00

Manufacturer P/N Kriwan 69SU

Kriwan 69SU

New Installations
The copper-coated steel suction and discharge tubes on scroll
compressors can be brazed in approximately the same manner as any

T1-T2 Module Power


Voltage Supply

120V & 240V

Frequency

50Hz & 60Hz

copper tube.
Recommended brazing materials: Any silfos material is recommended,

M1-M2 Module Output Contacts


Maximum Voltage

preferably with a minimum of 5% silver. However, 0% silver is acceptable.


250VAC

Maximum Current

5 Amps

Minimum Current

100 milliamps

prior to assembly. If oil film is present wipe with denatured alcohol,

Relay Output

5 A, 300 VA

Dichloro-Trifluoroethane or other suitable solvent.

Power Output

<3 VA

Be sure compressor tube fittings I.D. and connecting tube O.D. are clean

Using a double-tipped torch apply heat in Area 1. As tube approaches

S1-S2 Thermal Protection


Trip Out Resistance

brazing temperature, move torch flame to Area 2.

4500W 20%

Reset Resistance

2750W 20%

Reset Time

30 min 5 min

Manual Reset

T1-T2 interrupt for minimum of 5 sec

Heat Area 2 until braze temperature is attained, moving torch up and


down and rotating around tube as necessary to heat tube evenly. Add
braze material to the joint while moving torch around joint to flow

L1-L2-L3 Phase Monitoring

braze material around circumference.

Phase Sensor

Non Phase Sensing

Phase Monitoring Circuit Rating

Non Phase Sensing

After braze material fl ows around joint, move torch to heat Area 3.

Trip Delay

Non Phase Sensing

This will draw the braze material down into the joint. The time spent

Lockout

Non Phase Sensing

heating Area 3 should be minimal.

Reset For Lockout

Non Phase Sensing

As with any brazed joint, overheating may be detrimental to the


final result.

13

ZB Series
Application Guide

Field Service

6.2 Compressor Replacement after Motor Burn

Unbrazing System Components

In the case of a motor burn, the majority of contaminated oil will be


removed with the compressor. The rest of the oil is cleaned through use

CAUTION!

of suction and liquid line filter dryers. A 100% activated alumina suction

If the refrigerant charge is removed from a scroll unit by bleeding the

filter drier is recommended but must be removed after 72 hours. Separate

high side only, it is sometimes possible for the scrolls to seal preventing

bulletins are available on request for clean up procedures and for liquid

pressure equalization through the compressor. This may leave the low

line filter drier recommendations. AE Bulletin 24-1105 for clean up

side shell and suction line tubing pressurized. If a brazing torch is then

procedures AE Bulletin 11-1297 for liquid line filter drier recommendations.

applied to the low side, the pressurized refrigerant oil mixture could
ignite as it escapes and contacts the brazing flame. It is important to

It is highly recommended that the suction accumulator be replaced if

check both the high and low sides with manifold gauges before unbrazing.

the system contains one. This is because the accumulator oil return

In the case of an assembly line repair, remove the refrigerant from both

orifice or screen may be plugged with debris or may become plugged

the high and low sides. Instructions should be provided in appropriate

shortly after a compressor failure. This will result in starvation of oil to

product literatures and assembly areas

the replacement compressor and a second failure.

To disconnect: Reclaim refrigerant from both the high and low side of

6.3 System Charging Procedure

the system. Cut tubing near compressor.

Systems should be charged with liquid on the high side to the extent
possible. The majority of the charge should be pumped into the high side

To reconnect. Recommended brazing material is Silfos with minimum

of the system to prevent hi pot failures, and bearing washout during first

5% silver or silver braze material with flux. Insert tubing stubs into

time start. If additional charge is needed, it should be added as liquid, in

fitting and connect to the system with tubing connectors. Follow New

a controlled manner, to the low side of the system with the compressor

Installation brazing instructions.

operating. Pre-charging on the high side and adding liquid on the low side
of the system are both meant to protect the compressor from operating

Brazing Procedure

with abnormally low suction pressures during charging.

Figure 2 discusses the proper procedures for brazing the suction and
Do not start the compressor while the system is in a deep vacuum. Internal

discharge lines to a Copeland Scroll compressor. It is important to flow


nitrogen through the system while brazing all joints during the system

arcing may occur when a compressor is started in a vacuum Do not operate

assembly process. Nitrogen displaces the air and prevents the formation

compressor without enough system charge to maintain at least 7 psig

of copper oxides in the system.

(0.5Kg/cm) suction pressure. Do not operate with a restricted suction.


Do not operate with the low pressure cut-out jumpered. Allowing pressure

If allowed to form, the copper oxide flakes can later be swept through

to drop below 2F(-16C) for more than a few seconds may overheat scrolls

the system and block screens such as those protecting capillary tubes,

and cause early drive bearing damage or cause the scroll temperature

thermal expansion valves, and accumulator oil return holes. The blockage

protection to activate. Do not use compressor to test opening set point

- whether it is of oil or refrigerant - is capable of doing damage resulting

of high pressure cutout. Bearings are susceptible to high load damage

in compressor failure.

before they have had several hours of normal running for proper break in.
Never install a system in the field and leave it unattended with no charge,
or with the service valves closed without securely locking out the system.
This will prevent unauthorized personnel from accidentally operating the
system and potentially ruining the compressor by operating with no
refrigerant flow.

14

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB15KQ

ZB19KQ

ZB21KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

4000
3850
3550
3250
2650

4350
4200
3850
3500
2900
2700

5250
5050
4700
4250
3850
3400
3150

870
960
1150
1400
1730

870
950
1150
1400
1720
1910

870
960
1150
1390
1710
1900
2120

4650
4450
4100
3700
3050

5000
4800
4450
4050
3350
3100

6050
5850
5400
4900
4400
3900
3600

980
1080
1300
1580
1940

980
1070
1290
1570
1930
2150

980
1080
1290
1570
1930
2140
2390

5850
5600
5150
4700
3850

6300
6100
5600
5100
4200
3950

7650
7350
6800
6200
5550
4900
4550

1360
1500
1800
2200
2700

1360
1490
1800
2190
2690
3000

1370
1500
1800
2180
2680
2980
3320

6250
6050
5600
5150
4600
4350
3900
3600
890
970
1160
1400
1710
1900
2110
2360
7250
6950
6450
5900
5300
5000
4500
4150
1000
1090
1300
1570
1920
2140
2380
2650
9100
8800
8150
7450
6700
6300
5650
5200
1390
1520
1810
2190
2680
2970
3310
3690

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

15

10

12.5

7200
6650
6100
5500
5200
4850
4500

7900
7250
6550
6200
5800
5400

8600
7900
7150
6750
6350
5900

990
1170
1400
1710
1890
2110
2340

1180
1410
1700
1890
2090
2330

1180
1400
1700
1880
2080
2310

8300
7700
7050
6350
6000
5600
5200

9100
8350
7550
7150
6700
6250

9900
9100
8250
7800
7350
6800

1110
1320
1580
1920
2130
2370
2640

1330
1580
1920
2120
2350
2620

1330
1580
1910
2110
2340
2600

10450
9700
8900
8000
7550
7050
6550

11500
10550
9550
9000
8450
7850

12500
11500
10400
9850
9250
8600

1550
1830
2200
2680
2970
3300
3670

1850
2200
2670
2950
3270
3640

1850
2200
2660
2940
3260
3620

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB26KQ

ZB29KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

6750
6450
5950
5400
4400

7300
7000
6450
5900
4850
4550

8800
8500
7850
7150
6400
5700
5250

1470
1610
1940
2360
2900

1460
1600
1930
2350
2890
3220

1470
1610
1930
2340
2880
3200
3570

7850
7600
7000
6400
5400

8550
8300
7650
6950
5900
5650

10250
10000
9300
8500
7650
6850
6500

1640
1790
2120
2530
3030

1660
1800
2130
2540
3050
3340

1710
1850
2170
2580
3090
3390
3720

10500
10150
9400
8600
7750
7250
6550
6000
1500
1630
1950
2350
2870
3190
3550
3960
12050
11800
11100
10150
9150
8600
7800
7350
1770
1900
2210
2610
3130
3430
3770
4150

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

16

10

12.5

12050
11200
10250
9250
8700
8150
7550

13300
12200
11000
10400
9750
9050

14450
13300
12050
11350
10650
9950

1660
1970
2360
2870
3190
3540
3940

1980
2360
2860
3170
3520
3910

1980
2360
2850
3150
3500
3890

13800
13050
12050
10900
10250
9600
9000

15350
14300
13000
12250
11500
10750

16650
15600
14250
13450
12650
11800

1940
2250
2650
3160
3470
3810
4200

2270
2670
3180
3490
3840
4230

2280
2670
3190
3500
3850
4240

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQ

ZB19KQ

ZB21KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

4050
3900
3550
3200
2650

4400
4250
3900
3500
2900
2700

5250
5100
4700
4250
3800
3350
3100

780
870
1090
1350
1680

780
870
1090
1350
1680
1880

800
890
1100
1370
1700
1890
2110

4650
4500
4100
3700
3050

5050
4850
4450
4050
3300
3100

6050
5850
5450
4900
4350
3850
3600

880
990
1240
1540
1910

880
990
1240
1540
1910
2130

900
1010
1250
1550
1930
2150
2400

5900
5650
5200
4650
3800

6350
6150
5650
5100
4200
3900

7650
7400
6850
6200
5500
4850
4550

1150
1290
1610
2000
2480

1150
1290
1610
1990
2480
2760

1170
1310
1620
2010
2500
2790
3110

6200
6050
5650
5150
4550
4250
3850
3550
830
920
1120
1390
1720
1920
2140
2380
7150
7000
6500
5900
5250
4950
4400
4100
940
1040
1280
1570
1950
2180
2430
2710
9050
8800
8200
7450
6650
6200
5550
5150
1220
1350
1660
2040
2530
2820
3150
3510

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

17

10

12.5

7150
6700
6100
5450
5100
4750
4400

7850
7250
6500
6100
5700
5250

8500
7850
7100
6650
6200
5750

960
1150
1410
1740
1940
2160
2410

1180
1420
1750
1940
2160
2410

1180
1420
1740
1940
2160
2410

8200
7700
7050
6300
5900
5500
5050

9050
8350
7500
7050
6550
6050

9800
9050
8150
7700
7150
6650

1090
1310
1600
1970
2200
2450
2730

1340
1620
1980
2210
2460
2740

1340
1620
1980
2200
2450
2730

10350
9700
8900
7950
7450
6900
6400

11450
10500
9450
8850
8250
7650

12400
11450
10300
9700
9050
8350

1410
1700
2080
2560
2850
3180
3550

1730
2100
2570
2860
3190
3550

1740
2100
2570
2860
3180
3540

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB26KQ

ZB29KQ

ZB38KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

6900
6650
6100
5550
4600

7500
7200
6650
6050
5050
4750

8950
8700
8050
7350
6600
5850
5500

1230
1380
1740
2210
2840

1200
1360
1720
2180
2800
3190

1200
1350
1710
2170
2770
3140
3570

7900
7600
6950
6250
5100

8550
8250
7550
6800
5600
5250

10250
9900
9200
8300
7400
6500
6050

1460
1640
2050
2540
3150

1460
1640
2040
2540
3160
3520

1490
1670
2060
2560
3190
3550
3960

9800
9450
8650
7750
6350

10600
10200
9400
8450
6950
6500

12700
12350
11400
10300
9200
8100
7550

1850
2070
2580
3210
3980

1850
2070
2580
3210
3990
4450

1890
2100
2610
3230
4020
4490
5010

10650
10350
9650
8800
7900
7400
6650
6200
1220
1380
1740
2190
2780
3140
3550
4030
12150
11800
11000
10000
8900
8350
7450
6900
1560
1720
2110
2600
3230
3600
4010
4470
15050
14650
13650
12400
11050
10350
9250
8550
1970
2180
2660
3290
4070
4540
5070
5650

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

18

10

12.5

12350
11550
10550
9450
8850
8250
7650

13850
12700
11400
10700
9950
9200

15150
13950
12550
11750
10950
10150

1410
1770
2210
2790
3140
3540
4000

1760
2200
2760
3100
3490
3930

1730
2170
2720
3060
3440
3880

13900
13000
11900
10650
9950
9250
8550

15350
14100
12700
11900
11100
10250

16600
15350
13800
13000
12100
11200

1790
2160
2640
3260
3630
4050
4510

2210
2670
3280
3650
4060
4520

2220
2670
3270
3640
4050
4510

17300
16150
14800
13250
12400
11500
10650

19050
17550
15750
14800
13800
12750

20650
19050
17150
16150
15050
13950

2270
2730
3340
4120
4590
5110
5700

2790
3370
4140
4600
5130
5710

2810
3380
4130
4590
5110
5700

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB45KQ

ZB48KQ

ZB58KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

11800
11350
10450
9450
7650

12750
12300
11350
10300
8400
7750

15350
14800
13700
12500
11100
9750
8950

2080
2340
2950
3710
4650

2100
2360
2970
3730
4680
5230

2160
2410
3010
3760
4710
5270
5890

12950
12500
11500
10400
8400

14000
13500
12450
11300
9250
8550

16900
16300
15050
13700
12200
10750
9850

2290
2570
3250
4080
5120

2310
2600
3270
4100
5140
5750

2380
2660
3310
4140
5180
5800
6480

15400
14650
13300
11850
9250

16650
15900
14500
13000
10350
9300

20150
19350
17750
16100
14150
12250
11000

2740
3100
3900
4880
6140

2760
3110
3900
4880
6140
6900

2790
3150
3930
4890
6120
6870
7720

18350
17700
16400
14950
13400
12500
11150
10200
2230
2470
3050
3790
4720
5280
5900
6590
20200
19500
18050
16450
14700
13750
12300
11200
2460
2720
3350
4160
5200
5810
6490
7250
24200
23300
21450
19600
17450
16200
14250
12750
2860
3210
3970
4910
6110
6840
7670
8620

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

19

10

12.5

21100
19500
17800
16000
15000
13950
12800

23100
21100
18950
17850
16650
15350

25100
22950
20650
19400
18150
16800

2550
3100
3810
4730
5280
5890
6580

3170
3850
4750
5290
5890
6570

3230
3890
4770
5300
5890
6570

23200
21450
19600
17550
16500
15350
14100

25400
23200
20850
19600
18300
16900

27600
25250
22700
21350
19950
18450

2810
3400
4190
5200
5810
6480
7240

3490
4240
5220
5810
6480
7220

3550
4280
5240
5830
6480
7220

27800
25700
23550
21150
19800
18250
16600

30500
28050
25300
23800
22150
20300

33150
30500
27600
26000
24250
22350

3310
4050
4960
6120
6830
7640
8570

4190
5060
6180
6860
7650
8540

4270
5120
6220
6900
7670
8550

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB66KQ

ZB76KQ

ZB88KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

17200
16550
15300
13950
11400

18650
17950
16550
15150
12500
11600

22600
21750
20100
18450
16550
14650
13500

2840
3330
4270
5340
6710

2850
3350
4300
5360
6720
7560

2900
3400
4360
5410
6740
7570
8540

20300
19500
18000
16400
13350

22000
21150
19500
17850
14700
13600

26750
25700
23700
21750
19500
17200
15800

3020
3700
4950
6270
7930

3030
3710
4970
6300
7950
8980

3060
3750
5030
6360
8000
9020
10210

23550
22700
20850
18750
15100

25400
24550
22600
20400
16600
15300

30500
29600
27500
24950
22050
19300
17650

3940
4470
5660
7120
8920

3980
4500
5690
7150
8960
10030

4120
4610
5770
7220
9040
10120
11320

27150
26150
24200
22200
20050
18800
16850
15450
2970
3480
4430
5470
6770
7580
8520
9620
32250
30950
28550
26150
23600
22200
19850
18150
3140
3840
5110
6430
8040
9040
10210
11580
36150
35200
32900
30100
26800
24950
22150
20100
4350
4800
5890
7290
9090
10160
11370
12720

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

20

10

12.5

31200
28850
26500
23950
22550
21100
19450

34200
31400
28400
26800
25100
23300

37100
34050
30850
29150
27300
25400

3590
4540
5550
6820
7600
8510
9570

4690
5680
6890
7650
8530
9560

4790
5760
6950
7690
8550
9560

36900
34000
31200
28200
26600
24850
22950

40150
36850
33350
31500
29550
27450

43500
39900
36150
34200
32100
29850

3990
5240
6530
8100
9070
10210
11550

5470
6700
8210
9150
10240
11540

5620
6820
8290
9210
10280
11550

41300
38850
35800
32100
30000
27800
25400

45350
42000
37950
35650
33150
30500

48750
45300
41050
38650
36050
33200

5100
6080
7410
9150
10210
11400
12740

6410
7610
9260
10280
11450
12760

6620
7760
9350
10350
11490
12790

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB95KQ

ZB114KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

25350
24350
22350
19550

27400
26350
24200
21450

33200
31800
29350
26500
22450

39950
38200
35150
32050
28050
25350

4660
5170
6450
8040

4730
5220
6490
8080

4990
5410
6590
8180
10120

5340
5680
6740
8280
10230
11350

30500
29400
26750
23200

32950
31800
29050
25550

39700
38400
35400
31700
27050

47300
45850
42500
38550
33700
30900

5730
6320
7760
9610

5790
6380
7790
9630

5990
6550
7920
9710
12030

6250
6780
8090
9830
12090
13460

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

21

10

12.5

45550
41800
38250
34100
31450
28350
24600

49350
45200
40700
38000
34900
31250

53550
49000
44250
41500
38400
34750

6040
6940
8380
10320
11460
12690
14030

7200
8510
10380
11520
12770
14140

7350
8580
10410
11530
12790
14160

54250
50450
46100
41000
38050
34850
31350

59350
54500
48950
45850
42500
38850

64150
59050
53250
50050
46600
42850

7080
8330
9990
12190
13520
15020
16710

8630
10220
12340
13630
15100
16750

8820
10360
12440
13710
15150
16780

R404A/R507

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

ZB29KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

3700
3350
2950
2550
2150

4500
4050
3600
3150
2600
2050
740
920
1150
1450
1810
2250
5100
4700
4200
3650
3000
2350
900
1140
1430
1810
2290
2900
6550
6000
5350
4650
3850
3000
1150
1450
1830
2310
2920
3690
7300
6600
5800
4900
3900
2800
1470
1850
2330
2950
3730
4710
8700
7900
7050
6050
5000
3800
1660
1960
2350
2850
3470
4210

5450
4900
4350
3800
3150
2500
740
930
1160
1450
1810
2260
6200
5700
5050
4400
3650
2850
910
1140
1430
1810
2290
2890
7950
7250
6500
5600
4650
3600
1150
1450
1820
2300
2910
3680
8900
8050
7100
6050
4900
3600
1440
1810
2280
2880
3640
4600
10600
9600
8550
7400
6150
4750
1700
1990
2370
2870
3480
4240

730
920
1150
1440
1800
4200
3850
3450
3000
2450
900
1140
1430
1810
2290
5350
4900
4400
3800
3150
1150
1450
1830
2310
2920
5950
5350
4700
3950
3100
1490
1880
2380
3000
3800
7100
6450
5700
4900
4000
1630
1930
2330
2830
3440

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

22

-5

10

5900
5250
4550
3800
3000

7000
6200
5400
4500
3600

7300
6350
5350
4250

8550
7450
6250
5050

930
1160
1450
1810
2260

930
1160
1450
1810
2250

1150
1450
1810
2250

1140
1440
1800
2240

6800
6100
5300
4400
3400

8150
7250
6300
5250
4100

8600
7450
6200
4900

10100
8750
7300
5800

1140
1430
1800
2280
2880

1140
1420
1790
2260
2860

1410
1780
2240
2830

1400
1760
2220
2800

8700
7750
6750
5600
4350

10400
9250
8050
6700
5250

10950
9500
7950
6250

12900
11200
9350
7400

1450
1820
2290
2900
3660

1450
1810
2280
2880
3640

1800
2260
2860
3610

1790
2240
2820
3570

9800
8650
7400
6000
4500

11750
10400
8950
7350
5650

12450
10750
8900
6950

14800
12850
10750
8500

1770
2230
2810
3550
4480

1730
2160
2720
3440
4350

2100
2630
3320
4200

2020
2530
3190
4040

11550
10300
8900
7400
5800

13800
12250
10650
8850
7000

14500
12550
10500
8300

17000
14750
12350
9800

2020
2400
2890
3500
4260

2070
2440
2910
3520
4270

2480
2950
3550
4290

2540
2990
3580
4320

R404A/R507

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

ZB29KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

3650
3300
2900
2400
1850

4450
4050
3550
3000
2400
1650
750
980
1250
1630
2180
2970
5350
4900
4350
3800
3150
2450
930
1170
1480
1870
2360
2990
6400
5850
5250
4550
3750
2900
1110
1400
1770
2240
2830
3580
7500
6850
6100
5300
4400
3400
1300
1640
2070
2610
3310
4180
8700
7950
7100
6150
5100
3950
1480
1860
2350
2960
3750
4750

5450
4950
4350
3700
2950
2150
700
950
1230
1590
2100
2840
6500
5900
5300
4600
3800
2950
930
1170
1480
1860
2360
2980
7800
7100
6350
5500
4550
3550
1120
1400
1770
2230
2820
3570
9100
8300
7400
6400
5350
4150
1310
1640
2070
2610
3300
4170
10550
9600
8600
7450
6200
4800
1480
1860
2340
2960
3740
4730

780
1000
1270
1670
2260
4350
4000
3600
3100
2550
930
1170
1480
1870
2360
5250
4800
4300
3700
3100
1110
1400
1770
2240
2830
6100
5600
5000
4350
3600
1300
1640
2070
2610
3310
7100
6500
5800
5050
4150
1470
1860
2340
2960
3750

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

23

-5

10

5950
5250
4450
3600
2650

7150
6300
5350
4300
3250

7450
6350
5150
3900

8800
7450
6100
4600

920
1200
1550
2030
2710

880
1170
1510
1970
2610

1160
1490
1920
2520

1160
1490
1900
2460

7100
6350
5500
4600
3550

8500
7550
6550
5450
4300

8950
7750
6500
5100

10500
9150
7650
6050

1170
1470
1860
2350
2960

1170
1470
1840
2330
2940

1460
1830
2310
2920

1450
1810
2290
2890

8550
7600
6600
5500
4300

10200
9050
7850
6550
5150

10750
9300
7750
6100

12600
10950
9150
7250

1400
1760
2220
2810
3550

1400
1750
2210
2790
3530

1750
2190
2770
3490

1730
2170
2740
3460

9950
8900
7700
6400
5000

11900
10600
9200
7650
6000

12550
10900
9100
7150

14750
12800
10700
8450

1640
2060
2600
3280
4150

1640
2050
2580
3260
4120

2040
2560
3240
4090

2020
2540
3200
4040

11550
10300
8950
7450
5800

13800
12300
10650
8900
6950

14550
12600
10550
8300

17100
14850
12400
9800

1860
2340
2950
3730
4710

1860
2330
2930
3700
4680

2310
2910
3670
4630

2300
2880
3630
4580

R404A/R507

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB38KQE

ZB45KQE

ZB48KQE

ZB58KQE

ZB66KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

8950
8200
7350
6350
5250

10950
10000
8950
7750
6450
4950
1870
2350
2960
3740
4740
5990
12800
11750
10500
9100
7550
5800
2110
2660
3350
4240
5360
6780
14100
12900
11550
10000
8300
6400
2320
2930
3690
4660
5900
7460
16750
15250
13650
11850
9650
6850
3080
3730
4540
5630
7120
9130
19200
17450
15550
13500
11250
8650
3450
4170
5090
6290
7850
9890

13300
12150
10850
9400
7800
6050
1870
2350
2960
3730
4720
5970
15550
14200
12700
11000
9150
7100
2120
2660
3350
4230
5350
6760
17100
15650
13950
12100
10050
7800
2330
2930
3680
4650
5880
7440
20300
18500
16600
14500
12000
9000
3140
3820
4620
5670
7080
8980
23350
21150
18800
16350
13650
10650
3550
4260
5160
6340
7880
9870

1860
2350
2960
3740
4740
0
10450
9600
8600
7450
6150
2110
2660
3350
4240
5360
11500
10550
9450
8150
6750
2320
2920
3690
4660
5900
13750
12450
11100
9450
7400
3000
3640
4480
5630
7210
15700
14300
12750
11050
9100
3370
4100
5030
6240
7830

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

24

-5

10

14600
13000
11300
9400
7300

17400
15500
13450
11200
8750

18350
15900
13300
10450

21550
18700
15650
12400

2350
2950
3720
4700
5940

2350
2940
3700
4670
5900

2920
3670
4630
5850

2900
3630
4580
5790

17100
15250
13200
11000
8550

20400
18150
15750
13100
10250

21500
18650
15550
12200

25250
21900
18350
14500

2660
3340
4210
5320
6730

2660
3320
4190
5290
6680

3310
4150
5240
6620

3280
4110
5190
6550

18800
16750
14500
12050
9400

22400
20000
17300
14400
11300

23650
20500
17100
13450

27800
24100
20150
15950

2930
3670
4630
5860
7400

2920
3660
4600
5820
7350

3640
4570
5770
7280

3610
4530
5700
7200

22250
19950
17450
14600
11250

26600
23800
20800
17500
13700

28200
24600
20700
16350

33200
28900
24350
19300

3870
4690
5720
7090
8900

3870
4730
5770
7100
8850

4710
5770
7100
8800

4600
5720
7060
8740

25450
22550
19550
16350
12850

30400
26900
23250
19450
15350

31900
27500
22950
18150

37550
32350
27000
21400

4370
5250
6390
7900
9850

4510
5350
6460
7920
9830

5480
6540
7950
9800

5620
6630
7990
9780

R404A/R507

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB76KQE

ZB95KQE

ZB114KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

18400
16700
14900
12900
10600

22400
20350
18250
15900
13250
10050
4030
4870
5930
7310
9120
11480
27700
25300
22700
19600
15500

27150
24700
22150
19350
16200
12550
4110
4980
6030
7390
9160
11440
33700
30500
27400
23850
19500
13950
5220
6290
7670
9500
11920
15070
40300
36700
32750
28250
23000
16750
6240
7540
9170
11310
14150
17870

3930
4750
5820
7230
9100
22750
20800
18550
15600

4880
5980
7440
9400

5050
6120
7540
9430
11940

27350
24850
21900
18300

33300
30350
27000
23050
18250

5930
7240
8940
11220

6080
7390
9050
11260
14200

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

25

-5

10

29700
26600
23250
19500
15250

35450
31700
27650
23250
18300

37450
32650
27450
21750

44000
38300
32200
25550

5070
6130
7480
9210
11430

5130
6220
7560
9260
11430

6270
7620
9300
11430

6300
7650
9330
11420

36700
32750
28550
23750
17850

43900
38950
33900
28350
21900

46150
40000
33550
26300

54500
47050
39400
31150

6450
7810
9590
11940
14990

6590
7940
9690
11980
14950

8040
9780
12020
14920

8110
9830
12040
14880

44050
39350
34100
28200
21350

52450
46800
40700
33950
26350

55350
48200
40450
31900

65050
56700
47800
38100

7710
9310
11380
14120
17710

7880
9450
11470
14110
17570

9610
11570
14130
17460

9780
11690
14160
17380

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

ZB29KQE

30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

1900
1800
1600

2400
2300
2000
1700

3000
2900
2600
2200
1800

800
800
1000

800
800
1000
1300

800
800
1000
1300
1600

2200
2000
1800

2800
2700
2300
2000

3500
3300
3000
2500
2100

900
1000
1200

900
1000
1200
1500

900
1000
1200
1500
1800

2800
2700
2300

3500
3300
2900
2500

4400
4200
3700
3200
2700

1100
1200
1500

1100
1200
1500
1800

1100
1200
1500
1800
2200

3200
3000
2600

4100
3900
3300
2900

5100
4800
4300
3700
3100

1200
1300
1700

1200
1300
1700
2100

1200
1400
1700
2100
2600

3850
3500
3050

4750
4500
3900
3300

5900
5600
5000
4200
4000

1370
1540
1940

1380
1550
1940
2420

1390
1560
1950
2430
3020

3700
3500
3200
2700
2300
1900
800
900
1100
1300
1600
2000
4300
4100
3700
3100
2700
2200
900
1000
1200
1500
1800
2300
5400
5100
4600
4000
3400
2700
1100
1200
1500
1800
2300
2800
6200
5900
5300
4600
3900
3200
1200
1400
1700
2100
2600
3200
7200
6850
6100
5250
4450
3600
1400
1570
1960
2440
3020
3750

4500
4300
3900
3400
2900
2400
800
900
1100
1300
1600
2000
5200
5000
4500
3900
3300
2700
900
1000
1200
1500
1900
2300
6500
6200
5600
4900
4200
3500
1100
1200
1500
1900
2300
2800
7600
7200
6500
5700
4900
4000
1200
1400
1700
2100
2600
3200
8750
8300
7450
6550
5550
4550
1410
1580
1970
2440
3030
3760

5400
5200
4700
4100
3500
3000
800
900
1100
1300
1600
2000
6300
6000
5400
4700
4100
3400
900
1000
1200
1500
1900
2300
7900
7500
6800
6000
5100
4300
1100
1200
1500
1900
2300
2800
9100
8700
7800
6900
5900
5000
1300
1400
1700
2100
2600
3200
10500
10050
9000
7950
6800
5600
1420
1590
1980
2450
3040
3770

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

26

15

5600
4900
4200
3500

1100
1300
1600
2000

6400
5700
4900
4000

1200
1500
1900
2300

8100
7200
6200
5100

1500
1900
2300
2900

9400
8300
7100
5900

1700
2100
2600
3300

10100
8950
7650
6250

1990
2460
3050
3770

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase
Condensing
Temperature
o
C

Model

ZB38KQE

ZB45KQE

ZB48KQE

ZB58KQE

ZB66KQE

30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

4700
4300
3800

5900
5600
4900
4200

7400
7000
6300
5400
4600

1700
1900
2300

1700
1900
2400
3000

1700
1900
2400
3000
3700

5700
5200
4500

7100
6800
5800
5000

8900
8500
7500
6300
5300

2000
2200
2700

2000
2200
2700
3400

2000
2200
2800
3400
4300

6400
5900
5200

8050
7650
6600
5700

9900
9450
8450
7200
6050

2280
2540
3170

2290
2560
3190
4000

2300
2570
3210
4010
5020

7450
6250
5400

9200
8700
6900
5900

11200
10600
9350
7450
6150

2690
3010
3720

2710
3030
3750
4590

2760
3070
3800
4660
5640

8550
7150
6200

10500
9950
7900
6700

12750
12100
10700
8500
7000

3000
3360
4150

3020
3380
4190
5120

3080
3430
4250
5210
6300

9100
8600
7800
6700
5700
4600
1800
2000
2400
3000
3700
4700
10900
10400
9300
8000
6700
5400
2000
2200
2800
3500
4300
5400
12150
11550
10350
8950
7600
6200
2310
2590
3220
4020
5030
6280
13400
12700
11300
9300
7750
6100
2820
3130
3850
4720
5730
6880
15300
14550
12900
10600
8850
7000
3150
3490
4300
5280
6410
7690

11100
10500
9400
8300
7100
5800
1800
2000
2400
3000
3700
4700
13300
12700
11400
10000
8400
6800
2000
2300
2800
3500
4300
5400
14700
14000
12550
11050
9450
7800
2330
2610
3250
4040
5040
6290
15850
15100
13500
11650
9650
7700
2880
3180
3890
4760
5790
6970
18150
17250
15450
13350
11000
8800
3210
3540
4340
5320
6470
7790

13300
12700
11400
10100
8700
7200
1800
2000
2500
3000
3800
4700
15900
15200
13700
12100
10300
8500
2000
2300
2800
3500
4400
5400
17600
16900
15100
13350
11450
9600
2370
2650
3290
4080
5050
6300
18600
17650
15750
13750
11600
9550
2910
3190
3880
4750
5790
7000
21200
20200
18050
15700
13250
10950
3250
3560
4340
5310
6470
7820

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

27

15

13700
12100
10400
8900

2500
3100
3800
4700

16300
14400
12300
10100

2800
3500
4400
5400

17300
15250
13100
10850

3360
4150
5120
6340

18300
16000
13500
10900

3820
4670
5710
6940

20900
18250
15400
12450

4270
5220
6390
7760

ZB Series

50 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase

Model

Condensing
Temperature
o
C

ZB76KQE

30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

9800
8150
7100

12050
11400
9000
7700

14650
13900
12250
9700
8050

3520
3940
4870

3550
3960
4900
5990

3610
4020
4970
6080
7350

17600
16700
14800
12150
10100
8000
3700
4100
5040
6160
7460
8950

20850
19800
17700
15250
12550
10050
3770
4150
5080
6200
7540
9070

24350
23150
20650
17950
15150
12500
3800
4160
5070
6190
7540
9110

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

28

15

23950
20900
17650
14300

4970
6080
7440
9040

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB15KQ

ZB19KQ

ZB21KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

5800
5500
4300
3900
3200

6250
5900
4650
4250
3500
3150

7450
7050
5650
5150
4600
3850
3400

1060
1190
1370
1660
2050

1060
1190
1360
1660
2040
2590

1070
1190
1360
1650
2030
2590
2890

5600
5350
4950
4500
3650

6050
5800
5350
4900
4050
3750

7300
7050
6500
5950
5300
4700
4350

1250
1370
1660
2020
2480

1250
1370
1650
2010
2470
2750

1260
1380
1650
2000
2460
2730
3050

7050
6750
6200
5650
4600

7600
7350
6750
6150
5100
4750

9200
8850
8200
7500
6700
5950
5500

1590
1750
2110
2570
3160

1590
1740
2100
2560
3150
3500

1600
1750
2100
2550
3130
3480
3880

8850
8400
6750
6200
5550
4850
4150
3550
1060
1190
1370
1660
2030
2590
2890
3220
8700
8400
7800
7100
6400
6000
5400
5000
1280
1400
1670
2010
2460
2730
3040
3390
11000
10600
9800
9000
8100
7600
6800
6300
1630
1780
2120
2560
3130
3470
3870
4310

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

29

10

12.5

9900
8050
7350
6650
5750
5100
4450

9550
8750
7950
6800
6050
5250

10400
9550
8650
7350
6550
5700

1180
1390
1670
2030
2580
2880
3210

1400
1670
2020
2570
2870
3190

1400
1660
2010
2560
2860
3180

10000
9250
8500
7650
7200
6750
6250

11000
10100
9150
8600
8100
7500

11950
11000
9950
9400
8850
8250

1420
1680
2020
2460
2720
3030
3370

1690
2020
2450
2710
3010
3340

1700
2020
2440
2700
2990
3320

12600
11700
10700
9650
9100
8500
7900

13850
12750
11500
10850
10200
9450

15100
13900
12550
11900
11150
10400

1810
2140
2570
3130
3470
3850
4290

2160
2570
3120
3450
3830
4260

2160
2570
3100
3430
3810
4230

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB26KQ

ZB29KQ

ZB38KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

8100
7800
7200
6500
5350

8800
8450
7800
7100
5850
5450

10600
10250
9450
8650
7750
6850
6350

1820
2000
2410
2930
3610

1820
1990
2400
2920
3590
4000

1830
2000
2400
2910
3570
3970
4430

9500
9150
8450
7700
6500

10300
10000
9250
8400
7100
6800

12400
12050
11250
10250
9250
8300
7850

2100
2280
2710
3220
3860

2120
2300
2720
3240
3880
4260

2180
2350
2770
3290
3940
4320
4740

12000
11400
10400
9450
7700

12700
12100
11000
9950
8150
7450

15150
14450
13200
12000
10550
9150
8250

2500
2720
3270
3970
4830

2540
2750
3290
3980
4840
5340

2660
2860
3360
4030
4890
5390
5940

12700
12250
11350
10350
9350
8750
7850
7250
1860
2030
2420
2920
3570
3970
4410
4920
14550
14250
13400
12250
11050
10400
9450
8850
2250
2420
2820
3330
3990
4380
4810
5290
18100
17400
16100
14750
13150
12250
10750
9550
2780
2970
3460
4120
4970
5470
6030
6640

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

30

10

12.5

14550
13500
12350
11150
10500
9800
9100

16000
14700
13300
12550
11750
10950

17450
16050
14500
13700
12850
12000

2060
2450
2930
3570
3960
4400
4900

2460
2940
3560
3940
4370
4860

2460
2930
3540
3920
4350
4830

16650
15800
14550
13150
12400
11600
10850

18550
17300
15700
14800
13900
12950

20150
18850
17200
16250
15250
14250

2480
2860
3370
4030
4420
4860
5350

2900
3400
4060
4450
4900
5390

2910
3410
4060
4460
4900
5400

20400
19100
17750
16100
15100
13950
12650

21900
20550
18950
17950
16750
15400

23000
21750
20150
19150
18000
16650

3060
3530
4180
5040
5540
6110
6730

3560
4210
5070
5580
6160
6790

3540
4190
5060
5580
6160
6800

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQ

ZB19KQ

ZB21KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

4950
4750
4300
3850
3150

5350
5150
4650
4200
3450
3350

6400
6200
5650
5100
4550
4200
3900

930
1040
1310
1630
2020

940
1050
1310
1620
2020
2160

980
1080
1320
1640
2040
2190
2420

5550
5350
4900
4450
3650

6050
5800
5350
4850
4000
3700

7250
7000
6500
5900
5300
4650
4300

1200
1340
1640
2010
2520

1200
1340
1640
2010
2510
2830

1200
1340
1650
2010
2490
2800
3150

7150
6900
6400
5800
4750

7750
7500
6900
6300
5200
4900

9300
9050
8400
7650
6850
6100
5700

1350
1500
1870
2300
2810

1360
1520
1880
2310
2830
3130

1430
1570
1910
2340
2870
3180
3510

7600
7400
6750
6150
5500
5350
4850
4500
1050
1130
1350
1660
2060
2220
2460
2720
8650
8400
7750
7100
6350
5950
5350
4900
1210
1370
1670
2020
2480
2770
3110
3510
11100
10750
10050
9200
8250
7800
7000
6500
1510
1640
1960
2380
2910
3220
3560
3940

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

31

10

12.5

8750
8000
7350
6550
6400
6000
5600

9450
8700
7800
7600
7100
6650

10200
9450
8500
8250
7750
7200

1200
1380
1690
2090
2240
2480
2740

1410
1710
2100
2260
2500
2760

1420
1710
2090
2270
2500
2770

9950
9250
8500
7650
7150
6700
6150

10950
10050
9100
8550
8000
7400

11850
10950
9900
9350
8750
8100

1390
1700
2040
2480
2750
3070
3450

1720
2050
2470
2730
3030
3380

1730
2060
2460
2710
3010
3350

12700
11900
10950
9850
9300
8700
8100

13950
12900
11650
11000
10350
9650

15100
13950
12650
11950
11250
10500

1740
2020
2420
2940
3250
3600
3980

2100
2470
2970
3280
3620
4000

2150
2500
2990
3290
3630
4010

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB26KQ

ZB29KQ

ZB38KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

8400
8050
7400
6700
5500

9050
8700
8000
7300
6000
5600

10950
10500
9700
8850
7950
7050
6500

1500
1690
2140
2700
3410

1490
1680
2120
2670
3380
3810

1510
1700
2130
2680
3380
3790
4260

9850
9450
8650
7800
6350

10650
10250
9450
8500
7000
6550

12800
12400
11450
10350
9200
8150
7550

1760
1980
2470
3060
3800

1760
1980
2460
3060
3810
4240

1800
2010
2490
3090
3840
4280
4780

11950
11550
10650
9650
7900

12900
12500
11550
10500
8700
8150

15500
15050
14000
12750
11450
10150
9450

2260
2530
3140
3860
4730

2290
2550
3150
3880
4760
5260

2400
2630
3210
3940
4830
5340
5900

13050
12550
11600
10600
9550
9000
8100
7450
1580
1760
2190
2730
3410
3820
4280
4800
15150
14750
13700
12450
11100
10400
9300
8600
1880
2080
2540
3140
3890
4340
4840
5390
18450
17950
16750
15350
13800
13000
11700
10850
2540
2750
3290
4000
4890
5410
5980
6610

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

32

10

12.5

14950
13800
12650
11400
10750
10050
9300

16300
14950
13500
12700
11900
11050

17700
16200
14650
13850
12950
12050

1830
2260
2780
3460
3860
4310
4820

2280
2800
3460
3850
4300
4790

2260
2770
3430
3820
4260
4750

17350
16250
14850
13300
12450
11600
10700

19150
17600
15800
14850
13850
12800

20750
19150
17250
16200
15150
14000

2160
2610
3190
3930
4380
4880
5440

2660
3220
3950
4390
4890
5450

2680
3220
3950
4380
4880
5440

21200
19850
18250
16450
15500
14550
13550

23300
21500
19450
18400
17250
16100

25150
23250
21100
19950
18750
17500

2920
3400
4070
4940
5460
6040
6680

3530
4150
4990
5510
6090
6730

3610
4190
5020
5530
6100
6740

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB45KQ

ZB48KQ

ZB58KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

14450
13900
12800
11600
9450

15550
15000
13850
12550
10300
9550

18650
18050
16700
15250
13600
11950
11050

2560
2880
3610
4450
5450

2580
2890
3620
4470
5480
6060

2670
2970
3660
4520
5570
6170
6830

15900
15300
14100
12750
10350

17100
16500
15250
13800
11350
10500

20500
19850
18400
16750
14950
13150
12150

2810
3170
3970
4900
5990

2830
3180
3980
4920
6030
6660

2940
3270
4030
4970
6120
6790
7510

18600
17850
16300
14650
11650

20050
19300
17700
15950
12900
11800

24150
23300
21550
19600
17350
15200
13850

3500
3940
4900
6040
7420

3550
3970
4920
6040
7430
8230

3680
4070
4970
6070
7440
8250
9150

22200
21500
20000
18350
16450
15400
13750
12650
2840
3100
3750
4590
5640
6260
6940
7690
24400
23650
22000
20150
18050
16950
15150
13900
3130
3410
4130
5050
6210
6880
7630
8450
28800
27900
25950
23750
21250
19800
17650
16000
3860
4220
5050
6100
7450
8250
9160
10170

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

33

10

12.5

25400
23750
21850
19650
18500
17250
15900

27850
25700
23300
21950
20550
19050

30100
27800
25250
23800
22300
20750

3290
3870
4670
5700
6320
7010
7780

4020
4750
5750
6360
7050
7820

4110
4800
5770
6370
7060
7830

27950
26100
24000
21600
20300
18950
17500

30650
28300
25600
24150
22600
20950

33100
30600
27750
26200
24550
22800

3620
4260
5130
6280
6960
7720
8560

4420
5230
6330
7000
7760
8610

4520
5280
6350
7010
7760
8610

33150
30950
28450
25600
24000
22300
20500

36600
33750
30550
28750
26850
24800

36700
33250
31350
29350
27150

4420
5170
6170
7470
8270
9160
10170

5350
6270
7530
8300
9180
10180

5460
6340
7570
8330
9200
10200

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB66KQ

ZB76KQ

ZB88KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

20450
19800
18400
16850
13800

22150
21450
19950
18300
15150
14150

26850
26000
24200
22250
20050
17800
16550

3890
4360
5380
6590
8070

3940
4400
5420
6630
8120
8990

4080
4530
5530
6730
8220
9090
10070

24500
23750
22150
20250
16500

26550
25700
23950
21900
18100
16800

32200
31150
28950
26550
23850
21100
19500

4810
5250
6360
7820
9680

4870
5310
6410
7860
9710
10800

5040
5460
6530
7950
9790
10870
12070

33400
30200
25400
22150
18000

36250
32900
27800
24200
19700
18350

43650
40050
34350
30050
26350
23100
21150

5380
5930
7210
8790
10780

5450
6000
7270
8850
10840
12020

5680
6190
7420
8980
10970
12160
13480

32300
31300
29150
26800
24200
22850
20600
19100
4250
4680
5660
6840
8310
9180
10150
11240
38700
37350
34650
31800
28700
27000
24300
22450
5250
5640
6670
8060
9860
10930
12120
13440
51200
47400
41350
36550
32300
30100
26750
24200
5970
6450
7610
9130
11090
12270
13590
15070

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

34

10

12.5

37350
34750
32000
28950
27300
25650
23850

41200
37850
34300
32400
30450
28400

44700
41100
37250
35200
33100
30900

4870
5800
6950
8400
9260
10220
11300

5980
7080
8500
9340
10290
11370

6080
7160
8550
9390
10330
11400

44400
41100
37700
34100
32200
30200
28100

48350
44300
40150
37950
35700
33350

52250
47900
43400
41050
38650
36150

5870
6850
8200
9960
11010
12190
13490

7090
8390
10100
11130
12280
13560

7240
8500
10190
11210
12350
13620

54650
48450
43400
38800
36400
33850
30950

55300
50250
45500
43000
40300
37300

58500
53500
48800
46300
43550
40550

6790
7860
9310
11220
12390
13700
15170

8200
9560
11400
12530
13820
15270

8410
9710
11510
12620
13900
15340

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB95KQ

ZB114KQ

15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65
15
20
30
40
50
55
60
65

o
Evaporating Temperature C

-12

-10

-5

30650
29550
26950
23850

33150
31950
29300
26050

40000
38650
35650
32100
28050

47850
46250
42800
38850
34400
32000

5940
6510
8020
9980

6050
6590
8070
10030

6380
6850
8230
10160
12590

6840
7220
8450
10300
12720
14130

36600
35050
32150
28800

39800
38050
34850
31450

49050
46550
42350
38400
33850

60300
56850
51100
46200
41300
38500

7290
7990
9700
11880

7390
8080
9760
11930

7740
8380
9970
12080
14780

8230
8790
10270
12290
14930
16500

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

35

10

12.5

54850
50800
46400
41450
38800
36000
33000

59750
54700
49250
46300
43250
40000

64600
59200
53400
50300
47100
43750

7710
8760
10490
12860
14270
15820
17500

9170
10740
13020
14400
15950
17640

9430
10900
13110
14480
16010
17710

69200
61500
55200
49400
46400
43200
39650

73800
65600
58500
55050
51550
47850

80700
71450
63500
59750
56000
52150

9360
10690
12580
15130
16670
18400
20350

11250
12990
15410
16890
18580
20490

11580
13240
15580
17040
18700
20580

R404A/R507

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

4400
4000
3550
3100
2550

5400
4900
4350
3750
3150
2450
950
1180
1480
1850
2320
2890
6750
6100
5400
4700
3900
3050
1180
1480
1850
2310
2890
3610
8050
7300
6450
5600
4650
3650
1420
1770
2220
2780
3470
4330
9400
8500
7550
6550
5450
4250
1660
2070
2590
3240
4050
5050

6550
5900
5250
4550
3800
3800
950
1190
1490
1860
2320
2320
8150
7350
6550
5650
4750
3700
1190
1490
1860
2320
2900
3610
9750
8800
7800
6800
5650
4450
1430
1780
2230
2790
3480
4330
11400
10300
9150
7900
6600
5200
1660
2080
2600
3250
4060
5060

940
1170
1470
1840
2310
5500
5000
4450
3850
3200
1170
1470
1840
2300
2890
6600
5950
5300
4600
3800
1410
1760
2200
2760
3460
7700
6950
6200
5350
4450
1640
2050
2570
3230
4040

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

36

-5

10

7050
6300
5450
4550
3600

8400
7450
6450
5400
4300

8800
7600
6400
5100

10250
8900
7500
6050

1190
1490
1860
2320
2890

1190
1490
1860
2320
2890

1480
1850
2320
2880

1470
1840
2300
2870

8850
7850
6800
5700
4500

10500
9300
8050
6750
5350

10950
9500
8000
6400

12800
11150
9400
7550

1490
1860
2330
2900
3610

1480
1860
2330
2900
3610

1850
2320
2890
3600

1830
2300
2880
3580

10550
9350
8100
6800
5350

12550
11100
9650
8100
6400

13100
11150
9550
7650

15350
13300
11200
9000

1790
2230
2790
3480
4330

1780
2230
2790
3480
4330

2220
2850
3470
4320

2200
2760
3450
4300

12350
10950
9500
7950
6250

14650
13000
11250
9450
7500

15300
13300
11150
8900

17900
15550
13100
10500

2080
2610
3260
4070
5060

2080
2600
3260
4060
5050

2590
3240
4050
5040

2560
3220
4030
5020

R404A/R507

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1-Phase
Condensing
Temperature
o
C

Model

ZB29KQE

ZB38KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

8600
7800
6900
5900
4800

10550
9550
8500
7350
6050
4600
2110
2500
3000
3630
4420
5370
13200
12100
10750
9150
7500
5800
2630
3090
3720
4520
5510
6670

12800
11600
10350
8950
7400
5750
2160
2530
3030
3660
4440
5400
15800
14600
13050
11250
9250
7150
2750
3160
3770
4560
5560
6740

2070
2460
2970
3610
4390
10900
9900
8700
7350
6000
2550
3040
3680
4480
5440

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

37

-5

10

13950
12450
10750
8950
7000

16650
14800
12850
10700
8450

17500
15150
12700
10050

20500
17800
14900
11850

2580
3060
3680
4470
5430

2640
3110
3720
4490
5450

3160
3760
4520
5470

3240
3820
4560
5500

17400
15650
13550
11200
8750

20450
18500
16150
13450
10550

21650
19000
16000
12600

25050
22150
18750
14950

3270
3840
4620
5600
6800

3430
3950
4690
5660
6860

4100
4790
5730
6920

4300
4940
5840
7010

R404A/R507

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

ZB29KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

4400
3950
3500
2950
2350

5400
4850
4300
3650
3000
2200
930
1200
1530
1940
2470
3140
6700
6050
5350
4650
3900
3000
1140
1420
1780
2220
2780
3470
8050
7250
6450
5600
4650
3600
1360
1700
2130
2670
3340
4160
9350
8450
7500
6500
5400
4200
1590
1990
2490
3120
3900
4860
10600
9600
8500
7400
6150
4750
1770
2220
2770
3470
4340
5420

6550
5900
5250
4500
3700
2800
910
1190
1510
1920
2450
3110
8100
7300
6500
5650
4700
3700
1140
1430
1780
2230
2790
3470
9750
8750
7800
6750
5650
4400
1370
1710
2140
2680
3340
4160
11350
10200
9050
7850
6550
5150
1600
2000
2500
3130
3910
4870
12850
11600
10300
8950
7450
5850
1780
2230
2790
3480
4350
5420

950
1210
1530
1950
2480
5450
4950
4400
3800
3150
1130
1410
1760
2210
2770
6550
5950
5300
4600
3800
1350
1690
2120
2660
3330
7650
6900
6150
5350
4400
1580
1980
2470
3100
3890
8700
7850
7000
6050
5000
1760
2200
2760
3460
4330

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

38

-5

10

7100
6300
5400
4450
3450

8550
7550
6500
5350
4150

8950
7700
6400
5000

10550
9100
7550
5900

1160
1500
1910
2420
3070

1140
1470
1880
2390
3040

1440
1850
2360
3000

1410
1820
2320
2950

8750
7750
6750
5650
4450

10400
9250
8000
6700
5350

10850
9450
7950
6350

12700
11050
9300
7450

1430
1790
2240
2790
3470

1430
1790
2230
2790
3470

1780
2230
2780
3460

1760
2210
2760
3440

10500
9350
8100
6750
5350

12500
11100
9600
8050
6400

13050
11350
9500
7600

15250
13250
11150
8950

1720
2150
2680
3350
4160

1710
2140
2680
3340
4160

2130
2670
3330
4150

2110
2650
3320
4130

12250
10850
9400
7900
6200

14550
12900
11200
9400
7450

15200
13200
11100
8850

17800
15450
13000
10450

2010
2510
3130
3910
4870

2000
2500
3130
3910
4860

2490
3120
3900
4850

2460
3100
3870
4820

13900
12350
10700
8950
7050

16550
14650
12700
10650
8450

17250
15000
12600
10050

20200
17550
14750
11850

2230
2790
3490
4360
5420

2230
2790
3490
4350
5410

2770
3480
4340
5400

2750
3450
4320
5370

R404A/R507

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB38KQE

ZB45KQE

ZB48KQE

ZB58KQE

ZB66KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

10950
9900
8800
7600
6300

13400
12100
10750
9300
7750
6000
2240
2800
3500
4380
5480
6840
15900
14350
12750
11050
9200
7150
2620
3270
4090
5120
6400
7980
17450
15750
14000
12150
10100
7850
2880
3600
4500
5630
7040
8780
20100
18350
16550
14400
11750
8350
3800
4580
5570
6850
8480
10530
23200
21050
18800
16350
13700
10700
4250
5150
6260
7640
9350
11440

16200
14600
13000
11250
9400
7350
2250
2820
3520
4400
5500
6840
19250
17350
15400
13350
11150
8750
2630
3290
4110
5140
6420
7990
21150
19100
16950
14700
12250
9600
2890
3620
4520
5650
7060
8790
24400
22200
19950
17450
14550
10950
3910
4690
5680
6930
8530
10540
28200
25550
22750
19800
16600
13100
4420
5310
6400
7770
9460
11540

2220
2780
3480
4360
5470
13000
11750
10450
9050
7500
2590
3240
4060
5090
6380
14300
12900
11500
9950
8250
2850
3570
4470
5600
7020
16500
15100
13550
11600
9050
3680
4460
5480
6780
8460
18950
17250
15400
13400
11150
4110
5020
6130
7520
9240

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

39

-5

10

17550
15550
13500
11250
8900

20850
18450
16000
13400
10650

21750
18900
15850
12650

25450
22100
18600
14950

2820
3530
4410
5500
6840

2810
3520
4400
5500
6840

3500
4390
5480
6820

3470
4360
5450
6790

20800
18450
16000
13400
10550

24750
21900
19000
15950
12650

25850
22400
18850
15050

30250
26250
22100
17750

3290
4120
5150
6420
7990

3290
4110
5140
6420
7980

4090
5120
6400
7960

4050
5090
6360
7920

22900
20300
17600
14700
11600

27200
24100
20900
17500
13900

28400
24650
20700
16550

33250
28850
24300
19500

3620
4530
5660
7060
8790

3610
4520
5660
7060
8780

4500
5640
7040
8760

4460
5600
7000
8710

26700
23900
20950
17600
13650

31950
28500
24900
21000
16600

33850
29500
24950
19900

40100
34850
29450
23700

4790
5770
7020
8590
10570

4840
5840
7080
8640
10600

5850
7110
8670
10610

5810
7080
8650
10580

30750
27300
23700
19850
15700

36750
32500
28150
23550
18650

38500
33250
27800
22000

45300
39050
32600
25850

5480
6550
7900
9570
11620

5650
6700
8020
9660
11690

6840
8120
9740
11740

6950
8200
9780
11740

R404A/R507

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 3-Phase
Condensing
Temperature
o
C

Model

ZB76KQE

ZB95KQE

ZB114KQE

10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60
10
20
30
40
50
60

o
Evaporating Temperature C

-20

-15

-10

22250
20200
18050
15850
13600

27100
24650
22050
19300
16450
13500
4960
6000
7320
8910
10750
12820
33350
30450
27300
23700
19500

32800
29850
26650
23300
19750
16000
5150
6140
7460
9080
10990
13170
40450
36850
33000
28750
23950
18400
6750
7980
9600
11750
14510
18010
48750
44200
39450
34250
28500
21950
8000
9600
11560
14010
17120
21010

4800
5860
7170
8710
10450
27350
25000
22300
19150

6180
7500
9240
11500

6440
7720
9400
11610
14430

32800
29800
26500
22750

40150
36450
32550
28150
23200

7490
9070
11050
13570

7740
9330
11300
13790
16940

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

40

-5

10

35850
32000
27900
23550
19000

42800
38150
33200
27950
22450

45150
39250
33000
26450

53100
46200
38850
31150

6290
7580
9210
11180
13450

6450
7690
9320
11310
13650

7800
9400
11400
13790

7920
9460
11450
13870

44250
39550
34450
28850
22500

52800
47050
40950
34350
27050

55700
48350
40550
32100

65550
56850
47650
37850

8260
9830
11910
14610
18040

8580
10080
12100
14720
18080

10350
12290
14840
18110

10620
12480
14950
18150

53100
47350
41200
34450
27000

63300
56350
49000
41150
32550

66550
57900
48700
38800

78050
67900
57200
45800

9860
11810
14240
17290
21110

10100
12040
14440
17450
21210

12250
14620
17580
21270

12410
14760
17670
21300

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase
Condensing
Temperature
o
C

Model

ZB15KQE

ZB19KQE

ZB21KQE

ZB26KQE

ZB29KQE

30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

2300
2200
1950

2900
2800
2400
2050

3600
3500
3150
2650
2200

960
960
1200

960
960
1200
1560

960
960
1200
1560
1920

2650
2400
2200

3400
3250
2800
2400

4200
4000
3600
3000
2550

1080
1200
1440

1080
1200
1440
1800

1080
1200
1440
1800
2160

3400
3250
2800

4200
4000
3500
3000

5300
5050
4450
3850
3250

1320
1440
1800

1320
1440
1800
2160

1320
1440
1800
2160
2640

3850
3600
3150

4950
4700
4000
3500

6150
5800
5200
4450
3750

1440
1560
2040

1440
1560
2040
2520

1440
1680
2040
2520
3120

4600
4150
3650

5700
5400
4650
3950

7050
6700
5950
5050
4750

1640
1850
2330

1660
1860
2330
2900

1670
1870
2340
2920
3620

4450
4200
3850
3250
2800
2300
960
1080
1320
1560
1920
2400
5200
4950
4450
3750
3250
2650
1080
1200
1440
1800
2160
2760
6500
6150
5550
4800
4100
3250
1320
1440
1800
2160
2760
3360
7450
7100
6400
5550
4700
3850
1440
1680
2040
2520
3120
3840
8650
8200
7350
6300
5350
4300
1680
1880
2350
2930
3620
4500

5400
5200
4700
4100
3500
2900
960
1080
1320
1560
1920
2400
6250
6000
5400
4700
4000
3250
1080
1200
1440
1800
2280
2760
7800
7450
6750
5900
5050
4200
1320
1440
1800
2280
2760
3360
9150
8650
7800
6850
5900
4800
1440
1680
2040
2520
3120
3840
10450
10000
8950
7850
6650
5450
1690
1900
2360
2930
3640
4510

6500
6250
5650
4950
4200
3600
960
1080
1320
1560
1920
2400
7600
7200
6500
5650
4950
4100
1080
1200
1440
1800
2280
2760
9500
9000
8200
7200
6150
5200
1320
1440
1800
2280
2760
3360
10950
10450
9400
8300
7100
6000
1560
1680
2040
2520
3120
3840
12600
12050
10800
9500
8150
6750
1700
1910
2380
2940
3650
4520

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

41

15

6750
5900
5050
4200

1320
1560
1920
2400

7700
6850
5900
4800

1440
1800
2280
2760

9750
8650
7450
6150

1800
2280
2760
3480

11300
10000
8550
7100

2040
2520
3120
3960

12100
10700
9150
7500

2390
2950
3660
4520

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase
Condensing
Temperature
o
C

Model

ZB38KQE

ZB45KQE

ZB48KQE

ZB58KQE

ZB66KQE

30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

5650
5200
4600

7100
6750
5900
5050

8900
8400
7600
6500
5550

2040
2280
2760

2040
2280
2880
3600

2040
2280
2880
3600
4440

6850
6250
5400

8550
8200
7000
6000

10700
10200
9000
7600
6400

2400
2640
3240

2400
2640
3240
4080

2400
2640
3360
4080
5160

7700
7100
6250

9650
9150
7950
6850

11900
11300
10150
8650
7250

2740
3050
3800

2750
3070
3830
4800

2760
3080
3850
4810
6020

8950
7500
6500

11050
10450
8250
7050

13400
12700
11250
8900
7350

3230
3610
4470

3250
3630
4500
5500

3310
3690
4560
5590
6760

10250
8550
7450

12600
11900
9450
8050

15300
14500
12850
10150
8400

3600
4030
4980

3630
4050
5030
6150

3690
4120
5100
6250
7560

10950
10350
9400
8050
6850
5550
2160
2400
2880
3600
4440
5640
13100
12500
11200
9600
8050
6500
2400
2640
3360
4200
5160
6480
14550
13850
12450
10750
9150
7450
2770
3110
3860
4820
6040
7540
16100
15250
13550
11150
9250
7300
3390
3760
4630
5670
6870
8250
18400
17450
15500
12750
10600
8400
3780
4190
5170
6340
7690
9220

13350
12600
11300
10000
8550
7000
2160
2400
2880
3600
4440
5640
16000
15250
13700
12000
10100
8200
2400
2760
3360
4200
5160
6480
17600
16800
15100
13300
11300
9350
2800
3130
3900
4850
6050
7550
19050
18100
16200
14000
11550
9200
3460
3810
4670
5710
6940
8360
21750
20700
18550
16000
13200
10550
3850
4250
5210
6380
7770
9350

16000
15250
13700
12150
10450
8650
2160
2400
3000
3600
4560
5640
19100
18250
16450
14550
12400
10200
2400
2760
3360
4200
5280
6480
21150
20250
18150
16000
13750
11500
2840
3180
3950
4900
6060
7560
22300
21200
18900
16450
13900
11500
3500
3830
4660
5700
6950
8390
25450
24250
21650
18850
15850
13100
3900
4270
5200
6370
7770
9390

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

42

15

16450
14550
12500
10700

3000
3720
4560
5640

19600
17300
14800
12150

3360
4200
5280
6480

20750
18300
15750
13050

4030
4980
6140
7610

21950
19150
16200
13100

4580
5610
6860
8330

25050
21900
18500
14950

5120
6270
7670
9310

ZB Series

60 Hz

Performance Data
Q=Capacity (Watts) P=Power input (Watts) 1 & 3-Phase

Model

Condensing
Temperature
o
C

ZB76KQE

30
35
45
55
65
75
30
35
45
55
65
75

o
Evaporating Temperature C

-15

-10

-5

10

11750
9800
8500

14450
13650
10800
9200

17600
16650
14700
11650
9650

4220
4730
5840

4250
4750
5890
7190

4340
4830
5960
7290
8820

21100
20000
17750
14550
12100
9600
4440
4920
6040
7390
8960
10740

25000
23750
21250
18300
15100
12050
4520
4980
6090
7450
9040
10880

29200
27800
24800
21550
18150
15000
4560
5000
6080
7430
9040
10930

+ Max return gas temperature of 18.3C in non shaded region


+ Max Suction superheat of 11K only in shaded region
+ Sub cooling 0K

43

15

28700
25050
21200
17150

5970
7300
8930
10840

ZB Series
Technical Data

Model

50Hz

Motor type
60Hz

Displacement (M/HR)

LRA

RLA

Max Continuous Current

Run Capacitor (1 phase)


Run Capacitor (1 phase)

50Hz
60Hz
PFJ
TF5/TW5
50Hz
TFD
PFV
TF5/TW5
60Hz
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQ
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQE
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQ
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQE
TF7/TW7
TFD
PFJ
50Hz
PFV
60Hz
Nominal power(HP)
Crankcase Heater(W)

Connection Tube size(inch)


Discharge Tube outer Diameter
Suction Tube outer Diameter
Dimension(mm)
Length
Width
Height
Mounting pants installation size (hole size)
Oil Recharge(L)
PFJ/PFV
TFD/TF5/TF7
Weight(kg)
Net
Gross

ZB15KQ
ZB15KQE

ZB19KQ
ZB19KQE

ZB21KQ
ZB21KQE

ZB26KQ
ZB26KQE

ZB29KQ
ZB29KQE

ZB38KQ
ZB38KQE

ZB45KQ
ZB45KQE

PFJ
TF5
TFD

PFJ
TF5
TFD

PFJ
TF5
TFD

PFJ
TF5
TFD

PFJ
TF5
TFD

TF5
TFD

TF5
TFD

PFV
TF5
TF7
TFD

PFV
TF5
TF7
TFD

PFV
TF5
TF7
TFD

PFV
TF5
TF7
TFD

PFV
TF5
TF7
TFD

TF5
TF7
TFD

TF5
TF7
TFD

5.9
7.1
58.0
56.0
26.0
61.0
55.0
27.0
27.0
11.4
13.6
8.9
5.0
4.3
13.2
15.7
8.9
5.1
5.0
16.0
19.0
12.5
7.0
6.0
18.5
22.0
12.5
7.2
7.0
40/440
40/370
2
70

6.8
8.2
61.0
70.0
32.0
72.5
63.0
30.0
31.0
12.9
15.0
10.0
5.8
4.3
14.6
17.1
10.0
5.9
5.0
18.0
21.0
14.0
8.1
6.0
20.5
24.0
14.0
8.3
7.0
45/370
45/370
2.5
70

8.6
10.4
82.0
83.0
40.0
95.0
77.0
39.0
39.0
16.4
18.4
11.4
7.5
5.7
15.4
20.7
12.1
7.4
7.4
23.0
25.8
16.0
10.5
8.0
21.5
29.0
17.0
10.3
10.3
60/370
50/370
3
70

9.9
12.0
97.0
95.0
46.0
109.0
88.0
41.0
44.0
17.1
20.4
13.9
7.3
7.1
18.9
23.6
13.2
7.6
6.4
24.0
28.6
19.4
10.2
10.0
26.5
33.0
18.5
10.7
9.0
60/370
60/370
3.5
70

11.4
13.8
114.0
98.0
50.0
137.0
91.0
54.0
50.0
19.3
22.1
16.4
9.3
7.9
20.0
25.0
17.1
9.6
7.9
27.0
31.0
23.0
13.0
11.0
28.0
35.0
24.0
13.5
11.0
60/370
60/440
4
70

14.4
17.3

17.1
20.6

139.0
65.5

172.0
74.0

128.0
64.0
63.0

156.0
70.0
75.0

20.7
10.7
10.0

20.7
10.7
11.5

24.0
12.4
9.6

26.0
12.6
10.1

29.0
15.0
13.5

29.0
15.0
16.1

33.6
17.4
14.0

32.4
17.7
14.2

5
70

6
70

1/2
3/4

1/2
3/4

1/2
3/4

1/2
3/4

1/2
7/8

1/2
7/8

1/2
7/8

242
242
383
190x190(8.5)

242
242
389
190x190(8.5)

243
244
412
190x190(8.5)

243
244
425
190x190(8.5)

242
242
430
190x190(8.5)

242
242
457
190x190(8.5)

242
242
457
190x190(8.5)

1.24
1.24

1.30
1.36

1.45
1.45

1.45/1.48
1.48

1.36
1.36

2.07

1.89

23
26

25
29

27
30

28
31

33
37

38
41

40
44

44

ZB Series
Technical Data

Model

50Hz

Motor type
60Hz

Displacement (M/HR)

LRA

RLA

Max Continuous Current

Run Capacitor (1 phase)


Run Capacitor (1 phase)

50Hz
60Hz
PFJ
TF5/TW5
50Hz
TFD
PFV
TF5/TW5
60Hz
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQ
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQE
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQ
TF7/TW7
TFD
PFJ
PFV
TF5/TW5
KQE
TF7/TW7
TFD
PFJ
50Hz
PFV
60Hz
Nominal power(HP)
Crankcase Heater(W)

Connection Tube size(inch)


Discharge Tube outer Diameter
Suction Tube outer Diameter
Dimension(mm)
Length
Width
Height
Mounting pants installation size (hole size)
Oil Recharge(L)
TFD/TF5/TF7
Weight(kg)
Net
Gross

ZB48KQ
ZB48KQE

ZB58KQ
ZB58KQE

ZB66KQ
ZB66KQE

ZB76KQ
ZB76KQE

ZB88KQ

ZB95KQ

ZB114KQ

TF5
TFD

TF5
TFD

TF5
TFD

TF5
TFD

TF5
TFD

TFD
TW5

TFD
TW5

TF5
TF7
TFD

TF5
TF7
TFD

TF5
TF7
TFD

TF5
TF7
TFD

TF5
TF7
TFD

33.2
40.1

TFD
TW5
TW7
36.4
43.9

TFD
TW5
TW7
43.3
52.3

18.8
22.6

22.1
26.7

25.7
31.0

28.8
34.8

179.0
101.0

203.0
95.0

231.0
111.0

239.0
118.0

273.0
118.0

140.0

174.0

164.0
100.0
100.0

195.0
123.0
95.0

225.0
140.0
114.0

239.0
145.0
125.0

245.0
145.0
125.0

300.0
139.0
150.0

340.0
196.0
179.0

25.0
12.1
12.1

32.1
16.7
16.4

33.6
18.6
17.3

41.4
23.6
20.0

47.1
24.4
22.1

53.6
28.6
25.0

58.6
35.7
27.9

26.0
13.6

32.1
17.1
16.4

33.6
18.6
17.3

41.4
23.6
20.0

61.4
35.0
26.4

65.0
42.9
28.6

35.0
17.0
17.0

45.0
23.4
23.0

47.0
26.0
24.2

54.0
33.1
26.9

75.0
40.0
35.0

82.0
50.0
42.0

36.4
19.1

43.0
24.0
23.0

44.0
29.0
24.5

58.0
33.0
28.0

86.0
49.0
37.0

91.0
60.0
40.0

7
70

8
90

9
90

10
90

12
90

13
90

15
90

3/4
7/8

7/8
1 1/8

7/8
1 3/8

7/8
1 3/8

7/8
1 3/8

7/8
1 3/8

7/8
1 3/8

242
242
457
190x190(8.5)

264
284
477
190x190(8.5)

264
284
546
190x190(8.5)

264
284
546
190x190(8.5)

264
284
546
190x190(8.5)

264
285
552
190x190(8.5)

264
285
553
190x190(8.5)

1.80

2.51

3.25

3.25

3.25

3.30

3.30

40
44

57
60

59
62

62
65

62
65

62
65

63
66

45

66.0
34.2
31.0

ZB Series
Dimensions

Brazing Connection

ZB15~ZB29 (BOM 524)

239.6-245.6
121.3
190.5
4 x 19.00-19.50

95.3

121.3

83.1

115.5

97.3

225.3

190.5

95.3

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

Scale 2:1
49

58.4

Copper Plated Steel


Discharge Fitting Check Valve
12.78-12.95 I.D.
10.00 Min

31

A
B

165.9
D

C
13.1

19.1

236.5

Detail A
Scale 2:1

See Detail A

A3

B3

C3

D3

363.8

338.3

244.5

202.9

ZB21KQ/ZB21KQE

386.4

360.9

264.4

222.8

ZB26KQ/ZB26KQE

400.2

374.6

277.1

235.5

ZB29KQ/ZB29KQE

417.8

389.9

294.1

252.5

Compressor model
ZB15KQ/ZB15KQE
ZB19KQ/ZB19KQE

46

Copper Plated Steel


Suction Fitting
19.12-19.30 I.D.
16.00 Min
0.038 Min
Thick Exterior and
0.038 Min
Thick Interior

ZB Series
Dimensions

Brazing Connection

ZB38~ZB48 (BOM 524)

245.6
122.8
190.5
95.3

245.6

122.8

103.5

190.5

250.4

95.3

17.45 Pin Circle


Models: TFD, TFE,TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

Scale 3:2
44

31

62.2

F: 19.10-19.25 I.D.
16.9 Min
Copper Discharge Fitting/
Steel Check Valve

233.2
12.7

Detail A
Scale 2:1

185.5
233.2 3.0

296.7 3.0

19.1

22.30-22.43 I.D.
19.9 Min
0.06 Min Thick
Interior Copper Plated
Steel Suction Fitting

296.7

E: 12.78-12.90 I.D.
10.1 Min
Copper Plated Steel
Discharge Fitting/
Check Valve

242.3

See Detail A

47

Compressor model

A3

B3

ZB38/45KQ(E)

437.7

409.6

124.7

ZB48KQ(E)

443.4

413.7

128.7

ZB Series
Dimensions

Brazing Connection

ZB58 (BOM 524)

242.5 MAX
95.0

121.3
190.5

47.5

95.3
17.45
Pin Circle

164.0

121.2

47.9
121.3

157.8

95.3

190.5
132.8

30

40

T-Box layout
Standard

142.3

76.6

Section A-A
Scale 1:1

See Detail FOOT

48

Detail FOOT
Scale 1:1

12.6

19.1

201.5

476.3

444.3

232.2

201.5

93.6

28.49~28.67 ID
22.6 Min
0.038 Min. Thick
Exterior and Interior Copper Plated
Steel Suction Fitting
93.6

444.3

22.30~22.42 ID
20.0 Min.
0.038 Min. Thick
Exterior and Interior Copper
Discharge Fitting/
Steel Check Valve

476.3

242.5 MAX

4x 19.00-19.50

ZB Series
Dimensions

Brazing Connection

ZB66~ZB88 (BOM 524)

242.5 MAX
121.3
95.0
190.5

47.5

95.3

47.9

17.45
Pin Circle

121.2

157.8

95.3
121.3

164.0

190.5

133.0

30
76.8

40
142.3

T-Box layout
Standard
Section A-A
Scale 1:1

See Detail FOOT

49

Detail FOOT
Scale 1:1

533.2

501.2

122.1
19.1

242.8

122.1

232.2

12.6

501.2

34.84~35.02 ID
22.6 Min
0.038 Min. Thick
Exterior and Interior Copper Plated
Steel Suction Fitting

242.8

22.30~22.42 ID
20.0 Min.
0.038 Min. Thick
Exterior and Interior Copper
Discharge Fitting/
Steel Check Valve

533.2

242.5 MAX

4x 19.00-19.50

ZB Series
Dimensions

Rotalock Connection

ZB15~ZB29 (BOM 523)

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

237.9-243.9
121.5
190.5

107.2

116.7

227.8

190.5

95.3

95.3

64.4
Scale 2:1

49

31.0
239.0

25.4 Thread
Rotalock Spud
Discharge Fitting

13.1

Detail B
Scale 2:1

19.1

31.75 Thread
Rotalock Spud
Suction Fitting

165.9

Compressor model

A3

D3

ZB15/19KQ(E)

363.8

338.3

244.5

202.9

ZB21KQ(E)

386.4

360.9

264.4

222.8

ZB26KQ(E)

400.8

372.9

277.1

235.5

252.5

ZB29KQ(E)
See Detail B

50

417.8

389.9

294.1

ZB Series
Dimensions

Rotalock Connection

ZB38~ZB48 (BOM 523)

245.6
122.8
190.5
95.3

44

122.8

125.3

115.2

250.4

190.5

245.6

95.3

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

Terminal Box Layout Options


Terminal Box Cover Not Shown
View A-A
Scale 3:2

31
69.2
242.1

31.75 Thread
Rotalock Spud
Suction

296.7 3.0

Compressor model

A3

B3

ZB38/45KQ(E)

437.7

409.6

ZB48KQ(E)

443.4

413.7

185.5
233.2

A
Detail A
Scale 2:1

12.7

19.1

233.21

296.70

25.4 Thread
Rotalock Spud
Discharge

See Detail A

51

ZB Series
Dimensions

Rotalock Connection

ZB58 (BOM 523)

242.5 MAX
95.0

121.3
190.5

47.5

95.3

17.45
Pin Circle

47.9
121.2

159.3

157.8

95.3

124.6

190.5

121.3

30
71.9

40
142.3

T-Box layout
Standard

See Detail FOOT

52

Detail FOOT
Scale 1:1

12.7

93.6

19.1

201.5

232.2

476.3

444.3

93.6

444.3

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 40.6-54.2
Newton-Meters
(360-480 in-Ibs)

201.5

Section A-A
Scale 1:1

(1.25-12) Thread Rotalock Spud


Discharge Check Valve
Torque Range 27.1-40.6 Newton-Meters
Steel Check Valve (240-360 in-Ibs)

476.3

242.5 MAX

4x 19.00-19.50

ZB Series
Dimensions

Rotalock Connection

ZB66~ZB88 (BOM 523)

242.5 MAX
121.3

95.0
190.5
47.5

95.3

47.9
121.2

159.3

157.8

121.3

124.6

95.3

190.5

30
71.9

40
142.3

Section A-A
Scale 1:1
(1.25-12) Thread Rotalock Spud
Discharge Check Valve
Torque Range 27.1-40.6 Newton-Meters
(240-360 in-Ibs)

See Detail FOOT

53

Detail FOOT
Scale 1:1

12.7

19.1

122.1

242.8

533.2

501.2

232.2

242.8

122.1

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 40.6-54.2
Newton-Meters
(360-480 in-Ibs)

501.2

533.2

242.5 MAX

4x 19.00-19.50

ZB Series
Dimensions

Brazing & Sight Glass

ZB15~ZB29 (BOM 558)

242.1-248.1
239.6-245.6
121.3
190.5
4 x 19.00-19.50

49

121.3

97.3

83.1

225.3
115.5

89

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

190.5

95.3

95.3

Scale 2:1

58.4
31

236.5

13.1

Copper Plated Steel


Suction Fitting
19.12-19.30 I.D.
16.00 Min
0.038 Min
Thick Exterior and
0.038 Min
Thick Interior

Detail A
Scale 2:1

165.9

19.1

Copper Plated Steel


Discharge Fitting Check Valve
12.78-12.95 I.D.
10.00 Min

A3

B3

C3

D3

E3

363.8

338.3

244.5

202.9

69.6

ZB21KQ/ZB21KQE

386.4

360.9

264.4

222.8

64.9

ZB26KQ/ZB26KQE

400.2

372.9

277.1

235.5

77.6

ZB29KQ/ZB29KQE

417.8

389.9

294.1

252.5

67.4

Compressor model
E

ZB15KQ/ZB15KQE
ZB19KQ/ZB19KQE

See Detail A

Sight Glass/Socket Plug


Per Bill of Material

54

ZB Series
Dimensions

Brazing & Sight Glass

ZB38~ZB48 (BOM 558)

253.3-259.3
245.6
122.8
190.5
95.3

245.6

122.8

103.5

190.5

250.4

95.3

17.45 Pin Circle


Models: TFD, TFE,TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

Scale 3:2
31

233.2

Detail A
Scale 2:1

185.5
233.2 3.0

Sight Glass
C

296.7 3.0

22.30-22.43 I.D.
19.9 Min
0.06 Min Thick
Interior Copper Plated
Steel Suction Fitting

12.7

E: 12.78-12.90 I.D.
10.1 Min
Copper Plated Steel
Discharge Fitting/
Check Valve

296.7

62.2
242.3

F:19.10-19.25 I.D.
16.9 Min
Copper Discharge Fitting/
Steel Check Valve

132

19.1

44

See Detail A

55

Compressor model

A3

B3

C3

ZB38KQ/ZB38KQE

437.7

409.6

91.3

124.7

ZB45KQ/ZB45KQE

437.7

409.6

77.2

124.7

ZB48KQ/ZB48KQE

443.4

413.7

77.2

128.7

ZB Series
Dimensions

Brazing, Sight Glass & Oil Schrader Valve

ZB58 (BOM 550)

95.0

17.45
Pin Circle

47.5
242.5 MAX
121.3
190.5
95.3

121.2
164.0

121.3

157.8

95.3

190.5
132.8

30

30

40

76.6

142.3

Sight glass Layout


T-box Removed

T-Box layout
Standard

Detail FOOT
Scale 1:1

74.3

201.5

93.6

232.24

67.6

See Detail FOOT


See Detail VALVE

Detail VALVE
Scale 3:4

56

476.3

444.3

201.5

12.7

19.1

444.3

28.49~28.67 ID
22.6 Min
0.06 Min Thick Exterior
and 0.038 Min Thick
Interior Copper Plated Steel
Suction Fitting

93.6

22.30~22.42 ID
20.0 Min Copper
Discharge Fitting/Steel
Check Valve

74.3

Section A-A
Scale 1:1

476.3

242.5 MAX

47.9

160.0

ZB Series
Dimensions

Brazing, Sight Glass & Oil Schrader Valve

ZB66~ZB88 (BOM 550)


17.45
Pin Circle

95.0
242.5 MAX

47.5

121.3
190.5
160.0

121.2
157.8

121.3

164.0

95.3

190.5
132.8

30

30

40

Sight glass Layout


T-box Removed

142.3

76.6

T-Box layout
Standard

12.7
82.1

See Detail FOOT

Detail FOOT
Scale 1:1

242.8

122.1

92.3

232.24

19.1

501.2

See Detail VALVE

Detail VALVE
Scale 3:4

57

533.2

501.2

242.8

34.84~35.02 ID
22.6 Min
0.06 Min Thick Exterior
and 0.038 Min Thick
Interior Copper Plated Steel
Suction Fitting

122.1

22.30~22.42 ID
20.0 Min Copper
Discharge Fitting/Steel
Check Valve

92.3

Section A-A
Scale 1:1

533.2

242.5 MAX

47.9

95.3

ZB Series
Dimensions

Brazing, Sight Glass & Oil Schrader Valve

ZB95~ZB114 TFD (BOM 550)

242.5 MAX

95.0

121.3

17.45
Pin Circle

47.5
190.5
160.0

47.9
157.8

121.3

164.0

95.3

121.2

190.5

40

30

Sightglass Layout
T-Box Removed

140.5

Spacer-Mounting Assm
Per Bill of Material

12.7

33.3

519.6

34.84-35.02 ID
22.6 Min
0.06 Min Thick Exterior
And 0.038 Min Thick
Interior Copper Plated Steel
Suction Fitting

261.2

Detail FOOT
Scale 1:1

140.5

92.6

234.0

See Detail VALVE

85.5

See Detail FOOT

Detail VALVE
Scale 3:4

58

551.6

22.30-22.42 ID
20.0 Min Copper
Discharge Fitting/Steel
Check Valve

519.6

T-Box Layout
Standard
Section A-A
Scale 1:1

261.2

142.3

92.6

132.8

30
76.6

551.6

242.5 MAX

95.3

ZB Series
Dimensions

Brazing, Sight Glass & Oil Schrader Valve

ZB95~ZB114 TW7/TW5 (BOM 550)

242.5 MAX
121.3
190.5

164.0
40

34.84~35.02 ID
22.6 Min
0.038 Min. Thick Exterior
and Interior Copper Plated
Steel Suction Fitting

Detail FOOT
Scale 1:1

See Detail FOOT


See Detail VALVE

Detail VALVE
Scale 3:4

59

92.6

85.5

182.0

140.5

519.5

551.5

22.30~22.42 ID
20.0 Min.
0.038 Min. Thick Exterior
and Interior Copper Plated
Discharge Fitting/
Steel Check Valve

12.6

Terminal Box layout Standard


Scale 3:4

207.4

33.3

133.0

30
76.8

173.8

121.3
95.3

190.5

242.5 MAX

95.3

ZB Series
Dimensions

Rotalock & Sight Glass

ZB15~ZB29 (BOM 559)

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

242.1-248.1
237.9-243.9
121.5
190.5

107.2

116.7

227.8

190.5

95.3

95.3

40

64.4
49

31.0
239.0

Scale 2:1

25.4 Thread
Rotalock Spud
Discharge Fitting

See Detail B

Sight Glass/Socket Plug


Per Bill of Material

60

D
13.1

19.1

165.9

31.75 Thread
Rotalock Spud
Suction Fitting

Detail B
Scale 2:1

ZB Series
Dimensions

Rotalock & Sight Glass

ZB38~ZB48 (BOM 559)

253.3-259.3
245.6
122.8
190.5
95.3

132

44

122.8

125.3

115.2

250.4

190.5

245.6

95.3

17.45 Pin Circle


Models: TFD, TFE, TFM, TF7
13.46 Pin Circle
Models: PFJ, PFV, TFW, TF5, PFZ

31

Terminal Box Layout Options


Terminal Box Cover Not Shown

69.2

View A-A
Scale 3:2

242.1

233.21

296.70

31.75 Thread
Rotalock Spud
Suction

Sight Glass
Per Bill of Material

See Detail A

61

12.7

19.1

233.2

185.5

296.7 3.0

25.4 Thread
Rotalock Spud
Discharge

Detail A
Scale 2:1

ZB Series
Dimensions

Rotalock, Sight Glass & Oil Schrader Valve

ZB58 (BOM 551)

95.0
47.5

17.45
Pin Circle

242.5 MAX
121.3
190.5
160.0

121.2
157.8

121.3

159.3

95.3

190.5
124.6

242.5 MAX

47.9

95.3

30
71.9

30

40

Sight glass Layout


T-box Removed

142.3

T-Box layout
Standard

444.3

232.2
74.3
67.6

201.5
See Detail FOOT
See Detail VALVE

Detail VALVE
Scale 3:4

62

476.3

444.3

74.3
12.7

19.1

Detail FOOT
Scale 1:1

93.6

476.3

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 40.6-54.2
Newton-Meters
(360-480 in-Ibs)

93.6

(1.25-12) Thread Rotalock Spud/


Discharge Check Valve
Torque Range 27.1-40.6 Newton-Meters
(240-360 in-Ibs)

201.5

Section A-A
Scale 1:1

ZB Series
Dimensions

Rotalock, Sight Glass & Oil Schrader Valve

ZB66~ZB88 (BOM 551)

95.0

190.5

47.9

121.2

242.5 MAX
121.3

160.0

157.8

159.3

121.3

124.6

95.3

190.5

95.3

242.5 MAX

17.45
Pin Circle

47.5

30
71.9

30

40

Sight glass Layout


T-box Removed

142.3

T-Box layout
Standard

232.2

92.3
82.1

See Detail FOOT


See Detail VALVE

Detail VALVE
Scale 3:4

63

533.2

501.2

242.8

12.7

19.1

Detail FOOT
Scale 1:1

242.8

122.1

501.2

533.2

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 40.6-54.2
Newton-Meters
(360-480 in-Ibs)

122.1

(1.25-12) Thread Rotalock Spud/


Discharge Check Valve
Torque Range 27.1-40.6 Newton-Meters
(240-360 in-Ibs)

92.3

Section A-A
Scale 1:1

ZB Series
Dimensions

Rotalock, Sight Glass & Oil Schrader Valve

ZB95~ZB114 TFD (BOM 551)


95.0

242.5 MAX
47.5

121.3

17.45
Pin Circle

47.9

160.0

159.3

121.3

95.3

157.8

190.5
124.6

242.5 MAX

95.3

121.2

190.5

30
71.9

40

30

Sightglass Layout
T-Box Removed

142.3

T-Box Layout
Standard
Section A-A
Scale 1:1

234.0

140.5

261.2

Detail FOOT
Scale 1:1
92.6

See Detail VALVE

85.5

See Detail FOOT

Detail VALVE
Scale 3:4

64

551.6

519.6

92.6

33.3

140.5

Spacer-Mounting Assm
Per Bill of Material

12.7

519.6

551.6

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 170-180
Newton-Meters
(1500-1590 in-Ibs)

261.2

(1.25-12) Thread Rotalock Spud


Discharge Check Valve
Torque Range 100-110 Newton-Meters
(885-975 in-Ibs)

ZB Series
Dimensions

Rotalock, Sight Glass & Oil Schrader Valve

ZB95~ZB114 TW7/TW5 (BOM 551)

242.5 MAX
121.3
190.5

164.0
30
76.8

173.5

121.3
95.3

190.5
133.0

242.5 MAX

95.3

40
204.7

Terminal Box Layout Standard


Scale 3:4

12.7

Spacer-Mounting Assm
Per Bill of Material

33.3

(1.75-12) Thread Rotalock Spud


Suction Fitting
Torque Range 40.6-54.2
Newton-Meters
(360-480 in-Ibs)

519.5

Detail FOOT
Scale 1:1

See Detail FOOT

85.5

92.6

182.0

140.5

551.5

(1.25-12) Thread Rotalock Spud


Discharge Check Valve
Torque Range 27.1-40.6 Newton-Meters
(240-360 in-Ibs)

See Detail VALVE

Detail VALVE
Scale 3:4

65

ZB Series
Electrical Wiring Diagram
ZB15~ZB114

Q1
L1
N
PE
F6

F1
K1
L1 N

To Control Circuit
C2

Single Phase Circuit (ZB15-ZB29)


Electrical Schematics
L1/N/PE: Single Phase Lines (line/neutral/ground)
Q1: Manual Switch
F1/F6: Fuse
K1: Compressor Contactor
C2: Run Capacitor
M: Compressor Motor
R/C/S: Compressor Terminal

M
1

Q1
L1
L2
L3
N
PE
F1

3 Phase (ZB15-ZB114)
(with Motor Protection Code F)
Electrical Schematics
L1/L2/L3/N/PE: 3 Phase Lines (line/neutral/ground)
Q1: Manual Switch
F1/F6..8: Fuse
K1: Compressor Contactor
M: Compressor Motor
L1/L2/L3: Compressor Terminal

F6...8

L1

To Control Circuit

K1
L1

L2

L3
M

66

ZB Series
Electrical Wiring Diagram
ZB15~ZB114 Control Circuit
220/230 V Alternating Current

Traditional Solid-state Timer (optional)

Fuse
A
Attention:
If you use timer,do
not connect A&B

Exhaust-pipe
Thermostat
(Optional)

B
Thermostat

Compressor Connector
C
CDU Fan connector
(optional)

Other protection
device
(optional)

C1

Crankcase heater

L1
L1
L2

L2
T2 T1 S2

L3

3 Phase (ZB95-114 TW*)


(with Motor Protection Code W)

S1 M2 M1

L3

Protector
Module
Voltage

Motor Winding Connection

L1

L2

T1

T2

M1

M2

S1

S2

Discharge
Pressure
Switch

Suction
Pressure
Switch

OMB Oil
Level Control

(Reference Table 4)
Discharge Line
Thermostat

Compressor
Conatctor
Coil

White

Black

Red

S1
S2

Motor Overload Protector

To Control
Circuit

(To Motor Overload Sensors)

(To Compressor Terminal Block)

67

(To 24VAC Supply)

Contact us at:
Emerson Climate Technologies,
Asia Pacific Headquarters
10/F, Pioneer Building,
213 Wai Yip Street,
Kwun Tong, Kowloon, Hong Kong.
Tel: (852) 2866 3108
Fax: (852) 2520 6227

India - PUNE
Emerson Climate Technologies (India) Ltd
Plot No. 23, Rajiv Gandhi Infotech Park,
Phase - II, Hinjewadi,
Pune 411 057, Maharashtra,India
Tel: (91-20) 2553 4988
Fax: (91-20) 2553 6350

Australia
Emerson Climate Technologies Australia Pty Ltd
Unit R7, 391 Park Road
Regents Park, NSW 2143, Australia
Tel: (61-2) 9795 2800
Fax: (61-2) 9738 1699

India - Mumbai
Emerson Climate Technologies (India) Ltd
Unit No. 4,5,6 & 7, Bhaveshwar Arcade
LBS Marg, Opp. Shreyas Cinema
Ghatkopar (West)
Mumbai 400 086, Maharashtra, India
Tel: (91-22) 2500 6630/ 2500 6632
Fax: (91-22) 2500 6570

China - Shanghai
c/o Emerson Climate Technologies (Suzhou) Co. Ltd
Shanghai Sales Office
11th Floor, Innov Tower,
1801 Hong Mei Road,
XuJiaHui District
Shanghai 200233, P. R. China
Tel: (86-21) 3395 0000
Fax: (86-21) 3367 8100
China - Beijing
c/o Emerson Climate Technologies (Suzhou) Co. Ltd
Beijing Sales Office
Room 310, Canway Building
66 Nan Lishi Road, Xicheng District
Beijing 100045, China
Tel: (86-10) 6805 7825
Fax: (86-10) 6805 6301
China - Guangzhou
c/o Emerson Climate Technologies (Suzhou) Co. Ltd
Guangzhou Sales Office
Room 508-509, R&F Yinglong Plaza
No. 76 Huangpu Road West,
Guangzhou 510623, PRC.
Tel: (86-20) 2886 7668
Fax: (86-20) 2886 7622
China - Suzhou
c/o Emerson Climate Technologies (Suzhou) Co. Ltd
Suzhou Plant
No. 69 Suhong West Road ,
Suzhou Industrial Park , Suzhou ,
Jiangsu Province , P.R.C. 215021 China.
Tel: (86-512) 6257 5505
Fax: (86-512) 6257 5506

Taiwan
c/o Emerson Electric (Taiwan) Co. Ltd
5th Floor, No.2 Jen Ai Road
Section 4, Taipei 10650, Taiwan
Tel: (886-2) 2325 9555
Fax: (886-2) 2702 9630/ 2784 0022

Indonesia
PT. Emerson Indonesia
Wisma Kota BNI 46 16th floor Suite 16.01
Jl. Jend.Sudirman Kav.1.Jakarta 10220
Tel: (62)21-2513003 ext.6000
Fax: (62)21-2510622

Thailand - Rayong Plant


c/o Emerson Electric (Thailand) Ltd
No. 24 Moo 4 Tambol Pluakdaeng, Amphur
Pluakdaeng, Rayong 21140, Thailand
Tel: (66-38) 957 000
Fax: (66-38) 954 251

Japan
c/o Emerson Japan Ltd
Shin-yokohama Tosho Building No. 3
3-9-5 Shin-Yokohama, Kohoku-ku
Yokohama 222-0033 Japan
Tel: (81-45)475 6371
Fax: (81-45)475 3565

Thailand - Bangkok
c/o Emerson Electric (Thailand) Ltd
34th Floor Nation Tower
1858/133 Bangna Trad
Bangkok 10260 , Thailand
Tel: (66-2) 716-4700
Fax: (66-2) 751-4240

South Korea
c/o Emerson Electric (South Korea) Ltd
12F, Narae B/D, 719-1, Yeoksam-dong
Gangnam-gu, Seoul, South Korea 135-080
Tel: (82-2) 3483-1500
Fax: (82-2) 592-7883 / 592-7886
Malaysia
c/o Emerson Electric (Malaysia) Sdn. Bhd.
Level M2, Blk A, Menara PKNS-PJ
Jalan Yong Shook Lin
46050 Petaling Jaya, Selangor, Malaysia
Tel: (60-3) 7949 9222
Fax: (60-3) 7949 9333

aprefrigeration@emersonclimate.com
September 2009

Philippines
Emerson Climate Technologies
Global Service Centre - Manila
4th floor, San Miguel Properties Center (SMPC),
No. 7, St. Francis Avenue., Mandaluyong City
Philippines
Trunkline: (63-2) 4795-100/4795-200/4795-300
Tel: (63-2) 702 1579
Fax: (63-2) 479 5271