Sei sulla pagina 1di 7

C-BUS TEcHNOLOGY | INPUT UNiTS

Outdoor Motion Sensor, 110 Degrees


The C-Bus Outdoor Occupancy Sensors are surface mount, input units used to detect movement by sensing natural thermal radiation emitted from any moving body. When movement is detected, the unit issues commands over the C-Bus network to control C-Bus output devices. In addition, the unit features a light level sensor to automatically switch lighting on, under low light conditions. The sensor has a detection field that covers an area up to 18 metres from the unit, with a field of view of 110 degrees. Advanced microprocessor circuit technology and a flat multi-segmented lens, divide the field of view into 28 zones located at four different levels. This ensures immediate reaction of body movement and reduces the number of dead zones that can be penetrated. The sensor features learn mode, which permits the unit to be programmed without the need for a PC connected to the system. The sensor features an environmental rating of IP66 and is suitable for outdoor applications.
T E C HN I C A L I N F O R M A T I ON Catalogue Number 5750WPL E5750WPL Base, Mounting Centres 84mm 60.3mm C-Bus Supply Voltage 15-36VDC @ 18mA Programmable, 1 sec - 18 hrs Timer Range Timer Resolution 1 sec Light Threshold Adjustment User adjustable, 1 Lux to full sunlight Mounting Height 2.4m nominal, (2.0 to 3.2m) 110 degrees Field of View Detection Area 18m radius x 110 degrees Lens Type Frensel, multi-segmented Maximum Number of Units on 100 a Single C-Bus Network Status Indicator Walk test LED Warm Up Time 5 seconds Fly lead x 2 C-Bus Termination IP Rating IP66 Operating Temperature Range 0C to 45C
138 58 74 20 38

5750WPL PRODUC T FEATURES Programmable by learn mode or using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable walk test LED for commissioning. User adjustable light level threshold, from low light (1 Lux) to full sunlight. Dual element detectors to minimise false triggering. Optical bandpass filter minimises unwanted heat sources from triggering the circuitry. C-Tick (Australia/New Zealand), CE (European Community) compliant.

InFRASCAN

111

5750WPL illustrated

48

CataLOGUe NUmber E5750WPL 5750WPL

DeScriptiON Occupancy Sensor, Infared, IP66, 110 Degrees (British Standard) Occupancy Sensor, Infared, IP66, 110 Degrees (Australian/US Standard)

C-BUS TecHNOLOGY | INPUT UNiTS

Indoor Motion Sensor, 90 Degrees


The C-Bus Indoor Occupancy Sensors are surface mount, input units used to detect movement by sensing natural thermal radiation emitted from any moving body. When movement is detected, the unit issues commands over the C-Bus network to control C-Bus output devices. In addition, the unit features a light level sensor to automatically switch lighting on, under low light conditions. The sensor has a detection field that covers an area up to 8.5 metres from the unit, with a field of view of 90 degrees. The unit features a lens less design with 12 overlapping zones forming a continuous detection field. Therefore resulting in uniform sensitivity across the whole of the detection field, with no dead zones. This features allows the sensor to be ceiling or wall mounted. The sensor features learn mode, which permits the unit to be programmed without the need for a PC connected to the system. The sensor features an environmental rating of IP44 and is suitable for indoor applications. The sensor is designed for surface mount applications, and located in the corner of the room where detection is required.
T E C HN I C A L I N F O R M A T I ON Catalogue Number Base, Mounting Centres C-Bus Supply Voltage Timer Range Timer Resolution Light Threshold Adjustment Mounting Height Field of View Detection Area Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time IP Rating C-Bus Termination Operating Temperature Range Operating Humidity Range 5751L 84mm E5751L 60.3mm E5751L

15-36VDC @ 18mA Programmable, 1 sec - 18 hrs 1 sec User adjustable, 1 Lux to full sunlight 2.4m nominal, (2.0 to 3.2m) 90 degrees 6m x 6m 100 Walk test LED 5 seconds IP44 Fly lead x 2 0C to 45C 0 - 95% RH, non-condensing

PRODUC T FEATURES Programmable by learn mode or using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable walk test LED for commissioning. User adjustable light level threshold, from low light (1 Lux) to full sunlight. Dual element detectors to minimise false triggering. Optical bandpass filter minimises unwanted heat sources from triggering the circuitry. C-Tick (Australia/New Zealand), CE (European Community) compliant.

VIEW

+ 108

+ 18 70
90 Field of View R48

E5751L illustrated

CataLOGUe NUmber E5751L 5751L 751MB

DeScriptiON Occupancy Sensor, Infrared, 90 Degrees (British Standard) with Mounting Base Occupancy Sensor, Infrared, 90 Degrees (Australian/US Standard) Mounting Base for 5751L Sensor

49

C-BUS TEcHNOLOGY | INPUT UNiTS

Indoor Motion Sensor, 360 Degrees


The C-Bus Indoor Occupancy Sensors are flush mount, input units used to detect movement by sensing natural thermal radiation emitted from any moving body. When movement is detected, the unit issues commands over the C-Bus network to control C-Bus output devices. In addition, the unit features a light level sensor to automatically switch lighting on, under low light conditions. The sensor has a detection field that covers an elliptical area up to 12m x 14m, with a field of view of 360 degrees. The unit features a multi-segmented Fresnel lens design, for superior detection capability. The sensor features learn mode, which permits the unit to be programmed without the need for a PC connected to the system. The sensor features an environmental rating of IP44 and is suitable for indoor applications. The sensor is compact in size, and is designed for flush mount applications, located at the centre of the detection area.
T E C HN I C A L I N F O R M A T I ON Catalogue Number C-Bus Supply Voltage Timer Range Timer Resolution Light Threshold Adjustment Mounting Height Field of View Detection Area Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time IP Rating C-Bus Termination Operating Temperature Range Operating Humidity Range 5753L 5753L 15-36VDC @ 18mA Programmable, 1 sec - 18 hrs 1 sec User adjustable, 1 Lux to full sunlight 2.4m nominal, (2.0 to 3.2m) 360 degrees 12m x 14m 100 Walk test LED 5 seconds IP44 Screw terminals 0C to 45C 0 - 95% RH, non-condensing PRODUC T FEATURES Programmable by learn mode or using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable walk test LED for commissioning. User adjustable light level threshold, from low light (1 Lux) to full sunlight. Dual element detectors to minimise false triggering. Optical bandpass filter minimises unwanted heat sources from triggering the circuitry. Designed for flush mount applications, protrudes only 8mm. C-Tick (Australia/New Zealand), CE (European Community), FCC (United States) compliant.

72

36

Warranty Void If Removed

47

50

15

MOD. STATE 1 2 3 4 5 6

Unit Address Group Addresses


R

103 88

Network

50

CataLOGUe NUmber 5753L

1036318

DeScriptiON Occupancy Sensor, Infrared, Flash Mount, 360 Degrees

C-BUS TecHNOLOGY | INPUT UNiTS

Indoor Multi-Sensor, 360 Degrees


The C-Bus Indoor Occupancy Sensors are surface mount, input units used to detect movement by sensing natural thermal radiation emitted from any moving body. When movement is detected, the unit issues commands over the C-Bus network to control C-Bus output devices. In addition, the unit features a light level sensor to automatically switch lighting on, under low light conditions. The sensor has a detection field that covers an area up to 8.5 metres from the unit, with a field of view of 90 degrees. The unit features a lens less design with 12 overlapping zones forming a continuous detection field. Therefore resulting in uniform sensitivity across the whole of the detection field, with no dead zones. This features allows the sensor to be ceiling or wall mounted. The sensor features learn mode, which permits the unit to be programmed without the need for a PC connected to the system. The sensor features an environmental rating of IP44 and is suitable for indoor applications. The sensor is designed for surface mount applications, and located in the corner of the room where detection is required.
T E C HN I C A L I N F O R M A T I ON Catalogue Number C-Bus Supply Voltage Timer Range Timer Resolution Light Threshold Adjustment Light Regulation Mounting Height Field of View Detection Area IR Receiver Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time IP Rating C-Bus Termination Operating Temperature Range Operating Humidity Range 5753PEIRL 15-36VDC @ 18mA Programmable, 1 sec - 18 hrs 1 sec Programmable, 1 Lux to full sunlight 40 - 3000 Lux 2.4m nominal, (2.0 to 3.2m) 360 degrees Programmable, up to 12m x 8.5m Remote enabled/disable control 100 Walk test and IR receive LED 5 seconds IP44 Screw terminals 0C to 45C 0 - 95% RH, non-condensing 5753PEIRL PRODUC T FEATURES Programmable by learn mode or using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable walk test LED for commissioning. User adjustable light level threshold, from low light (1 Lux) to full sunlight. Dual element detectors to minimise false triggering. Optical bandpass filter minimises unwanted heat sources from triggering the circuitry. C-Tick (Australia/New Zealand), CE (European Community) compliant.

72

36

Warranty Void If Removed

47

50

15

MOD. STATE 1 2 3 4 5 6

Unit Address Group Addresses


R

103 88

Network

CataLOGUe NUmber 5753PEIRL

1036318

DeScriptiON Combination Sensor, Motion with Light Level Sensor and IR Receiver, Flush Mount, 360 Degrees

51

C-BUS TEcHNOLOGY | INPUT UNiTS

Clock Modules
The C-Bus Clock Modules are surface mount, input units used to provide basic timing functions and convenient control of C-Bus output units. The clock modules are 7-day timers, featuring 42 program storage locations for event programming. Events may be programmed up to 6 days in advance and event durations may be up to 99 days. Whereas, the clock modules are powered from the two wire C-Bus connection, they feature a rechargeable power storage that maintains the clock for up to 24 hours, in the event of loss of the C-Bus power supply. The clock modules also feature a daylight saving option and random check generator from 5 to 60 minutes.
T E C HN I C A L I N F O R M A T I ON C-Bus Supply Voltage Timer Number of Channels Memory Locations Accuracy Timer Resolution Running Reserve Reserve Charge Time Daylight Saving Mode Random Event Generator Display Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time C-Bus Termination Standard Colours Operating Temperature Range Operating Humidity Range
87 sq. 23

E5031/2TC7, WE 15-36VDC @ 18mA 7 day 2 42 2.5 sec/day @ 20C 1 minute 24 hours (without C-Bus power) 2 minutes Yes 5 to 60 minutes Iconic LCD display, grey scale 100 Programmable 5 seconds Screw terminals WE, SG, DS, CM, BR and BK 0C to 45C 0 - 95% RH, non-condensing
23

5031V2TC7, WE PRODUC T FEATURES Programmable using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Reserve power backup in case of loss of C-Bus supply. C-Tick (Australia/New Zealand), CE (European Community) compliant.

67 116 72

E5031/2TC7 illustrated
52

5031V2TC7 illustrated
48 76

CataLOGUe NUmber DeScriptiON Australian/US Standard 5031H2TC7 2 Channel Clock, 7 Days, Horizontal Mount 5031V2TC7 2 Channel Clock, 7 Days, Vertical Mount Colour Selection: (WE) White, (SG) Soft Grey, (DS) Desert Sand, (CM) Cream, (BR) Brown, (BK) Black British Standard E5031/2TC7 2 Channel Clock, 7 Days, Horizontal Mount Colour Selection: (WE) White, (BK) Black

52

C-BUS TEcHNOLOGY | INPUT UNiTS

Temperature Sensors
The C-Bus Temperature Sensors are surface mount, input units used to measure ambient temperature and control either cooling mode or heating mode, but not both simultaneously. The sensor has a range of 0 to 50 degrees Centigrade, with programmable target temperature and margin. In addition, the unit features an economy mode where the target temperature is stepped back. This feature is used to save energy when the room is unoccupied. The temperature sensor is used in conjunction with C-Bus, interlocked relays to control HVAC equipment.
T E C H N I C A L I N F O R M A T I ON C-Bus Supply Voltage Accuracy Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time C-Bus Termination Standard Colours Operating Temperature Range Operating Humidity Range
87 sq. 36

15-36VDC @ 18mA +/- 1C 100 Programmable 5 seconds Screw terminals WE, SG, DS, CM, BR and BK 0C to 50C 0 - 95% RH, non-condensing
76 36

E5031RDTSL WE

5031RDTSL WE
67 116 72

E5031TS illustrated 5031TS illustrated

P R O D U C T F E A T U R ES Programmable using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable Target Temperature and Margin. Programmable heating or cooling mode. C-Tick (Australia/New Zealand), CE (European Community) compliant.

52

48

CATALOGUE NUMBER DESCRIPTION Australian/US Standard 5031RDTSL WE Remote Digital Temperature Senor-EN Colour Selection: (WE) White, (SG) Soft Grey, (DS) Desert Sand, (CM) Cream, (BR) Brown, (BK) Black British Standard E5031RDTSL WE Remote Digital Temperature Senor Colour Selection: (WE) White, (BK) Black

53

C-BUS TEcHNOLOGY | INPUT UNiTS

Light Level Sensors


The C-Bus Light Level Sensors are surface mount input units used to measure ambient light levels and regulate lighting loads. The sensor has a field of view of 180 degrees, and is capable of measuring lighting levels in the range of 20 to 3000 Lux and regulating lighting in the range of 40 to 1600 Lux, which is suitable for most commercial applications. The light level sensor may be used in conjunction with non-dimmable ballasts to bank switch luminaires or with dimmable electronic ballasts to regulate lighting levels continuously, within a programmed target range. The unit features built in lag, to prevent rapid changes in output, due to changes in environmental conditions, such as cloud cover or rapid movement through the detection area.
T E C HN I C A L I N F O R M A T I ON C-Bus Supply Voltage Light Level (measure) Light Level (regulate) Time Constant Mounting Height Field of View Maximum Number of Units on a Single C-Bus Network Status Indicator Warm Up Time C-Bus Termination Standard Colours Operating Temperature Range Operating Humidity Range
87 sq. 23

E5031PE, WE 15-36VDC @ 18mA 20 - 3000 Lux 40 - 1600 Lux Approx. 90 seconds 2.4m nominal, (2.0 to 3.2m) 180 degrees 100 Programmable 5 seconds Screw terminals WE, SG, DS, CM, BR and BK 0C to 45C 0 - 95% RH, non-condensing
23

5031PE, WE PRODUC T FEATURES Programmable using the C-Bus Toolkit Software. Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power. Programmable Target Light Level and Margin. Bank switching or light level regulation. C-Tick (Australia/New Zealand), CE (European Community) compliant.

67

116

72

E5031PE illustrated
52

5031PE illustrated
48 76

CATALOGUE NUMBER DESCRIPTION Australian/US Standard 5031PE Light Level Sensor, 40-1600 Lux Colour Selection: (WE) White, (SG) Soft Grey, (DS) Desert Sand, (CM) Cream, (BR) Brown, (BK) Black British Standard E5031PE Light Level Sensor, 40-1600 Lux Colour Selection: (WE) White, (BK) Black IP66 Weatherproof Series E5031PEWP Light Level Sensor, 40-1600 Lux, IP56