OUTDOOR SOLID CORE POST INSULATORS

BIL 1800 - 2100 kV BIL 1050 - 1300 kV BIL 450 - 650 kV BIL 125 - 170 kV

BIL 2250 - 2550 kV BIL 1425 - 1675 kV BIL 750 - 950 kV BIL 200 - 325 kV

ANKARA SERAMIK A.S.


www.ankaraseramik.com

BIL 60 - 95 kV

Outdoor Solid Core Post Insulators About us ANKARA SERAMK A.


Ankara Seramik A.S established in 1996 is one of the largest porcelain insulator companies in Turkey. Ankara Seramik is the most progressive porcelain insulator manufacturing company in Turkey because of new and innovative production flow systems and manufacturing concepts integrated with Ankara Seramik A.S ISO 9001:2000 Quality programs. Our quality policy is to design and manufacture quality products at competitive prices with decreased lead times to exceed the needs and expectations of our customers.Today, Ankara Seramik with a built up area of 20.500 m2 (10.250 m2 closed plant facilities) has a wide range of insulators produced at low, medium and high voltage levels.We are able to carry out the routine tests in line with the international and national standards.At the time, Ankara Seramik believes in retaining a strong domestic market while serving global (international) markets.

ANKARA SERAMIK A.S.

Page 1

www.ankaraseramik.com

Outdoor Solid Core Post Insulators


ANKARA SERAMIK A.S.

Index

Iso 9001 IEC Index


>> Page >> Page >> Page >> Page >> Page >> Page >> Page >> Page >> Page >> Page >> Page >> Page 2 - 10 > Design 10 - 12 > Product 13 14 15 16 > Advantages > Type Bil 60 - 95 kV > Type Bil 125 - 170 kV > Type Bil 200 - 325 kV

17 - 18 > Type Bil 450 - 650 kV 19 - 20 > Type Bil 750 - 950 kV 21 - 22 > Type Bil 1050 - 1300 kV 23 - 24 > Type Bil 1425 - 1675 kV 25 - 26 > Type Bil 1800 - 2100 kV 27 - 28 > Type Bil 2250- 2550 kV

Page 2

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Design


Introduction

ANKARA SERAMIK A.S.

According to IEC60273, an IEC post insulator is defined by the following designation: Post insulators are designed to comply with the demands of the level of electrical insulation and mechanical strength, while also taking into account the environmental situation where the insulators are intended for service.To specify the correct standard outdoor porcelain solid core post insulator, the following characteristics have to be defined :

IEC post insulator Type C10-1050-II

means outdoor post insulator with external metal fittings means a minimum bending failing load of 10 kN means a lightning impulse withstand voltage, dry of 1050 kV means creepage distance class II (in reference to IEC60273)

10 > Lightning impulse withstand voltage, dry > Switching impulse withstand voltage, wet (when a switching impulse level is required) > Power frequency withstand voltage, wet > Mechanical failing load > Minimum nominal creepage distance > Fixing arrangement of top and bottom metal fitting > Color of glaze

1050

II

According to IEC60273, an IEC operating rod can be defined by the following designation:

Standarts
Ankara Sramik A.S. Insulators manufactures outdoor porcelain solid core post insulators with external metal fittings and outdoor operating rods with external metal fittings (for High Voltage Switchgears) according to standard IEC60273. Components according to other standards or special customer requirements can be supplied upon request.

IEC operating rod Type T3-1050-II

means outdoor operating rod with external metal fittings means a minimum failing load torsion 3 kNm

1050 means a lightning impulse withstand voltage, dry of 1050 kV II means creepage distance class II (in reference to IEC60273)

These designations do not always fully specify the insulator type; sometimes there are alternative constructions regarding the fixing arrangement and creepage distance included in the standards

Page 3

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Electrical Design

The insulation performance of a post insulator column is a function of the height, creepage distance, arcing distance of the insulating part(s) as well as the number of insulator units for a defined height and follows the standards IEC60071 and IEC60273.

Nominal system voltage Un


kV (r.m.s.)
3 6 10 15 20 30 45 66 110 132 150 220

Max . system voltage Um


kV (r.m.s.)
3,6 7.2 12 17.5 24 36 52 72 .5 123 145 170 245

One minute withstand voltage wet 50 cs


kV (r.m.s.)
10 20 28 38 50 70 95 140 185 - 230 185 - 230 -325 230 - 275 - 325
275 - 325 - 360 -395 -460

Lightning impulse withstand voltage 1,2/50 s


kV (peak value)
20 - 40 40 - 60 60 - 75 - 95 75 - 95 95 - 125 - 145 145 - 170 250 325 450 - 550 450 - 550 -650 550 - 650 -750
650 -750 - 850 - 950 - 1050

Nominal system voltage Un


kV (r.m.s.)

Max. system voltage Um


kV (r.m.s.)

Switching impulse with stand voltage 250/2500


kV (peak value)

Lightning impulse withstand voltage 1,2/50 s


kV (peak value)

275 330 380

300 362 420

750 850 850 950 850 950 1050 850 950 1050 1300 1425 1550

480

525 (550)

700

765 (800)

850 950 1050 950 1050 1175 1050 1175 1300 1425 1175 1300 1425 1550 1675 1800 1950 2100

Page 4

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Design

ANKARA SERAMIK A.S.

RIV
The RIV performance of single post insulator styles will be tested in accordance with the standard IEC60437 upon request. If corona rings are necessary to reach a certain RIV level for a single insulator column, the appropriate ones will be offered with the insulator column.

Mechanical Design
In-service stresses on post insulators are mainly due to bending loads (e.g., weight, wind force, seismic conditions, short circuit loads). A few applications require compression strength (e.g., capacitors banks) or torsion strength (e.g., rotating disconnectors) or tensile strength (e.g., underhung post insulator).

The high strength C130 porcelain body allows for a reduction in the number of components on insulators comprised of multiple units. The advantages provided by the reduction of additional fittings include increased arcing distance/creep and less assembly time. All insulators up to and including the C20-1050 are available in a one-unit design.

Page 5

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Pollution Levels and Creepage Distances

Note : Creepage distances and max. nominal diameters of sheds can be designed according to pollution levels and customer requirement.
In standard IEC60273, creepage distances are standardized for post insulators in class I and II,which is not in accordance with the general recommendations of the guide IEC60815 Guide for the selection of insulators in respect to environmental conditions. In IEC60815 the basic pollutionlevels are defined qualitatively with examples of typical environmental situations. The corresponding minimum nominal creepage distance is given in mm/kV.

Level
1

Pollution
Light

Specific Creepage Distance


16 mm/kV

> Areas without industry and with low housing density


equipped with heating plants.

> Areas with low density of industry or houses but subjected


to frequent winds and/or rainfall.

> Agricultural areas. > Mountainous areas.


Level
2

Pollution
Medium

Specific Creepage Distance


20 mm/kV

Regular sheds
Dm = (De + Dc) / 2

> Industrial areas not producing particulate polluting smoke


and/or with average housing density equipped with heating plants. > Areas with high density of houses and/or industry but subjected to frequent winds and/or rainfall. > Areas exposed to wind from the sea but not too close to the coast (at least several kilometers distant).

Level
3

Pollution
Heavy

Specific Creepage Distance


25 mm/kV

> Areas with high density of industries and suburbs of large


cities with high density of heating plants producing pollution.

> Areas close to the sea in any case exposed to relatively


strong winds from the sea.

Alternating sheds
Dm= (De1 + De2 + (2*Dc) )/4

Level
4

Pollution
Very Heavy

Specific Creepage Distance


31 mm/kV

> Areas generally of moderate extent, subjected to conductive


dusts and to industrial smoke producing particularly thick conductive deposits. > Areas generally of moderate extent, very close to the coast and exposed to sea-spray or to very strong and polluting winds from the sea. > Desert areas, characterized by no rain for long periods, exposed to strong winds carrying sand and salt, and subjected to regular condensation.

The creepage distance shouldbe increased in relation to the average diameter, Dm . Dm< 300 mm D m 300-500 mm Dm> 500 mm

kd =1.0 kd =1.1 kd =1.2

De Dc De1 De

Shed diameter Core diameter Greater shed diameter Smaller shed diameter

Page 5

Page 6

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Design

ANKARA SERAMIK A.S.

d1

d2

Page 7 5

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Pollution Levels and Creepage Distances

Alternating Shed

Plain Shed

Standart (Traditonal) Shed

Page 5

Page 8

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Design


K-Value Increased Pollution Performance Equalized Field Distribution
K-value design is a method to improve traditional creepage distance. In its full extent, K-value design is a method to reduce weight, volume and space while improving properties in-service by increasing pollution performance and equalizing the electrical field.
K-value is the unit for insulator shape and IEC 60507 defines the formula as form factor:

ANKARA SERAMIK A.S.

l is the creepage distance p(l) is the circumference of the insulator as a function of l.

Form factor used as a design method is referred to as K-value and can be used for different types of improvements. Creepage distance considers a leakage current as traveling along the insulator, in a strict line, identifying only distance. K-value considers a leakage current as traveling along the insulator,over its complete surface. It calculates reduced diameter and/or increased creepage distance for higher resistance against the leakage currents. K-value identifies an insulators total shape, i.e., geometric (ohmic) resistance against leakage currents. The shape of the insulator must be calculated for optimum design of pollution performance. The traditional calculation of creepage distance is sometimes sufficient, but to achieve best performance in relation to material and space used, K-value design is necessary.

ANKARA SERAMK A.. Insulators offers complete computer design of K-value, integrated with electrical, mechanical, dimension and material calculations.

Page 9 5

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Design

Insulating Material
The insulator body of the unit is made from high quality aluminium oxide porcelain, C130 or C120, which conforms to standard IEC60672. Glazing provides a dirt repellent surface. Glazing is normally brown in colour, though Blue grey can also be provided upon request. Semi-conductive surface glazing can be provided for special polluted environments.

Fittings
Fittings are made in malleable cast iron according to standard En1562 or spheroidal graphite cast iron according to standard En1563. All fittings are hot dip galvanized according to standard EN ISO 1461 with a zinc weight of min. 600 g/m2 (min. 85 m) as average value. The following table shows the standard dimensions for fittings according to IEC60273.

Pitch circle diameter p.c.d. d1 mm

Depth of the tabbed blind holes h2 mm

Number Of Holes n -

Bolt holes tapped d2 -

Bolt holes plain d2 mm

Nominal maximum diameter of mounting face d3 mm

76 127 178 200 225 254 275 300 325 356 375

12 18 (22)

4 4 4 4 4 8 8 8 8 8 8

M12 M16 -

18 18 18 18 18 18 18 18 18

115 165 225 245 270 300 320 345 370 400 420

Fittings with other dimensions (e.g., for operation rod columns) can be supplied on request. Threads are generally tapped after hot dip galvanizing; for shipment and storage, the threads will be protected by a protective layer and/or special plastic plugs.
NOTE: Multiple unit insulator columns will be delivered with hardware (bolts, nuts and spring washers) for the interconnection of the insulator units.

Page 5

Page 10

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Production Cementing

ANKARA SERAMIK A.S.

The fittings are assembled to the porcelain body with a special cement mortar as standard. The cement 's basic material is calcium aluminate which has a stronger strength.The properties of this cement are setting in a short time , useful at cold weather conditions and strong strength.

Page 11 5

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Production

Page 12

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Advantages


Advantages
of porcelain solid core post insulators with external fittings

ANKARA SERAMIK A.S.

> puncture proof


The theoretical puncture path through the porcelain body is almost equal to the dry arcing distance. Since porcelain has several times the dielectric breakdown strength of air, flashover, if any, always occurs in the air outside the porcelain body.

> insulator body made of aluminium oxide porcelain > high mechanical strength > free of internal stresses > no measurable aging > resistant to salt pollution > high resistance to temperature variations > high resistance to vandalism > electrically and mechanically stressed zones are separated > low surface leakage current resulting in reduced transmission losses > the creepage distance is made from sheds and core parts which have > good self-cleaning properties with respect
to the climatic conditions

Ankara Seramik A..

Production and Product Tables


Insulators production facilities for IEC station post insulators manufacture in full accordance to IEC60273. Operating rod columns for disconnectors are manufactured corresponding to the relevant post insulators. Insulation requirements are available in

ratings from BIL 60kV to 2550kV. This catalogue includes standard IEC solid core station post insulators with external metal fittings. Insulator creepage distances are in accordance with IEC60273 and IEC608 1 5. Special requirements, such as other creepage distances, special shed forms, other top bending moments or pitch circle diameters, can also be offered upon request

>

better insulation performance under pollution conditions

> routine test load =70% of the minimum failing load > can be checked ultrasonically for mechanical soundness > lowest maintenance costs > minimum total life cycle costs by high reliability > packaging in crates offers the maximum protection during shipping and storage

Page 13

www.ankaraseramik.com

ANKARA SERAMIK A.S.


Porcelain Tolerance Fittings

Outdoor Solid Core Post Insulators TYPE BIL 60 - 95 kV


C130 (or C120) according to IEC60672-3 Brown glazed according to IEC60168 malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461 Calcium aluminate cement
TYPE PRODUCT NO
C4-60 381103 C6-60 382103 C8-60 383103 C10-60 384103

Cementing
IEC POST INSULATOR DESIGNATION

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 190 1 175 76/4x M12 76/4x M12 1901 175 76/4x M12 76/4x M12 1901 185 76/4x M12 76/4x M12 190 1 185 76/4x M12 76/4x M12

d2

BIL 60 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

4 0.38 0.76 0.6

6 0.57 1.14 0.6

8 0.76 1.52 0.8

10 0.95 1.9 1

60 20

60 20
C6-75 382101

60 20
C8-75 383101

60 20
C10-75 384101

TYPE PRODUCT NO

C4-75 381101

Dimensions Dimensions Height H [mm] Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern

215 1 180 76/4x M12 76/4x M12

215 1 180 76/4x M12 76/4x M12

215 1 190 76/4x M12 76/4x M12

215 1 190 76/4x M12 76/4x M12

BIL 75 kV

Mechanical Values Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

4 0.43 0.86 0.6

6 0.65 1.29 0.6

8 0.86 1.72 0.8

10 1.08 2.15 1

d1

75 28
C4-95 381201 C6-95 382201

75 28
C8-95 383201

75 28
C10-95 384201

75 28
C12.5-95 385201

TYPE PRODUCT NO

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 255 1 190 76/4x M12 76/4x M12 255 1 190 76/4x M12 76/4x M12 255 1 190 76/4x M12 76/4x M12 255 1 210 76/4x M12 76/4x M12 255 1 210 76/4x M12 76/4x M12

BIL 95 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.] 95 38 95 38 95 38 95 38 95 38 4 0.51 1.02 0.8 6 0.77 1.53 0.8 8 1.02 2.04 1.2 10 1.28 2.55 1.2 12.5 1.6 3.19 1.8

d3

TYPE BIL 60 Page 5- 95 kV

Page 14

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 125 - 170 kV


Porcelain C1 30 (or C1 20) according to IEC60672-3 Brown glazed according to IEC601 68

ANKARA SERAMIK A.S.

Tolerance Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvized according to ENISO 1461

Cementing
IEC POST INSULATOR DESIGNATION

Calcium aluminate cement


TYPE PRODUCT NO
C4-125 381301 C6-125 382301 C8-125 383301 C10-125 384301 C12.5-125 385301

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

BIL 125 kV

305 1 195 76/4x M12 76/4x M12

305 1 195 76/4x M12 76/4x M12

305 1 195 76/4x M12 76/4x M12

305 1 230 76/4x M12 76/4x M12

305 1 230 76/4x M12 76/4x M12

4 0.61 1.22 0.8

6 0.92 1.83 0.8

8 1.22 2.44 1.2

10 1.53 3.05 1.2

12.5 1.91 3.82 2

125 50
C4-150 381501

125 50
C6-150 382501

125 50
C8-150 383501

125 50
C10-150 384501

125 50
C12.5-150 385501

TYPE PRODUCT NO

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

BIL 150 kV

355 1 195 76/4x M12 76/4x M12

355 1 195 76/4x M12 76/4x M12

355 1 195 76/4x M12 76/4x M12

355 1 235 76/4x M12 76/4x M12

355 1 235 76/4x M12 76/4x M12

4 0.71 1.42

6 1.07 2.13 1.2

8 1.42 2.84 1.5

10 1.78 3.55 1.8

12.5 2.22 4.44 2.5

150 50
C4-170

150 50
C6-170

150 50
C8-170

150 50
C10-170

150 50
C12.5-170

TYPE PRODUCT NO

381401

382401

383401

384401

385401

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.] 170 70 170 70 170 70 170 70 170 70 4 0.89 1.78 1.2 6 1.34 2.67 1.5 8 1.78 3.56 2 10 2.23 4.45 2.5 12.5 2.79 5.57 3 445 1 205 76/4x M12 76/4x M12 445 1 205 76/4x M12 76/4x M12 445 1 205 76/4x M12 76/4x M12 445 1 245 76/4x M12 76/4x M12 445 1 245 127/4x M16 127/4x M16

BIL 170 kV

Page 15

Type BIL 125 - 170 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.


Porcelain

Outdoor Solid Core Post Insulators TYPE BIL 200 - 325 kV


C1 30 (or C1 20) according to IEC60672-3 Brown glazed according to IEC601 68 malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN 1563, hot dip galvanized according to ENISO1461 Calcium aluminate cement
TYPE PRODUCT NO
C4-200 711001 C6-200 712001 C8-200 713001 C10-200 714001 C12.5-200 715001

Tolerance Fittings

Cementing
IEC POST INSULATOR DESIGNATION
Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.] 200 70 200 70 4 0.95 1.9 1.2 6 1.43 2.85 1.8 475 1 210 76/4x M12 76/4x M12 475 1 210 76/4x M12 76/4x M12

BIL 200 kV

475 1 210 76/4x M12 76/4x M12

475 1 245 76/4x M12 76/4x M12

475 1 245 127/4x M16 127/4x M16

8 1.9 3.8 2

10 2.38 4.75 2.5

12.5 2.97 5.94 3

200 70

200 70

200 70

IEC POST INSULATOR DESIGNATION


Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern

TYPE PRODUCT NO

C4-250 711002

C6-250 712002

C8-250 713002

C10-250 714002

C12.5-250 715002

BIL 250 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Power frequency withstand voltage, wet [kV r.m.s.]

560 1 215 76/4x M12 127/4x M16 76/4x M12 127/4x M16

560 1 215 76/4x M12 127/4x M16 76/4x M12 127/4x M16

560 1 215 127/4x M16 127/4x M16

560 1 255 127/4x M16 127/4x M16

560 1 255 127/4x M16 127/4x M16

4 1.12 2.24 1.8

6 1.68 3.36 2

8 2.24 4.48 2.5

10 2.8 5.6 3

12.5 3.5 7 4

250 95

250 95

250 95

250 95

250 95

IEC POST INSULATOR DESIGNATION


Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]

TYPE PRODUCT NO

C4-325 711003

C6-325 712003

C8-325 713003

C10-325 714003

C12.5-325 715003

C16-325 716014

C20-325 717012

BIL 325 kV

770 1 225 127/4x M16 127 /4x M16

770 1 225 127 /4x M16 127 /4x M16

770 1 260 127 /4x M16 127 /4x M16

770 1 270 127 /4x M16 127 /4x M16

770 1 270 127 /4x M16 127 /4x M16

770 1 300 127 /4x M16 225/4x18

770 1 300 127 /4x M16 254/8x18

4 1.54 3.08 2

6 2.31 4.62 2.5

8 3.08 6.16 3

10 3.85 7.7 4

12.5 4.82 9.63 4

16 6.16 12.32 5

20 7.7 15.4 6

325 140

325 140

325 140

325 140

325 140

325 140

325 140

TYPE BIL 200 Page 5 - 325 kV

Page 16

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 450- 650 kV

ANKARA SERAMIK A.S.

IEC POST INSULATOR DESIGNATION

TYPE PRODUCT NO

C4-450 711004

C6-450 712004

C8-450 713004

C10-450 714004

C12.5-450 715004

C16-450 716001

C20-450 717001

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 1020 1 235 127 /4x M16 127 /4x M16 178/4x18 1020 1 260 127 /4x M16 127 /4x M16 178/4x18 1020 1 260 127 /4x M16 127 /4x M16 200/4x18 1020 1 290 127 /4x M16 127 /4x M16 225/4x18 1020 1 300 127 /4x M16 225/4x18 1020 1 300 127 /4x M16 254/8x18 1020 1 300 127 /4x M16 254/8x18

BIL 450 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR IEC POST INSULATOR DESIGNATION

4 2.04 4.08 2.5

6 3.06 6.12 3.5

8 4.08 8.16 4

10 5.1 10.2 4

12.5 6.38 12.75 6

16 8.16 16.32 6

20 10.2 20.4 6

450 185
C4-550 711005

450 185
C6-550 712005

450 185
C8-550 713004

450 185
C10-550 714004

450 185
C12.5-550 715005

450 185
C16-550 716001

450 185
C20-550 717002

TYPE PRODUCT NO

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 1220 1 300 127 /4x M16 127 /4x M16 178/4x18 1220 1 300 127 /4x M16 127 /4x M16 200/4x18 1220 1 300 127 /4x M16 127 /4x M16 200/4x18 1220 1 350 127 /4x M16 127 /4x M16 225/4x18 1220 1 350 127 /4x M16 254/8x18 1220 1 350 127 /4x M16 254/8x18 1220 1 350 127 /4x M16 275/8x18

BIL 550 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]
IEC IEC POST POST INSULATOR INSULATOR DESIGNATION

4 2.44 4.88 3

6 3.66 7.32 4

8 4.88 9.76 4

10 6.1 12.2 4

12.5 7.63 15.25 6

16 9.76 19.52 6

20 12.2 24.4 6

550 230
C4-650 711006

550 230
C6-650 712006

550 230
C8-650 713006

550 230
C10-650 714006

550 230
C12.5-650 715006

550 230
C16-650 716003

550 230
C20-650 717003

TYPE PRODUCT NO

Dimensions
Height H [mm] Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 1500 2.5 350 127 /4x M16 127 /4x M16 200/4x18 1500 2.5 350 127 /4x M16 127 /4x M16 200/4x18 1500 2.5 350 127 /4x M16 225/4x18 127 /4x M16 225/4x18 1500 2.5 400 127 /4x M16 225/4x18 254/8x18 1500 2.5 400 127 /4x M16 225/4x18 254/8x18 1500 2.5 400 225/4x18 275/8x18 1500 2.5 420 225/4x18 300/8x18

BIL 650 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.] 650 275 650 275 650 275 650 275 650 275 650 275 650 275 4 3 6 3 6 4.5 9 3 8 6 12 4 10 7.5 15 4 12.5 9.33 18.75 6 16 12 24 6 20 15 30 6

Page 17

Type BIL 450 - 650 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators TYPE BIL 450 - 650 kV


d2

Porcelain

C1 30 (or C1 20) according to IEC60672-3, Brown glazed according to IEC601 68 malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Tolerance Fittings

Cementing

Calcium aluminate cement

TYPE BIL 450 Page 5 - 650 kV

Page 18

www.ankaraseramik.com

Outdoor Solid Core Solid Post Core Insulators Post Insulators Type BIL 750- 950 kV
IEC POST INSULATOR DESIGNATION

ANKARA SERAMIK A.S.

TYPE PRODUCT NO

C4-750 711007

C6-750 712007

C8-750 713007

C10-750 714007

C12.5-750 715007

C16-750 716004

C20-750 717004

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 1700 2.5 350 127 /4x M16 127 /4x M16 200/4x18 1700 2.5 350 127 /4x M16 225/4x18 127 /4x M16 225/4x18 1700 2.5 350 127 /4x M16 225/4x18 127 /4x M16 225/4x18 1700 2.5 400 127 /4x M16 225/4x18 254/8x18 1700 2.5 400 127 /4x M16 225/4x18 254/8x18 1700 2.5 400 225 /4x 18 254/8x18 275/8x18 1700 2.5 420 225 /4x18 254/8x18 300/8x18

BIL 750 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

4 1.36 6.8 3

6 2.04 10.2 3

8 2.72 13.6 4

10 3.4 17 4

12.5 4.25 21.25 6

16 5.44 27.2 6

20 6.8 34 6

750 325

750 325
C6-850 712008

750 325
C8-850 713008

750 325
C10-850 714008

750 325
C12.5-850 715008

750 325
C16-850 C16-850 716005

750 325
C20-850 C20-850 717005

TYPE PRODUCT NO

C4-850 711008

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 1900 3.5 400 127/4x M16 200/4x18 1900 3.5 400 127/4x M16 225/4x18 225/4x18 1900 3.5 400 127/4x M16 225/4x18 254/8x18 1900 3.5 400 127/4x M16 225/4x18 254/8x18 1900 3.5 400 127/4x M16 254/8x18 225/4x18 254/8x18 1900 3.5 400 225/4x18 254/8x18 275/8x18 1900 3.5 420 225/4x18 254/8x18 300/8x18

BIL 850 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR IEC POST INSULATOR DESIGNATION DESIGNATION

4 1.52 7.6 3

6 2.28 11.4 3

8 3.04 15.2 4

10 3.8 19 4

12.5 4.75 23.75 6

16 6.08 30.4 6

20 7.6 38 6

850 360

850 360
C6-950 712009

850 360
C8-950 713009

850 360
C10-950 714009

850 360
C12.5-950 715009

850 360
C16-950 716006

850 360
C20-950 717006

TYPE PRODUCT NO

C4-950 711009

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 2100 3.5 450 127/4x M16 200/4x18 2100 3.5 450 127/4x M16 225/4x18 225/4x18 2100 3.5 450 127/4x M16 225/4x18 254/8x18 2100 3.5 450 127/4x M16 225/4x18 254/8x18 2100 3.5 450 127/4x M16 225/4x18 254/8x18 275/8x18 2100 3.5 450 225/4x18 254/8x18 300/8x18 2100 3.5 450 225/4x18 254/8x18 325/8x18

BIL 950 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.] 950 750 395 950 750 395 950 750 395 950 750 395 950 750 395 950 750 395 950 750 395 4 1.68 8.4 3 6 2.52 12.6 3 8 3.36 16.8 4 10 4.2 21 4 12.5 5.25 26.25 6 16 6.72 33.6 6 20 8.4 42 6

Page 19

Type BIL 750 - 950 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Type BIL 750- 950 kV

Porcelain

C1 30 (or C1 20) according to IEC60672-3, Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement

TYPE BIL 750 Page 5 - 950 kV

Page 20

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 1050- 1300 kV


IEC POST INSULATOR DESIGNATION

ANKARA SERAMIK A.S.

TYPE PRODUCT NO

C4-1050 711010

C6-1050 712010

C8-1050 713010

C10-1050 714010

C12.5-1050 715010

C16-1050 716007

C20-1050 717007

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 2300 3.5 450 127 /4x M16 200/4x18 2300 3.5 450 127 /4x M16 225/4x18 225/4x18 2300 3.5 450 127 /4x M16 225/4x18 254/8x18 2300 3.5 450 127 /4x M16 225/4x18 275/8x18 2300 3.5 450 127 /4x M16 225/4x18 254/8x18 275/8x18 2300 3.5 450 225/4x18 254/8x18 300/8x18 2300 3.5 450 225/4x18 254/8x18 325/8x18

BIL 1050 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

4 1.84 9.2 3

6 2.76 13.8 3

8 3.68 18.4 4

10 4.6 23 4

12.5 5.75 28.75 6

16 7.36 36.8 6

20 9.2 46 6

1050 750 460


C4-1175 711011

1050 750 460


C6-1175 712011

1050 750 460


C8-1175 713011

1050 750 460


C10-1175 714011

1050 750 460


C12.5-1175 715011

1050 750 460


C16-1175 716008

1050 750 460


C20-1175 717008

TYPE PRODUCT NO

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 2650 4.5 450 127/4x M16 225/4x18 225/4x18 2650 4.5 450 127 /4x M16 225/4x18 254/8x18 2650 4.5 450 127 /4x M16 225/4x18 254/8x18 2650 4.5 450 127 /4x M16 225/4x18 275/8x18 2650 4.5 450 127 /4x M16 225/4x18 254/8x18 300/8x18 2650 4.5 450 225/4x18 254/8x18 325/8x18 2650 4.5 450 225/4x18 254/8x18 356/8x18

BIL 1175 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 2.12 10.6 3

6 3.18 15.9 3

8 4.24 21.2 4

10 5.3 26.5 4

12.5 6.63 33.13 6

16 8.48 42.4 6

20 10.6 53 6

1175 850
C4-1300 711012

1175 850
C6-1300 712012

1175 850
C8-1300 713012

1175 850
C10-1300 714012

1175 850
C12.5-1300 715012

1175 850
C16-1300 716009

1175 850
C20-1300 717009

TYPE PRODUCT NO

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 29004.5 450 127/4x M16 225/4x18 225/4x18 29004.5 450 127 /4x M16 225/4x18 254/8x18 29004.5 450 127 /4x M16 225/4x18 275/8x18 29004.5 450 127 /4x M16 225/4x18 275/8x18 29004.5 450 127 /4x M16 225/4x18 254/8x18 300/8x18 29004.5 450 225/4x18 254/8x18 325/8x18 29004.5 450 225/4x18 254/8x18 356/8x18

BIL 1300 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] 1300 950 1300 950 1300 950 1300 950 1300 950 1300 950 1300 950 4 2.32 11.6 3 6 3.48 17.4 3 8 4.64 23.2 4 10 5.8 29 4 12.5 7.25 36.25 6 16 9.28 46.4 6 20 11.6 58 6

Page 21

Type BIL 1050 - 1300 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Type BIL 1050 - 1300 kV

Porcelain

C1 30 (or C1 20) according to IEC60672-3, Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement

TYPE BIL 1050 Page 5 - 1300 kV

Page 22

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 1425 - 1675 kV


TYPE PRODUCT NO
C4-1425 711013 C6-1425 712013 C8-1425 713013 C10-1425 714013 C12.5-1425 715013

ANKARA SERAMIK A.S.

IEC POST INSULATOR DESIGNATION

C16-1425 716010

C20-1425 717010

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 3150 4.5 450 127/4x M16 225/4x18 225/4x18 3150 4.5 450 127 /4x M16 225/4x18 254/8x18 3150 4.5 450 127 /4x M16 225/4x18 275/8x18 3150 4.5 450 127 /4x M16 225/4x18 300/8x18 3150 4.5 450 127 /4x M16 225/4x18 254/8x18 325/8x18 3150 4.5 450 225/4x18 254/8x18 356/8x18 3150 4.5 450 225/4x18 254/8x18 356/8x18

BIL 1425 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 2.52 12.6 3

6 3.78 18.9 3

8 5.04 25.2 4

10 6.3 31.5 4

12.5 7.88 39.38 6

16 10.08 50.4 6

20 12.6 63 6

1425 950
C4-1550 711014

1425 950
C6-1550 712014

1425 950
C8-1550 713014

1425 950
C10-1550 714014

1425 950
C12.5-1550 715014

1425 950
C16-1550 716011

1425 950
C20-1550 717011

TYPE PRODUCT NO

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 3350 4.5 450 127/4x M16 225/4x18 225/4x18 3350 4.5 450 127 /4x M16 225/4x18 254/8x18 3350 4.5 450 127 /4x M16 225/4x18 275/8x18 3350 4.5 450 127 /4x M16 225/4x18 300/8x18 3350 4.5 450 127 /4x M16 225/4x18 254/8x18 325/8x18 3350 4.5 450 225/4x18 254/8x18 356/8x18 3350 4.5 450 225/4x18 254/8x18 356/8x18

BIL 1550 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 2.68 13.4 3

6 4.02 20.1 3

8 5.36 26.8 4

10 6.7 33.5 4

12.5 8.38 41.88 6

16 10.72 53.6 6

20 13.4 67 6

1550 1050

1550 1050
C4-1675

1550 1050
C6-1675

1550 1050
C8-1675

1550 1050
C10-1675 714015

1550 1050
C12.5-1675 715015

1550 1050
C16-1675 716012

TYPE PRODUCT NO

711015

712015

713015

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 3650 5.5 450 127 /4x M16 225/4x18 254/8x18 3650 5.5 450 127 /4x M16 225/4x18 275/8x18 3650 5.5 450 127 /4x M16 225/4x18 300/8x18 3650 5.5 450 127 /4x M16 225/4x18 300/8x18 3650 5.5 450 225/4x18 254/8x18 325/8x18 3650 5.5 450 225/4x18 254/8x18 356/8x18

BIL 1675 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] 1675 1050 1675 1050 1675 1050 1675 1050 1675 1050 1675 1050 4 2.92 14.6 3 6 4.38 21.9 3 8 5.84 29.2 4 10 7.3 36.5 4 12.5 9.13 45.63 6 16 11.68 58.4 6

Page 23

Type BIL 1425 - 1625 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Type BIL 1425 - 1675 kV


C1 30 (or C1 20) according to IEC60672-3, Brown glazed

Porcelain

Tolerance

according to IEC60 1 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement

TYPE BIL1425 Page 5 - 1675kV

Page 24

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 1800 - 2100 kV


IEC POST INSULATOR DESIGNATION

ANKARA SERAMIK A.S.

TYPE PRODUCT NO

C4-1800 711016

C6-1800 712016

C8-1800 713016

C10-1800 714016

C12.5-1800 715016

C16-1800 716013

Dimensions
Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 4000 5.5 450 225/4x18 254/8x18 254/8x18 4000 5.5 450 225/4x18 254/8x18 275/8x18 4000 5.5 450 225/4x18 254/8x18 300/8x18 4000 5.5 450 225/4x18 254/8x18 325/8x18 4000 5.5 450 225/4x18 254/8x18 356/8x18 4000 5.5 450 225/4x18 254/8x18 356/8x18

BIL 1800 kV

Mechanical Values Min. failing load - Bending [kN] Min. failing load - Bending moment underhung [kNm] Min. failing load - Bending moment upright [kNm] Min. failing load - Torsion [kNm] Electrical Values Lightn. impulse withst. voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] IEC POSTINSULATOR INSULATOR DESIGNATION IEC POST DESIGNATION 1800 1175 1800 1175 C6-1950
712017

4 3.2 16 3

6 4.8 24 3

8 6.4 32 4

10 8 40 4

12.5 10 50 6

16 12.8 64 6

1800 1175 C8-1950


713017

1800 1175 C10-1950


714017

1800 1175

1800 1175 C12.5-1950


715017

TYPE PRODUCT NO

C4-1950
711017

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 4400 5.5 450 225/4x18 254/8x18 254/8x18 4400 5.5 450 225/4x18 254/8x18 275/8x18 4400 5.5 450 225/4x18 254/8x18 300/8x18 4400 5.5 450 225/4x18 254/8x18 325/8x18 4400 5.5 450 225/4x18 254/8x18 356/8x18

BIL 1950 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 3.52 17.6 3

6 5.28 26.4 3

8 7.04 35.2 4

10 8.8 44 4

12.5 11 55 6

1950 1300
C4-2100
711018

1950 1300
C6-2100
712018

1950 1300
C8-2100
713018

1950 1300
C10-2100
714018

1950 1300
C12.5-2100
715018

TYPE PRODUCT NO

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 4700 5.5 450 225/4x18 254/8x18 254/8x18 47005.5 450 225/4x18 254/8x18 275/8x18 4700 5.5 450 225/4x18 254/8x18 300/8x18 4700 5.5 450 225/4x18 254/8x18 325/8x18 4700 5.5 450 225/4x18 254/8x18 356/8x18

BIL 2100 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] 2100 1300 2100 1300 2100 1300 2100 1300 2100 1300 4 3.76 18.8 3 6 5.64 28.2 3 8 7.52 37.6 4 10 9.4 47 4 12.5 11.75 58.75 6

Page 25

Type BIL 1800 - 2100 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Type BIL 1800 - 2100 kV

Porcelain

C1 30 (or C1 20) according to IEC60672-3, Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement

TYPE BIL1800 Page 5 - 2100kV

Page 26

www.ankaraseramik.com

Outdoor Solid Core Post Insulators Type BIL 2250- 2550 kV

ANKARA SERAMIK A.S.

IEC POST INSULATOR DESIGNATION


IEC POST INSULATOR DESIGNATION

TYPE PRODUCT NO

C4-2250
711019

C6-2250
712019

C8-2250
713019

C10-2250
714019

C12.5-2250
715019

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 5000 6.5 450 225/4x18 254/8x18 254/8x18 5000 6.5 450 225/4x18 254/8x18 300/8x18 5000 6.5 450 225/4x18 254/8x18 325/8x18 5000 6.5 450 225/4x18 254/8x18 356/8x18 5000 6.5 450 225/4x18 254/8x18 356/8x18

BIL 2250 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 4 20 3

6 6 30 3

8 8 40 4

10 10 50 4

12.5 12.5 62.5 6

2250 1425
C4-2400
711020

2250 1425
C6-2400
712020

2250 1425
C8-2400
713020

2250 1425
C10-2400
714020

2250 1425
C12.5-2400
715019

C12.5-2400

TYPE PRODUCT NO

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 5300 6.5 450 225/4x18 254/8x18 254/8x18 5300 6.5 450 225/4x18 254/8x18 300/8x18 5300 6.5 450 225/4x18 254/8x18 325/8x18 5300 6.5 450 225/4x18 254/8x18 356/8x18 5300 6.5 450 225/4x18 254/8x18 356/8x18

BIL 2400 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

4 4.24 21.2 3

6 6.36 31.8 3

8 8.48 42.4 4

10 10.6 53 4

12.5 13.25 66.25 6

2400 1425

2400 1425
C4-2550
711021

2400 1425
C6-2550
712021

2400 1425
C8-2550
713021

2400 1425
C10-2550
714021

TYPE PRODUCT NO

Dimensions Height H [mm] Max. nom. diameter of insulating part d1 [mm] Top fitting p.c.d. d2 [mm] / hole pattern Bottom fitting p.c.d. d3 [mm] / hole pattern 57006.5 450 225/4x18 254/8x18 275/8x18 57006.5 450 225/4x18 254/8x18 300/8x18 57006.5 450 225/4x18 254/8x18 325/8x18 57006.5 450 225/4x18 254/8x18 356/8x18

BIL 2550 kV

Mechanical Values Minimum failing load - Bending [kN] Minimum failing load - Bending moment underhung [kNm] Minimum failing load - Bending moment upright [kNm] Minimum failing load - Torsion [kNm] Electrical Values Lightning impulse withstand voltage, dry [kV peak value] Switching impulse withstand voltage, wet [kV peak value] 2550 1550 2550 1550 2550 1550 2550 1550 4 4.56 22.8 3 6 6.84 34.2 3 8 9.12 45.6 4 10 11.4 57 4

Page 27

Type BIL 2250 - 2550 kV

www.ankaraseramik.com

ANKARA SERAMIK A.S.

Outdoor Solid Core Post Insulators Type BIL 2250- 2550 kV

Porcelain

C1 30 (or C1 20) according to IEC60672-3, Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement

TYPE BIL2250 Page 5 - 2550kV

Page 28

www.ankaraseramik.com

OUTDOOR SOLID CORE POST INSULATORS