Analog modules

SM 331 analog input module

Overview

Analog inputs For connection of voltage and current sensors, thermocouples, resistors and resistance thermometers

Area of application Analog input modules can be used to connect the PLC to analog process signals. They are suitable for the connection of voltage and current sensors, thermocouples, resistors and resistance thermometers. Functions The analog input modules convert analog signals from the process into digital signals for processing within the PLC. The modules feature:

Resolution from 9 to 15 bit + sign (for different conversion times), configurable Different measuring ranges; the basic current/voltage range settings are adjusted mechanically via measurement range modules. Fine adjustments are made with the STEP7 Hardware Configuration tool on a PG. Interrupt capability; the modules transmit diagnostic and limit value interrupts to the programmable controller's CPU Diagnostics; the module sends detailed diagnostic information to the CPU.

Technical specifications
Supply voltages Load voltage L+ Rated value (DC) reverse polarity protection Current consumption from load voltage L+ (without load), max. from backplane bus DC 5 V, max. Current consumption/power loss Power loss, typ. Connection point required front connectors Isochronous mode Isochronouos mode Analog inputs Number of analog inputs 6ES7 331-7KF02-0AB0 24V Yes 200mA 50mA 1W 20-pin No 8 6ES7 331-7HF01-0AB0 24V Yes 50mA 60mA 1.5W 20-pin Yes 8 200m No Yes Yes Yes 6ES7 331-1KF01-0AB0 90mA 0.4W 40-pin No 8 8 200m; max. 50 m at 50 mV Yes Yes No Yes 6ES7 331-7KB02-0AB0 24V Yes 80mA 50mA 1.3W 20-pin No 2 1 200m; 50 m at 80 mV and with thermocouples No Yes No Yes

Number of analog inputs for 4 resistance measurement cable length, shielded, max. Input ranges (rated values), voltages 0 to +10 V 1 to 5 V 1 to 10 V -1 V to +1 V 200m; 50 m at 80 mV and with thermocouples No Yes No Yes

Page 2 of 7

-10 V to +10 V -2.5 V to +2.5 V -250 mV to +250 mV -5 V to +5 V -50 mV to +50 mV -500 mV to +500 mV -80 mV to +80 mV Input ranges (rated values), currents 0 to 20 mA -10 to +10 mA -20 to +20 mA -3.2 to +3.2 mA 4 to 20 mA Input ranges (rated values), thermoelements Type Type Type Type Type Type Type Type Type Type B E J K L N R S T U

Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes No Yes No No No No No No Yes; Standard No No No No No Yes; Standard No No No Yes Yes Yes No 20V; continuous; 75 V for max. 1 s (mark to space ratio 1:20)

Yes No No Yes No Yes Yes Yes Yes No Yes No No No No No No No No No No No No No No No No No No 20V; 20 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) 40mA

Yes No No Yes Yes Yes No Yes No Yes No Yes No No No No No No No No No No No No Yes; Standard/climate Yes Yes; Standard/AirCon No No No Yes; Standard/climate No No No No No Yes Yes 30V; 12 V continuous, 30 V for max. 1 s

Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes No No No No No No Yes Yes Yes Yes Yes No 20V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) 40mA

Typ TXK/TXK(L) to GOST Input ranges (rated values), resistance thermometers Cu 10 Ni 100 Ni 1000 LG-Ni 1000 Ni 120 Ni 200 Ni 500 Pt 100 Pt 1000 Pt 200 Pt 500 Input ranges (rated values), resistors 0 to 150 Ohm 0 to 300 Ohm 0 to 600 Ohm 0 to 6000 Ohm permissible input frequency for voltage input (destruction limit), max.

permissible input current 40mA for current input (destruction limit), max. Characteristic curve linearization programmable for thermoelements for thermoresistor Yes Type E, J, K, L, N

40mA

Yes yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LGNi1000 standard/air con.

Yes Type E, J, K, L, N Pt100 (standard, climatic range), Ni100 (standard, climatic range)

Pt100 (standard, climatic range), Ni100 (standard, climatic range)

Page 3 of 7

Temperature compensation programmable internal temperature compensation external temperature compensation with compensations socket Analog value creation Measurement principle Integration and conversion time/resolution per channel

Yes Yes Yes

Yes Yes Yes

integrating

Actual value encryption

integrating

integrating 15Bit; unipolar: 9/12/12/14 bits; bipolar: 9 bits + sign/12 bits + sign/12 bits + sign/14 bits + sign Yes; 2.5/ 16.67/ 20/ 100 ms 6/ 34/ 44/ 204 ms

Resolution with overload 15Bit; unipolar: area (bit including sign), 9/12/12/14 bits; bipolar: 9 bits + sign/12 bits + max. sign/12 bits + sign/14 bits + sign Integration time, parameterizable Basic conversion time, ms Basic conversion time, including integration time, ms Interference voltage suppression for interference frequency f1 in Hz Encoder Connection of signal encoders Yes; 2.5/ 16.67/ 20/ 100 ms 3/ 17/ 22/ 102 ms

14Bit; unipolar: 14 bits; 13Bit bipolar: 13 bits + sign

Yes 52 s per channel

Yes; 60 / 50 ms 66 / 55 ms 66 / 55 ms

400 / 60 / 50 / 10 Hz

400 / 60 / 50 / 10 Hz

50 / 60 Hz

400 / 60 / 50 / 10 Hz

Yes Yes

Yes; with external supply Yes Yes

Yes Yes Yes

for current measurement Yes as 2-wire transducer for current measurement Yes as 4-wire transducer for resistance measurement with 2conductor connection for resistance measurement with 3conductor connection for resistance measurement with 4conductor connection Errors/accuracies Operational limit in overall temperature range Yes

Yes

Yes

Yes

Yes

Yes

Yes

+/- 0,4 %

+/- 0,6 %; +/-0.6% (+/5 V, 10 V, 1 to 5 V, 0 to 10 V); +/-0.5% (+/50 mV, 500 mV, 1 V) +/- 0,5 %; +/-20 mA, 0 to 20 mA, 4 to 20 mA +/- 0,5 %; 0 to 6 kohms, 0 to 600 kohms 1 Kelvin (Pt100, Ni100, climatic; Ni1000, LGNi1000, standard; Ni1000, LG-Ni1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard) +/- 0,4 %; 0.4% (+/-5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (+/-50 mV, 500 mV, 1 V) +/- 0,3 %; +/-20mA,0-

+/- 1 %; +/-1% (80 mV); +/-0.6% (250 to 1000 mV); +/-0.8% (2.5 to 10 V) +/- 0,7 %; from 3.2 to 20 mA +/- 0,7 %; 150, 300, 600 Ohm +/- 0,7 %; +/-0.7% (Pt100/ Ni100); +/-0.8% (Pt100 climate)

Voltage, relative to input +/- 1 %; +/-1% (80 mV); +/-0.6% (250 to area 1000 mV); +/-0.8% (2.5 to 10 V) Current, relative to input +/- 0,7 %; from 3.2 to 20 mA area Impedance, relative to input area Resistance-type thermometer, relative to input area +/- 0,7 %; 150, 300, 600 Ohm +/- 0,7 %; +/-0.7% (Pt100/ Ni100); +/-0.8% (Pt100 climate)

+/- 0,3 %

Basic error limit (operational limit at 25 C) Voltage, relative to input +/- 0,6 %; +/-0.4% (250 to 1000 mV); +/-0.6% area (2.5 to 10 mV); +/-0.7% (80 mV) Current, relative to input +/- 0,5 %; 3.2 to 20

+/- 0,25 %

+/- 0.6 %; +/-0.6% (80 mV, 2.5 to 10 V); +/0.4% (250 to 1000 mV) +/- 0,5 %; 3.2 to 20

+/- 0,2 %

Page 4 of 7

area Impedance, relative to input area Resistance-type thermometer, relative to input area

mA +/- 0,5 %; 150, 300, 600 Ohm +/- 0,6 %; +/-0.5% (Pt100/ Ni100); +/-0.6% (Pt100 climate)

20mA,4-20mA +/- 0,3 %; 0 to 6 kohms, 0 to 600 kohms 1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LGNi1000, climatic) No No No 500 VDC No Yes 40mm 125mm 117mm 250g

mA +/- 0,5 %; 150, 300, 600 Ohm +/- 0.6 %; +/-0.5% (Pt100/ Ni100); +/-0.6% (Pt100 climate)

Status information/alarms/diagnostics Alarms Diagnostic alarm Limit value alarm Diagnoses Diagnostic information readable Isolation Isolation checked with Isolation Isolation, analog inputs between the channels between the channels and the backplane bus Dimensions Dimensions Width Height Depth Weights Weight, approx. Yes; parameterizable, channels 0 and 2 Yes; parameterizable Yes 500 VDC No Yes 40mm 125mm 120mm 250g

Yes; Parameterizable Yes; parameterizable, channels 0 and 2 Yes 500 VDC No Yes 40mm 125mm 120mm 200g

Yes Yes; parameterizable, channel 0 Yes 500 VDC No Yes 40mm 125mm 120mm 250g

Supply voltages Load voltage L+ Rated value (DC) reverse polarity protection Current consumption from load voltage L+ (without load), max. from backplane bus DC 5 V, max. Current consumption/power loss Power loss, typ. Connection point required front connectors Isochronous mode Isochronouos mode Analog inputs Number of analog inputs

6ES7 331-7PF01-0AB0 24V Yes 240mA 100mA 4.6W 40-pin No 8

6ES7 331-7PF11-0AB0 24V Yes 200mA 100mA 3W 40-pin No 8 100m No

6ES7 331-7NF00-0AB0 130mA 0.6W 40-pin No 8 200m No

6ES7 331-7NF10-0AB0 24V Yes 200mA 100mA 3W 40-pin No 8 200m No

Number of analog inputs for 8 resistance measurement cable length, shielded, max. Input ranges (rated values), voltages 0 to +10 V 200m No

Page 5 of 7

1 to 5 V 1 to 10 V -1 V to +1 V -10 V to +10 V -2.5 V to +2.5 V -250 mV to +250 mV -5 V to +5 V -50 mV to +50 mV -500 mV to +500 mV -80 mV to +80 mV Input ranges (rated values), currents 0 to 20 mA -10 to +10 mA -20 to +20 mA -3.2 to +3.2 mA 4 to 20 mA Input ranges (rated values), thermoelements Type Type Type Type Type Type Type Type Type Type B E J K L N R S T U

No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 75V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)

No No No No No No No No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No No 75V; 20 V continuous, 75 V for max. 1 s (mark to space ratio 1:20)

Yes No No Yes No No Yes No No No Yes Yes No Yes No No No No No No No No No No No No No No No No No No No No No No No No No No 50V; permanent

Yes No No Yes No No Yes No No No Yes Yes No Yes No No No No No No No No No No No No No No No No No No No No No No No No No No 75V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) 40mA

Typ TXK/TXK(L) to GOST Input ranges (rated values), resistance thermometers Cu 10 Ni 100 Ni 1000 LG-Ni 1000 Ni 120 Ni 200 Ni 500 Pt 100 Pt 1000 Pt 200 Pt 500 Input ranges (rated values), resistors 0 to 150 Ohm 0 to 300 Ohm 0 to 600 Ohm 0 to 6000 Ohm permissible input frequency for voltage input (destruction limit), max.

permissible input current for current input (destruction limit), max. Characteristic curve linearization programmable for thermoelements for thermoresistor Yes Pt100, Pt200, Pt500,

32mA

Yes Type B, E, J, K, L, N, R, S. T, U, C

Page 6 of 7

Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10; (standard/climate) Temperature compensation programmable internal temperature compensation external temperature compensation with compensations socket external temperature compensation with Pt100 Analog value creation Measurement principle Integration and conversion time/resolution per channel Yes Yes Yes

Yes

integrating

integrating 16Bit; Two's complement

integrating 16Bit; unipolar: 15/15/15/15 bits; bipolar: 15 bits + sign/15 bits + sign/15 bits + sign/15 bits + sign Yes; 10 / 16.67 / 20 / 100 ms

integrating 16Bit; unipolar: 15/15/15/15 bits; bipolar: 15 bits + sign/15 bits + sign/15 bits + sign/15 bits + sign Yes; 23 / 72 / 83 / 95 ms 10 ms (4-channel mode); 95/83/72/23 ms (8-channel mode)

Resolution with overload 16Bit; Two's area (bit including sign), complement max.

Integration time, parameterizable Basic conversion time, ms

Yes up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms 400 / 60 / 50 Hz

Yes up to 4 channels: 10 ms per module, as of 5 channels: 190 ms per module 400 / 60 / 50 Hz

Interference voltage suppression for interference frequency f1 in Hz Encoder Connection of signal encoders

400 / 60 / 50 / 10 Hz

400 / 60 / 50 Hz, combinations of 400, 60, 50 Hz Yes; with external transmitter, current supply; possible with separate supply for transmitter Yes

Yes; with external transmitter; possible with separate supply for transmitter Yes

for current measurement as 2-wire transducer

for current measurement as 4-wire transducer for resistance measurement with 2conductor connection for resistance measurement with 3conductor connection for resistance measurement with 4conductor connection Errors/accuracies Operational limit in overall temperature range Yes; without resistance correction Yes

Yes

+/-1 K

+/- 0,1 %; +/-0.7% +/- 0,3 %; +/-0.9%

+/- 0,1 % +/- 0,1 %

Voltage, relative to input area Current, relative to input area Impedance, relative to input area Resistance-type thermometer, relative to input area +/- 0,1 % +/-1 K

Basic error limit (operational limit at 25 C) Voltage, relative to input area

+/- 0,05 %

+/- 0,05 %

Page 7 of 7

Current, relative to input area Impedance, relative to input area Resistance-type thermometer, relative to input area +/- 0,05 % +/-0.5 K

+/- 0,05 %

+/- 0,05 %

Status information/alarms/diagnostics Alarms Diagnostic alarm Limit value alarm Yes; parameters can be set per group Yes; parameterizable

Yes; parameters can be set per group Yes; parameterizable

Yes; Parameterizable Yes; parameterizable, channels 0 and 2

Yes; Parameterizable Yes; parameterizable all channels (end of cycle interrupt is also supported across modules) Yes 500 V AC No 2 Yes 40mm 125mm 120mm 272g

Diagnoses Diagnostic information readable Isolation Isolation checked with Isolation Isolation, analog inputs between the channels between the channels, in groups of between the channels and the backplane bus Dimensions Dimensions Width Height Depth Weights Weight, approx.

Yes 500 VDC No 2 Yes 40mm 125mm 120mm 272g

Yes 500 VDC No 2 Yes 40mm 125mm 120mm 272g

Yes 500 VDC No 2 Yes 40mm 125mm 120mm 272g