STAIR CASE 05 3 Doors open,

PRESSURIZATION CALCULATIONS:
ZONE 1

Method 1

Q= Kf *Al*(DP) 1/2

NOTES

Q = Flow Rate (cfm)

Eqn. 4.8a - from ASHRAE Design of Smoke Management Systems, pg. 42

Q= Kf *Al*(DP)

1/2

Kf = Coefficient, 2610 Al = Flow Area, ft DP = Pressure Diff., 0.05, in H2O


2

Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 48 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 14.40 31.50

Closed Doors Open Doors

Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors

21

Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 45.90 ft2 2610 0.05 in H20 26787.87 cfm 26787.87 cfm SC- 05 SPF/25-2 SPF/49-1 Total

45.90

IFC 9860 7820 17680

STAIR CASE 06 , 3 Doors open

PRESSURIZATION CALCULATIONS:
ZONE 1

Method 1

Q= Kf *Al*(DP) 1/2

NOTES

Q = Flow Rate (cfm)

Eqn. 4.8a - from ASHRAE Design of Smoke Management Systems, pg. 42

Q= Kf *Al*(DP)

1/2

Kf = Coefficient, 2610 Al = Flow Area, ft DP = Pressure Diff., 0.05, in H2O


2

Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 50 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 15.00 31.50

Closed Doors Open Doors

Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors

21

Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 46.50 ft2 2610 0.05 in H20 27138.04 cfm 27138.04 cfm

46.50

SC- 06 SPF/25-1 SPF/50-1 Total

IFC 9860 8160 18020

STAIR CASE 07, 3 Doors open

PRESSURIZATION CALCULATIONS:
ZONE 1

Method 1

Q= Kf *Al*(DP) 1/2

NOTES

Q = Flow Rate (cfm)

Eqn. 4.8a - from ASHRAE Design of Smoke Management Systems, pg. 42

Q= Kf *Al*(DP)

1/2

Kf = Coefficient, 2610 Al = Flow Area, ft DP = Pressure Diff., 0.05, in H2O


2

Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 5 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 1.50 31.50

Closed Doors Open Doors

Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors

21

Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 33.00 ft2 2610 0.05 in H20 19259.25 cfm 19259.25 cfm

33.00

SC- 07 SPF/14 -1 Total

IFC 10840 10840

STAIR CASE 05

PRESSURIZATION CALCULATIONS:
ZONE 1

Method 1

Q= Kf *Al*(DP) 1/2

NOTES

Q = Flow Rate (cfm)

Eqn. 4.8a - from ASHRAE Design of Smoke Management Systems, pg. 42

Q= Kf *Al*(DP)

1/2

Kf = Coefficient, 2610 Al = Flow Area, ft DP = Pressure Diff., 0.05, in H2O


2

Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 48 0 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 14.40 0.00

Closed Doors Open Doors

Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors

21

Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 14.40 ft2 2610 0.2 in H20 16808.08 cfm 16808.08 cfm SC- 05 SPF/25-2 SPF/49-1 Total

14.40

IFC 9860 7820 17680

STAIR CASE 05

PRESSURIZATION CALCULATIONS:
ZONE 1

Method 1

Q= Kf *Al*(DP) 1/2

NOTES

Q = Flow Rate (cfm)

Eqn. 4.8a - from ASHRAE Design of Smoke Management Systems, pg. 42

Q= Kf *Al*(DP)

1/2

Kf = Coefficient, 2610 Al = Flow Area, ft DP = Pressure Diff., 0.05, in H2O


2

Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 50 0 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 15.00 0.00

Closed Doors Open Doors

Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors

21

Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 15.00 ft2 2610 0.2 in H20 17508.41 cfm 17508.41 cfm

15.00

SC- 06 SPF/25-1 SPF/50-1 Total

IFC 9860 8160 18020

1 staircase 7 fan capacity installed at 14 CASE 1 ALL DOOR CLOSED with bypass damper open Measured pressure at level 8 Measured pressure at level 6 Measured pressure at level 4 Measured pressure at level 2 Measured pressure at level 1 case 2 With one door open(level1) & with bypass damper closed Measured pressure at level 8 Measured pressure at level 5 Measured pressure at level 3 Measured pressure at level 2 With Three door open(level 1,3 &4) & with bypass damper closed Measured pressure at level 8 Measured pressure at level 7 Measured pressure at level 6 Measured pressure at level 5 Measured pressure at level 2 220pa 215pa 210pa 205pa 200pa air flow esp 27000 cfm 620 pa Serving level 1 - level 8

38pa 38pa 35pa 33pa

case 3

15pa 15pa 14pa 13pa 13pa

1 staircase 5 fan capacity installed at 49 fan capacity installed at 25 CASE 1 ALL DOOR CLOSED with bypass damper open Measured pressure at level 48 Measured pressure at level 40 Measured pressure at level 30 Measured pressure at level 20 Measured pressure at level GF Measured pressure at level B3 case 2 With one door open(level 5) & with bypass damper closed Measured pressure at level 48 Measured pressure at level 30 Measured pressure at level 3 Measured pressure at level 1 Measured pressure at level B1 Measured pressure at level B3 With Three door open(level GF,3 &4) & with bypass damper closed Measured pressure at level 48 Measured pressure at level 40 Measured pressure at level 30 Measured pressure at level 5 Measured pressure at level 2 Measured pressure at level 2 Measured pressure at level B1 Measured pressure at level B3 125pa 122pa 120pa 118pa 108pa 106pa air flow esp 27000 cfm 620 pa 11000cfm 550pa Serving level 48 Basement 3

95pa 89pa 38pa 30pa 22pa 22pa

case 3

85pa 78pa 74pa 20pa 20.2pa 15pa 9.5pa 8pa