Sei sulla pagina 1di 1

- -

Technical DataSheet
Overall Specifications ofDVSeries Gensets
320to625KVA
DG SetSpecifications
Genset Model
Parameters Unit
KG320 WS2 KG380WS KG400 WS2 KG500 WS3 KG600 WS3 KG625 WS3
kVA (kW) Prime!!.ating at 0.8 PF 320 (256) 380 (304) 40Q. (320) 500 (400)_ 600 l480) 625 (500)
Voltage V 415 415 415 415
' ,1
415 415
_ Hz 50 50 50 50 50 50
.. ..
Overall Dimensionswith canopy mm (LxWxH) 5700x2000x2555 5700x2000x2555 5700x2000x2555 6200x2000x2555 6660x2000x2705 6660x2000x2705
DryWeight ?! genset with (Aprox) kg. 5750 5850 6000 6655 7500 7500
.-
Electricalstarting system Volt-DC 24(2x12v) 24 12v) (2x12 v) 24(2x12v) 24 (2x12 v) 24 (2x12v)
BatteryCapacit y Ah 180 180 180 180 180 180
DG set Noi selevel asperCPCB Norms dBA <75 <75 <75 <75 <75 <75
Engine Specifications
Engine Model
Parameters Unit
OVB SRl OV8 SR2 OVB OV10 DV12 DV12 SRl
Ratedoutput (PrimeRating)
kW(hp) 294 (400) 346 (471) 360 (490) 448(608) 532 (723) 552 (750)
asper ISO 3046
No. 01 cylinder No 8 8 8 10 12 12
Bore xStroke mm 130 x150 130 x150 130 x150 130 x150 130 x159 130 x159
Aspiration TA TA TA TA TA TA TA
Governer/Class ElectronicA 1 ElectronicA 1 ElectronicA 1 ElectronicA 1 ElectronicA 1 ElectronicA 1
SFC at 75%load (glHp-hr) 147' 145' 144' 146' 144' 144'
SFC at 100%load

146' 143' 143' 143' 143' 143'
Lube oilConsumption %01 SFC 0.12' 0.12' 0.12' 0.12' 0.12' 0.12'
Lube oil change period hrs 500 500 500 500 500 500
Lubeoil Surnpcapacity Ltrs 41 41 41 45 50 50
AlternatorSpecifications
.-
Parameters Unit Alternator Model
KG 284 C KG 354 Sl KG 354 S2 KG 354 MI 354 L1 35412
Rating kVA 320 kVA 380kVA 400 kVA 500 kVA 600 kVA 625 kVA
InsulationClass H H H H H H
Protection IP IP23 IP23 IP23 IP23 IP23 IP23
Time to built up ratedvoltage at rated RPM sec 5
AlternatorEfliciency at 100%load % 93.8 94.1 94.1 94.8 955 95.5
Voltage regulation % 1 !,1 1 1 :,: 1
-
Wave form Distortion at Noload and at
% <1.8 &<4 <1.8 &<4 <1.8 & <4 <1.8 &<4 <1.8 &<4 <1.8 &<4
Non-distorting balancelinerarLoad
In ofconlil'l"'Jouc:: productupdationanddesignchanges.all above and dimensionsare subject to change without prior notice
Notes:
Gensetratings areasperISO 8528 periormance cl ass G2.
PrimePower Rati ng is the maximum poweravailable continuouslyforavariable electricalload forunlimitednumberof
hours peryearunderstandardoperating conditions.
ForIhesiteconditionsotherthan standardoperatingconditions,consultKOEL foravailable prime power.
----.-
' Specificgravityofdi esel is considered as0.845 (+5% toleranceas per ISO3046). --
I
All canopy dimensionshavetoleranceof+50mill.
.....
** Firstoilchangeat50hours.