Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, Finland Telephone: +358 10 2211 Facsimile: +358 10 22 41094 http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The IED is designed in accordance with the international standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5 Intended audience..............................................................................5 Product documentation.......................................................................6 Product documentation set............................................................6 Document revision history.............................................................7 Related documentation..................................................................8 Symbols and conventions...................................................................8 Safety indication symbols..............................................................8 Manual conventions.......................................................................9 Functions, codes and symbols......................................................9
Section 2
RET615 overview...........................................................13
Overview...........................................................................................13 Product version history................................................................13 PCM600 and IED connectivity package version..........................13 Operation functionality......................................................................14 Optional functions........................................................................14 Physical hardware............................................................................14 Local HMI.........................................................................................16 Display.........................................................................................17 LEDs............................................................................................18 Keypad........................................................................................18 Web HMI...........................................................................................18 Authorization.....................................................................................19 Communication.................................................................................20
Section 3
Table of contents
Functional diagrams for control and interlocking....................48 Standard configuration B..................................................................53 Applications.................................................................................53 Functions.....................................................................................53 Default I/O connections..........................................................55 Default disturbance recorder settings.....................................56 Functional diagrams....................................................................56 Functional diagrams for protection.........................................57 Functional diagrams for disturbance recorder and supervision functions..............................................................63 Functional diagrams for control and interlocking....................65 Standard configuration C..................................................................70 Applications.................................................................................70 Functions.....................................................................................70 Default I/O connections..........................................................72 Default disturbance recorder settings.....................................73 Functional diagrams....................................................................73 Functional diagrams for protection.........................................74 Functional diagrams for disturbance recorder and supervision functions..............................................................80 Functional diagrams for control and interlocking....................82 Standard configuration D..................................................................87 Applications.................................................................................87 Functions.....................................................................................87 Default I/O connections..........................................................89 Default disturbance recorder settings.....................................90 Functional diagrams....................................................................90 Functional diagrams for protection.........................................91 Functional diagrams for disturbance recorder and supervision functions .............................................................97 Functional diagrams for control and interlocking....................99 Standard configuration E................................................................104 Applications...............................................................................104 Functions...................................................................................104 Default I/O connections........................................................106 Default disturbance recorder settings...................................107 Functional diagrams..................................................................107 Functional diagrams for protection.......................................108 Functional diagram for disturbance recorder and supervision functions............................................................115 Functional diagrams for control and interlocking..................116 Standard configuration F................................................................121 Applications...............................................................................121 Functions...................................................................................121
2 RET615 Application Manual
Table of contents
Default I/O connections........................................................123 Default disturbance recorder settings...................................124 Functional diagrams..................................................................125 Functional diagrams for protection.......................................125 Functional diagram for disturbance recorder and supervision functions............................................................132 Functional diagrams for control and interlocking..................133 Standard configuration G................................................................138 Applications...............................................................................138 Functions...................................................................................138 Default I/O connections........................................................140 Default disturbance recorder settings...................................141 Functional diagrams..................................................................142 Functional diagrams for protection.......................................142 Functional diagram for disturbance recorder and trip circuit supervision ................................................................149 Functional diagrams for control and interlocking..................151 Standard configuration H................................................................155 Applications...............................................................................155 Functions...................................................................................155 Default I/O connections........................................................157 Default disturbance recorder settings...................................158 Functional diagrams..................................................................159 Functional diagrams for protection.......................................159 Functional diagram for disturbance recorder and supervision functions............................................................166 Functional diagrams for control and interlocking..................167
Section 4
Section 5
Table of contents
Auxiliary supply voltage input....................................................178 Binary inputs..............................................................................179 Optional light sensor inputs.......................................................180 Outputs...........................................................................................181 Outputs for tripping and controlling............................................181 Outputs for signalling.................................................................181 IRF.............................................................................................183
Section 6
Glossary.......................................................................185
1MRS756886 E
Section 1 Introduction
Section 1
Introduction
1.1
This manual
The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.
1.2
Intended audience
This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as communication and protocols.
Section 1 Introduction
1MRS756886 E
1.3
1.3.1
Product documentation
Product documentation set
Decommissioning deinstalling & disposal Planning & purchase
Commissioning
Engineering
Engineering manual Installation manual Commissioning manual Operation manual Service manual Application manual Technical manual Communication protocol manual en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as
Operation
Installing
Maintenance
1MRS756886 E
Section 1 Introduction
well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The service manual contains instructions on how to service and maintain the IED. The manual also provides procedures for de-energizing, de-commissioning and disposal of the IED. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Some of the manuals are not available yet.
1.3.2
Section 1 Introduction
1MRS756886 E
Download the latest documents from the ABB web site http:// www.abb.com/substationautomation.
1.3.3
Related documentation
Name of the document Modbus Communication Protocol Manual DNP3 Communication Protocol Manual IEC 60870-5-103 Communication Protocol Manual IEC 61850 Engineering Guide Engineering Manual Installation Manual Operation Manual Technical Manual Document ID 1MRS756468 1MRS756709 1MRS756710 1MRS756475 1MRS757121 1MRS756375 1MRS756708 1MRS756887
1.4
1.4.1
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader to important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a certain function.
1MRS756886 E
Section 1 Introduction
Although warning hazards are related to personal injury, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this manual. Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the push button icons, for example: To navigate between the options, use and . HMI menu paths are presented in bold, for example: Select Main menu/Settings. LHMI messages are shown in Courier font, for example: To save the changes in non-volatile memory, select Yes and press . Parameter names are shown in italics, for example: The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "On" and "Off". IED input/output messages and monitored data names are shown in Courier font, for example: When the function starts, the START output is set to TRUE.
1.4.3
PHLPTOC2
3I> (2)
51P-1 (2)
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>> (1)
50P/51P (1)
Section 1 Introduction
Function Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, low stage, instance 2 Non-directional earth-fault protection, high stage, instance 1 Non-directional earth-fault protection, high stage, instance 2 Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase thermal overload protection for power transformers, two time constants Stabilized and instantaneous differential protection for 2W transformers Numerical stabilized low impedance restricted earth-fault protection High impedance based restricted earth-fault protection Circuit breaker failure protection Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Multi-purpose protection, instance 11) Multi-purpose protection, instance 21) Table continues on next page IEC 61850 PHIPTOC2 EFLPTOC1 EFLPTOC2 EFHPTOC1 EFHPTOC2 NSPTOC1 NSPTOC2 ROVPTOV1 ROVPTOV2 PHPTUV1 PHPTUV2 PHPTOV1 PHPTOV2 T2PTTR1 IEC 60617 3I>>> (2) Io> (1) Io> (2) Io>> (1) Io>> (2) I2> (1) I2> (2) Uo> (1) Uo> (2) 3U< (1) 3U< (2) 3U> (1) 3U> (2) 3Ith>T
1MRS756886 E
IEC-ANSI 50P/51P (2) 51N-1 (1) 51N-1 (2) 51N-2 (1) 51N-2 (2) 46 (1) 46 (2) 59G (1) 59G (2) 27 (1) 27 (2) 59 (1) 59 (2) 49T
TR2PTDF1
3dI>T
87T
LREFPNDF1 HREFPDIF1 CCBRBRF1 TRPPTRC1 TRPPTRC2 ARCSARC1 ARCSARC2 ARCSARC3 MAPGAPC1 MAPGAPC2
dIoLo> dIoHi> 3I>/Io>BF Master Trip (1) Master Trip (2) ARC (1) ARC (2) ARC (3) MAP (1) MAP (2)
87NL 87NH 51BF/51NBF 94/86 (1) 94/86 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3) MAP (1) MAP (2)
10
1MRS756886 E
Section 1 Introduction
Function Multi-purpose protection, instance 31) Control Circuit-breaker control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication Tap changer position indication Condition monitoring Circuit-breaker condition monitoring Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Fuse failure supervision Runtime counter for machines and devices Measurement Disturbance recorder Three-phase current measurement, instance 1 Three-phase current measurement, instance 2 Sequence current measurement Residual current measurement, instance 1 Residual current measurement, instance 2 Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement, including power factor RTD/mA measurement RDRE1 CMMXU1 CMMXU2 CSMSQI1 RESCMMXU1 RESCMMXU2 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 XRGGIO130 3I 3I(B) I1, I2, I0 Io Io(B) 3U Uo U1, U2, U0 P, E X130 (RTD) 3I 3I(B) I1, I2, I0 In In(B) 3U Vn U1, U2, U0 P, E X130 (RTD) SSCBR1 TCSSCBR1 TCSSCBR2 SEQRFUF1 MDSOPT1 CBCM TCS (1) TCS (2) FUSEF OPTS CBCM TCM (1) TCM (2) 60 OPTM CBXCBR1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 TPOSSLTC1 I <-> O CB I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES TPOSM I <-> O CB I <-> O DC (1) I <-> O DC (2) I <-> O DC (3) I <-> O ES 84M IEC 61850 MAPGAPC3 IEC 60617 MAP (3) IEC-ANSI MAP (3)
11
12
1MRS756886 E
Section 2
RET615 overview
2.1
Overview
RET615 is a dedicated transformer protection and control IED (intelligent electronic device) for power transformers, unit and step-up transformers including power generator-transformer blocks in utility and industry power distribution systems. RET615 is a member of ABBs Relion product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable-unit design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service. The 615 series IEDs support a range of communication protocols including IEC 61850 with GOOSE messaging, IEC 60870-5-103, Modbus and DNP3.
2.1.1
2.1.2
1MRS756886 E
Lifecycle Traceability Signal Matrix Communication Management IED Configuration Migration Configuration Wizard Label Printing IED User Management Application Configuration Graphical Display Editor Differential Characteristics Tool
Download connectivity packages from the ABB web site http:// www.abb.com/substationautomation
2.2
2.2.1
Operation functionality
Optional functions
Arc protection Modbus TCP/IP or RTU/ASCII IEC 60870-5-103 DNP3 TCP/IP or serial RTD/mA measurements and multi-purpose protection (configurations A, B, C and D only)
2.3
Physical hardware
The IED consists of two main parts: plug-in unit and case. The content depends on the ordered functionality.
14
1MRS756886 E
Table 2:
Main unit Slot ID Plug-in unit X100
X000
Rated values of the current and voltage inputs are basic setting parameters of the IED. The binary input thresholds are selectable within the range 18176 V DC by adjusting the binary input setting parameters. The connection diagrams of different hardware modules are presented in this manual. See the installation manual for more information about the case and the plug-in unit.
Table 3:
Conf.
15
1MRS756886 E
CT 7 7 7 7 7
RTD/mA 6/22) -
D E F G H
2.4
Local HMI
REF615
Overcurrent Dir. earth-fault Voltage protection Phase unbalance Thermal overload Breaker failure Disturb. rec. Triggered CB condition monitoring Supervision Arc detected Autoreclose shot in progr.
A070704 V3 EN
Figure 2:
16
1MRS756886 E
2.4.1
Display
The LHMI includes a graphical display that supports two character sizes. The character size depends on the selected language. The amount of characters and rows fitting the view depends on the character size.
Table 4:
Character size Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels)
3
A070705 V2 EN
Figure 3:
1 Header 2 Icon 3 Content
Display layout
17
1MRS756886 E
The LHMI includes three protection indicators above the display: Ready, Start and Trip. There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected with the LHMI, WHMI or PCM600.
2.4.3
Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons you can give open or close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
A071176 V1 EN
Figure 4:
LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port
2.5
Web HMI
The WHMI enables the user to access the IED via a web browser. The supported web browser version is Internet Explorer 7.0 or later. WHMI is disabled by default.
Programmable LEDs and event lists System supervision Parameter settings Measurement display
RET615 Application Manual
1MRS756886 E
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754 V3 EN
Figure 5:
The WHMI can be accessed locally and remotely. Locally by connecting your laptop to the IED via the front communication port. Remotely over LAN/WAN.
2.6
Authorization
The user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords. The default passwords can be changed with Administrator user rights. User authorization is disabled by default but WHMI always uses authorization.
19
1MRS756886 E
Table 5:
Username VIEWER OPERATOR
ENGINEER
Changing settings Clearing event list Clearing disturbance records Changing system settings such as IP address, serial baud rate or disturbance recorder settings Setting the IED to test mode Selecting language All listed above Changing password Factory default activation
ADMINISTRATOR
2.7
Communication
The IED supports a range of communication protocols including IEC 61850, IEC 60870-5-103, Modbus and DNP3. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication between the IEDs, is only enabled by the IEC 61850 communication protocol. The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter settings, disturbance recordings and fault records can be accessed using the IEC 61850 protocol. Disturbance recordings are available to any Ethernet-based application in the standard COMTRADE file format. The IED can send and receive binary signals from other IEDs (so called horizontal communication) using the IEC61850-8-1 GOOSE profile, where the highest performance class with a total transmission time of 3 ms is supported. Further, the IED supports sending and receiving of analog values using GOOSE messaging. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. The IED can simultaneously report events to five different clients on the station bus. The IED can support five simultaneous clients. If PCM600 reserves one client connection, only four client connections are left, for example, for IEC 61850 and Modbus.
20
1MRS756886 E
All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernetbased communication systems via the RJ-45 connector (100Base-TX) or the fibreoptic LC connector (100Base-FX). If connection to a serial bus is required, the 10pin RS-485 screw-terminal or the fibre-optic ST connector can be used.
Client A Client B
Network Network
RED615
REF615
RET615
REU615
REM615
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN
Figure 6:
The Ethernet ring solution supports the connection of up to thirty 615 series IEDs. If more than 30 IEDs are to be connected, it is recommended that the network is split into several rings with no more than 30 IEDs per ring.
21
22
1MRS756886 E
Section 3
3.1
Standard configurations
RET615 is available in eight alternative standard configurations. The standard signal configuration can be altered by means of the graphical signal matrix or the optional graphical application functionality of the Protection and Control IED Manager PCM600. Further, the application configuration functionality of PCM600 supports the creation of multi-layer logic functions utilizing various logical elements including timers and flip-flops. By combining protection functions with logic function blocks the IED configuration can be adapted to user specific application requirements.
Table 6:
Description Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the high-voltage (HV) side, optional RTD/mA inputs Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side, optional RTD/mA inputs Three-phase transformer differential protection for two-winding transformers, highimpedance based restricted earth-fault protection for the high-voltage (HV) side, optional RTD/mA inputs Three-phase transformer differential protection for two-winding transformers, highimpedance based restricted earth-fault protection for the low-voltage (LV) side, optional RTD/mA inputs Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the high-voltage (HV) side, phase-voltage based protection and measurement functions Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the low-voltage (LV) side, phase-voltage based protection and measurement functions Three-phase transformer differential protection for two-winding transformers, highimpedance based restricted earth-fault protection for the high-voltage (HV) side, phasevoltage based protection and measurement functions Three-phase transformer differential protection for two-winding transformers, highimpedance based restricted earth-fault protection for the low-voltage (LV) side, phasevoltage based protection and measurement functions
Standard configurations
Std. conf. A B C
23
1MRS756886 E
Table 7:
Functionality Protection
Supported functions
A B C D E F G H
Stabilized and instantaneous differential protection for two-winding transformers Multi-purpose protection, instance 11) Multi-purpose protection, instance 21) Multi-purpose protection, instance 31) Master trip, instance 1 Master trip, instance 2 HV-side protection Numerical stabilized low impedance restricted earth-fault protection High impedance based restricted earthfault protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Negative-sequence overcurrent protection, instance 1 Residual overvoltage protection, instance 14) Residual overvoltage protection, instance 24) Three-phase undervoltage protection, instance 1 Three-phase undervoltage protection, instance 2 Three-phase overvoltage protection, instance 1 Three-phase overvoltage protection, instance 2 Three-phase thermal overload protection for power transformers, two time constants Circuit breaker failure protection3) LV-side protection Numerical stabilized low impedance restricted earth-fault protection Table continues on next page
o o o
o o o
o o o
o o o
2) 2)
3) 3)
2) 2)
3) 3)
5)
5)
24
1MRS756886 E
25
1MRS756886 E
26
1MRS756886 E
3.2
Connection diagrams
GUID-529F6F95-5742-4D6F-8C55-04F6C14BFD94 V2 EN
Figure 7:
27
1MRS756886 E
GUID-80F82A38-4519-4C09-A25D-86131D51331B V2 EN
Figure 8:
28
1MRS756886 E
GUID-32E5D770-0A2D-4FF3-9EAF-E7A82DB8A66C V2 EN
Figure 9:
29
1MRS756886 E
GUID-FC955C0D-4BF9-40A8-B953-429DE884FFE1 V2 EN
Figure 10:
30
1MRS756886 E
GUID-D26C5FA8-D7E4-4959-AA36-B77D1A53392C V1 EN
Figure 11:
31
1MRS756886 E
GUID-787C00E6-BEC2-4612-8183-195E01D9F5EF V
Figure 12:
32
1MRS756886 E
GUID-AE41CEEF-C6E8-4292-8F0A-A5B962EBBC9C V1 EN
Figure 13:
33
1MRS756886 E
GUID-4F252355-C97B-4110-8AAF-EB9816A13113 V1 EN
Figure 14:
34
1MRS756886 E
GUID-59EE9058-5928-4E74-A3C1-3F2C9B6D3EB1 V1 EN
Figure 15:
Connection diagram for the E, F, G and H configurations (transformer current differential protection with phase-to-earth voltage protection and measurement)
3.3
35
1MRS756886 E
Protection function blocks are part of the functional diagram. They are identified based on their IEC 61850 name but the IEC based symbol and the ANSI function number are also included. Some function blocks, such as PHHPTOC, are used several times in the configuration. To separate the blocks from each other, the IEC 61850 name, IEC symbol and ANSI function number are appended with a running number, that is an instance number, from one upwards. If the block has no suffix after the IEC or ANSI symbol, the function block has been used, that is, instantiated, only once. The IEDs internal functionality and the external connections are separated with a dashed line presenting the IEDs physical casing.
3.4
3.4.1
Standard configuration A
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the highvoltage (HV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.4.2
Functions
36
1MRS756886 E
Table 8:
Functionality Protection
Stabilized and instantaneous differential protection for two-winding transformers Multi-purpose protection, instance 1 Multi-purpose protection, instance 2 Multi-purpose protection, instance 3 Master trip, instance 1 Master trip, instance 2 HV-side protection Numerical stabilized low impedance restricted earth-fault protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Negative-sequence overcurrent protection, instance 1 Three-phase thermal overload protection for power transformers, two time constants Circuit breaker failure protection LV-side protection Three-phase non-directional overcurrent protection, low stage, instance 2 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 Negative-sequence overcurrent protection, instance 2 Arc protection, instance 1 Arc protection, instance 2 Arc protection, instance 3 Control Disconnector position indication, instance 1 Disconnector position indication, instance 2 Disconnector position indication, instance 3 Earthing switch indication Table continues on next page
3dI>T MAP (1) MAP (2) MAP (3) Master Trip (1) Master Trip (2)
87T MAP (1) MAP (2) MAP (3) 94/86 (1) 94/86 (2)
dIoLo> 3I> (1) 3I>> (1) 3I>>> (1) Io> (1) Io>> (1) I2> (1) 3Ith>T 3I>/Io>BF
87NL 51P-1 (1) 51P-2 (1) 50P/51P (1) 51N-1 (1) 51N-2 (1) 46 (1) 49T 51BF/51NBF
3I> (2) 3I>> (2) 3I>>> (2) I2> (2) ARC (1) ARC (2) ARC (3)
51P-1 (2) 51P-2 (2) 50P/51P (2) 46 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
37
1MRS756886 E
X130 (RTD)
3I I1, I2, I0 In
3I(B)
3.4.2.1
38
1MRS756886 E
Table 10:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
Table 11:
LED 1 2 3 4 5 6 7 8 9 10 11
3.4.2.2
39
1MRS756886 E
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.4.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the neutral current measured between the start point of the transformer and grounding.
3.4.3.1
40
1MRS756886 E
GUID-924EE5B6-2E53-4547-AFEC-2BF37660AA66 V2 EN
Figure 16:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal. For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF. All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
41
1MRS756886 E
GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V2 EN
Figure 17:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side
42 RET615 Application Manual
1MRS756886 E
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1). A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-16AE196B-0ED9-478B-91FB-70CF4A9C0B23 V2 EN
Figure 18:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the high-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 5 is used for non-directional earth-fault protection operate indication.
GUID-A8AB50BA-0D0A-454D-860C-2C721B3793F3 V2 EN
Figure 19:
The configuration includes restricted low-impedance earth-fault protection function for low-voltage side of two-winding power transformers (LREFPNDF1). The numerical differential current stage operates exclusively on earth faults occurring
43
1MRS756886 E
in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
GUID-BEC39E21-713A-434C-88E5-702CA4622699 V2 EN
Figure 20:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-B4800F23-400A-40DF-BAED-A99B116638A5 V2 EN
Figure 21:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
44
1MRS756886 E
GUID-C9527B95-0F59-42C3-A0D1-B468DD54B465 V2 EN
Figure 22:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
45
1MRS756886 E
GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN
Figure 23:
Arc protection
Arc protection (ARCSARC1...3) is included as an optional function. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.4.3.2
46
1MRS756886 E
GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN
Figure 24:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
47
1MRS756886 E
GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN
Figure 25:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
3.4.3.3
48
1MRS756886 E
GUID-FCB8739C-C3C7-4994-BAC6-18BA323962F7 V2 EN
Figure 26:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
49
1MRS756886 E
GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN
Figure 27:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 13: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
50
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
GUID-EF27034F-786A-460C-9350-6A2E02C4A3BC V2 EN
Figure 28:
51
1MRS756886 E
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN
Figure 29:
To increase the sensitivity of the stabilized differential function, the tap position information from the tap changer is connected to the IED via the tap changer position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary inputs of the X130 BIO card or alternatively to the mA input of the RTD card. TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap changer position.
52
1MRS756886 E
3.5
3.5.1
Standard configuration B
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers and numerical restricted earth-fault protection for the low-voltage (LV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.5.2
Functions
Table 14:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Multi-purpose protection, instance 1 Multi-purpose protection, instance 2 Multi-purpose protection, instance 3 Master trip, instance 1 Master trip, instance 2 HV-side protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Negative-sequence overcurrent protection, instance 1 Three-phase thermal overload protection for power transformers, two time constants Circuit breaker failure protection LV-side protection Numerical stabilized low impedance restricted earth-fault protection Three-phase non-directional overcurrent protection, low stage, instance 2 Table continues on next page LREFPNDF1 PHLPTOC2 dIoLo> 3I> (2) 87NL 51P-1 (2) PHLPTOC1 PHHPTOC1 PHIPTOC1 NSPTOC1 T2PTTR1 CCBRBRF1 3I> (1) 3I>> (1) 3I>>> (1) I2> (1) 3Ith>T 3I>/Io>BF 51P-1 (1) 51P-2 (1) 50P/51P (1) 46 (1) 49T 51BF/51NBF TR2PTDF1 MAPGAPC1 MAPGAPC2 MAPGAPC3 TRPPTRC1 TRPPTRC2 3dI>T MAP (1) MAP (2) MAP (3) Master Trip (1) Master Trip (2) 87T MAP (1) MAP (2) MAP (3) 94/86 (1) 94/86 (2)
53
1MRS756886 E
IEC-ANSI 51P-2 (2) 50P/51P (2) 51N-1 (2) 51N-2 (2) 46 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
X130 (RTD)
3I I1, I2, I0
3I(B) In(B)
54
1MRS756886 E
3.5.2.1
Table 16:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
Table 17:
LED 1 2 3 4
55
1MRS756886 E
TCS, fuse failure, measuring circuit fault or circuit breaker supervision Arc protection operate Protection trip from external device
3.5.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.5.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings.
56
1MRS756886 E
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with IoB represents the neutral current measured between the start point of the transformer and grounding.
3.5.3.1
GUID-B811E0D7-9BFE-4C6A-B275-4AE76A09300A V2 EN
Figure 30:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal.
57
1MRS756886 E
For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF. All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
58
1MRS756886 E
GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V2 EN
Figure 31:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side
RET615 Application Manual 59
1MRS756886 E
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1). A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-BEF98714-E04C-4ABF-B846-F8B76D498FC9 V2 EN
Figure 32:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the low-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 5 is used for non-directional earth-fault protection operate indication.
GUID-CF15BA10-B412-4F4B-8A67-99BB35C5BC46 V2 EN
Figure 33:
The configuration includes restricted low-impedance earth-fault protection function for low-voltage side of two-winding power transformers (LREFPNDF1). The numerical differential current stage operates exclusively on earth faults occurring
60
1MRS756886 E
in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
GUID-9A441D12-9499-40BA-BB9A-6BD00E3CC8AC V2 EN
Figure 34:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-B4800F23-400A-40DF-BAED-A99B116638A5 V2 EN
Figure 35:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
61
1MRS756886 E
GUID-EA2D09F5-24DD-45DD-A9FA-C4CA406B2C26 V2 EN
Figure 36:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
62
1MRS756886 E
GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN
Figure 37:
Arc protection
Arc protection (ARCSARC1...3) is included as an optional function. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.5.3.2
63
1MRS756886 E
GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN
Figure 38:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
64
1MRS756886 E
GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN
Figure 39:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
3.5.3.3
65
1MRS756886 E
GUID-03F2EA33-E140-4D1A-869A-386ECA907242 V2 EN
Figure 40:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
66
1MRS756886 E
GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN
Figure 41:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 19: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
67
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
GUID-F547F546-47E2-476E-B058-134B92F109FF V2 EN
Figure 42:
68
1MRS756886 E
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN
Figure 43:
To increase the sensitivity of the stabilized differential function, the tap position information from the tap changer is connected to the IED via the tap changer position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary inputs of the X130 BIO card or alternatively to the mA input of the RTD card. TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap changer position.
69
1MRS756886 E
3.6
3.6.1
Standard configuration C
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers and high impedance based restricted earth-fault protection for the high-voltage (HV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.6.2
Functions
Table 20:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Multi-purpose protection, instance 1 Multi-purpose protection, instance 2 Multi-purpose protection, instance 3 Master trip, instance 1 Master trip, instance 2 HV-side protection High impedance based restricted earthfault protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Negative-sequence overcurrent protection, instance 1 Three-phase thermal overload protection for power transformers, two time constants Table continues on next page HREFPDIF1 PHLPTOC1 PHHPTOC1 PHIPTOC1 EFLPTOC1 EFHPTOC1 NSPTOC1 T2PTTR1 dIoHi> 3I> (1) 3I>> (1) 3I>>> (1) Io> (1) Io>> (1) I2> (1) 3Ith>T 87NH 51P-1 (1) 51P-2 (1) 50P/51P (1) 51N-1 (1) 51N-2 (1) 46 (1) 49T TR2PTDF1 MAPGAPC1 MAPGAPC2 MAPGAPC3 TRPPTRC1 TRPPTRC2 3dI>T MAP (1) MAP (2) MAP (3) Master Trip (1) Master Trip (2) 87T MAP (1) MAP (2) MAP (3) 94/86 (1) 94/86 (2)
70
1MRS756886 E
71
1MRS756886 E
Table 22:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
Table 23:
LED 1 2 3 4
72
1MRS756886 E
3.6.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.6.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings.
73
1MRS756886 E
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the neutral current measured between the start point of the transformer and grounding.
3.6.3.1
GUID-CE6678E5-8383-4CB0-9F75-C1BA8B3662D1 V2 EN
Figure 44:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal.
74
1MRS756886 E
For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF. All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
75
1MRS756886 E
GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V2 EN
Figure 45:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side
76 RET615 Application Manual
1MRS756886 E
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1). A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-405919EB-7FA4-45D9-BCCB-B876E72A6950 V2 EN
Figure 46:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection uses the residual current calculated from the high-voltage side phase currents. All operate signals are connected to the Master Trip 1 and also to the alarm LEDs. LED 5 is used for non-directional earth-fault protection operate indication.
GUID-5CD36CE2-EE91-4A16-A93A-92786B73C331 V2 EN
Figure 47:
The configuration includes restricted high-impedance earth-fault protection function for high-voltage side of two-winding power transformers (HREFPDIF1).
77
1MRS756886 E
The restricted earth-fault current stage operates exclusively on earth faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
GUID-9DCFCF0A-C00E-4642-AA74-CB18F9A2F755 V2 EN
Figure 48:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-B4800F23-400A-40DF-BAED-A99B116638A5 V2 EN
Figure 49:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
78 RET615 Application Manual
1MRS756886 E
GUID-5BF71150-B75E-405A-91CF-87CDF86639BE V2 EN
Figure 50:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
79
1MRS756886 E
GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN
Figure 51:
Arc protection
Arc protection (ARCSARC1...3) is included as an optional function. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.6.3.2
80
1MRS756886 E
GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN
Figure 52:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
81
1MRS756886 E
GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN
Figure 53:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
3.6.3.3
82
1MRS756886 E
GUID-FCB8739C-C3C7-4994-BAC6-18BA323962F7 V2 EN
Figure 54:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
83
1MRS756886 E
GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN
Figure 55:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 25: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
84
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
GUID-EF27034F-786A-460C-9350-6A2E02C4A3BC V2 EN
Figure 56:
85
1MRS756886 E
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN
Figure 57:
To increase the sensitivity of the stabilized differential function, the tap position information from the tap changer is connected to the IED via the tap changer position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary inputs of the X130 BIO card or alternatively to the mA input of the RTD card. TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap changer position.
86
1MRS756886 E
3.7
3.7.1
Standard configuration D
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers and high impedance based restricted earth-fault protection for the low-voltage (LV) side. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.7.2
Functions
Table 26:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Multi-purpose protection, instance 1 Multi-purpose protection, instance 2 Multi-purpose protection, instance 3 Master trip, instance 1 Master trip, instance 2 HV-side protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Negative-sequence overcurrent protection, instance 1 Three-phase thermal overload protection for power transformers, two time constants Circuit breaker failure protection LV-side protection High impedance based restricted earthfault protection Three-phase non-directional overcurrent protection, low stage, instance 2 Table continues on next page HREFPDIF1 PHLPTOC2 dIoHi> 3I> (2) 87NH 51P-1 (2) PHLPTOC1 PHHPTOC1 PHIPTOC1 NSPTOC1 T2PTTR1 CCBRBRF1 3I> (1) 3I>> (1) 3I>>> (1) I2> (1) 3Ith>T 3I>/Io>BF 51P-1 (1) 51P-2 (1) 50P/51P (1) 46 (1) 49T 51BF/51NBF TR2PTDF1 MAPGAPC1 MAPGAPC2 MAPGAPC3 TRPPTRC1 TRPPTRC2 3dI>T MAP (1) MAP (2) MAP (3) Master Trip (1) Master Trip (2) 87T MAP (1) MAP (2) MAP (3) 94/86 (1) 94/86 (2)
87
1MRS756886 E
IEC-ANSI 51P-2 (2) 50P/51P (2) 51N-1 (2) 51N-2 (2) 46 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
X130 (RTD)
3I I1, I2, I0
3I(B) In(B)
88
1MRS756886 E
3.7.2.1
Table 28:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
Table 29:
LED 1 2 3 4
89
1MRS756886 E
TCS, fuse failure, measuring circuit fault or circuit breaker supervision Arc protection operate Protection trip from external device
3.7.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.7.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings.
90
1MRS756886 E
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the neutral current measured between the start point of the transformer and grounding.
3.7.3.1
GUID-99A6097A-7411-40E3-B6CE-694B1246D4B9 V3 EN
Figure 58:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal.
91
1MRS756886 E
For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF. All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
92
1MRS756886 E
GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V2 EN
Figure 59:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side
RET615 Application Manual 93
1MRS756886 E
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1). A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-9EA539DB-B9C7-4C3D-BFF4-810F66403743 V2 EN
Figure 60:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection uses the residual current calculated from the low-voltage side phase currents. All operate signals are connected to the Master Trip 2 and also to the alarm LEDs. LED 5 is used for non-directional earth-fault protection operate indication.
GUID-5CD36CE2-EE91-4A16-A93A-92786B73C331 V2 EN
Figure 61:
The configuration includes restricted high-impedance earth-fault protection function for low-voltage side of two-winding power transformers (HREFPDIF1). The restricted earth-fault current stage operates exclusively on earth faults
94
1MRS756886 E
occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
GUID-9DCFCF0A-C00E-4642-AA74-CB18F9A2F755 V2 EN
Figure 62:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-B4800F23-400A-40DF-BAED-A99B116638A5 V2 EN
Figure 63:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
95
1MRS756886 E
GUID-6566AA82-9287-4D87-B41C-F9D0BE9B63A0 V2 EN
Figure 64:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
96
1MRS756886 E
GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN
Figure 65:
Arc protection
Arc protection (ARCSARC1...3) is included as an optional function. The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.7.3.2
97
1MRS756886 E
GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN
Figure 66:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
98
1MRS756886 E
GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN
Figure 67:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
3.7.3.3
99
1MRS756886 E
GUID-03F2EA33-E140-4D1A-869A-386ECA907242 V2 EN
Figure 68:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
100
1MRS756886 E
GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN
Figure 69:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 31: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
101
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
GUID-F547F546-47E2-476E-B058-134B92F109FF V2 EN
Figure 70:
102
1MRS756886 E
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN
Figure 71:
To increase the sensitivity of the stabilized differential function, the tap position information from the tap changer is connected to the IED via the tap changer position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary inputs of the X130 BIO card or alternatively to the mA input of the RTD card. TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap changer position.
103
1MRS756886 E
3.8
3.8.1
Standard configuration E
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers and numerical restricted earth-fault protection for the high-voltage (HV) side, phase-voltage based protection and measurement functions. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.8.2
Functions
Table 32:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Master trip, instance 1 Master trip, instance 2 HV-side protection Numerical stabilized low impedance restricted earth-fault protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Negative-sequence overcurrent protection, instance 1 Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Three-phase undervoltage protection, instance 1 Table continues on next page LREFPNDF1 PHLPTOC1 PHHPTOC1 PHIPTOC1 EFLPTOC1 EFHPTOC1 NSPTOC1 ROVPTOV1 ROVPTOV2 PHPTUV1 dIoLo> 3I> (1) 3I>> (1) 3I>>> (1) Io> (1) Io>> (1) I2> (1) Uo> (1) Uo> (2) 3U< (1) 87NL 51P-1 (1) 51P-2 (1) 50P/51P (1) 51N-1 (1) 51N-2 (1) 46 (1) 59G (1) 59G (2) 27 (1) TR2PTDF1 TRPPTRC1 TRPPTRC2 3dI>T Master Trip (1) Master Trip (2) 87T 94/86 (1) 94/86 (2)
104
1MRS756886 E
105
1MRS756886 E
3I(B)
3.8.2.1
Table 34:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
106
1MRS756886 E
Table 35:
LED 1 2 3 4 5 6 7 8 9 10 11
3.8.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.8.3
Functional diagrams
107
1MRS756886 E
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the measured neutral current measured between the start point of the transformer and grounding.
3.8.3.1
108
1MRS756886 E
GUID-B444DCDF-F010-467A-9B00-07C1E37207B9 V1 EN
Figure 72:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal. For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF.
109
1MRS756886 E
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
GUID-2AF3E8AD-2FB2-4C2B-9855-52DDE5B57495 V1 EN
Figure 73:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side (PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1).
110
1MRS756886 E
A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-B50BF279-890D-479D-9E31-F71C6D852AA5 V1 EN
Figure 74:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the low-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 3 is used for non-directional earth-fault protection operate indication.
GUID-9E516077-7D60-44B0-AE40-8A6C17B43B4B V1 EN
Figure 75:
The configuration includes restricted low-impedance earth-fault protection function for high-voltage side of two-winding power transformers (LREFPNDF1). The numerical differential current stage operates exclusively on earth faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
111
1MRS756886 E
GUID-CEDAF363-53D4-4C49-B570-C78AC13DDF82 V1 EN
Figure 76:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-6FC50ECB-7261-420F-9F79-F09F274A823D V1 EN
Figure 77:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
112
1MRS756886 E
GUID-F10B950D-2141-44DC-9107-3983DD3234EA V1 EN
Figure 78:
Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.
GUID-C53C6AD2-061B-4483-9931-A227EFF66AA8 V1 EN
Figure 79:
The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. The operation signal is connected to alarm LED 5.
113
1MRS756886 E
GUID-0D218E13-46B7-4299-A30C-793B72E43572 V1 EN
Figure 80:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-3AEB5B1A-9FE5-40E3-A199-F976B4127C87 V1 EN
Figure 81:
Arc protection
114
1MRS756886 E
The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.8.3.2
GUID-8A18CD3E-F811-4A8A-B01B-BC38004F1891 V1 EN
Figure 82:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
115
1MRS756886 E
GUID-2D158BA9-0D4F-4389-8D6A-FE415C4EDD91 V1 EN
Figure 83:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
GUID-5495E5E0-2282-4370-A0BA-D8B4649B9E22 V1 EN
Figure 84:
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as open miniature circuit breaker, are detected and the alarm is connected to supervision alarm LED 9. The generic operation time counter function MDSOPT calculates accumulated operation time of the transformer. The alarm is connected to the alarm LED 9.
3.8.3.3
116
1MRS756886 E
GUID-EC39937B-DB3E-4F77-A4FA-6949E5EF777A V1 EN
Figure 85:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
117
1MRS756886 E
GUID-D85EB0CA-9C9F-4847-ABB7-3CA9C740EC80 V1 EN
Figure 86:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 37: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
118
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
119
1MRS756886 E
GUID-3FBEA8E7-F72F-43CD-B4E5-68582DAC6B7E V1 EN
Figure 87:
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
120
1MRS756886 E
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
3.9
3.9.1
Standard configuration F
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection for the lowvoltage (LV) side, phase-voltage based protection and measurement functions. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.9.2
Functions
Table 38:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Master trip, instance 1 Master trip, instance 2 HV-side protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Negative-sequence overcurrent protection, instance 1 Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Three-phase undervoltage protection, instance 1 Table continues on next page PHLPTOC1 PHHPTOC1 PHIPTOC1 NSPTOC1 ROVPTOV1 ROVPTOV2 PHPTUV1 3I> (1) 3I>> (1) 3I>>> (1) I2> (1) Uo> (1) Uo> (2) 3U< (1) 51P-1 (1) 51P-2 (1) 50P/51P (1) 46 (1) 59G (1) 59G (2) 27 (1) TR2PTDF1 TRPPTRC1 TRPPTRC2 3dI>T Master Trip (1) Master Trip (2) 87T 94/86 (1) 94/86 (2)
121
1MRS756886 E
87NL 51P-1 (2) 51P-2 (2) 50P/51P (2) 51N-1 (2) 51N-2 (2) 46 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
122
1MRS756886 E
3.9.2.1
Table 40:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1
1MRS756886 E
Table 41:
LED 1 2 3 4 5 6 7 8 9 10 11
3.9.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the
124
1MRS756886 E
connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.9.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the measured neutral current measured between the start point of the transformer and grounding.
3.9.3.1
125
1MRS756886 E
GUID-049BD680-D526-4585-9682-7A11A034434A V1 EN
Figure 88:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal. For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF.
126
1MRS756886 E
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
GUID-41BDB2C0-0742-4475-8348-A0B65198AAD7 V1 EN
Figure 89:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side (PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1).
127
1MRS756886 E
A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-D2C7FF7C-75CF-40CA-85A4-D59967FD7E85 V1 EN
Figure 90:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the low-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 3 is used for non-directional earth-fault protection operate indication.
GUID-3EC397CB-3B6C-4F34-88B2-184F75F355AD V1 EN
Figure 91:
The configuration includes restricted low-impedance earth-fault protection function for low-voltage side of two-winding power transformers (LREFPNDF1). The numerical differential current stage operates exclusively on earth faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
128
1MRS756886 E
GUID-6CADBBD9-E389-48FA-B63E-DCE207E3AC11 V1 EN
Figure 92:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-4A274797-A978-427C-A646-19421DB3AC6A V1 EN
Figure 93:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
129
1MRS756886 E
GUID-B1AE475D-8F14-4510-B9EC-D84AA7EC66E6 V1 EN
Figure 94:
Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.
GUID-6D0DF1EB-1B51-40A1-A973-E53F30969D4A V1 EN
Figure 95:
The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. The operation signal is connected to alarm LED 5.
130
1MRS756886 E
GUID-7B01B31F-4C73-4908-9228-25A007A8F10D V1 EN
Figure 96:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-941081CB-1566-42DA-83EA-06B53C531D88 V1 EN
Figure 97:
Arc protection
131
1MRS756886 E
The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.9.3.2
GUID-6A46C2D2-1109-4E77-99AE-D47F6BB4B375 V1 EN
Figure 98:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
132
1MRS756886 E
GUID-3F90CE14-EF57-48E1-81F0-85F37C06B26B V1 EN
Figure 99:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
GUID-9A8E1D37-4EE6-489B-B930-1DE6BB24978B V1 EN
Figure 100:
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as open miniature circuit breaker, are detected and the alarm is connected to supervision alarm LED 9. The generic operation time counter function MDSOPT calculates accumulated operation time of the transformer. The alarm is connected to the alarm LED 9.
3.9.3.3
133
1MRS756886 E
GUID-A3B7EF01-A345-4D54-8BA0-7E370EE20E2B V1 EN
Figure 101:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
134
1MRS756886 E
GUID-D53DC028-0381-4E85-BCCC-08B0E168B6D2 V1 EN
Figure 102:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 43: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
135
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
136
1MRS756886 E
GUID-FA535501-759C-48BA-A909-76336E08EED8 V1 EN
Figure 103:
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
137
1MRS756886 E
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
3.10
3.10.1
Standard configuration G
Applications
The standard configuration includes three-phase differential, short-circuit, overcurrent, earth-fault, thermal overload, voltage and negative-phase sequence protection in power transformer feeders. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.10.2
Functions
Table 44:
Functionality Protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, low stage, instance 2 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 2 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 2 Non-directional earth-fault protection, low stage, instance 1 Non-directional earth-fault protection, high stage, instance 1 Negative-sequence overcurrent protection, instance 1 Negative-sequence overcurrent protection, instance 2 Table continues on next page PHLPTOC1 PHLPTOC2 PHHPTOC1 PHHPTOC2 PHIPTOC1 PHIPTOC2 EFLPTOC1 EFHPTOC1 NSPTOC1 NSPTOC2 3I> (1) 3I> (2) 3I>> (1) 3I>> (2) 3I>>> (1) 3I>>> (2) Io> (1) Io>> (1) I2> (1) I2> (2) 51P-1 (1) 51P-1 (2) 51P-2 (1) 51P-2 (2) 50P/51P (1) 50P/51P (2) 51N-1 (1) 51N-2 (1) 46 (1) 46 (2)
138
1MRS756886 E
139
1MRS756886 E
3.10.2.1
Table 46:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1 X110-SO2 X110-SO3 X110-SO4
140
1MRS756886 E
Table 47:
LED 1 2 3 4 5 6 7 8 9 10 11
3.10.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
141
1MRS756886 E
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the measured neutral current measured between the start point of the transformer and grounding.
3.10.3.1
142
1MRS756886 E
GUID-56FA9AE4-C0DC-4E61-9BA2-D01B4DE65687 V1 EN
Figure 104:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal. For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF.
143
1MRS756886 E
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
GUID-D8FD1F06-95D6-427E-9975-B41130865CFF V1 EN
Figure 105:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side (PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1).
144
1MRS756886 E
A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-B2CBE815-01C2-4856-8BC1-426815374D99 V1 EN
Figure 106:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the low-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 3 is used for non-directional earth-fault protection operate indication.
GUID-E2C14CE9-1974-4C13-8AE2-7A062ADF68A0 V1 EN
Figure 107:
The configuration includes restricted high-impedance earth-fault protection function for high-voltage side of two-winding power transformers (HREFPDIF1). The restricted earth-fault current stage operates exclusively on earth faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
145
1MRS756886 E
GUID-AAA89F5C-737E-460E-8B01-A45F56A945C7 V1 EN
Figure 108:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-CA2DCDB9-3DFA-4CAE-BE98-5EA5923BDB0D V1 EN
Figure 109:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
146
1MRS756886 E
GUID-8C4ECD1A-D84A-4B87-BAE8-54A1686E161E V1 EN
Figure 110:
Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.
GUID-724B9856-A0F8-4711-AD17-B458C4265512 V1 EN
Figure 111:
The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. The operation signal is connected to alarm LED 5.
147
1MRS756886 E
GUID-B178FFDE-45CA-4546-8D8A-645837AC21CB V1 EN
Figure 112:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-17B182C7-7A27-4F4D-BB00-6980945E453E V1 EN
Figure 113:
Arc protection
148
1MRS756886 E
The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.10.3.2
GUID-D068A0A3-49B4-4D02-95D1-3DF5F46EAB74 V1 EN
Figure 114:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
149
1MRS756886 E
GUID-696685EC-212D-4526-825C-91DCCF4A7134 V1 EN
Figure 115:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
GUID-0A88DBE8-B765-4A96-8BBB-BD824159B0AF V1 EN
Figure 116:
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as open miniature circuit breaker, are detected and the alarm is connected to supervision alarm LED 9. The generic operation time counter function MDSOPT calculates accumulated operation time of the transformer. The alarm is connected to the alarm LED 9.
150
1MRS756886 E
3.10.3.3
GUID-1EC3ED90-6920-4B83-B947-B4DFDFC83D59 V1 EN
Figure 117:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
151
1MRS756886 E
GUID-42E5CCDE-2D8E-4E27-83C9-65C3707B10AC V1 EN
Figure 118:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 49: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
152
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
153
1MRS756886 E
GUID-8C2D5158-3D5A-4E47-9909-25903815F026 V1 EN
Figure 119:
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
154
1MRS756886 E
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
3.11
3.11.1
Standard configuration H
Applications
The standard configuration includes three-phase transformer differential protection for two-winding transformers, high impedance based restricted earth-fault protection for the low-voltage (LV) side, phase voltage based protection and measurement functions. The standard configuration is mainly intended for protection of the power transformer between current transformers. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.11.2
Functions
Table 50:
Functionality Protection Stabilized and instantaneous differential protection for two-winding transformers Master trip, instance 1 Master trip, instance 2 HV-side protection High impedance based restricted earthfault protection Three-phase non-directional overcurrent protection, low stage, instance 1 Three-phase non-directional overcurrent protection, high stage, instance 1 Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 Negative-sequence overcurrent protection, instance 1 Residual overvoltage protection, instance 1 Residual overvoltage protection, instance 2 Table continues on next page HREFPDIF1 PHLPTOC1 PHHPTOC1 PHIPTOC1 NSPTOC1 ROVPTOV1 ROVPTOV2 dIoHi> 3I> (1) 3I>> (1) 3I>>> (1) I2> (1) Uo> (1) Uo> (2) 87NH 51P-1 (1) 51P-2 (1) 50P/51P (1) 46 (1) 59G (1) 59G (2) TR2PTDF1 TRPPTRC1 TRPPTRC2 3dI>T Master Trip (1) Master Trip (2) 87T 94/86 (1) 94/86 (2)
155
1MRS756886 E
51P-1 (2) 51P-2 (2) 50P/51P (2) 51N-1 (2) 51N-2 (2) 46 (2) 50L/50NL (1) 50L/50NL (2) 50L/50NL (3)
156
1MRS756886 E
3.11.2.1
Table 52:
Binary output X100-PO1 X100-PO2 X100-SO1 X100-SO2 X100-PO3 X100-PO4 X110-SO1
1MRS756886 E
Table 53:
LED 1 2 3 4 5 6 7 8 9 10 11
3.11.2.2
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering settings are selected depending on the
158
1MRS756886 E
connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by default.
3.11.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and functionto-function connections. The default connections can be viewed and changed with PCM600 according to the application requirements, if necessary. The analog channels have fixed connections towards the different function blocks inside the IEDs standard configuration. Exceptions from this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable and a part of the disturbance recorders parameter settings. The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase currents of the high-voltage side of the transformer and 3IB represents the three phase currents of the low-voltage side of the transformer. The signal marked with Io represents the measured neutral current measured between the start point of the transformer and grounding.
3.11.3.1
159
1MRS756886 E
GUID-1603E90A-FED5-4063-9307-8D4F62D42921 V1 EN
Figure 120:
The stabilized and instantaneous differential protection for 2Wtransformers (TR2PTDF1) provides protection of power transformer unit including, for example, winding short-circuit and interturn faults. The IED compares the phase currents on both sides of the object to be protected. If the differential current of the phase currents in one of the phases exceed the setting of the stabilized operation characteristic or the instantaneous protection stage of the function, the function provides an operate signal. For transformers having an on-line tap changer, the tap position information is recommended to be used in differential protection, as the ratio difference of tap changer movements can be corrected in TR2PTDF.
160
1MRS756886 E
All operate signals are connected to the Master Trip 1 and 2 and also to the alarm LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for instantaneous high-stage of the differential protection.
GUID-9FF363C0-C581-47D7-9218-36121D6B5285 V1 EN
Figure 121:
Three stages for both high-voltage and low-voltage sides as a total of six overcurrent stages are offered for overcurrent and short-circuit protection. The highvoltage side high stage (PHHPTOC1) can be blocked by energizing the binary input 1 (X120:1-2) or by starting the high stage of the low-voltage side (PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by activating the binary input (X120_BI1).
161
1MRS756886 E
A selective backup overcurrent protection can be achieved by using blockings between high-voltage side and low-voltage side overcurrent stages. This kind of blocking scheme enables coordinated overlapping of overcurrent protection zones. The operate of the overcurrent protection functions is connected to the output SO1 (X110:14-15-16). This output is used for giving a specific alarm of the overcurrent protection operation.
GUID-0030A115-1F44-480C-9D60-7DC6DC91D081 V1 EN
Figure 122:
Two stages are offered for non-directional earth-fault protection. The earth-fault protection measures the neutral current of the low-voltage side. All operate signals are connected to the Master Trip as well as to the alarm LEDs. LED 3 is used for non-directional earth-fault protection operate indication.
GUID-9D9E76F8-547A-4D73-930F-D2DB10081970 V1 EN
Figure 123:
The configuration includes restricted high-impedance earth-fault protection function for low-voltage side of two-winding power transformers (HREFPDIF1). The restricted earth-fault current stage operates exclusively on earth faults occurring in the protected area, that is, in the area between the phase and neutral current transformers. An earth fault in this area appears as a differential current between the residual current of the phase currents and the neutral current of the conductor between the star-point of the transformer and earth.
162
1MRS756886 E
GUID-6EF3B245-3E4E-4D0B-8F72-384C074F85CE V1 EN
Figure 124:
NSPTOC is designed for negative-phase sequence protection whenever the operating characteristic is appropriate. It is applied for the protection of transformers against thermal stress and damage. NSPTOC1 measures negative-sequence current from the high-voltage side and NSPTOC2 from the low-voltage side.
GUID-FB2F2B5B-9009-4903-8A73-6225E8DF03DE V1 EN
Figure 125:
Three-phase thermal overload protection for power transformers (T2PTTR1) provides indication on overload situations. The operate signal of the thermal overload protection is connected to the Master Trip 2. LED 7 is used for the thermal overload protection alarm indication, the same as for negative-sequence overcurrent protection operate indication.
163
1MRS756886 E
GUID-DFAAC066-D9D5-4188-B371-1A2DE2CACF4B V1 EN
Figure 126:
Three overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV) offer protection against abnormal phase voltage conditions. The operation of voltage functions is connected to alarm LED 3. A failure in the voltage measuring circuit is detected by the fuse failure function and the activation is connected to undervoltage protection functions to avoid faulty undervoltage tripping.
GUID-3A11CB90-5E73-488A-8D9B-362487AE218B V1 EN
Figure 127:
The residual overvoltage protection (ROVPTOV) provides earth-fault protection by detecting abnormal level of residual voltage. The operation signal is connected to alarm LED 5.
164
1MRS756886 E
GUID-93238FE5-8F1B-4398-B3FB-0EDEE60DE2B5 V1 EN
Figure 128:
The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input by a number of different protection stages in the IED. CCBRBRF1 offers different operating modes associated with the circuit-breaker position and the measured phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping its own circuit breaker through the Master Trip Logic 2. The TRBU output is used for retripping both the high-voltage and low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU) operate indication.
GUID-D3FFC16D-D97F-4EB5-B851-677E2E41CE9E V1 EN
Figure 129:
Arc protection
165
1MRS756886 E
The arc protection offers individual function blocks for three arc sensors that can be connected to the IED. Each arc protection function block has two different operation modes, with or without the phase and residual current check. Operate signals from the arc protection function blocks are connected to the Master Trip and also to the alarm LED 10 as a common operate indication.
3.11.3.2
GUID-A788BFC0-0EBA-4451-AC0B-6D56B37ADEB4 V1 EN
Figure 130:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the ARC protection signals and the four binary inputs from X110 are also connected.
166
1MRS756886 E
GUID-29073B9E-44C7-4622-AB1E-6ECBBF6FAF0F V1 EN
Figure 131:
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact.
GUID-F6B3D3D0-6A64-4852-8533-6491AC0D8DB5 V1 EN
Figure 132:
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. Failures, such as open miniature circuit breaker, are detected and the alarm is connected to supervision alarm LED 9. The generic operation time counter function MDSOPT calculates accumulated operation time of the transformer. The alarm is connected to the alarm LED 9.
3.11.3.3
167
1MRS756886 E
GUID-B306F9D8-14BC-42A3-9C3D-2190AB0468FB V1 EN
Figure 133:
Master Trip
The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip to enable external reset with a push button. The external trip indication is connected also to the alarm LED 11.
168
1MRS756886 E
GUID-8335EE7E-3951-434C-8B1D-D19DD3FEF1C6 V1 EN
Figure 134:
There are three disconnector status blocks (DCSXSWI13) available in the IED. The remaining two not described in the functional diagram are available in PCM600 for connection where applicable. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication.
Table 55: Device positions indicated by binary inputs 5 and 6
Input to be energized Input 5 (X110:8-9) Busbar disconnector closed Busbar disconnector open Circuit breaker truck in service position Circuit breaker truck in test position x x x x Input 6 (X110:10-9)
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector position status and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from the DCSXSWI block defines if the disconnector or the breaker truck is definitely either open (in test position) or close (in service position). This, together with non-active trip signal and non-active gas pressure alarm, activates the close-enable signal to the circuit-breaker control function block. The open operation is always enabled.
169
1MRS756886 E
The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE and BLK_CLOSE signals are completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 9.
170
1MRS756886 E
GUID-81A0A8A4-B3F6-4571-AE68-1B5B24260E95 V1 EN
Figure 135:
The signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100:13-15) Operation (trip) of differential protection function SO1 (X110:14-15-16) Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-18-19) Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-21-22) Operation (trip) of thermal or current negative-sequence protection function SO4 (X110:23-24)
171
1MRS756886 E
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable.
172
1MRS756886 E
Section 4
4.1
4.1.1
Current transformers
Current transformer requirements for non-directional overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be chosen carefully. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity, and co-ordination of protection. However, when the CT is correctly selected, a fast and reliable short circuit protection can be enabled. The selection of a CT depends not only on the CT specifications but also on the network fault current magnitude, desired protection objectives, and the actual CT burden. The protection settings of the IED should be defined in accordance with the CT performance as well as other factors.
4.1.1.1
5P 10P
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protection. The 5P class provides a better accuracy. This should be noted also if there are accuracy requirements for the metering functions (current metering, power metering, and so on) of the IED.
173
1MRS756886 E
The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy. Beyond this level, the secondary current of the CT is distorted and it might have severe effects on the performance of the protection IED. In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limit factor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden. The actual accuracy limit factor is calculated using the formula:
Fa Fn
A071141 V1 EN
Sin + Sn Sin + S
Fn Sin S
the accuracy limit factor with the nominal external burden Sn the internal secondary burden of the CT the actual external burden
4.1.1.2
174
1MRS756886 E
The factor 0.7 takes into account the protection IED inaccuracy, current transformer errors, and imperfections of the short circuit calculations. The adequate performance of the CT should be checked when the setting of the high set stage overcurrent protection is defined. The operate time delay caused by the CT saturation is typically small enough when the overcurrent setting is noticeably lower than Fa. When defining the setting values for the low set stages, the saturation of the CT does not need to be taken into account and the start current setting is simply according to the formula.
4.1.1.3
175
1MRS756886 E
A071142 V1 EN
Figure 136:
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59. The start current setting for low-set stage (3I>) is selected to be about twice the nominal current of the cable. The operate time is selected so that it is selective with the next IED (not visible in the figure above). The settings for the high-set stage and instantaneous stage are defined also so that grading is ensured with the downstream protection. In addition, the start current settings have to be defined so that the IED operates with the minimum fault current and it does not operate with the maximum load current. The settings for all three stages are as in the figure above. For the application point of view, the suitable setting for instantaneous stage (I>>>) in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the criteria given by the current transformer selection formula is fulfilled and also the IED setting is considerably below the Fa. In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons.
176
1MRS756886 E
Section 5
5.1
5.1.1
5.1.1.1
Inputs
Energizing inputs
Phase currents
The IED can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied. However, at least terminals X120/7-8 must be connected.
Table 57:
Terminal X120-1, 2 X120-3, 4 X120-5, 6 X120-7, 8 X120-9, 10 X120-11, 12
Phase currents
Description IL1B IL2B IL3B IL1 IL2 IL3
5.1.1.2
Residual current
Table 58:
Terminal X120-13, 14
5.1.1.3
Phase voltages
Table 59:
Terminal X130-11, 12 X130-13, 14 X130-15, 16
177
1MRS756886 E
5.1.2
RTD/mA inputs
RTD/mA inputs are optional for configurations A, B, C and D.
Table 61:
Terminal X130-1 X130-2 X130-3 X130-4 X130-5 X130-6 X130-7 X130-8 X130-9 X130-10 X130-11 X130-12 X130-13 X130-14 X130-15 X130-16 X130-17 X130-18 1) Common ground for RTD channels 1-3. 2) Common ground for RTD channels 4-6.
RTD/mA inputs
Description mA1 (AI1), + mA1 (AI1), mA2 (AI2), + mA2 (AI2), RTD1 (AI3), + RTD1 (AI3), RTD2 (AI4), + RTD2 (AI4), RTD3 (AI5), + RTD3 (AI5), Common1) Common2) RTD4 (AI6), + RTD4 (AI6), RTD5 (AI7), + RTD5 (AI7), RTD6 (AI8), + RTD6 (AI8), -
5.1.3
178
1MRS756886 E
5.1.4
Table 64:
Terminal X120-1 X120-2 X120-3 X120-2 X120-4 X120-2 X120-5 X120-6
179
1MRS756886 E
Table 65:
Terminal X130-1 X130-2 X130-2 X130-3 X130-4 X130-5 X130-5 X130-6 X130-7 X130-8 X130-8 X130-9
5.1.5
180
1MRS756886 E
Table 67:
Terminal X13 X14 X15
5.2
5.2.1
Outputs
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. On delivery from the factory, the trip signals from all the protection stages are routed to PO3 and PO4.
Table 68:
Terminal X100-6 X100-7 X100-8 X100-9 X100-15 X100-16 X100-17 X100-18 X100-19 X100-20 X100-21 X100-22 X100-23 X100-24
Output contacts
Description PO1, NO PO1, NO PO2, NO PO2, NO PO3, NO (TCS resistor) PO3, NO PO3, NO PO3 (TCS1 input), NO PO3 (TCS1 input), NO PO4, NO (TCS resistor) PO4, NO PO4, NO PO4 (TCS2 input), NO PO4 (TCS2 input), NO
5.2.2
181
1MRS756886 E
Table 69:
Terminal X100-10 X100-11 X100-12 X100-13 X100-14
Table 70:
Terminal X110-14 X110-15 X110-16 X110-17 X110-18 X110-19 X110-20 X110-21 X110-22 X110-23 X110-24
Output contacts of slot X130 are available in the optional BIO module (BIOB02A). Output contacts of slot X130 are optional for configurations A, B, C and D.
Table 71:
Terminal X130-10 X130-11 X130-12 X130-13 X130-14 X130-15 X130-16 X130-17 X130-18
182
1MRS756886 E
5.2.3
IRF contact
Description IRF, common Closed; IRF, or Uaux disconnected Closed; no IRF, and Uaux connected
183
184
1MRS756886 E
Section 6 Glossary
Section 6
Glossary
American National Standards Institute American Standard Code for Information Interchange Current transformer A distributed network protocol originally developed by Westronic. The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution. Electromagnetic compatibility Generic Object Oriented Substation Event Human-machine interface International Electrotechnical Commission Communication standard for protective equipment; A serial master/slave protocol for point-to-point communication International standard for substation communication and modelling Intelligent electronic device A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol. Local area network Connector type for glass fibre cable Liquid crystal display Light-emitting diode Local human-machine interface A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Modbus RTU protocol which uses TCP/IP and Ethernet to carry data between devices Protection and Control IED Manager Power output Galvanic connector type
185
Section 6 Glossary
1MRS756886 E
Remote terminal unit Simplified notation for representing a three-phase power system. Instead of representing each of three phases with a separate line or terminal, only one conductor is represented. Wide area network Web human-machine interface
WAN WHMI
186
187
Contact us
ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 Fax +358 10 22 41094
ABB Limited Distribution Automation Maneja Vadodara 390013, India Phone +91 265 2604032 Fax +91 265 2638922
ABB Transmission and Distribution Automation Equipment (Xiamen) Co. Ltd. ABB Industrial Park, Torch Hi-tech Development Zone 361006 Xiamen, Fujian, China Phone +86 592 5702288 Fax +86 592 5718598 www.abb.com/substationautomation