The D7044 Multiplex Singleinput Module connects a normallyopen (NO) contact to the multiplex bus of a D7024, DS9400M, or FPD7024 Addressable Fire Alarm Control Panel (FACP). Use the D7044 supervised input in a Class B configuration. All operating power for the input module is drawn from the FACP. Note D7024 and DS9400M are not listed under UL864, 9th edition.
Rotary switches allow convenient address setting. An onboard status LED on the module indicates normal, alarm, and trouble conditions and is visible on the module or on an attractive, lowprofile faceplate.
Installation/Configuration Notes
Compatible Products The following products are compatible with the D7044 Multiplex Singleinput Module:
www.boschsecurity.com
Product Description Addressable FACP Addressable FACP for export Addressable FACP Addressable FACP Multiplex expansion module
Mechanical Properties Color: Dimensions: Material: Weight: White 4.3125 in. (10.9 cm) square by 1.0625 in. (2.7 cm) deep ABS plastic 3.9 oz (110 g)
Modules Mounting
D7039
Power Requirements (supplied from FACP's MUX bus) Current: Voltage (minimum): 0.55 mA 8 V peak (12 VDC nominal)
Mount the D7044 on a doublegang or fourinch square back box. Wiring Make connections to the terminals on the rear of the D7044. All terminals can accommodate up to 12 AWG (2.3 mm) wire; however, follow wiring guidelines specified by the National Electrical Code (NFPA-70). All wiring is power limited and supervised. Note Supervise the input loop with the supplied EOL resistor.
Ordering Information
D7044 Multiplex Singleinput Module Connects a normallyopen (NO) contact to the multiplex bus of a D7024, DS9400M, or FPD7024 Addressable FACP D7044
Parts Included
Quant. 1 1 1 1 Component D7044 module 2.21 k endofline (EOL) resistor (P/N: 25899) Literature pack Hardware pack
Technical Specifications
Circuit Designation MUX Bus: Input: Supervised Class A (Style 6) SLC or Class B (Style 4) SLC Supervised Class B (Style B) IDC
Environmental Considerations Environment: Relative Humidity: Temperature (operating): Input Type: One normallyopen (NO) contact input supervised by a 2.21 k EOL resistor (P/N: 25899) Indoor, dry Up to 93% noncondensing +32F to +120F (0C to +49C)
Americas: Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Europe, Middle East, Africa: Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Asia-Pacific: Represented by Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.com
Bosch Security Systems Inc. 2010 | Data subject to change without notice T1312426379 | Cur: en-US, V6, 4 Jul 2010