Dry-type Transformer
en.chintelectric.com
2011/2012
Dry-type Transformer
Brief Introduction
About CHINT T&D CHINT T&D is a branch company of CHINT Group Corporation. Covering 900,000m2, with an investment of 450 million USD. CHINT T&D has one of the world largest power transmission & distribution equipment manufacturing centers in Shanghai. Sales Turnover Around 535 million USD in the year of 2010 Employee 4,300 employees
Product Range Power Transformer up to 750kV Distribution Transformer up to 35kV Dry-type Transformer up to 35kV Reactor up to 220kV GIS up to 252kV HV Circuit Breaker & Disconnector up to 252kV VCB 12~40.5kV MV & LV Switchgear Panel, Prifabricated Substation up to 40.5kV LV T erminal Box, Bus Bar Duct Surge Arrester & Insulator up to 500kV, CT & PT up to 220kV Power Distribution Automation System Cable up to 36kV Capacitor Turn-key Solution About CHINT Group CHINT is the leading player in the Power Transmission & Distribution industry and Low-voltage electrics industry in China. Founded in 1984 by a few local entrepreneurs and currently hiring 18,000 employees worldwide. Ranked in The 2011 BCG 100 New Global Challengers (The Boston Consulting Group, 2011) CHINT Low-voltage Electrics launched IPO at the Shanghai Stock Exchange of China (2010) No.2 in China Electricity Industry's Top 10 Most Competitive Enterprises (China Machinery Industry Information Institute, 2009) No.3 in China Electricity Industry(China Machinery Industry Information Institute, 2009) No.240 in Top 500 Chinese-Companies (China Enterprise Federation, 2009). No.1 in Power T&D and the controlling devices (China Machinery Summit, 2009) Ranked in Top 100 Best Employers in China (China Entrepreneurs Summit, 2008) No.15 in Top 100 Private & Public Companies in China (Forbes, 2006) National Quality Management Award(2004) (One of top honours for manufacturing companies in China) Worldwide business operation with 2,000 sales offices, agents, distributors, and local partners in domestic Chinese market and distributors & local partners in over 105 countries. International branches or regional offices set up in USA, UAE, Germany, Russia, Brazil, Ukraine, Hong Kong of China, UK and Nigeria. CHINT stretches its business to a new frontier of solar energy by setting up a branch company specialized in the solar energy products development. The R&D center of CHINT is recognized as the National Level R&D Center run by the companies, which means the R&D level of CHINT Group has reached the leading position in the industry of China.
Table of Contents
Dry-type Transformer
1. General 2. Technical Feature 3. Structure Feature 4. Component 5. Quality Management, Product Certificate, After-sales Service 6. Customer-oriented Support System 7. Main Technical Data Epoxy Resin Cast Dry-type Transformer SC(B)9-30~2500/10 SC(B)9-50~2500/20 SC(B)9-50~2500/35 SC(B)9-800~20000/35 H-class Impregnated Insulated Dry-type Transformer SG(B)10-100~2500/10 Amorphous Alloy Core Dry-type Transformer SCBH15-30~2500/10 8. Overall and Installation Dimension 9. Ordering Information 1 2 3 7 8 9 11 11 11 12 13 13 14 14 15 15 16 20
Dry-type Transformer
1. General
1.1 Main Feature
Dry-type transformer mainly con sists of core and w indi ngs, it doesn't immerse in insulating liquide. Our dry-type transformer designs according to IEC standards and China national standards. With no leakage of oil and gas , securit y, envi ronm enta l pr otec tion , and low-noise performances.
1.2 Application
Mainl y use d for loca tions having special fire safety requirements such as commercial buildings,hi gh -r is e bui ldi ngs ,air port s, i ndust rial and mining enterprises, power plants, oil platforms, subways and tunnel. Applicable for 50/60Hz system.
1.4 Standard
IEC 60076-11:2004; ANSI, etc.
P1.
Dry-type Transformer
2. Technical Feature
2.1 Transformer technology of CHINT Power T&D is based on model experiments, self-developed calculation software of leakage flux, short circuit mechanical strength, on load losses etc, to realize overall optimizati on of ele ctrical performance of transformer, therefore low-cost and high-performed solutions could be provided to the customers. 2.2 The structure design is based on three-dimension finite element analysis software ,to do analysis on transformer iron c ore a nd clamping pieces,which provides a guarantee to enhance mechanical strength,anti-short-circuit capacity and reduce noise.
LV lead-in
Performance Feature
Safety, fireproofing, non-polluting, direct operation on the load center. Strong mechanical strength, excellent insulation capacity, low partial discharge ,strong radiation capability , high reliability and long life. Low loss, low noise, energy-saving. High heat dispersion and strong serviceability , forced
Clamping piece
HV winding
Fan
air cooling can improve the operation of capacity. High humidity-resistant, environmental protection, fire-retardant, explosion-proof, less maintenance compact design and light weight.
Base
LV lead-in
Lift lug
Iron core
Clamping piece
Performance Feature
Lower temperature rise, long thermal life. Fire-retardant, long time burning under 800 temperature without smoke generation. Strong thermal shock resistance ,at -50 immediately increase full load. High humidity-resistant performance. Low loss, a significant energy saving effect. Easy recycling on insulating material and copper at life end for envirnmental protection. Temperature control meter.
Base Fan HV winding Tapping connector
high
LV winding
HV lead-in
can
Lift lug
LV lead-in
Performance Feature
Clamping piece
Safe, reliable, no pollution, can operate directly in the load center; High mechanical strength, strong ability to withstand short circuit, low partial discharge, good thermal stability, high reliability, long use life; Low no-load loss, high performance, low noise, efficient energy conservation; High thermal performance, high operation capacity, when forced air cooling the capacity can be improved to run; Good moisture resistant ability, can operate in high humidity and other harsh environments;
Base
HV winding
With features of environmental protection, flame retardant, explosionproof and free of maintenance; Small size, light weight;
P2.
Dry-type Transformer
3. Structure Feature
3.1 Iron Core
The iron core is m ade of high quali ty, cold-rolled, granule-oriented silicon-steel sheets and machined with completely automatic cutting line superposed with 45 six-level bias seams.Core column adopts special banding technique the surface of iron core is painted with the special rustproof coating to resist humidity and rust,which can effectively reduce the no-load losses, no-load current and iron-core noise.Facilitated with six sets of cutting lines for iron core such as, Soenen from Belgium.
Sending materials
Core joints
Core molding
P3.
Dry-type Transformer
Conveyor feed Automatic cutting & stack Iron core rolling machine
Fixation
P4.
Dry-type Transformer
3.2 Winding
F-class insulation HV winding: it is made of lacquered wire. With hardness ranges from 120 to 210 Mpa. The insulation material is a compo site of silicon micro-powder and epoxy resin, featuring high performances of good thermal shock resistance,fire resistance, no emission of hazardous gases, good heat dispersion and low winding temperature rise.
Vacuum casting equipment from Germany HUBERS adopts patented technology such as film defoaming and static mixer,ensure the transformer low partial discharge .
P5.
Dry-type Transformer
H-class insulation HV winding: it adopts NOMEX paper wrapped flat copper wire and continuous winding process. The winding made after dry treatment by VPI vacuum pressure device, several times impregnated in special H class insulating paint,and baking fea tures high mecha nical strength, good heat dispersion.
LV winding: LV winding is mainly made of foils. It adopts interior argon gas protection welding,with high precision and reliability as no external welding joint. It solves the winding turns imbalance , effectively improves thermal performance and enhance short circuit withstanding capability.
LV foil winding
TUBOLY LV foil winding machine from Switzerland which with constant tension, deburring, autom atic bypas s sys tem and the corrective function
P6.
Dry-type Transformer
4. Component
4.1 Protection Enclosure
Protection enclosure can be made of general steel plate,stainless steel plate or aluminum alloy materials. For example, protection enc losure of IP20 can prevent solid object which is 12mm from entering, and this type is suitable for indoor installation. Protection enclosure of IP23 inherits the characters of IP20 enclosure and can prevent water dropping at an angle within 60 to the vertical line from inflooding, as we ll wh ich is a dapt ed t o outdoor installation.
P7.
Dry-type Transformer
QC System
Environmental Management System: ISO14001 Occupational Health & Safety Management: OHSAS18001 Survey Management System: ISO10012 To create a world famous brand and to provide
QC Policy
satisfied products and solutions for customers. An independent and systematic QC system, 30 quality control points for
each key procedures. QC Activities Training of total quality control philosophy for new employees each year.. "Quality Month" in May each year to improve quality awareness. Internal audit in April every year. Scheme the quality improvement each year. QC Review Record and analyze quality loss each month to correct and prevent significant defects. QC Honors National Quality Management Award. China Top Quality Management Award. All the suppliers for raw materials are strictly selected. Materials outsourced are strictly tested. Quality inspectors are responsible for process inspection and final quality inspection. Quality engineers are responsible for random inspections and quality auditing. Finished products are strictly tested before delivery. Third party inspection and end user inspection are scheduled before delivery. We adopt the Zero Defect Theory from Philip B. Crosby to make things right from the beginning.
Raw Material
Process Control
Zero Defect
P8.
Dry-type Transformer
P9.
Dry-type Transformer
Punctual Delivery
P10.
Dry-type Transformer
Sheet 1
No-load Short circuit current impedance (%) (%)
HV (kV)
HV tap range
SC9-30 SC9-50 SC9-80 SC9-100 SC9-125 SC9-160 SC(B)9-200 SC(B)9-250 SC(B)9-315 SC(B)9-400 SC(B)9-500 SC(B)9-630 SC(B)9-630 SC(B)9-800 SC(B)9-1000 SC(B)9-1250 SC(B)9-1600 SC(B)9-2000 SC(B)9-2500 SC(B)9-1600 SC(B)9-2000 SC(B)9-2500
6 6.3
5
6.6
Dyn11
or
10
0.4 2 2.5
or Yyn0
10.5 11
220 310 420 450 530 610 700 810 990 1100 1310 1510 1460 1710 1990 2350 2760 3400 4000 2760 3400 4000
750 1060 1460 1670 1960 2250 2680 2920 3670 4220 5170 6220 6310 7360 8610 10260 12400 15300 18180 13700 16900 20000
2.4 2.4 1.8 1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.2 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.8 1.0 0.8 0.8
7.1.2 10 Series 10kV Free Excitation Voltage Regulation Distribution Transformer Voltage combination
Model
Sheet 2
No-load Short circuit current impedance (%) (%)
HV (kV)
HV tap range
LV (kV)
Load loss Connection No-load under F symbol loss (W) class (W) (120 )
SC10-30 SC10-50 SC10-80 SC10-100 SC10-125 SC10-160 SC(B)10-200 SC(B)10-250 SC(B)10-315 SC(B)10-400 SC(B)10-500 SC(B)10-630 SC(B)10-630 SC(B)10-800 SC(B)10-1000 SC(B)10-1250 SC(B)10-1600 SC(B)10-2000 SC(B)10-2500 SC(B)10-1600 SC(B)10-2000 SC(B)10-2500
6 6.3
5
6.6
Dyn11
or
10
0.4 2 2.5
or Yyn0
10.5 11
190 270 370 400 470 540 620 720 880 980 1160 1340 1300 1520 1770 2090 2450 3050 3600 2450 3050 3600
710 1000 1380 1570 1850 2130 2530 2760 3470 3990 4880 5880 5960 6960 8130 9690 11730 14450 17170 12960 15960 18890
2.4 2.4 1.8 1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.2 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.8 1.0 0.8 0.8
P11.
Dry-type Transformer
7.1.3 9 Series 20kV Free Excitation Voltage Regulation Distribution Transformer Voltage combination Model HV (kV) HV tap range LV (kV) Load loss Connection No-load under F loss (W) class (W) symbol (120 )
SC9-50 SC9-100 SC9-160 SC(B)9-200 SC(B)9-250 SC(B)9-315 SC(B)9-400 SC(B)9-500 SC(B)9-630 SC(B)9-800 SC(B)9-1000 SC(B)9-1250 SC(B)9-1600 SC(B)9-2000 SC(B)9-2500 SC(B)9-2000 SC(B)9-2500
20; 22; 24
5 or 2 2.5 0.4
Dyn11 or Yyn0
380 600 750 820 940 1080 1280 1500 1700 1950 2300 2650 3100 3600 4300 3600 4300
1300 2100 2600 3100 3600 4300 5100 6100 7200 8700 10300 12150 14600 17250 20400 18800 22400
2.4 2.2 1.8 1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.0 1.0 1.0 0.8 0.8 0.8 0.8
7.1.4 10 Series 20kV Free Excitation Voltage Regulation Distribution Transformer Voltage combination Model HV (kV) HV tap range LV (kV) Load loss Connection No-load under F loss (W) class (W) symbol (120 )
SC10-50 SC10-100 SC10-160 SC(B)10-200 SC(B)10-250 SC(B)10-315 SC(B)10-400 20 SC(B)10-500 SC(B)10-630 22 SC(B)10-800 SC(B)10-1000 24 SC(B)10-1250 SC(B)10-1600 SC(B)10-2000 SC(B)10-2500 SC(B)10-2000 SC(B)10-2500
5 or 2 2.5 0.4
Dyn11 or Yyn0
345 540 675 740 845 975 1155 1350 1530 1755 2070 2385 2790 3240 3870 3240 3870
1235 1995 2470 2945 3420 4085 4845 5795 6840 8265 9785 11545 13870 16390 19380 17860 21280
2.4 2.2 1.8 1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.0 1.0 1.0 0.8 0.8 0.8 0.8
P12.
Dry-type Transformer
7.1.5 9 Series 35kV Free Excitation Voltage Regulation Distribution Transformer Voltage combination Model HV (kV) HV tap range LV (kV) Load loss Connection No-load under F loss (W) class (W) symbol (120 )
SC9-50 SC9-100 SC9-160 SC(B)9-200 SC(B)9-250 SC(B)9-315 5 SC(B)9-400 SC(B)9-500 35~38.5 or SC(B)9-630 2 SC(B)9-800 SC(B)9-1000 SC(B)9-1250 SC(B)9-1600 SC(B)9-2000 SC(B)9-2500
Dyn11
0.4 2.5
or Yyn0
500 700 880 980 1100 1310 1530 1800 2070 2400 2700 3150 3600 4250 4950
1500 2200 2960 3500 4000 4750 5700 7000 8100 9600 11000 13400 16300 19200 23000
2.8 2.4 1.8 1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.0 0.9 0.9 0.9 0.9
7.1.6 9 Series 35kV Free Excitation Voltage Regulation Power Transformer Voltage combination Model HV (kV) HV tap range LV (kV) Load loss Connection No-load under F loss (W) class (W) symbol (120 )
SC(B)9-800 SC(B)9-1000 SC(B)9-1250 SC(B)9-1600 SC(B)9-2000 SC(B)9-2500 5 SC(B)9-3150 SC(B)9-4000 35~38.5 or SC(B)9-5000 2 SC(B)9-6300 SC(B)9-8000 SC(B)9-10000
Dyn11 Yd11,YNd11
2500 2970 3480 4100 4700 5400 6700 7800 9300 11000 12600 14400
9900 11500 13600 16300 19200 23000 25800 31000 36800 43000 48500 58500
1.1 1.1 1.0 1.0 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.6
P13.
Dry-type Transformer
SG9-100 SG9-125 SG9-160 SG9-200 SG9-250 SG(B)9-315 SG(B)9-400 SG(B)9-500 SG(B)9-630 SG(B)9-630 SG(B)9-800 SG(B)9-1000 SG(B)9-1250 SG(B)9-1600 SG(B)9-2000 SG(B)9-2500 SG(B)9-1600 SG(B)9-2000 SG(B)9-2500
6 6.3
5
6.6
Dyn11
or
10
0.4 2 2.5
or Yyn0
10.5 11
450 530 610 700 810 990 1100 1310 1510 1460 1710 1990 2350 2760 3400 4000 2760 3400 4000
1780 2100 2410 2870 3120 3930 4520 5530 6660 6750 7880 9210 10980 13270 16370 19460 14660 18000 21400
1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.2 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.8 1.0 0.8 0.8
7.2.2 10 Series 10kV Free Excitation Voltage Regulation Distribution Transformer Voltage combination Model HV (kV) HV tap range LV (kV) Load loss Connection No-load under H loss (W) class (W) symbol (145 )
SG10-100 SG10-125 SG10-160 SG10-200 SG10-250 SG(B)10-315 SG(B)10-400 SG(B)10-500 SG(B)10-630 SG(B)10-630 SG(B)10-800 SG(B)10-1000 SG(B)10-1250 SG(B)10-1600 SG(B)10-2000 SG(B)10-2500 SG(B)10-1600 SG(B)10-2000 SG(B)10-2500
6 6.3
5
6.6
Dyn11
or
10
0.4 2 2.5
or Yyn0
10.5 11
400 470 540 620 720 880 980 1160 1340 1300 1520 1770 2090 2450 3050 3600 2450 3050 3600
1690 1980 2280 2710 2960 3730 4280 5230 6290 6400 7460 8760 10370 12580 15560 18450 13900 17110 20290
1.8 1.6 1.6 1.4 1.4 1.2 1.2 1.2 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.8 1.0 0.8 0.8
P14.
Dry-type Transformer
SCBH15-30 SCBH15-50 SCBH15-80 SCBH15-100 SCBH15-125 SCBH15-160 SCBH15-200 SCBH15-250 SCBH15-315 SCBH15-400 SCBH15-500 SCBH15-630 SCBH15-630 SCBH15-800 SCBH15-1000 SCBH15-1250 SCBH15-1600 SCBH15-2000 SCBH15-2500 SCBH15-1600 SCBH15-2000 SCBH15-2500
6 6.3
5
6.6
or
10
0.4 2 2.5
Dyn11
10.5 11
70 90 120 130 150 170 200 230 280 310 360 420 410 480 550 650 760 1000 1200 760 1000 1200
670 940 1290 1480 1740 2000 2370 2590 3270 3750 4590 5530 5610 6550 7650 9100 11050 13600 16150 12280 15020 17760
710 1000 1380 1570 1850 2130 2530 2760 3470 3990 4880 5880 5960 6960 8130 9690 11730 14450 17170 12960 15960 18890
760 1070 1480 1690 1980 2280 2710 2960 3730 4280 5230 6290 6400 7460 8760 10370 12580 15560 18450 13900 17110 20290
1.6 1.4 1.3 1.2 1.1 1.1 1.0 1.0 0.9 0.8 0.8 0.7 0.7 0.7 0.6 0.6 0.6 0.5 0.5 0.6 0.5 0.5
Note : (1) The values of load loss (W) listed in the sheet 9 are under particular temperature levels corresponding with specific insulated heat-resistant levels listed in the parenthesises. (2) If user adopts other connection symbols, the specific technical requirements are negotiable between the manufacturer and the user.
P15.
Dry-type Transformer
c d
4-24
a L
b B
30
15
20
30
40
12
12
14
(a)
(b)
(c)
100
20
80 40
25
50
14
40
50
18
18
(d)
(e)
(f)
E/2 E/2
60
(i)
E
E/2
12
E/2
(g)
(h)
Note: The width(dimension E) of the bus bar of the connection terminals in the LV neutral point is equivalent to the width of the bus bar of the connection terminals in LV a/b/c phase.
P16.
E/2
30
120 60
30
15
40
Dry-type Transformer
Sheet 10
LV Terminal a/b/c Phase Neutral Point
Installation dimension
a 400 400 400 550 550 550 660 660 660 660 660 660 660 660 660 820 1070 1070 1070
b 400 400 400 550 550 550 660 660 660 660 820 820 820 820 820 820 1070 1070 1070
c 290 305 325 335 350 365 395 405 415 440 455 480 485 530 535 560 600 650 695
d 145 150 160 165 175 180 197.5 202.5 210 200 225 240 242.5 265 267.5 280 300 325 347.5
e 175 175 175 175 175 175 150 120 180 180 200 200 195 195 220 225 240 265 275
f 275 280 285 295 300 305 315 320 325 335 345 337 333 342 349 360 369 497
g 185 190 195 205 210 215 245 245 250 270 280 300 321 334 321
h 850 875 915 960 980 1030 1070 1110 1145 1200 1305 1298 1233 1293 1358
500 500 500 650 650 650 760 760 760 760 920 920 920 920 920 920 1170 1170 1170
935 955 995 1045 1060 1110 1160 1200 1240 1280 1405 1398 1333 1393 1458 1628 1658 1766 2160
(a) (a) (a) (a) (a) (a) (a) (a) (b) (c) (d) (d) (d) (d) (d) (e) (e) (f) (f)
630 kVA.
(g) (g) (g) (g) (g) (g) (g) (g) (g) (h) (h) (h) (h) (h) (h) (i ) (i ) (i ) (i )
1080 1180 1200 1230 1300 1350 1500 1525 1670 1650
Note: (1) H is the height from temperature controller to the base if rated capacity is (2) Customized products are available.
Sheet 11
LV Terminal a/b/c Phase Neutral Point
Installation dimension
a 400 400 400 550 550 550 660 660 660 660 660 660 660 660 660 820 1070 1070 1070
b 400 400 400 550 550 550 660 660 660 660 820 820 820 820 820 820 1070 1070 1070
c 290 305 325 335 350 365 395 405 415 440 455 480 485 510 530 560 610 625 695
d 145 150 160 165 175 180 197.5 202.5 210 200 225 240 242.5 255 265 280 305 312.5 347.5
e 175 175 175 175 175 175 150 120 180 180 200 200 195 195 220 225 240 265 275
f 275 280 285 295 300 305 315 320 325 335 345 337 333 337 342 360 374 383 497
g 185 190 195 205 210 215 245 245 250 270 280 300 321 320 340 365 438
h 850 875 915 960 980 1030 1070 1110 1145 1200 1305 1298 1233 1353 1420.5 1638 2009.5
500 500 500 650 650 650 760 760 760 760 920 920 920 920 920 920 1170 1170 1170
935 955 995 1045 1060 1110 1160 1200 1240 1280 1405 1398 1333 1453 1520.5 1628 1728 1815.5 2159.5
(a) (a) (a) (a) (a) (a) (a) (a) (b) (c) (d) (d) (d) (d) (d) (e) (e) (f) (f)
630 kVA.
(g) (g) (g) (g) (g) (g) (g) (g) (g) (h) (h) (h) (h) (h) (h) (i ) (i ) (i ) (i )
1080 1180 1200 1230 1300 1350 1500 1525 1640 1640
Note: (1) H is the height from temperature controller to the base if rated capacity is (2) Customized products are available.
P17.
Dry-type Transformer
50
h
Body centerline
m Lw
hn
4-18
n Bw
Hw
Sheet 12
h 980 1030 1070 1110 1145 1200 1305 1305 1315 1380 1445 1625 1660 1760 1855 H 1060 1110 1160 1200 1240 1280 1405 1405 1415 1480 1575 1740 1790 1910 2005 hn 140 140 140 140 140 140 140 140 140 140 140 140 140 140 140
Installation dimension
m 550 550 660 660 660 660 660 660 660 660 660 820 1070 1070 1070 n 1090 1090 1090 1090 1090 1140 1140 1140 1240 1240 1240 1340 1440 1440 1540
c 350 365 395 405 415 440 455 455 485 500 520 540 570 605 645
d 175 180 197.5 202.5 210 200 225 210 225 250 260 270 285 300 645
e 175 175 150 120 180 180 200 200 195 195 220 225 240 265 275
f 300 305 315 320 325 335 345 345 340 345 350 350 365 380 430
g 210 215 245 245 250 270 280 290 280 280 290 290 305 320 337
P18.
Dry-type Transformer
e f
j g
2 4 6 35 7
2 4 6 35 7
2 4 6 35 7
c a
d b
LV Connection Terminal
0-phase copper bus bar ( ~ )
14
(18)
B 30 B/2 15 B/2 40 20 60 30 80 40
15
20
25
30
30
40
12
12
14
14
40
50
18
18
B/2
12
Sheet 13
Copper Bus Bar Overall dimension 1550 1550 1550 1550 1700 1750 1750 1850 1950 2000 2050 2200 2250 2400 1200 1200 1200 1200 1200 1400 1400 1400 1400 1500 1500 1500 1500 1500 1800 1800 1800 1800 1900 1900 1950 1950 2100 2100 2200 2200 2400 2600
Note: (1) The above data is just for reference. (2) Customized products are available.
P19.
60
30
100 50
120 60
P20.
140
50
252-750kV
126-145kV
145kV Mini GIS 145kV Mini GIS 145kV GIS
36-40.5kV
Fixed Type Metal Enclosed Switchgear Outdoor SF6 Circuit Breaker
Network Switch Dispatching Center Dispatching Center Primary Communication Server NZT3 Primary Communication Server NZT3 NZL308 Intelligent Measurement and Control Device NZB379 Motor Intelligent Control and Protection Device
Printer
Engineer Station Operator Station (Based on NRS6000 Monitoring Software)(Based on NRS6000 Monitoring Software)
NZB60 Series digital Protective Relay NZB63 Series Microcomputer Protective Measurement and Control Device
3.6-24kV
XGN15-12 (SF6) Air-insulated Ring Main Unit HXGN15A-12 Air-insulated Ring Main Unit NV Series Vacuum Circuit Breaker (VCB) ZN63A-12(VS1) Vacuum Circuit Breaker (VCB)
S9.S11-M R Three-phase Fully-sealed Roll-core Transformer SC(B) series Epoxy Resin Dry-type Transformer
0.38-0.6kV
7.2kV-252kV PT & CT
XKGKL Dry Type Air-core Current-limiting Reactor CKGKL Dry Type Air-core Reactor
Cable
T&D
International Business:
Attributed to our reliable quality and perfect after-sales service, CHINT T&D has been relied on and entrusted with by many of our clients around the world. We will continue to supply best products and try hard to win more compliments through our best service. For inquiries, further interests for products cooperation, partnership, international alliance,investment discussion with us, please contact the following representatives.
Area
Representative
Tel
MV/HV
Address:
2011-006EN0505