Modeling of DFIG Based Wind Generator and Transient Characteristics Analysis

G.H. Li, B.H. Zhang, Z.G. Hao, J. Wang


School of Electrical Engineering, Xian Jiaotong University Xian, China gofeilee@gmail.com
Abstract As a renewable, clean energy, wind energy has attract more and more attention. It has become a common understanding of the world to vigorously develop wind energy. In order to guarantee the safety and reliability for wind power integration operation, it is of great significance to establish an appropriate wind power generator system model and analyze its electromagnetic transient characteristics. This paper analyzes the control strategy of doubly-fed induction generator (DFIG) based wind generator. Vector decoupling control technology has been adopted to establish the mathematical model of DFIG based wind generator. Furthermore, an electromagnetic dynamic simulation model of DFIG based wind generator is established based on the platform of PSCAD/EMTDC. A short circuit fault is simulated to study the dynamic response of DFIG based wind generator. Finally, transient characteristic of DFIG is analyzed by this paper. Keywords-DFIG; Vector decoupling control; dynamic model; transient characteristic

Z.Q. Bo, David Writer, Tony Yip


ALSTOM T&D Ltd Stafford ST17 4LX, UK

its control system [2]. Overall structure of DFIG based wind generator is shown in Fig. 1.
Prate
PG
TM Vw

QG

Us

TG

Pg

PG

Figure 1. Overall structure of DFIG based wind generator model

I.

INTRODUCTION

Energy depletion and pollution problems compel us to find a clean and renewable energy. The end of 2008, the global total installed capacity of wind power had reached 120 000MW. At present, wind power still keeps the fastest growth rate in the renewable energy industry. Commonly used wind turbines can be divided into 4 types, as is mentioned in [1]. As an economical wind power generation, doubly-fed induction generator (DFIG) based wind generator has become the most widely used wind turbine. To further study the impact of wind turbine on the existing power grid, the electromagnetic transient modeling of DFIG based wind generator has become a research hotspot in recent years. Complete mathematical model of DFIG based wind generator is analyzed in this paper and an electromagnetic dynamic simulation model based on the PSCAD/EMTDC platform is established by adopting vector decoupling control method. A severe three-phase short circuit fault is simulated to study the response of DFIG wind generator and the transient characteristic is analyzed. II. DFIG BASED WIND GENERATOR MODEL

In order to describe the random and intermittent characteristics, wind speed Vw is constituted by basic wind, gust wind, ramp wind and random wind. The process of capturing wind energy and converting it to mechanical energy is simulated by aerodynamic model. Mechanical drive model includes low-speed shaft, gearbox and high-speed shaft. It can be simulated by a one-order inertial link. Aerodynamic model simulates the wind turbine to capture and convert wind power to mechanical energy. B. Pitch Angle Control System Model In order to improve the wind energy utilization ratio, almost all the wind turbines are equipped with the pitch angle control system. When the wind speed falls in between the start wind speed and rated wind speed, pitch angle is always zero and the wind turbine tracks the maximum wind power. When the wind speed is greater than the rated wind speed, pitch angle is adjusted to keep the wind turbine running on a constant speed [3]. Pitch angle control system model macro is shown in Fig. 2.
d max dt
Prate

max
1 s

P
PG

ref

1 Ts

d dt

d min dt

min

Vw

Vwrate

A. Overall Structure of DFIG Based Wind Generator The DFIG based wind generator model can be divided into five parts: wind speed model, aerodynamic model, pitch angle control model, mechanical drive model and DFIG model with
This work is supported by the Major State Basic Research Development Program of China (973 Program) (2009CB219704)

Figure 2. Pitch angle control system

978-1-4244-8782-0/11/$26.00 2011 IEEE

C. Vector Decoupling Control System of DFIG Vector decoupling control method is the core technology of DFIG based wind generator. The method is achieved by controlling the grid VSC and rotor VSC, as is shown in Fig. 3.

The exchanged active power is only related to the d-axis current id, and reactive power is only related to the q-axis current iq. Power decoupling control can be easily achieved if id and iq can be adjusted respectively. But the current cant be directly controlled by the grid VSC. It must be transformed into voltage variable which can be directly controlled by the grid VSC. By substitution of the equations ed=e, eq=0, (1) can be expressed in (4).
di * vd = Rid L d + 1 Liq + e dt di * v = Ri L q Li q q 1 d dt

(4)

Figure 3. Schematic diagram of DFIG wind turbine

1) The Grid VSC Control System Power grid voltage oriented vector control scheme is adopted in grid VSC to achieve power decoupling control between the grid VSC and power grid. The two main control targets are to keep the DC bus voltage stable and adjust the reactive power exchange with power grid. a) Mathematical Model of Grid VSC
ea
L R

In (4), vd* and vq* are the reference voltage vectors of grid VSC in synchronous reference frame. The grid VSC control system macro is shown in Fig. 5.

vcap v
* cap

* id

id

e + 1iq

* vd

eb

ec

Qr*
Qr

* iq

U dc

vb vc

va

ia
ib

iq

1id

* vq

Figure 5. Grid VSC control system macro

ic

Figure 4. Grid VSC macro

A double closed loop structure is adopted. External loop PI regulator is used to keep the DC bus voltage stable, adjust the reactive power exchange with power grid and produce reference current for the inner loop. Inner loop PI regulator is used to track given current in real time. 2) The Rotor VSC Control System Stator flux oriented vector control scheme is adopted in rotor VSC to achieve power decoupling control between the stator and power grid. The main control target is to realize maximum power tracing, cooperating with wind turbine. Another target is to adjust the reactive power exchange with power grid, to maintain a suitable power factor of the wind generator [5]. a) Mathematical Model of DFIG Assuming that stator and rotor windings are three-phase symmetrical, the air gap distributes in the circumference of the motor uniformly, the electronic and magnetic circuits are symmetrical. The mathematical model of DFIG in synchronous reference frame can be described with the following equations [6]. Voltage equations:
u sd u sq urd u rq = p sd 1 sq + Rs isd = p sq + 1 sd + Rs isq = p rd s1 rq + Rr ird = p rq + s1 rd + Rr irq (5)

From Fig. 4 above, the grid-side voltage source converter (VSC) can be described by (1) under synchronous reference frame [4].
di ed = Rid + L d 1 Liq + vd dt di e = Ri + L q + Li + v q 1 d q q dt

(1)

In the equations above, subscript d stands for d-axis component and subscript q stands for q-axis component; 1 is the angular frequency of the power grid voltage. The power exchange between the power and the grid VSC can be calculated in (2).
Pr = 1.5(ed id + eq iq ) Qr = 1.5(eq id ed iq ) (2)

b) Control Scheme of Grid VSC Set the d-axis on the direction of the grid voltage vector, qaxis ahead of the d-axis 90 degrees, which results in ed = e, eq=0, where e is the voltage vector of the power grid. The power equation turns into:
Pr = 1.5eid Qr = 1.5eiq (3)

Flux equations:

sd sq rd rq

= Ls isd + Lmird = Ls isq + Lmirq = Lr ird + Lmisd = Lr irq + Lmisq (6)

* Ls Lr L2 L L L2 m m pi rd s r s1irq u rd = Rr ird + Ls Ls (12) 2 2 u * = R i + Ls Lr Lm pi + Lm s + Ls Lr Lm s i rq r rq rq 1 1 1 rd Ls Ls Ls

Electromagnetic torque equation:


Te = Lm (ird isq irqisd ) (7)

In (12), urd* and urq* are the reference voltages vectors of rotor VSC in synchronous reference frame. The rotor VSC control system macro is shown in Fig. 6.
Qs

Stator power equations:


Ps = u sd isd + u sq isq Qs = u sq isd u sd isq (8)
Qsref

s
* isd
* ird

ird

Ls Lr L2 m s1irq Ls
* urd
* u rq

In the equations above, subscript s stands for stator; subscript r stands for rotor; p is the differential operator; 1 is the angular frequency of power grid voltage. b) Control Scheme of Rotor VSC The stator of DFIG is directly connected to the power grid. For stator resistance is much smaller than the reactance, it can be neglected. Thus the stator flux and the stator voltage vector is approximate perpendicular to each other. Set the d-axis on the direction of the stator flux vector, q-axis ahead of the d-axis 90 degrees [7]. Under this condition, d-axis component of the stator voltage is zero and q-axis component is constant. The result is expressed as in:

Psref

i
Ps

* sq

* rq

irq

Lm L L L2 m s1 s + s r s1ird Ls Ls

Figure 6. Rotor VSC control system macro

A double closed loop structure is adopted. External loop PI regulator is used to realize maximum power tracing by cooperating with wind turbine, adjust the reactive power exchange with power grid, and produce reference current for the inner loop. Inner loop PI regulator is used to track given current in real time. III. TRANSIENT CHARACTERISTICS ANALYSIS

sd = s , sq = 0, u sd = 0, u sq = u s

(9)

Where, s is the stator flux vector; us is the stator voltage vector. Conclusion can be obtained by joining (6) and (9).

s Lm ird isd = Ls i = Lm irq sq Ls

(10)

By joining (8), (9) and (10), the output power of the stator can be calculated in (11)
us Lm Ps = u s isq = L irq s u Qs = u sisd = s ( s Lmird ) Ls

A. EMTDC/PSCAD Simulation A 2 MW DFIG based wind generator is simulated in a single-machine infinite-system. A three phase symmetrical short circuit fault occurs at the high voltage side of the package transformer at the time t=3s and lasts for 200ms. Curves of the stator voltage (Vs), electromagnetic torque (Te), mechanical torque (Tm), rotor speed (n), DC voltage (Vdc), stator current (is) and the rotor current (ir) are shown in Fig. 7.
Voltage [p.u]

(11)

Voltage [kV]

By joining (5), (6) and (9), the reference voltage of rotor VSC can be calculated in (12).

Time [s]

Speed [p. u]

The stator active power is only related to the rotor q-axis current irq, and reactive power is only related to the rotor d-axis current ird. Power decoupling control can be easily achieved if irq and ird can be adjusted respectively. Similar to the grid VSC control method, control variables must be transformed from current to voltage which can be directly controlled.

Time [s]

Torque [p.u]

Time [s]

(a) Stator voltage

(b) Electromagnetic and mechanical torque

Time [s]

(c) DC bus voltage

(d) Rotor speed

Time [s]

(e) Stator current

that the calculated angular frequency of stator flux is zero, which is close to synchronous angular frequency under normal situation. Compared to angular frequency of stator flux, the rotating angular frequency of rotor can still be correctly observed by rotor position detector, which is close to synchronous angular frequency because the slip is very small in DFIG. So the angular frequency of rotor current is -rr, approximately corresponding to power-frequency current. According to electromechanical theory, the angular frequency of the stator current will be close to zero, approximately corresponding to DC current. IV. CONCLUSION

Voltage [kA]

Voltage [kA]

Time [s]

(f) Rotor current Figure 7. Curves of the DFIG based wind generator under short circuit fault.

B. Transient Characteristics Analysis DFIG terminal voltage drops to about 10% of the rated voltage during three phase short circuit fault. Electromagnetic torque decreases because the stator cant continue outputting active power. But the input mechanical torque keeps unchanged. Accumulated power makes the rotor accelerate. Meanwhile, Accumulated power will flow into rotor VSC. This will result in the increase of DC bus voltage. The analysis above is consistent with the simulation result. Simulation shows that, for the electromagnetic torque and rotor speed, the recoil phenomenon occurs on the fault instant. This is similar to synchronous machine. The simulation also shows that there is a large DC component in stator short circuit current, while the power frequency component almost disappears. For the rotor current, the situation is quite the reverse. The phenomenon is explained as follows. The angular frequency of rotor current is calculated by -r, where is the angular frequency of stator flux and r is rotating angular frequency of rotor. The method to observe the stator flux is shown in Fig. 8.

Vector decoupling control method is the core technology of DFIG based wind generator. A DFIG based wind generator model is established based on PSCAD/EMTDC in this paper, by adopting vector decoupling control method. The simulation result shows that in severe three-phase short circuit fault, the frequency of rotor current is close to power-frequency while the stator generates an approximate DC current. Thus the transient characteristic of DFIG based wind generator is completely inconsistent with the traditional synchronous machine. The phenomenon is analyzed in this paper. With the increasing popularity of DFIG based wind generator, powerfrequency based protection relay can be no longer applied to wind farm. It is necessary to develop new, special protection system for wind farm. ACKNOWLEDGMENT My deepest gratitude goes first and foremost to Inner Mongolia Electric Power Research Institute. This work is finished by the selfless help of researchers in Inner Mongolia Electric Power Research Institute. Thank for their many useful advice and standpoints. REFERENCES
[1] CHEN Z, Characteristics of induction generators and power system stability, Electrical Machines and Systems. China, vol. 2, pp. 919-924, September, 2005. Ekanayake J B, Holdworth L and Wu X G, Dynamic modeling of doubly fed induction generator wind turbines, Power Systems. vol. 2, no. 18, pp. 803-809, 2003. LIU Qihui, HE Yikang and ZHAO Rende, The maximal wind-energy tracing control of a variable-speed constant-frequency wind-power generation system, Power system automation. China, vol. 27, no. 20, pp. 62-67, 2003. Dongsheng Zhou, and R. Spee, Synchronous frame model and decoupled control development for doubly-fed machines, Proceedings of IEEE Industry Electronics Specialist Conference, PESC94, pp. 12291236, 1994. Mitsutoshi Yamamoto and Osamu Motoyoshi, Active and reactive power control for doubly-fed wound rotor induction generator, IEEE Trans. On Power Electronics, vol. 6, no. 4, pp. 624-629, 1997. Ruqi Li, Alan Wallace and R. Spee, Two-axis model development of cage-rotor brushless doubly-fed machines, IEEE Trans. Energy Conversion, vol. 6, no. 3, pp. 453-461, 1991. Yifan Tang and Longya, Stator field oriented control of doubly-excited induction machine in wind power generating system, Proceeding of the 35th Midwest Symposium on Circuit and Systems, pp. 1446-1449, 1992.

[2]

us is Rs

es
es

1 s 1 s

s
s

[3]

[4]

us is Rs

Figure 8. Stator flux observer macro

[5]

In Fig.8, us, us, is and is are the voltage and current of stator in two-phase rotating frame and Rs is the stator resistance, which is so small that can be neglected. Under normal operation, is equal to synchronous angular frequency 1. During severe three-phase fault as in the simulation, the stator voltage drops close to zero, i.e. us0 and us0. After the integral part, s and s basically keep unchanged during fault time. So the calculated keeps unchanged. This will result

[6]

[7]

Potrebbero piacerti anche