Sei sulla pagina 1di 5

Marketing Bulletin

Model PIRECL Combustible Gas Detector

Detector Electronics Corporation (Det-Tronics) is pleased to announce the release of an all-new, point-infrared combustible hydrocarbon gas detector: The Pointwatch Eclipse Model PIRECL ! Building upon the tradition of excellence established by the model PIR9400 Pointwatch IR gas detector, DetTronics now offers an all-new point-infrared gas detector for measurement of hydrocarbon vapors in the lower explosive limit (LEL) range. Ideally suited for on/off-shore oil/gas facilities as well as downstream hydrocarbon & chemical plants, the Pointwatch Eclipse provides a number of unique features and benefits, including: Superior Design No undisclosed failure modes Exceptional weather protection system Industrial-grade sapphire-coated, heated optics Stainless steel construction for maximum strength Integral wiring termination compartment Superior Communications Versatility Standard 4-20 ma, HART, RS-485 Modbus outputs Tri-Color LED provides external status indication Superior Flexibility and Options Routine calibration not required! Hand-held Programmer option (275 HART) Optional Relay Package (2 alarms, 1 fault) Eagle Quantum Premier compatibility Emerson AMS System compatibility Superior Approvals CENELEC-certified to ATEX directive 94/9/EC for EEx de [ib] area and performance compliance CE marked per EMC directive 89/336/EEC as per EN50081-1, EN50082-2, & EN50270 standards FM & CSA certified version for Class 1, Division 1, groups C, D, (T4) and Class 1, Division 2, groups A, B, C, D (T4) hazardous areas 5 year product warranty Det-Tronics factory, regional, and local product support network HART Communication Foundation listed device
Model PIRECL shown w/275 handheld communicator

Superior Support

Information on Pointwatch Eclipse model number structure, spare parts, accessories, and frequently asked questions (FAQ's) is provided on the following pages.

6901 West 110 Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.FIRE Fax: 952.829.8745

th

Page 1 of 5 14-Dec-01

Marketing Bulletin

Model PIRECL Combustible Gas Detector

Pointwatch Eclipse Model Number Structure


MODEL PIRECL DESCRIPTION Point Infrared Eclipse Gas Detector TYPE A B THREAD TYPE 3/4" NPT M25 TYPE 1 4 OUTPUT & MEASUREMENT OPTIONS 4-20 mA with HART protocol & RS-485: 0-100%LEL Full Scale Range Eagle Premier Compatible Only: 0-100%LEL Full Scale Range TYPE A B RELAY OUTPUT OPTION No Alarm & Fault Relay Option Board installed Alarm & Fault Relay Option Board installed (Not compatible with Eagle Premier) TYPE 1 2 5 WEATHER PROTECTION Standard External Black Plastic Weather Baffle with Hydrophobic filter Standard External Black Plastic Weather Baffle withOUT Hydrophobic filter No Weather Protection installed TYPE A E S R APPROVALS Americas (FM, CSA) European (CENELEC, ATEX, CE) SAA Russian

PIRECL Models available now


Model Number PIRECLA1A1A PIRECLB1A1E PIRECLA1A2A PIRECLB1A2E Part number 007168-001 007168-002 007168-003 007168-004 Ship Weight 7.5 lb (3.4 kg) 7.5 lb (3.4 kg) 7.5 lb (3.4 kg) 7.5 lb (3.4 kg) Delivery 8 weeks 8 weeks 8 weeks 8 weeks

PIRECL Spare parts


Part Number 007165-002 007165-001 007165-004 007165-003 006672-002 103035-001 107427-040 107427-052 107427-053 Description Weatherbaffle with std inlet nozzle, w/hydrophobic filter Weatherbaffle with std inlet nozzle, w/o hydrophobic filter Weatherbaffle with 1/8" NPT cal gas inlet, w/ hydrophobic filter Weatherbaffle with 1/8" NPT cal gas inlet, w/o hydrophobic filter PIRECL windshield calibration bag std inlet nozzle calgas cap, black o-ring, 3.75" i.d., j-box cover o-ring, 3.25" i.d., front flange (internal) o-ring, 2.43 i.d., weathershield

6901 West 110 Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.FIRE Fax: 952.829.8745

th

Page 2 of 5 14-Dec-01

Marketing Bulletin

Model PIRECL Combustible Gas Detector

PIRECL Accessories Accessories for the model PIRECL including duct-mount and sample extraction system configurations are scheduled for release by mid-year, 2002. Please contact the gas detection product marketing department for additional information.

Frequently Asked Questions 1. How is the PIRECL (Eclipse) different from the model PIR9400 Pointwatch gas detector? The PIRECL utilizes an entirely new mechanical and electrical design. All standard units will offer 420ma output with HART, as well as RS-485 Modbus output. In addition, a special Eagle Quantum Premier-compatible version PIRECL will be available by early 2002. This unit will be operate only with the Eagle Quantum Premier (EQP) System. The table below summarizes key product differences.
Material of Separate j-box Optional relay construction required? outputs available? PIR9400 aluminum Yes requires U9500H PIRECL stainless steel No Yes Isolated analog signal output? requires U9500H Yes HART, RS-485, or Eagle Dual safety ratings Premier compatible? available? No No Yes Yes

2.

Will the PIR9400 Pointwatch continue to be available?

There are no plans to discontinue the PIR9400A aluminum model. However, a phase-out plan will be implemented by mid-2002 to place the PIR9400S (stainless steel) version only on Retired Product Status (RPS). This plan will coincide with the release of the Russian-approved PIRECL, and also the release of new accessories for the PIRECL such as the duct-mount and sample extraction assemblies. The PIR9400S will continue to be available for the foreseeable future. 3. Are the U9500H Infiniti transmitter and R8471H controller devices compatible with PIRECL?

Yes, these devices are compatible. During the PIRECL setup routine, simply select the PIR9400 mode of communication to ensure the PIRECL diagnostic information and fault signal output levels mimic the PIR9400 detector. This device setup is completed using either a 275 handheld communicator or a HART system interface or Modbus system interface. 4. The PIRECL provides 4 different methods of initiating calibration. calibrate? How often should I

As this device has no undisclosed failure modes, routine calibration is not required. Device calibration is required whenever the gas signal-processing program is changed from the factory default methane setting. Calibration can be performed on a regular basis if desired, but should normally not be necessary. Calibration initiation options include via the on-board, non-intrusive magnetic switch, the 275 handheld communicator, an externally located, hardwired switch, or via the RS-485 Modbus command option.

6901 West 110 Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.FIRE Fax: 952.829.8745

th

Page 3 of 5 14-Dec-01

Marketing Bulletin
5. How will a customer use HART communication capability of the PIRECL?

Model PIRECL Combustible Gas Detector

There are a number of ways to utilize the HART communication. The primary master system is generally a distributed control system (DCS), programmable logic controller (PLC), or asset management system (AMS). The secondary master can be a handheld communicator or another PC. The PIRECL and most HART field devices will respond to commands from the primary or secondary master. This capability ensures global HART compatibility and provides customers with the confidence and security that the PIRECL will communicate reliably with their HART instrument network or plant-wide asset management system. 6. What are the differences between the FM/CSA certified PIRECL and the CENELEC/CE certified PIRECL models?

The FM/CSA-approved units provide (2) 3/4" NPT conduit openings, and the CENELEC/CE units offer (2) 25MM conduit openings. In addition, due to variation in testing criteria, the FM/CSAapproved units offer an explosion-proof HART communication port, while the CENELEC/CE-certified PIRECL provides an intrinsically-safe HART communication port. Even though the electronic circuitry for both versions includes an on-board i.s. zener barrier, and is identical, the net result of the testing differences is that our FM/CSA-approved product users should always de-classify the surrounding area before removing the threaded cover to the on-board HART port. Users of the CENELEC/CE units may use the HART connection without area de-classification. 7. Is the PIRECL position-sensitive, and is there a recommended mounting orientation?

The PIRECL will operate normally regardless of mounting orientation. However, we recommend that the device be installed with the long axis of the device parallel to the ground for maximum effectiveness of the weather baffle. The self-draining characteristics of the weather baffle will be optimized with the detector installed in this manner. 8. When will the PIRECL optional relay output model be available, and how will this option be installed?

The PIRECL with the optional relay output is planned for release by March, 2002. This PIRECL model will include the relay board pre-installed into the internal wiring compartment. It will be compatible with standard 4-20ma output version PIRECL only. Note the relay output board is a factory-fitted option only as a different cover is required and our approval agencies require a separate product label on the relay-output models. All relay output models are explosion-proof certified only. 9 What is the difference between the weatherbaffle assemblies with the standard inlet nozzle th and the 1/8 NPT inlet nozzle?

The standard inlet nozzle comes with a tethered plastic protective cap, and is used with a standard th calibration gas kit tube. The weatherbaffle with the 1/8 NPT inlet nozzle is provided to enable the installation of a compression fitting for use with permanently installed cal gas tubing.

6901 West 110 Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.FIRE Fax: 952.829.8745

th

Page 4 of 5 14-Dec-01

Marketing Bulletin
10. Will our existing model 275 HART communicator work with the PIRECL?

Model PIRECL Combustible Gas Detector

Yes, existing 275 communicators will talk with the PIRECL. However, unless the 275 includes the HART device descriptors (DD's) for Eclipse, the communication will be in a generic version only. Numerous global HART suppliers are capable of programming new DD's into the HART Communicator. Please visit the Hart Foundation website at www.hartcomm.org for a complete listing of suppliers and additional information regarding HART communication. The DD release to request for your model 275 is: RELEASE/00008f/007f/0101.AOT 11. What is the dual safety rating mentioned, and what advantage does this provide?

The CENELEC-certified PIRECL wiring terminal compartment uses an approved design that allows either an increased safety "Ex e" termination, or a flameproof "Ex d" termination of the field cabling. A CENELEC certified cable entry device or gland of either type is acceptable. The FM/CSA-certified PIRECL models provide an explosion-proof and nonincendive design only.

For additional information on the model PIRECL Pointwatch Eclipse, please contact your Inside Sales Representative or Dave Opheim, Gas Products Marketing Manager, at Detector Electronics Corporation, Minneapolis, Minnesota.

6901 West 110 Street Minneapolis, Minnesota 55438 USA Tel: 952.941.5665 or 800.765.FIRE Fax: 952.829.8745

th

Page 5 of 5 14-Dec-01