0 DATA:
: : : : : : : : : : : : : : : : : Source Impendence in P.U : 1.6 MVA 6.00% 74.6 kW 0.85 DOL 6 times the Full load current 526.56 kVA 1043.6 kVA 1570 kVA 0.2 0.97 1.6 MVA 0.415 kV 31.5 kA 11 kV 1.732X11X31.5 600.15MVA Base MVA /Source MVA 1.6 / (600.15) 0.00416 P.U
Transformer rating Transformer impedance Highest kW motor rating Power factor Mode of start Starting Current Motor Starting kVA Total Base Load Except motor Total load During Starting of Motor Starting power factor Sin Base MVA Base Voltage on transformer primary voltage Source faut kA Source Voltage Source fault MVA
:
:
1CX500 Sq.mm
Resistance of 11kV 500 sq.mm cable Reactance of 11kV 500 sq.mm cable Length Considered Number of Runs Cable resistance of transformer primary with 30 m length
: : : : : :
: :
: :
: :
: :
Cable size of MDB to SDB incomer Resistance of 1.1 kV 300 sq.mm cables Reactance of 1.1 kV 300 sq.mm cables Length Considered Number of Runs
: : : : :
: :
: :
(0.00192)+ (0.00176)
0.00260 ohms
: : : :
Cable size of SDB to MCC incomer Resistance of 1.1 kV 300 sq.mm cables Reactance of 1.1 kV 300 sq.mm cables Length Considered Number of Runs Cable resistance of motor incomer with 50 m length
: : : : : : :
2RX3.5CX300Sq.mm 0.0769 ohms/km 0.0705 ohms/km 50m 2 0.0769x (50/1000/2) 0.001925 ohms
0.0705x (50/1000/2)
0.0017625 ohms
(0.00192)+ (0.00176)
0.00260 ohms
: : : :
Cable size of MCC to Motor incomer Resistance of 1.1 kV 150 sq.mm cables Reactance of 1.1 kV 150 sq.mm cables Length Considered Number of Runs Cable resistance of motor incomer with 50 m length
: : : : : : :
2RX3.5CX150Sq.mm 0.159 ohms/km 0.0716 ohms/km 50m 2 0.159x (50/1000/2) 0.003975 ohms
: :
(0.00397)+ (0.00179)
0.00435 ohms
: : : :
0.05+0.034+0.034+0.00024
0.1272
Total Impedance
: :
(Total load during starting of motor in MVA x Impedance x Sin )/Base MVA
( 2.079x0.91x0.1848)/ (2.5)
13.9%
Maximum Allowable Voltage Drop during Starting of Highest kW motor as per Is Standard is 15% which is higher than our Actual Voltage drop 13.9 %. Hence 2.5 MVA transformer size is justified.