Sei sulla pagina 1di 80

Process Power and Marine Division Process,

SmartPlant 3D (SP3D) Oglaend Cable Ladder & Tray Specifications


Oglaend Catalogue 2012

SP3D : Contents

Introduction Cable Ladder & Cable Tray OE Cable Ladder System FOE Cable Ladder System LOE Cable Ladder System FTE Cable Tray System SPB Cable Tray System SP3D Oglaend Reports SP3D Oglaend Specifications Set-up

Slides Slides Slides Slides Slides Slides Slides Slides

3 - 11 12 - 22 23 - 33 34 - 46 47 - 53 54 - 63 64 - 66 67 - 78

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue


Oglaend Cable Ladder and Tray SP3D Specification

SP3D representation

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue


Oglaend Cable Ladder and Tray SP3D Specification Th f The following ll i presentation t ti i is d designed i dt to cover : An overview of each SP3D Oglaend specification including Design of specifications Selection of Cable Ladder and Tray types Loading of particular specification to cover project requirements Loading of SP3D Oglaend Reports S3D Preferred version S3D 2011 R1

S3D version required minimum SP3D 2009.1 Hot FIX 26

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue


Oglaend Cable Ladder and Tray SP3D Specification

Based on SP3D Cable part definition : Allowing easy change of SP3D specification Selection of Cable Ladder and Tray types L di of Loading f particular i l specification ifi i to cover customer project j requirements i Recommended work flow Read the following information Choose the specifications required for your project Refer to the load instructions at the end of this document

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder


Oglaend Cable Ladder and Tray SP3D Specification

SP3D representation

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder


Designed to cover Oglaend Cable Ladder
C bl L Cable Ladder dd systems t U Un-Lidded Lidd d OE FOE LOE OE-100, OE-125, OE-150 (Heavy Duty) FOE-70, FOE-100, FOE-150, FOE-150GA LOE-55, LOE-75, LOE-100 ( (Medium \ Light g duty) y) OE

Standard length : 3 metres OE offered in material finishes of : Hot Dipped Galvanized (HDG) Stainless Steel (SS) LOE offered in material finishes of : Hot Dipped Galvanized (HDG) Stainless St i l St Steel l (SS) Pre-Galvanized (PG) FOE offered in material finishes of: Polyester Resin

FOE

All SP3D specification types being designed for open requirements only
2012. Intergraph Process, Power & Marine. All Rights Reserved.

LOE

SP3D : Oglaend Catalogue : Ladder


Designed to cover Oglaend Cable Ladder
Cable Ladder systems Lidded OE FOE LOE OE-100, , OE-125, , OE-150 ( (Heavy y Duty) y) FOE-70, FOE-100, FOE-150, FOE-150GA LOE-55, LOE-75, LOE-100 (Medium \ Light duty) OE Lidded specifications have a CO in their name to designate Covered. The covers are implied and have no graphical representation Standard length : 3 metres OE offered in material finishes of : Hot H t Dipped Di dG Galvanized l i d (HDG) Stainless Steel (SS) LOE offered in material finishes of : Hot Dipped Galvanized ( (HDG) ) Stainless Steel (SS) Pre-Galvanized (PG) FOE offered in material finishes of: Polyester Resin All SP3D specification types being designed for open requirements only
2012. Intergraph Process, Power & Marine. All Rights Reserved.

FOE

LOE

SP3D : Oglaend Catalogue : IEC Trays


Oglaend Cable Trays SP3D Specification

SP3D representation

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Cable Trays


Designed to Cover Oglaend Cable trays

Cable Ladder systems Un-Lidded FTE SPB FTE-50, FTE-80 SPB-20, SPB-40, SPB-RF

FTE

FTE offered in material finishes of : Polyester Resin (C1, C2) SPB offered in material finishes of : Hot Dipped Galvanized (HDG) Stainless Steel (SS) Pre-Galvanized (PG) SPB SPB-RF RF offered in material finishes of: Hot Dipped Galvanized (HDG) Stainless Steel (SS)

SPB

SPB-RF

All SP3D specification types being designed for open requirements only
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Cable Trays


Designed to Cover Oglaend Cable trays
Cable Ladder systems Lidded
FTE

FTE SPB

FTE-50, FTE-80 SPB-20, SPB-40, SPB-RF

Lidded specifications have a CO in their name to designate Covered. The covers are implied and have no graphical representation FTE offered in material finishes of : Polyester Resin (C1, C2) SPB offered in material finishes of : Hot Dipped Galvanized (HDG) Stainless Steel (SS) Pre-Galvanized (PG) ( ) SPB-RF offered in material finishes of: Hot Dipped Galvanized (HDG) Stainless Steel (SS)
SPB

SPB-RF

All SP3D specification types being designed for open requirements only
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE-100, 125, 150 Ladder specification (Heavy Duty System ) Side rail height : 100mm 100mm, 125mm 125mm, 150mm Available cabling space : 75mm, 100mm, 125mm Available widths : 150, 300, 450, 600, 750, 900mm S Supplied li d as standard t d di in 3 meter t l lengths th Connections by splice plate

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend open Ladder specification

The specification is designed to place OE fittings in both manual and sketch modes Understanding of the specification is imperative to efficient construction and material purchase h Falling into two remits : Sketch mode : being the most effective manner to place Manual mode : used in restricted environments allowing manual modification and selection of individual fittings

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Designed around a series of specifications : By Material &Height
OGD_OE-100/125_HDG_ Hot dipped galvanized OGD_OE-100/125_SS Stainless steel OGD_OE-150_HDG_ Hot dipped galvanized OGD_OE-150_SS Stainless steel

Cableway selection of Oglaend Specifications

Selection of Specifications with routing Command

Materials to be loaded are specified in the load file


Allocation of Usable Cable Space, defined by specification Load Width & Depth

Selection Radius with routing Command

Selection of width widths s and radius during Placement

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification - connecting length to length OE straight lengths require splice connector for straight to Straight connections when connecting a straight to a straight, two splice plates are g generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification - connecting length to fitting OE straight lengths require splice connector for straight to fitting connections When connecting a straight to a fitting, one splice plate is generated as the fitting g g is already y delivered with a splice p p plate. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification - connecting fitting to fitting OE fittings require a splice connector for straight to fitting connections When connecting a fitting to a fitting, no splice plate is generated as each fitting is supplied with the required number splices by Oglaend. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Flat Bends
The specification is designed to place Oglaend fittings in both manual and sketch modes Flat bends have fixed angles of 30/45/60/90 B d are available Bends il bl with ith 600 600mm or 900 900mm radius di

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Inside or Outside Risers
The specification p is designed g to p place Oglaend g fittings g in both manual and sketch modes Flexi Risers have variable angles and can be used for 30/45/60/90. Number of segments may differ per angle & radius. Riser radius should set prior to placement Flexi Risers should be placed manually to ensure correct selection Combi Risers are available for 90 and 45deg vertical bends

Flexi Riser

Combi Riser

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Equal & Unequal Tees
The specification is designed to place Oglaend fittings in both manual and sketch modes Fixed Tees and Unequal tees have are available in 600mm and 900mm radius. Manual placement allows selection of specific fittings

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Left Hand & Right Hand Reducers
The specification is designed to manually place Oglaend offset reducer fittings. Automatic placement is not valid.

Ri ht H Right Hand dR Reducer d Left Hand Reducer


2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : OE range


Oglaend OE open Ladder specification Equal Crosses
The specification is designed to manually place Oglaend Cross fitti C fittings. Automatic A t ti placement l ti is not t valid lid. Available in 600mm and 900mm radius.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE-100, 125, 150 Ladder specification Side rail height : 70mm, 70mm 100mm 100mm, 150mm Available cabling space : 46mm, 71mm, 121mm Available widths : 150, 200, 300, 400, 450, 500, 600mm S Supplied li d as standard t d di in 3 meter t l lengths th Connections by splice plate

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend open Ladder specification

The specification is designed to place FOE fittings in both manual and sketch modes Understanding of the specification is imperative to efficient construction and material purchase h Falling into two remits : Sketch mode : being the most effective manner to place Manual mode : used in restricted environments allowing manual modification and selection of individual fittings

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend OE open Ladder specification Designed around a series of specifications : By Material &Height
OGD_FOE-70_C2 Polyester Class 2 OGD_FOE-100_C1 Polyester Class 1 OGD_FOE-150_C1 Polyester Class 1 OGD_FOE-150_GA_C1 Polyester Class 1

Cableway selection of Oglaend Specifications

Selection of Specifications with routing Command

Materials to be loaded are specified in the load file


Allocation of Usable Cable Space, defined by specification Load Width & Depth

Selection Radius with routing Command

Selection of width widths s and radius during Placement

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification - connecting length to length FOE straight lengths require splice connector for straight to Straight connections when connecting a straight to a straight, two splice plates are g generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification - connecting length to fitting FOE straight lengths require splice connector for straight to fitting connections When connecting a straight to a fitting, two splice plates are g generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification - connecting fitting to fitting FOE fittings require a splice connector for straight to fitting connections When connecting a fitting to a fitting, two splice plates are generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification Flat Bends
The specification is designed to place Oglaend fittings in both manual and sketch modes Flat bends have fixed angles of 45/90deg B d are available Bends il bl i in 300 300mm radius di

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification Inside or Outside Risers
The specification p is designed g to p place Oglaend g fittings g in both manual and sketch modes Flexi Risers have variable angles and can be used for 30/45/60/90. Number of segments may differ per angle & radius. Riser Radius 400, 600, 800mm available. Riser radius should set prior to placement Flexi Risers should be placed manually to ensure correct selection

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification Equal Tees
The specification is designed to place Oglaend fittings in both manual and sketch modes Fixed Tees are available in 300mm radius.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification Left Hand & Right Hand and Central Reducers
The specification is designed to manually place Oglaend offset reducer fittings manually. Standard and plate type (part) reducers are available Central Reducers can be placed Automatically or manually

Offset Reducer

Central Reducer

Reducer Part

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FOE range


Oglaend FOE open Ladder specification Equal Crosses
The specification is designed to manually place Oglaend Cross fittings. Automatic placement is not valid. A il bl i Available in 300 300mm radius. di

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE-55, 75, 100 Ladder specification (Medium \ Light Duty System ) Side rail height : 55mm 55mm, 75mm 75mm, 100mm Available cabling space : 24mm, 46mm, 68mm Available widths : 200, 300, 400, 500, 600mm S Supplied li d as standard t d di in 3 meter t l lengths th Connections by splice plate

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend open Ladder specification The specification p is designed g to p place LOE fittings g in both manual and sketch modes Understanding of the specification is imperative to efficient construction and material purchase F lli i Falling into two remits i : Sketch mode : being the most effective manner to place Manual mode : used in restricted environments allowing manual modification and selection of individual fittings Note the following information for LOE specifications : g length g to accommodate fitting g to straight g 100mm must be added to the straight joints. This is to allow for the straight insertion depth when a straight is connected to a Tee, Flat Bend or Cross. For example, a straight length between two flat bends means a total of 200mm being added to the straight length length.
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification Designed around a series of specifications : By Material &Height
OGD_LOE_HDG_ Hot dipped galvanized OGD_LOE_SS Stainless steel OGD_LOE-PG_ Pre-galvanized

Cableway selection of Oglaend Specifications

Selection of Specifications with routing Command

Materials to be loaded are specified in the load file


Allocation of Usable Cable Space, defined by specification L d Wid Load Width h&D Depth h

Selection Radius with routing Command

Selection of widths and radius during Placement

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification - connecting length to length LOE straight lengths require splice connector for straight to Straight connections when connecting g a straight g to a straight, g , two splice p p plates are generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice li plate l report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification - connecting length to fitting LOE straight lengths require splice connector for straight to fitting connections When connecting a straight to a fitting, no splice plate is generated as the fitting g g is already y delivered with a splice p p plate. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification - connecting fitting to fitting LOE fittings require a splice connector for straight to fitting connections When connecting a fitting to a fitting, two splice plate are generated as each fitting is supplied with the required number splices by Oglaend. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification Flat Bends
The specification is designed to place Oglaend fittings in both manual and sketch modes Flat bends are available in 90deg angles B d are available Bends il bl with ith 300 300mm radius di

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification Inside or Outside Risers
The specification p is designed g to p place Oglaend g fittings g in both manual and sketch modes Risers are available for 45 and 90deg bends. LOE 50 has 45deg Riser brackets. LOE 100 has Combi Risers for 45 and 90deg bends

Riser Bracket

Combi Riser

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification Equal Tees
The specification is designed to place Oglaend fittings in both manual and sketch modes Fixed Tees are available in 300mm radius.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : LOE range


Oglaend LOE open Ladder specification Equal Crosses
The specification is designed to manually place Oglaend Cross fittings. Automatic placement is not valid. A il bl i Available in 300 300mm radius. di

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE-50, 80 Tray specification Side rail height : 50mm, 50mm 80mm Available cabling space : 47mm, 77mm Available widths : 50, 100, 150, 200, 300, 400mm S Supplied li d as standard t d di in 3 meter t l lengths th Connections by splice plate

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend open Ladder specification

The specification is designed to place FTE fittings in both manual and sketch modes Understanding of the specification is imperative to efficient construction and material purchase h Falling into two remits : Sketch mode : being the most effective manner to place Manual mode : used in restricted environments allowing manual modification and selection of individual fittings

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Ladder specification Designed around a series of specifications : By Material &Height
OGD_FTE_C2 Polyester class 2 OGD_FTE_C1 Polyester class 1

Cableway selection of Oglaend Specifications

Selection of Specifications with routing Command

Materials to be loaded are specified in the load file


Allocation of Usable Cable Space, defined by specification L d Wid Load Width h&D Depth h

Selection Radius with routing Command

Selection of widths and radius during Placement

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Ladder specification - connecting length to length FTE straight lengths require splice connector for straight to Straight connections when connecting a straight to a straight, two splice plates are g generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Ladder specification - connecting length to fitting FTE straight lengths require splice connector for straight to fitting connections When connecting a straight to a fitting, one splice plate is generated as the fitting g g is already y delivered with a splice p p plate. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Ladder specification - connecting fitting to fitting FTE fittings require a splice connector for straight to fitting connections When connecting a fitting to a fitting, no splice plate is generated as each fitting is supplied with the required number splices by Oglaend. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Tray specification Flat Bends
The specification is designed to place Oglaend fittings in both manual and sketch modes Flat bends have fixed angles of 45 and 90deg

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Tray specification Inside or Outside Risers
The specification is designed to place Oglaend fittings in both manual and sketch modes Ri Risers have h fixed fi d angles l of f 45 and d 90d 90deg. 45deg Risers are Splice Angles. 90deg Risers are Combi Risers.

Combi Riser

Splice Angle 45deg

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : FTE range


Oglaend FTE open Tray specification Equal Tees
The specification is designed to place Oglaend Tee fittings in both manual and sketch modes

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Ladder : FTE range


Oglaend FTE open Ladder specification Left & Right Hand Simple Reducers
The specification is designed to manually place Oglaend offset reducer fittings. Automatic placement is not valid.

Left Hand Reducer


2012. Intergraph Process, Power & Marine. All Rights Reserved.

Right Hand Reducer

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB-20, 40, SPB-RF Tray specification Side rail height : 20mm, 20mm 40mm Available cabling space : 18mm, 18.5mm, 38.5mm Available widths : 50, 100, 150, 200, 300, 400, 500, 600mm A il bl widths Available idth : 50 50, 100 100, 150 150, 200, 200 300 300, 400 400mm Available widths : 50, 100, 150, 200, 300, 400, 500, 600mm Supplied as standard in 3 meter lengths C Connections ti b by splice li plate l t

SPB-20 SPB 40 SPB-40 SPB-RF

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend open Ladder specification

The specification is designed to place SPB fittings in both manual and sketch modes Understanding of the specification is imperative to efficient construction and material purchase h Falling into two remits : Sketch mode : being the most effective manner to place Manual mode : used in restricted environments allowing manual modification and selection of individual fittings Note the following g information for SPB specifications : 55mm must be added to the straight length to accommodate fitting to straight joints. This is to allow for the straight insertion depth when a straight is connected to a Tee, Flat Bend or Cross. For example example, a straight length between two flat bends means a total of 110mm being added to the straight length.
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification Designed around a series of specifications : By B Material M i l &Height &H i h
OGD_SPB_HDG_ Hot dipped galvanized OGD_SPB_SS Stainless steel OGD_SPB_PG Pre-Galvanized (straights only) OGD_SPB-RF_HDG_ Hot dipped pp galvanized g OGD_SPB-RF_SS Stainless steel

Cableway selection of Oglaend Specifications

Selection of Specifications with routing Command

Materials to be loaded are specified in the load file


Allocation of Usable Cable Space, defined by specification Load Width & Depth

Selection Radius with routing Command

Selection of widths and radius during Placement

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification - connecting Straight to Straight SPB straight lengths require splice connector for straight to Straight connections when connecting a straight to a straight, two splice plates are generated. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by y a specification p level rule and will appear pp on a splice p p plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification - connecting Straight to fitting SPBE straight lengths require splice connector for straight to fitting connections When connecting a straight to a fitting, one splice plate is generated as the fitting g is already y delivered with a splice p p plate. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPBE open Ladder specification - connecting fitting to fitting SPB fittings require a splice connector for straight to fitting connections When connecting a fitting to a fitting, no splice plate is generated as each fitting is supplied with the required number splices by Oglaend. The splice plates are not modeled or detailed in the SP3D parts list but are controlled by a specification level rule and will appear on a splice plate report.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification Flat Bends
The specification is designed to place Oglaend fittings in both manual and sketch modes Flat bends have fixed angles of 45/90deg Flexi Bends can be used for 30/45/90deg angles

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification Inside or Outside Risers
The specification is designed to place Oglaend fittings in both manual and sketch modes Flexi Risers have variable angles and can be used for 30/45/90deg Flexi Risers should be placed manually to ensure correct selection Combi Risers are available for 90deg vertical bends
Flexi Riser

Combi Riser

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification Equal Tees
The specification is designed to place Oglaend fittings in both manual and sketch modes Tees are available with a 75mm radius.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Tray : SPB range


Oglaend SPB open Ladder specification Central Left and Right Hand Reducers
The specification is designed to manually place Oglaend central and offset reducer fittings. Automatic placement of offset reducers is not valid.

Left Hand Reducer


2012. Intergraph Process, Power & Marine. All Rights Reserved.

Central Reducer

SP3D : Oglaend Catalogue : Reporting Oglaend Cable Ladder & Tray SP3D Specification - Reporting

3 Reports supplied: Oglaend g Fittings g Report p Oglaend Cover Report Oglaend Splice Report SP3D representation
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Reporting


Oglaend Ladder and Tray reporting from SP3D
Open SP3D Select> Tools > Run reports p Note: Reports can also be run from the Drawings and Reports Task

Select > Your system Select> OK

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Reporting


Output format: Excel spread Sheet

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Oglaend Cable Ladder & Tray SP3D Specification - Set up

SP3D representation
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Loading SP3D Specifications
Process Stages:

Creating SP3D Catalogue (optional for existing project ) Loading SP3D symbols Project Creation (Optional not covered in document) Updating the Catalogue with the particular specification files R l ti S Relating Specification ifi ti t to SP3D systems t Setting up delivered reports

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Supplied data directories :

Oglaend Final Deliverables \SmartPlant \FOE Final Deliverable (Contains FOE specifications, code lists and custom symbols) \FTE Final Deliverable \LOE Final Deliverable \OE Final Deliverable (Contains FTE specifications , code lists and custom symbols) (Contains LOE specifications, code lists and custom symbols) (Contains OE specifications , code lists and custom symbols)

\SPBE Final Deliverable (Contains SPBE specifications, code lists and custom symbols) \Reports \PPTS (Contains Custom report templates and DLL) (General overview of use and how to load)

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Loading SP3D specification
Please consider the following g before loading g Oglaend g specifications: p Loading into clean specification catalog Means only the new specification loaded for Oglaend can be used Use only specifications for project Avoids causal users selecting an incorrect Specifications Loading into clean database takes time but will not include other disciplines - piping, structural etc Recommend you load into standard database and just remove additionally supplies specifications

Using and existing specification Normal to use for change from one specification to another Allows change from existing specification to another

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D catalogue
Building your SP3D reference database Select > SP3D PROJECT MANAGER Select > Database > New > catalog Enter your data : Catalogue name : OGD_cdb (or whatever you prefer)
(recommend that you add _CDB at the end)

Catalogue schema name : ensure this is unique in your database Template file : point to your default template supplied

Apprepos.dat for clean or Catalogue.dat for standard product (best option)


Database Templates will be found in the 3dRef product directory

SharedContent Folder (Do not use product directories for working project) Normal SP3d Administrator function Associate your catalog to the SmartPlant 3d Project.

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D loading specification - Obtaining the latest symbols
O Open Your Y ecustomer t account: t Select > Software downloads > Products Select > SmartPlant 3D Select > SmartPlant Enterprise Content for SmartPlant 3D Select > software version - choose version Strongly recommended is version 2011 R1 and above Select > Cable tray Save to the Symbol directory and following next instructions. Note. Ecustomer is upgraded monthly

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D loading specification
Before loading the specification the custom symbols must be transferred to the plant catalogues sharedContent folder. Copy : Symbol Icons FOE Final Deliverable\Symbols\Symbol Icon's To \ SharedContent\SymbolIcons\ AND : symbols dlls FOE Final Deliverable\Symbols\Symbol Dll To \SharedContent\Custom Symbols Repeat this procedure for the other specifications in this delivery. Ie OE Final Deliverable
2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D loading specification
Registration of the new symbols: Open SP3D Project manager Select > Reference Data (then the plants Catalog ) Select > Tools > Update Custom Symbol Configuration. Note Do not move on to next step if this has not been completed

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D loading specification
With starting specification catalogue or Clean catalogue with previous screen completed Or Working catalogue

Bulk load Specifications Open Intergraph SmartPlant 3d >Database Tools >Bulk load reference data You can find these file in the following directories :
Specification\Data\Part Data or Specification\Data\Codelist
File Type Excel Code list File name AllcodelistsFOE CableTray Select Lists Required Required by Spec. Load Function Manufacture, material, span

Excel Code list

Required by Spec.

Cable Part Data Basis

Excel (Spec) Only load the specifications you require. i

Oglaend_FOE2011

Required by Spec.

Delivered spec and fittings

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Creating SP3D loading specification Reviewing you log files;
It is always important to check your log file after the load process : you should expect to see some warning messages relating to items existing this is due to the system telling you that item in the code list exist already these are not of concern: Expect WARNING: cannot create object . Object already exists in the database .Skipped This is normally and relates to class node or Part Class where the each a part will try to create even though all items require this and it has been created previously. Exists or created is acceptable Items to watch for : WARNING : Failed to set the Symbol Icon property. gif file is missing

The icon and symbol dll where not loaded and update :- contact local Intergraph Support

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Systems & Specifications
Open SP3D : Select > Task > Systems & Specifications Select > Highest level ( Oglaend) Select > Define allowed specification

Select > Specifications to relate to electrical systems Note. These may be removed / sub selected at the system Level. Loading all specifications on previous selection adds lost of parts to the database and should be avoided if not required

2012. Intergraph Process, Power & Marine. All Rights Reserved.

SP3D : Oglaend Catalogue : Setup


Loading SP3D Oglaend Custom SP3D reports
The setup of the SP3D Oglaend reports consist of four main steps: 1, Copying of the Ogleand Report Templates to the catalog SharedContent Reports folder. 2, Bulkloading the supplied Reports workbook. This contains the Oglaend custom report definitions. 3 Creation of 3 Catalog Report filters 3, Oglaend Fittings Oglaend Cover Parts Oglaend Splice Parts 4 R 4, Registration i t ti of f th the custom t R Report t DLL This process is detailed in the supplied Report Setup document which is found in the Oglaend Final Deliverables\Reports folder

2012. Intergraph Process, Power & Marine. All Rights Reserved.

Integrating I t ti the th Engineering Enterprise

2012. Intergraph Process, Power & Marine. All Rights Reserved.

Process, Power and Marine Division

F more information For i f ti in i the th UK contact: t t


Telephone : 01793-619999 Fax : 01793-492975 Web : www.intergraph.co.uk www.oglaend-system.com

Potrebbero piacerti anche