ETA-Danmark A/S Kollegievej 6 DK-2920 Charlottenlund Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.

dk Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to construction products

MEMBER OF EOTA

European Technical Approval ETA-10/0422


Trade name: Rotho Blaas GmbH/srl post bases type F10, F20, F30, F40, F50, F60, FD10, FD20, FD30, FD40, FD50, FD60, M10, M20, M30, M50, M60, M70, R10, R20, R30, R40, R50, R60, R70, R80, R90, S10, S20, S30, S40, FI10, FI50, RI40 and MI20 Rotho Blaas s.r.l Via dellAdige 2/1 IT-38040 Cortaccia (BZ) Tel. + 39 0471 818450 Fax + 39 0471 818484 Internet www.rothoblaas.com Three-dimensional nailing plate (Post bases for the support of timber columns and posts as load-bearing elements) 2011-01-11 2016-01-11 Rotho Blaas s.r.l Via dellAdige 2/1 IT-38040 Cortaccia (BZ) 53 pages including 2 annexes which form an integral part of the document

Holder of approval:

Generic type and use of construction product:

Valid from: to: Manufacturing plant:

This European Technical Approval contains:

Page 2 of 53 of European Technical Approval no. ETA-10/0422

LEGAL BASIS AND GENERAL CONDITIONS


This European Technical Approval is issued by ETA-Danmark A/S in accordance with: Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to construction products1), as amended by Council Directive 93/68/EEC of 22 July 19932). Bekendtgrelse 559 af 27-06-1994 (aflser bekendtgrelse 480 af 25-06-1991) om ikrafttrden af EF direktiv af 21. december 1988 om indbyrdes tilnrmelse af medlemsstaternes love og administrative bestemmelser om byggevarer. Common Procedural Rules for Requesting, Preparing and the Granting of European Technical Approvals set out in the Annex to Commission Decision 94/23/EC3). EOTA Guideline ETAG 015 Three-dimensional nailing plates, September 2002 edition. ETA-Danmark A/S is authorized to check whether the provisions of this European Technical Approval are met. Checking may take place in the manufacturing plant. Nevertheless, the responsibility for the conformity of the products to the European Technical Approval and for their fitness for the intended use remains with the holder of the European Technical Approval. This European Technical Approval is not to be transferred to manufacturers or agents of manufacturers other than those indicated on page 1, or manufacturing plants other than those indicated on page 1 of this European Technical Approval. This European Technical Approval may be withdrawn by ETA-Danmark A/S pursuant to Article 5(1) of Council Directive89/106/EEC.

Reproduction of this European Technical Approval including transmission by electronic means shall be in full. However, partial reproduction can be made with the written consent of ETA-Danmark A/S. In this case partial reproduction has to be designated as such. Texts and drawings of advertising brochures shall not contradict or misuse the European Technical Approval. This European Technical Approval is issued by ETADanmark A/S in English. This version corresponds fully to the version circulated within EOTA. Translations into other languages have to be designated as such.

1) 2) 3)

Official Journal of the European Communities No L40, 11 Feb 1989, p 12. Official Journal of the European Communities No L220, 30 Aug 1993, p 1. Official Journal of the European Communities No L 17, 20 Jan 1994, p 34.

Page 3 of 53 of European Technical Approval no. ETA-10/0422

I 1

SPECIAL CONDITIONS OF THE EUROPEAN TECHNICAL APPROVAL Definition of product and intended use

post bases type R20, R30, R40; R50, R60; R80, R90, S10, S20, S30 and RI40 larger distances are allowed. Annex B states the load-carrying capacities of the post bases for solid timber of strength class C24 according to EN 338:2003-09. Thus, when solid timber of strength class C20 is used, the characteristic load-carrying capacities of timber should be reduced by a factor of 0,9. The design of the connections shall be in accordance with Eurocode 3 and Eurocode 5 or a similar national code. The anchorage of the post base in the foundation (except for type M70) and imperfections exceeding the assumptions in Eurocode 5, 5.4.4 are not part of this ETA. The post bases are for use in timber structures subject to the service classes 1, 2 and 3 of Eurocode 5 and for connections subject to static or quasi-static loading. The corrosion protection is given by stainless steel or zinc coating with minimum thickness of 55 m according to EN1461, or by equivalent measures. The metal fasteners must also be of stainless steel or have a zinc coating for the intended use in service class 3 of EN 1995-1-1 (zinc coating Fe/Zn 25c according to EN ISO 2081). Assumed working life The assumed intended working life of concealed beam hangers for the intended use is 50 years, provided that they are subject to appropriate use and maintenance. The information on the working life should not be regarded as a guarantee provided by the manufacturer or ETA Danmark. An assumed intended working life means that it is expected that, when this working life has elapsed, the real working life may be, in normal use conditions, considerably longer without major degradation affecting the essential requirements.

Definition of the product The Rotho Blaas post bases are made of 2.0 mm to 8.0 mm thick steel plates. The post bases are produced of steel grade S235JR according to EN 10025-2:2005-04 with a minimum characteristic yield strength of ReH = 235 N/mm and a minimum characteristic tensile strength of Rm = 360 N/mm or of steel grade 1.4301 according to EN 10088-3:2005-09 with a minimum characteristic yield strength of Rp0,2 = 190 N/mm and a minimum characteristic tensile strength of Rm = 500 N/mm. For the connections with metal fasteners bolts 10 mm, screws HBS+/GHS+ 8x60 mm according to EN 14592 and srews HBS+/GHS+ 8x40 mm with minimum characteristic tensile strength of Rm = 360 N/mm are used. The screws shall be driven into pre-drilled holes according to EN 19951-1, 10.4.5. The outer diameter for washers of bolts shall be not less than 3dB, where dB is the diameter of the bolts. The thickness shall be not less than 0,3dB. For anchorage in the foundation reinforcement bars or steel profiles are used. Dimensions are shown in Annex A and B. Intended use The intended use of the post bases is the support of timber columns and posts as load-bearing elements, where requirements for mechanical resistance and stability and safety in use in the sense of the Essential Requirements 1 and 4 of Council Directive 89/106/EEC shall be fulfilled. The static and kinematical behaviour of the timber members or the supports shall be as described in Annex B. The timber posts may be of solid timber of strength class C20 or better according to EN 338:2003-09. Minimum dimensions for the post have to be considered (Annex A). The end grain of the timber post in general must be plane on the base plate of the post base. Post bases type M20 and M50 have a clearance between the end grain of the timber post and the base plate due to the geometry of the post bases. In order to avoid fungal attack due to permanent high moisture content, the end grain of timber posts with contact or only a very small distance to the foundation (post bases type F10, F20, F30, F40, FD30, FD50, FD60, M30 and M70) should be protected from humidity by other means. The maximum distance between the foundation and the base plate of the post base shall in general be 100 mm. For

Page 4 of 53 of European Technical Approval no. ETA-10/0422

Characteristics of product and assessment


ETAG paragraph Characteristic 2.1 6.1.1 6.1.2 6.1.3 2.2 6.2.1 Mechanical resistance and stability*) Characteristic load-carrying capacity Stiffness Ductility in cyclic testing Safety in case of fire Reaction to fire The post bases are made from aluminium classified as Euroclass A1 in accordance with EN 1350-1 See Annex B No performance determined No performance determined Assessment of characteristic

2.3 6.3.1 2.4 2.5 2.6 2.7 6.7.1 6.7.2

Hygiene, health and the environment Influence on air quality Safety in use Protection against noise Energy economy and heat retention Related aspects of serviceability Durability Serviceability The post bases have been assessed as having satisfactory durability and serviceability when used in timber structures using the timber species described in Eurocode 5 and subject to the conditions defined by service class 1, 2 and 3 See Annex A No dangerous materials **) Not relevant Not relevant Not relevant

6.7.3

Identification

*) See page 5 of this ETA **) In accordance with http://europa.eu.int-/comm/enterprise/construction/internal/dangsub/dangmain.htm In addition to the specific clauses relating to dangerous substances contained in this European Technical Approval, there may be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the EU Construction Products Directive, these requirements need also to be complied with, when and where they apply.

Page 5 of 53 of European Technical Approval no. ETA-10/0422 Safety principles and partial factors The characteristic load-carrying capacities are based on the characteristic values of the connections with metal fasteners, the steel plates, the timber post and the foundation (only for type M70). In the case of timber failure or failure of the metal fasteners, the design values shall be calculated according to EN 1995-1-1 by dividing the characteristic values of the load-carrying capacities by different partial factors for the strength properties, and in addition multiplied with the coefficient kmod. In the case of steel failure, the design value shall be calculated according to EN 1993-1-1 by reducing the characteristic values of the load-carrying capacity with different partial factors. In the case of foundation failure, the design value shall be calculated according to EN 1997-1 by reducing the characteristic values of the load-carrying capacity with different partial factors. The design value of the load-carrying capacity is the smaller value of all load-carrying capacities: F F F k FRd = min mod Rk,H ; Rk,S ; Rk,B M,H Mi,S Ri,B Therefore, for timber failure or failure of the metal fasteners the load duration class and the service class are included. The different partial factors M for steel, timber or foundation failure, respectively, are also correctly taken into account. 2.1 Mechanical resistance and stability See Annex B for the characteristic load-carrying capacity in the different directions F1 to F5 for solid timber of strength class C24 according to EN 338:2003-09. Solid timber of strength class C20 may be included by a reducing factor of 0,9 for the characteristic load-carrying capacity of timber. Using the load-carrying capacities of the post bases, the specifications in Annex A must be fulfilled. The end grain of the timber post must in general be plane on the base plate of the post base Post bases type M20 and M50 have a clearance between the end grain of the timber post and the base plate due to the geometry of the post bases. The characteristic capacities of the post bases are determined by calculation according to Eurocode 3 and Eurocode 5. They should be used for designs in accordance with Eurocode 3 and Eurocode 5 or a similar national code. For post base type M70 the characteristic capacities of the foundation are determined by calculation according to Eurocode 7 on condition that following soil characteristics are provided: bulk density =18 kN/m3, angle of shearing resistance =30, cohesion c=5 kN/m2. The characteristic capacities of post bases type R10 and R30 were determined by using test results of Holzforschung Austria. No performance has been determined in relation to ductility of a joint under cyclic testing. The contribution to the performance of structures in seismic zones, therefore, has not been assessed. No performance has been determined in relation to the joints stiffness properties - to be used for the analysis of the serviceability limit state. No performance has been determined in relation to the anchorage of the post bases in the foundation (except for type M70). It must be checked by the designer of the structure to ensure it is not less than the post base capacity and, if necessary, the post base capacity reduced accordingly. Therefore the specifications for the lever arms eF2/F3 (for load case F2 / F3) and eF4/F5 (for load case F4 / F5) in annex A have to be considered. The lever arm is the distance between the top edge of the foundation and the load. No performance has been determined in relation to ductility of a joint under cyclic testing. The contribution to the performance of structures in seismic zones, therefore, has not been assessed. No performance has been determined in relation to the joints stiffness properties - to be used for the analysis of the serviceability limit state.

2.7 Related aspects of serviceability 2.7.1 Corrosion protection in service class 1 and 2. In accordance with ETAG 015 the requirement is a zinc coating weight of min. 275 g/m2. In accordance with ETAG 015 the post bases are made from steel grade S235JR according to EN 10025-2:2005-04 with minimum characteristic yield strength of ReH = 235 N/mm and a minimum characteristic tensile strength of Rm = 360 N/mm with a zinc coating with minimum thickness of 55 m according to EN1461, or by equivalent measures. 2.7.2 Corrosion protection in service class 3 In accordance with ETAG 015 the requirement is a zinc coating of steel post bases is Fe/Zn 25c. This requirement is fulfilled by post bases with a corrosion protection hot-dip galvanized of approximately 55 m according to EN ISO 1461:1999 or stainless steel grade 1.4301 according to EN 10088-3:2005-09 with a minimum characteristic yield strength of Rp0,2 = 190 N/mm and a minimum characteristic tensile strength of Rm = 500 N/mm.

Page 6 of 53 of European Technical Approval no. ETA-10/0422

Attestation of Conformity and CE marking

3.1 Attestation of Conformity system The system of attestation of conformity is 2+ described in Council Directive 89/106/EEC (Construction Products Directive) Annex III. a) Tasks for the manufacturer: (1) Factory production control, (2) Initial type testing of the product, b) Tasks for the notified body: (1) Initial inspection of the factory and the factory production control, (2) Continuous surveillance

includes details of the extent, nature and frequency of testing and controls to be performed within the factory production control and has been agreed between the approval holder and ETA Danmark. The results of factory production control are recorded and evaluated. The records include at least the following information: Designation of the product, basic material and components; Type of control or testing; Date of manufacture of the product and date of testing of the product or basic material and components; Result of control and testing and, if appropriate, comparison with requirements; Signature of person responsible for factory production control.

3.2

Responsibilities

The records shall be presented to ETA Danmark on request. 3.2.1.1 Initial type testing of the product For initial type-testing the results of the tests performed as part of the assessment for the European Technical Approval shall be used unless there are changes in the production line or plant. In such cases the necessary initial type testing has to be agreed between ETA Danmark and the notified body. 3.2.2. Tasks of notified bodies 3.2.2.1 Initial inspection of the factory and the factory production control The approved body should ascertain that, in accordance with the control plan, the factory, in particular the staff and equipment, and the factory production control, are suitable to ensure a continuous and orderly manufacturing of the post bases with the specifications given in part 2. 3.2.2.2 Continuous surveillance The approved body shall visit the factory at least twice a year for routine inspections. It shall be verified that the system of factory production control and the specified manufacturing processes are maintained, taking account of the control plan. The results of product certification and continuous surveillance shall be made available on demand by the certification body to ETA Danmark. Where the provisions of the European Technical Approval and the control plan are no longer fulfilled, the certificate

3.2.1 Tasks of the manufacturer 3.2.1.1 Factory production control The manufacturer has a factory production control system in the plant and exercises permanent internal control of production. All the elements, requirements and provisions adopted by the manufacturer are documented in a systematic manner in the form of written policies and procedures. This production control system ensures that the product is in conformity with the European Technical Approval. The manufacturer shall only use raw materials supplied with the relevant inspection documents as laid down in the control plan4. The incoming raw materials shall be subject to controls and tests by the manufacturer before acceptance. Check of materials, such as sheet metal, shall include control of the inspection documents presented by suppliers (comparison with nominal values) by verifying dimension and determining material properties, e.g. chemical composition, mechanical properties and zinc coating thickness. The manufactured components are checked visually and for dimensions. The control plan, which is part of the technical documentation of this European Technical Approval,
4
The control plan has been deposited at ETA-Danmark and is only made available to the approved bodies involved in the conformity attestation procedure.

Page 7 of 53 of European Technical Approval no. ETA-10/0422 of conformity shall be withdrawn by the approved body. 3.3 CE marking The CE marking shall be affixed on each packaging of post bases. The initials "CE" shall be followed by the identification number of the notified body and shall be accompanied by the following information: - Name or identifying mark of the manufacturer - The last two digits of the year in which the marking was affixed - Number of the European Technical Approval - Name and size of product - Number of the ETA Guideline (ETAG no. 015) - Number of the EC Certificate of Conformity

Page 8 of 53 of European Technical Approval no. ETA-10/0422

4 Assumptions under which the fitness of the product for the intended use was favourably assessed
4.1 Manufacturing Rotho Blaas post bases are manufactured in accordance with the provisions of this European Technical Approval using the manufacturing processes as identified in the inspection of the plant by the notified inspection body and laid down in the technical documentation. 4.2 Installation The stated type of fasteners for each post base has to be applied in applicable holes in the post base. The installation instructions to be followed are: The timber post - shall be restrained against rotation, and supported at the lower and upper end - shall be strength class C20 according to EN 338:2003-09 or better, see section 3 of this evaluation report - shall be free from wane in the post base - must fulfil the requirements regarding minimum dimensions (see Annex A) - end grain must in general be plane on the base plate of the post base; post bases type M20 and have a clearance between the end grain of the timber post and the base plate of the post base due to the geometry of the post bases. The actual end bearing capacity of the timber member to be used in conjunction with the post base is checked by the designer of the structure to ensure it is not less than the post base capacity and, if necessary, the post base capacity reduced accordingly. To provide for constructive wood preservation, appropriate measures should be taken to protect the end grain of timber posts with contact or little distance to the foundation (post bases type F10, F20, F30, F40, FD30, FD50, FD60, M30 and M70). There are no specific requirements relating to preparation of the timber members. The maximum distance between the foundation and the base plate of the post base shall in general be 100 mm. For post bases type R20, R30, R40; R50, R60; R80, R90, S10, S20, S30 and RI40 larger distances are allowed. In case of post base type M70 the characteristic capacities of the foundation are determined by

calculation according to Eurocode 7 on condition that following soil characteristics are provided: bulk density =18 kN/m3, angle of shearing resistance =30, cohesion c=5 kN/m2. The anchorage of the post base in the foundation except for post base type M70 - is not part of this ETA. It must be checked by the designer of the structure to ensure it is not less than the post base capacity and, if necessary, the post base capacity reduced accordingly. Therefore the specifications for the lever arms eF2/F3 (for load case F2 / F3) and eF4/F5 (for load case F4 / F5) in Annex A have to be considered. The lever arm is the distance between the top edge of the foundation and the load The secondary structural member the concrete support - to which the post bases are fixed shall be: Made from concrete of at least strength class C15, unless otherwise is indicated in annex B of this ETA.

To ensure sufficient capacity the designer has to take into account splitting of the timber. The timber member shall be free from wane. There shall be no gap between the timber and the horizontal contact area Otherwise the gap between the timber member and the post base may not exceed 3 mm. The execution of the connection shall be in accordance with the approval holders technical literature.

4.3 Maintenance and repair Maintenance is not required during the assumed intended working life. Should repair prove necessary, it is normal to replace the post base.

Thomas Bruun Manager, ETA-Danmark

Page 9 of 53 of European Technical Approval no. ETA-10/0422 Annex A Product details and definitions Table A.1 Specifications of the post bases
Post base
Type F10 Dimension 71x71 91x91 81 F20 101 121 141 F30 F40 71x71 91x91 71x71 91x91 101x101 121x121 F50 141x141 161x161 181x181 201x201 121x120x150 141x140x150 F60 161x160x200 201x200x200 161x160x150 201x200x150 121x... 141x... FD10 161x... 181x... 201x... 121x... FD20 141x... 161x... 201x... FD30 FD30 internal FD40 FD40 internal FD50
1)

Quantity
Art.-Nr. F10_1 F10_2 F20_1 F20_2 F20_3 F20_4 F30_1 F30_2 F40_1 F40_2 F50_1 F50_2 F50_3 F50_4 F50_5 F50_6 F60_1 F60_2 F60_3 F60_4 F60_5 F60_6 FD10_1 FD10_2 FD10_3 FD10_4 FD10_5 FD20_1 FD20_2 FD20_3 FD20_4 FD30_1 FD30_2 FD30_1 FD30_2 FD40_1 FD40_2 FD40_1 FD40_2 FD50_1 FD50_2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2/4
1)

Metal Fasteners
2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 2x Bo 10mm 2x Bo 10mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 2x Bo 10mm 2x Bo 10mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm

Post [mm]
min b/h 71/71 91/91 81 101 121 141 71/71 91/91 71/71 91/91 101/101 121/121 141/141 161/161 181/181 201/201 121/120 141/140 161/160 201/200 161/160 201/200 121/120 141/131 161/151 181/171 201/191 121/76 141/92 161/106 201/140 80/120 80/120 80/120 80/120 80/120 80/120 80/120 80/120 82/82 127/127 -

Distances [mm]
max. a eF2/F3 77 77 77 77 77 77 122 122 122 122 83 83 83 108 108 108 119 119 119 119 119 119 108 108 108 108 108 94 94 94 94 90 eF4/F5 77 77 77 77 77 77 122 122 122 122 83 83 83 108 108 108 84 84 109 109 84 84 40 40 40 40 40 41 41 41 41 38 38 38 38 46 46 43 43 90

60x180 80x240 60x180 80x240 60x180 80x240 60x180 80x240 46x46 76x76

2 / 4 1)

When 4 angle brackets are used, the characteristic load-carrying capacity may be increased by a factor of 2,0.

Page 10 of 53 of European Technical Approval no. ETA-10/0422

Continuation of Table A.1 Specifications of the post bases


Post base Type FD60 M10 Dimension 46x46 76x76 71x71 91x91 71x60 M20 91x60 101x146 121x146 71x50 81x50 M30 91x50 101x50 121x50 71x150 M50 91x150 101x150 121x150 M60 80x130 71x71 M70 91x91 81 101 120x120 R10 160x160 200x200 120x120 R20 160x160 200x200 R30 120x120 160x160 105 R40 97 150 250 R50 R60 R70 170-285 110-210 160x100 100x350x20 140x450x24 100x350x16
2)

Quantity Art.-Nr. FD60_1 FD60_2 M10_1 M10_2 M20_1 M20_2 M20_3 M20_4 M30_1 M30_2 M30_3 M30_4 M30_5 M50_1 M50_2 M50_3 M50_4 M60_1 M70_1 M70_2 M70_3 M70_4 R10_1 R10_2 R10_3 R20_1 R20_2 R20_3 R30_1 R30_2 R40_1 R40_2 R40_3 R40_4 R50_1 R50_2 R60_1 R70_1 R70_2 R70_3 2/4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2)

Metal Fasteners 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 2x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 6x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 6x HBS+/GHS+ 8x60mm 4x Bo 10mm 2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 8x40mm 4x HBS+/GHS+ 6x90mm 4x HBS+/GHS+ 8x100mm 4x HBS+/GHS+ 8x100mm 4x HBS+/GHS+ 6x90mm 4x HBS+/GHS+ 8x100mm 4x HBS+/GHS+ 8x100mm 8x full thread 6x60mm 16x full thread 6x90mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm

Post [mm] min b/h 82/82 112/112 71/71 91/91 71/114 91/114 101/114 121/114 71/80 81/80 91/80 101/80 121/80 71/114 91/114 101/114 121/114 80/120 71/71 91/91 81 101 80/80 100/100 140/140 80/80 100/100 140/140 120/120 160/160 70 / 70 80 / 80 100/100 100/100 100/100 100/100 100/100 100/100 140/140 100/100 100 100 100 100 100 136 209 257 136 209 257 155 215 105 97 150 250 277 202 194 100 100 100

Distances [mm] max. a eF2/F3 89 45 45 139 139 139 139 185 185 185 185 185 235 235 235 235 218 eF4/F5 89 14 14 72 72 72 72 30 30 30 30 30 77 77 77 77 30 -

2 / 4 2)

When 4 angle brackets are used, the characteristic load-carrying capacities for F1 (Tension), F23 and F45 may be increased by a factor of 2,0.

Page 11 of 53 of European Technical Approval no. ETA-10/0422

Continuation of Table A.1 Specifications of the post bases


Post base Type R80 R90 S10 S20 Dimension 160x100 100x100 140 140 160x100 160x100 100x160 S30 140x160 100x120 140x160 S40 FI10 71x60 91x60 71x71 91x91 101x101 121x121 FI50 141x141 161x161 201x201 RI40 150 250 71x60 MI20 91x60 101x60 121x60 Art.-Nr. R80_1 R90_1 S10_1 S10_2 S20_1 S20_2 S30_1 S30_2 S30_3 S30_4 S40_1 S40_2 FI10_1 FI10_2 FI50_1 FI50_2 FI50_3 FI50_4 FI50_6 RI40_3 RI40_4 MI20_1 MI20_2 MI20_3 MI20_4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2-4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 2x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 4x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 5x HBS+/GHS+ 8x60mm 6x HBS+/GHS+ 8x60mm Quantity Metal Fasteners Post [mm] min b/h 80/80 100/100 140 140 100/100 100/100 100/100 140/140 100/100 140/140 71/98 91/98 71/71 91/91 101/101 121/121 141/141 161/161 201/201 100/100 100/100 71/114 91/114 101/114 121/114 Distances [mm] max. a 195 164 118 153 118 153 166 168 166 168 150 250 eF2/F3 86 86 107 107 83 83 83 108 108 139 139 139 139 eF4/F5 77 77 83 83 83 108 108 72 72 72 72

Page 12 of 53 of European Technical Approval no. ETA-10/0422

Table A.2 Specifications of the metal fasteners according to EN 14592 Fastener type (S235) Screws HBS+/GHS+ Screws HBS+/GHS+ Screws, full thread Bolts Washers Diameter 8 mm 6 mm 6 mm 10 mm 30 mm 3 mm Size (mm) Length 40/60/100 mm 90 mm 60/90 mm Thickness Galvanic zinc coating Galvanic zinc coating Galvanic zinc coating Galvanic zinc coating Galvanic zinc coating Finish

The load-carrying-capacities of the metal fasteners were calculated according to Eurocode 5 for lateral loads. The contribution to the load-carrying capacity due to the rope effect was considered according to Eurocode 5.

Page 13 of 53 of European Technical Approval no. ETA-10/0422 Annex B Characteristic load-carrying capacities Table B.1 Characteristic load-carrying capacities for post bases in kN
Post Base Type Art.Nr. F10_1 F10 F10_2 F1 (Compression) Timber 50,8 84,8
m

F1 (Tension) Timber Steel 4,3 3,8


m,0

F23 Timber -

F45 Steel Timber -

Steel -

Steel 9,5 10,2


m,0

6,2 8,2
m

5,0 9,9
m

4,5 4,7
m,0

7,6 13,3
m

F20_1 F20_2 F20 F20_3 F20_4

17,2 62,5 99,1 142,3


m

7,4 7,4 11,0 11,0


m

4,1 8,8 10,0 11,1


m,0

6,5 3,2 9,9 9,9


m

2,4 6,6 8,9 11,5


m,0

8,1 12,8 18,4 25,3


m

3,1 8,4 11,4 14,7


m,0

F30_1 F30 F30_2

50,8 84,8
m

7,1 9,5
m

6,5 13,0
m,0

7,6 7,6
m

2,9 2,9
m,0

7,6 7,6
m

2,9 2,9
m,0

F40_1 F40 F40_2

50,8 84,8
m

7,1 9,5
m

7,7 21,8
m,0

7,6 13,3
m

5,4 7,9
m,0

7,6 13,3
m

5,4 7,9
m,0

F50_1 F50_2 F50_3 F50 F50_4 F50_5 F50_6

29,4 33,6 42,0 42,0 42,0 46,2


m

29,1 33,3 41,6 41,6 41,6 45,7


m,0

7,1 7,1 7,1 7,1 7,1 7,1


m

11,5 13,8 16,1 17,3


m,0

17,2 17,2 17,2 20,4 20,4 21,0


m

9,0 8,7 11,9 10,6 13,9 14,4


m,0

17,2 17,2 17,2 20,4 20,4 21,0


m

9,0 8,7 11,9 10,6 13,9 14,4


m,0

F60_1 F60_2 F60_3 F60 F60_4 F60_5 F60_6

33,6 37,8 42,0 54,6 42,0 54,6


m

32,7 36,8 40,8 53,1 40,8 54,4


m,0

7,0 7,0 7,0 7,0 7,0 7,0


m

34,2 37,6 41,0 24,1 41,0 24,1


m,0

17,3 20,6 22,6 22,6 32,9 32,9


m

11,7 15,0 16,5 16,5 23,3 23,3


m,0

8,7 10,2 11,3 11,3 11,3 11,3


m

15,2 13,0 18,4


m,0

6,8 6,8 15,6 m,2

FD10_1 FD10_2 FD10_3 FD10 FD10_4 FD10_5

33,6 37,8 42,0 46,2 54,6


m

33,5 37,6 41,8 46,0 54,4


m,0

7,1 7,1 7,1 7,1 7,1


m

4,7 5,0 5,6 6,1 6,0


m,0

20,9 24,4 24,4 24,4 24,4


m

2,6 3,3 4,1 5,0 6,0


m,0

10,2 11,5 12,7 14,0 15,3


m

10,4 11,4 12,5 13,5 14,0


m,0

FD20_1 FD20_2 FD20 FD20_3 FD20_4

33,6 37,8 42,0 54,6


m

33,5 37,6 41,8 54,4


m,0

7,0 7,0 7,0 7,0


m

11,8 13,3 14,6 17,0


m,0

22,9 31,6 32,9 27,5


m

3,7 4,7 5,9 2,6


m,0

16,1 17,7 19,3 17,0


m

19,4 21,4 23,3 27,2


m,0

Page 14 of 53 of European Technical Approval no. ETA-10/0422

Continuation of Table B.1 Characteristic load-carrying capacities for post bases in kN


Post Base Type FD30 Dimension FD30_1 FD30_2 F1 (Compression) Timber 77,6 115,8 m FD30 internal FD30_1 FD30_2 77,6 115,8 m FD40_1 FD40 FD40_2 Steel 71,9 95,9 m,0 F1 (Tension) Timber 7,0 7,3 m Steel 4,7 3,6 m,0 4,7 3,6 m,0 Timber F23 Steel Timber 9,3 9,0 m F45 Steel 3,2 4,0 m,0 3,2 4,0 m,0 -

12,5 16,7
m,0

13,5 13,5
m

2,1 2,6
m

7,0 7,3
m

6,3 8,4
m,0

4,5 9,0
m

6,3 8,4
m,0

8,2 8,6
m

5,0 6,5
m,0

FD40 internal

FD40_1 FD40_2

19,8 20,7
m 69,4 203,8 m

12,5 16,7
m,0 14,0 14,4 m,1 m,1 7,8 5,5 4,8 3,8 m,0

8,1 8,1 8,1 8,1 m,2 8,5 8,5 8,5 8,5 m,2

13,5 13,5
m 7,8 m 7,8 m 3,5 7,1 m 7,4 7,4 7,4 7,4 m 3,7 5,1 5,1 5,1 7,4 m 7,8 7,8 7,8 7,8 m

6,3 8,4
m,0 10,0 m,0 17,7 m,0 10,0 11,5 m,1 7,8 5,4 4,7 3,8 m,0 12,9 21,8 21,8 21,8 21,8 m,0 7,8 5,5 4,8 3,8 m,0

8,1 8,1 8,1 8,1 m,2 -

m m 7,6 13,0 m 5,5 5,5 5,5 5,5 m 2,7 3,7 3,7 3,7 5,5 m 5,5 5,5 5,5 5,5 m

m,0 m,0 5,9 5,9 m,0 1,5 1,5 1,5 1,5 m,0 1,2 1,2 1,2 1,2 1,2 m,0 1,8 1,8 1,6 1,2 m,0

2,7 2,7 2,7 2,7 m,2

2,1 2,6
m m m 7,6 13,0 m 8,2 8,2 8,2 8,2 m 8,5 9,7 10,9 12,1 14,0 m 8,6 8,6 8,6 8,6 m

5,1 5,2
m,0 m,0 m,0 m,0 3,0 3,0 3,0 3,0 m,0 5,9 5,6 5,6 5,6 5,9 m,0 3,3 3,3 3,3 3,3 m,0

5,8 5,4 m,2 -

FD50_1 FD501) FD50_2

FD602)

FD60_1 FD60_2

75,6 263,4 m

M10_1 M10 M10_2

6,1 12,2 m

M20_1 M20_2 M20 M20_3 M20_4

7,4 7,4 7,4 7,4 m

M30_1 M30_2 M30 M30_3 M30_4 M30_5

89,2 101,8 114,4 127,0 152,2 m

M50_1 M50_2 M50 M50_3 M50_4

7,4 7,4 7,4 7,4 m

1) 2)

When 4 angle brackets are used, the characteristic load-carrying capacities may be increased by a factor of 2,0.

When 4 angle brackets are used, the characteristic load-carrying capacities for F1 (Tension), F23 and F45 may be increased by a factor of 2,0.

Page 15 of 53 of European Technical Approval no. ETA-10/0422

Continuation of Table B.1 Characteristic load-carrying capacities for post bases in kN


Post Base Type M60 Type Art.-Nr. M60_1 Art.-Nr. M70_1 M70_2 M70 M70_3 M70_4 Type Art.-Nr. R10_1 R10 R10_2 R10_3 R20_1 R20 R20_2 R20_3 R30_1 R30 R30_2 R40_1 R40_2 R40 R40_3 R40_4 R50_1 R50 R50_2 R60_1 R70_1 R70 R70_2 R70_3 R80 R90 R80_1 R90_1 F1 (Compression) Timber 51,0 m Timber 6,1 8,6 8,1 8,1 m Timber 71,2 111,8 222,8 m 55,8 90,4 189,0 m m 50,7 64,0 99,9 100,2 m 56,5 56,5 m R60 117,7 m 108,4 210,6 106,2 m 125,5 m 71,6 m m,0 m,0 m,0 23,3 38,1 41,9 50,7 m,0 50,7 50,7 m,0 66,9 m,0 66,9 79,5 54,0 m,0 69,7 m,0 42,6 m,0 Steel 55,1 m,0 F1 (Tension) Timber 26,4 m Steel 65,3 m,2 Timber 11,8 m F23 Steel 2,8 m,0 3,6 m,2 Timber 2,2 m F45 Steel 5,7 m,0 Foun. 5,2 9,9 3,3 3,8 R,c -

Steel Foun. Timber 12,1 9,4 m,2 1,6 3,0 2,3 3,1 R,v Steel 48,3 75,4 108,6 m,1 48,3 75,4 108,6 m,1 48,3 75,4 m,1 39,6 100,6 57,1 65,3 m,1 88,7 92,0 m,1 92,9 m,1 66,4 99,8 39,6 m,1 107,7 m,1 39,7 m,1 m m Timber 18,7 62,4 m -

Steel Foun. Timber Steel 24,3 36,4 m,0 7,6 10,1 8,1 10,3 m -

Steel Foun. Timber Steel 7,6 6,7 6,5 6,9 m,0 5,2 9,9 3,3 3,8 R,c 7,6 10,1 8,1 10,3 m 7,6 6,7 6,5 6,9 m,0

m,0 m,0

Page 16 of 53 of European Technical Approval no. ETA-10/0422

Continuation of Table B.1 Characteristic load-carrying capacities for post bases in kN


Post Base Type S10 Art.-Nr. S10_1 S10_2 F1 (Compression) Timber 88,3 88,3 m S20_1 S20 S20_2 88,3 88,3 m S30_1 S30_2 S30 S30_3 S30_4 104,8 214,3 104,8 214,3 m FI10_1 FI10 FI10_2 50,8 84,8 m FI50_1 FI50_2 FI50_3 FI50 FI50_4 FI50_6 42,0 46,2 m RI40_3 RI40 RI40_4 99,9 100,2 m MI20_1 MI20_2 MI20 MI20_3 MI20_4 7,4 7,4 7,4 7,4 m Type Dimension Angle 0 15 S40_1 30 45 60 S40 0 15 S40_2 30 45 60 Timber 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4
m

F1 (Tension) Timber Steel 3,5 3,1 m,0 9,3 11,2 14,0 m,0 6,3 4,4 3,8 3,0 m,0 m,2 m,2 Timber 5,0 5,0 m 15,5 15,5 15,5 18,4 18,9 m 5,5 5,5 5,5 5,5 m Timber 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5 5,5
m

F23 Steel 3,0 3,7 m,0 7,3 7,0 10,7 8,6 13,0 m,0 1,2 1,2 1,2 1,2 m,0 Steel 2,1 1,9 1,9 2,1 2,5 2,1 1,9 1,9 2,1 2,5
m,0

F45 Timber 7,6 13,0 m 15,5 15,5 15,5 18,4 18,9 m 8,2 8,2 8,2 8,2 m 5,5 5,0 4,9 5,2 6,1 5,5 5,0 4,9 5,2 6,1
m,2

Steel 49,2 49,2 m 49,2 49,2 m 100,9 212,2 100,9 212,2 m m,1 24,0 26,7 33,3 33,3 36,7 m,0 38,8 47,1 m,0 m,0 m,0 m,1 47,8 57,0 m,1 11,2 8,1 8,1 8,1 m,2 Steel 6,6 3,5 2,5 2,1 1,9 6,6 3,5 2,5 2,1 1,9
m,0

Steel 7,7 9,1 m,0 7,3 7,0 10,7 8,6 13,0 m,0 2,4 2,4 2,4 2,4 m,0 -

m,1 m,1 3,5 3,5 m 7,2 7,2 7,2 7,2 m 7,4 7,4 7,4 7,4 m Timber 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4 7,4
m

29,4 33,6 42,0

Steel 6,6 3,5 2,5 2,1 1,9 6,6 3,5 2,5 2,1 1,9
m,0

8,5 8,1 6,1 5,2 4,9 8,5 8,1 6,1 5,2 4,9
m,2

8,5 8,1 6,1 5,2 4,9 8,5 8,1 6,1 5,2 4,9
m,2

Page 17 of 53 of European Technical Approval no. ETA-10/0422 Definitions of forces, their directions and eccentricity Force F1: tensile or compression load
F1

Force F2 / F3: horizontal load parallel to the side plates of the post base

F23

Force F4 / F5: horizontal load perpendicular to the side plates of the post base

F45

Acting forces F1 axial force (tension or compression) acting along the central axis of the joint F2 and F3 horizontal force parallel to the side plates of the post base acting with the lever arm eF2/F3 above the foundation F4 and F5 horizontal force perpendicular to the side plates of the post base acting with the lever arm eF4/F5 above the foundation Combined forces If the forces F1 and F2/F3 or F4/F5 act at the same time, the following inequality shall be fulfilled:

Fi,d
i,d

The forces F2 and F3 or F4 and F5 are forces with opposite direction. Therefore only one force F2 or F3, and F4 or F5, respectively, is able to act simultaneously with F1.

Page 18 of 53 of European Technical Approval no. ETA-10/0422

Page 19 of 53 of European Technical Approval no. ETA-10/0422

Page 20 of 53 of European Technical Approval no. ETA-10/0422

Page 21 of 53 of European Technical Approval no. ETA-10/0422

Page 22 of 53 of European Technical Approval no. ETA-10/0422

Page 23 of 53 of European Technical Approval no. ETA-10/0422

Page 24 of 53 of European Technical Approval no. ETA-10/0422

Page 25 of 53 of European Technical Approval no. ETA-10/0422

Page 26 of 53 of European Technical Approval no. ETA-10/0422

Page 27 of 53 of European Technical Approval no. ETA-10/0422

Page 28 of 53 of European Technical Approval no. ETA-10/0422

Page 29 of 53 of European Technical Approval no. ETA-10/0422

Page 30 of 53 of European Technical Approval no. ETA-10/0422

Page 31 of 53 of European Technical Approval no. ETA-10/0422

Page 32 of 53 of European Technical Approval no. ETA-10/0422

Page 33 of 53 of European Technical Approval no. ETA-10/0422

Page 34 of 53 of European Technical Approval no. ETA-10/0422

Page 35 of 53 of European Technical Approval no. ETA-10/0422

Page 36 of 53 of European Technical Approval no. ETA-10/0422

Page 37 of 53 of European Technical Approval no. ETA-10/0422

Page 38 of 53 of European Technical Approval no. ETA-10/0422

Page 39 of 53 of European Technical Approval no. ETA-10/0422

Page 40 of 53 of European Technical Approval no. ETA-10/0422

Page 43 of 53 of European Technical Approval no. ETA-10/0422

Page 45 of 53 of European Technical Approval no. ETA-10/0422

Page 49 of 53 of European Technical Approval no. ETA-10/0422

Page 50 of 53 of European Technical Approval no. ETA-10/0422

Page 51 of 53 of European Technical Approval no. ETA-10/0422

Page 52 of 53 of European Technical Approval no. ETA-10/0422

Page 53 of 53 of European Technical Approval no. ETA-10/0422