TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0




TABLE OF CONTENTS


1.0 SCOPE


2.0 CROSS REFERENCES


3.0 APPLICABLE CODES AND STANDARDS


4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General
4.2 Ratings
4.3 Construction
4.4 Capacitor Unit or Stack
4.5 Electromagnetic Unit
4.6 LV Terminal Box
4.7 HV Porcelain Bushing
4.8 HV Terminal
4.9 Polarity and Terminal Markings
4.10 Grounding
4.11 Insulating Oil
4.12 Nameplate


5.0 TESTS


6.0 DATA SCHEDULE


PAGE NO. 2 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



1.0 SCOPE

This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of Capacitor Voltage Transformers (CVT) 110 kV through 380 kV intended to
be used outdoors in the system of the Saudi Electricity Company, Saudi Arabia.


2.0 CROSS REFERENCES

This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.

This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.


3.0 APPLICABLE CODES AND STANDARDS

The latest revision/amendments of the following Codes and Standards shall be applicable for
the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.

3.1 IEC 60044-5 Capacitor Voltage Transformers

3.2 IEC 62155 Tests on Hollow Insulators for use in Electrical Equipment

3.3 IEC 60507 Artificial Pollution Tests on High-Voltage Insulators to be
used in A.C.systems.

3.4 IEC 60529 Degrees of Protection Provided by Enclosures.

3.5 IEC 60867 Insulating liquids - Specifications for unused liquids based on
synthetic aromatic hydrocarbons

3.6 IEEE C57.13 Standard Requirements for Instrument Transformers

3.7 IEEE C62.11 Standard for Metal-Oxide Surge Arrestors for AC Power
Circuits ( > 1kV)

3.8 NEMA C93.1 Requirments for Power-Line Carrier Devices.

3.8 NEMA ICS 6 Enclosures for Industrial Control and Systems

3.9 ASTM D2296 Standard Specification for Continuity of quality of Electrical
Insulating Polybutene Oil for Capacitors

PAGE NO. 3 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



3.10 54-TMSS-01 Mineral Insulating Oil for Electrical Apparatus


4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

The capacitor voltage transformer (CVT) shall be of manufacturer's standard design
per IEC 60044-5 or NEMA C93.1 and shall meet or exceed the requirements of this
Specification in all respects.

4.2 Ratings

The ratings shall be as specified in Data Schedule. The rated insulation levels and
maximum primary voltage for CVT shall be based on the highest voltage at
emergency condition per 01-TMSS-01.

4.3 Construction

4.3.1 The CVT shall be of oil-filled, voltage connected type, rigid column structure
and freestanding unit (base mounted) for outdoor service.

4.3.2 The CVT for 380 kV nominal system voltage shall be supplied with a corona
ring.

4.3.3 The CVT shall be adequately designed and constructed to withstand
insulator-washing pressure of 3500 kPa without damage and without ingress
of water or moisture into the apparatus internals, or degradation of the
sealing.

4.3.4 Rated Voltage factor shall be as per IEC 60044-5 unless otherwise specified
in the data schedule.

4.3.5 The capacitor and EMU units of the CVT shall be hermatically sealed.

4.4 Capacitor Unit or Stack

4.4.1 The capacitor unit or stack shall consist of series connected oil impregnated
capacitor elements C1 (high voltage capacitor) and C2 ( Intermediate voltage
capacitor) housed in porcelain bushing completely filled with oil and
hermetically sealed. Each capacitor unit or stack shall be fitted with stainless
steel bellows (oil volume adjusting device) to allow for change in volume of
oil and maintain a slightly positive oil pressure at any temperature in the
operating range.



PAGE NO. 4 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



4.4.2 The capacitor unit or stack used with the voltage transformer shall have a
capacitor divider with intermediate voltage terminal for connection to
electromagnetic unit. The insulation of the low voltage terminal of the
capacitor voltage divider shall be tested for one minute per IEC 60044-5 or
NEMA C93.1.

4.4.3 The over voltage surges transmitted from primary to secondary terminals of
CVT shall not exceed the values given against Type A and Type B per IEC
60044-5 or equivalent standard for CVT installed in air-insulated Substation
and gas insulated metal-enclosed substation (GIS) respectively.

4.4.4 The low voltage end shall be terminated in a bushing insulated from the base
and capable of withstanding a test voltage of 10kV for 1 minute.

4.5 Electromagnetic Unit

4.5.1 The electromagnetic unit shall consist of intermediate voltage transformer,
compensating reactor, and associated protection circuitry. The
electromagnetic unit shall be housed in the base on which the capacitor unit
or stack is mounted on the top.The base housing shall be filled with oil and
hermetically sealed.

4.5.2 The voltage transformer shall have two secondary windings. The rated
secondary voltage (nominal) of each winding shall be 115/3 V or 110/3 V
or as specified in data schedule. All secondary circuits of voltage transformer
shall be provided with fuses or MCBs .

4.5.3 The CVT for relaying service shall have a rated burden of at least 100 VA at
a power factor of 0.85 lagging and shall be of standard accuracy class 3P per
IEC 60044-5 or 1.2R accuracy class per NEMA C93.1. Additional accuracy
classes ( T1, T2, T3 per IEC 60044-5) for transient performance for CVT for
relaying service shall be as specified in the data schedule. The CVT for
metering service (except for revenue) shall have an accuracy class 0.5 per
IEC 60044-5 or accuracy class 0.3 for burdens X, Y, and Z and power factor
per NEMA C93.1. The CVT for revenue metering service shall have accuracy
class of 0.2 per IEC 60044-5 and shall be capable of simultaneous loading of
accuracy of 0.2 per IEC 60044-5for all secondary windings up to their rated
burden and power factor.

4.6 LV Terminal Box

4.6.1 The voltage transformer secondary terminals and fuses/MCBs, damping
devices (for limiting over voltages, preventing sustained ferro-resonance and
acheiving a higher performance of transient response of CVT for relaying
per IEC 60044-5 or NEMA C93.1), protective devices and thermostatically
controlled space heater shall be enclosed in the LV terminal box which shall
be part of the base housing enclosure.

PAGE NO. 5 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



4.6.2 The internal face of the cover shall bear a metallic plate with the schematic
diagram of windings and of their terminal markings.

4.6.3 4.6.3 Terminals on terminal board or terminal block for
user's field wiring connections shall be non-captive pan head screw type.

4.6.4 The bottom plate of terminal box shall be furnished with cutout complete
with undrilled cable gland plate to accommodate cable gland of up to 40 mm
external diameter. Provisions for conduit entrance shall be provided.

4.6.5 The enclosure shall be weatherproof and dust-tight having degree of
protection in accordance with 01-TMSS-01.

4.6.6 An external earthing stud capable of accepting twin-copper conductor of
240mm
2
connected to the metal base shall be provided on all units.

4.6.7 The CVT shall have an earthing terminal provided within the secondary
terminal box for earthing the secondary windings and cable screens.

4.7 HV Porcelain Bushing

4.7.1 The HV porcelain shall be of electrical grade wet-processed porcelain, and
shall be as specified in Data Schedule. The porcelain bushing shall be
designed and constructed to withstand static and dynamic load.

4.7.2 Outdoor apparatus porcelain bushing shall be designed to have a creepage
distance per 01-TMSS-01. Color of the bushing shall be brown.

4.8 HV Terminal

The CVT shall be provided with standard high voltage NEMA CC1 ,4-hole terminal
pad or equivalent. The HV terminal pad shall be tin-plated and shall be suitable for
use with copper or aluminum terminal connectors.

4.9 Polarity and Terminal Markings

The relative polarity of the leads and terminals of the CVT shall be clearly identified
by permanent markings that cannot be easily obliterated, and shall be designated in
accordance with IEC 60044-5 or NEMA C93.1.

4.10 Grounding

The CVT shall be provided with a clamp type ground terminal located on the
external surface of the CVT base, and shall be sized to accommodate bare copper
conductor of size 1x240mm
2
for station fault current level upto 40 kA and
2x240mm
2
for fault current levels above 40 kA.
PAGE NO. 6 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



4.11 Insulating Oil

4.11.1 The capacitor unit or stack shall be filled-up with synthetic oil conforming to
class III sheet 1 per IEC 60867 or ASTM-D-2296 and shall not contain
Polychlorinated Biphenyl (PCB) substance. CVT with synthetic oil per sheet
4 of IEC 60867, having at least 5 years of proven field experience can also be
offered for review and final acceptance by SEC.

4.11.2 The electromagnetic unit shall be filled-up with mineral oil conforming to 54-
TMSS-01.

4.12 Nameplate

4.12.1 Each CVT and/or capacitor shall bear a nameplate permanently and legibly
marked in English with the information listed in IEC 60044-5 or NEMA
C93.1, plus additional information as follows:

a. The words kV Capacitor Voltage Transformer /
F Capacitor.

b. SEC Purchase Order Number, Contract No. or J.O. Number.

c. 50-TMSS-02, Rev. 0.

4.12.2 Nameplate of CVT manufactured per NEMA C93.1 shall additionally have
indication of primary, neutral and each secondary winding terminal.

4.12.3 The nameplate material shall be stainless steel and shall be fastened to the
equipment by stainless steel screws or rivets.


5.0 TESTS

All test results shall be submitted to SEC for review and approval.

5.1 Type (Design) Tests

5.1.1 All design (type) tests prescribed in IEC 60044-5 or NEMA
C93.1 shall be performed on the representative unit or on the first unit of
every new design or rating to be supplied to SEC.

5.1.2 Chopped impulse test shall be carried out additionally for all CVTs
manufactured per NEMA C93.1 standard.

PAGE NO. 7 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



5.2 Routine (Production) Tests

5.2.1 All production (routine) tests prescribed in IEC 60044-5 or NEMA C93.1
shall be performed on all CVTs and /or capacitors.

5.2.2 Partial Discharge measurement shall be carried out additionally for all CVTs
manufactured per NEMA C93.1 standard.

5.3 Special Tests

5.3.1 The following special tests shall be carried out on one representative CVT
per IEC 60044-5 or equivalent ANSI/IEEE, if specified in Technical data
Schedule.

a. Measurement of the transmission factor of high frequency
overvoltages.

b. Mechanical strength test

c. Determination of the temperature coefficient.

d. Tightness design test of capacitor units.

5.4 Apparatus Porcelain Bushing

5.4.1 All tests per IEC 62155 or equivalent ANSI/IEEE standard shall be
performed on apparatus porcelain bushing.

5.4.2 Artificial Pollution Tests shall be performed on one representative bushing
using Solid Layer Method per IEC 60507 or equivalent ANSI/IEEE
Standard, if specified in the data schedule.












PAGE NO. 8 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

SEC Enquiry No. Date:

SEC Purchase Order
No.
Date:
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

Nominal System Voltage (kV rms)
(110,115, 132, 230, 380)

System Fault Current Level
(at rated system voltage (kA rms)

Type of System Grounding
(Solidly grounded neutral,
resistance grounded, others)


3.0 APPLICABLE CODES AND STANDARDS

Applicable Industry Standards *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

Name of the manufacturer of CVT *

Type or Model Number *

4.2 Ratings

Maximum primary voltage (kVrms)

Rated primary voltage (kVrms)
(Phase to Ground)


'A'- SEC SPECIFIED DATA/PARAMETER.
'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

PAGE NO. 9 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.2 (Contd)

Voltage Transformation Ratio

Accuracy Class : Secondary 1
Secondary 2

Class for Transient response performance of
CVT for relaying service




Rated Secondary Burden:
Secondary 1 (VA)

Secondary 2 (VA)

Max. Simultaneous (VA) *

Continuous Thermal Burden (VA) *

Rated Voltage Factor
Continuous operation
*
Short time (30s) operation *

BIL of CVT (kV peak) *

BSL of CVT (kV peak) (for 380kV System) *

Power Frequency withstand Voltage (kV
rms
) *

Maximum Partial Discharge Level of
capacitor voltage divider@ kV (pC) *


Maximum Radio Influence Voltage of
capacitor voltage divider (for 110kV &
above) (RIV) at kV (V) 2500

CVT Application AIS/GIS
Transmitted Over Voltage (Type A or Type
B) per clause 7.5.2 of IEC 60044-5) *

Type A
/Type B





PAGE NO. 10 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.4 Capacitor Unit or Stack

Number of Capacitor units or stacks *

Dissipation factor (tan ) of Capacitor
stacks *


Temperature co-efficient of Capacitor
stacks *


Rated Capacitance:
Capacitor divider at 60Hz (pF) *

C
1
(high voltage capacitor) (pF) *
C
2
(Intermediate voltage capacitor) (pF) *

Mounting *

Weight of complete CVT (Kgs) *

Operating Temperature Range (C) *

Insulation of the low voltage terminal of the
capacitor voltage divider(kVrms) *


4.5 Electromagnetic Unit
No of taps availabe for secondary winding
Rated Secondary Voltage of each Winding
(V rms)


BIL (kV peak) *

Power Frequency Withstand Voltage:
1 min. dry (kV rms) *
10 sec. wet (kV rms) *


PAGE NO. 11 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.5 Number of Secondary Windings *
Contd.
Winding insulation and class *

Winding material (Al or Cu) *

Secondary fuse/MCB rating (A) *


4.7 LV Terminal Box

Type of Degree of protection of enclosure *

Space heater : *

Power (W) *

Voltage (Vrms) *


4.8 HV Porcelain Bushing

Name of manufacturer *

Type and designation number *

Rated Voltage (Nominal) (KV rms)

BIL (kV peak) *

BSL (kV peak) (for 380 kV System) *

Power Frequency Withstand Voltage:


1 min. dry (kV rms) *
10 sec. wet (kV rms) *

Creepage distance (mm) *

Flashover distance (mm) *

Color *
PAGE NO. 12 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.8 (Contd)

Cantilever Strength (kg) *

Maximum Horizontal Terminal pull in 150
km/hr wind (kg) *


Corona ring provided? * Yes / No

4.9 HV Terminal

For Conductor :
Size (mm)

Type
No. of conductor/phase

HV Terminal Pad :
Type *
Pad dimension (mm x mm) *
Thickness (mm) *
No. of holes *
Hole diameter (mm) *
Material *

4.10 Grounding

Clamp type ground terminal provided? *

4.11 Insulating Oil
[Refer to Data Schedule of 54-TMSS-01
and fill in Column 'B' for mineral oil in
Electromagnetic Unit. For synthetic oil in
Capacitor unit or stack, vendor to fill in
Column 'B' of the following.]


Type of Oil *

Make Designation *

Manufacturer *

Class of Oil *
PAGE NO. 13 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.11 (Contd)
Industry Standard *

Appearance *

Color, max. (initial) (if applicable) *

Density at 20C (Kg/cm) (if applicable) *

Specific Gravity at 15.6/15.6C, min. (if
applicable) *


Flash Point, min. (C) *

Pour Point, max. (C) *

Kinematic Viscosity at :
40C (mm/s) *

100C(cSt) *

Water content as shipped max.(mg/kg or
ppm) *


Chlorine Content (mg/Kg) (if applicable) *

Inorganic chlorides and sulfates
(if applicable) *


Neutralization Value, max. (mg KOH/g) *

Corrosive sulphur *

Dielectric Breakdown Voltage, min. (kV) *

Volume Resistivity at 90C, min. (T.m)
(if applicable) *


Resistivity, initial at 100C, min. (ohm-cm)
(if applicable) *


PAGE NO. 14 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'


4.11 ( Contd)
Dielectric dissipation factor, tan at 90C
and 40 Hz to 60 Hz, max. (if applicable) *


Stability under electrical stress and
ionization (gassing) Absorption, min.
(Method A) (mm/min.) (if applicable) *


Power Factor, initial, 60 Hz, at 100C, max.
(if applicable) *


Aging Test (after Heating 96 h at 115C)
(if applicable) :
- Color, max. *

- Neutralization Value, max.
(mg KOH/g) *

- Power Factor, 60 Hz at 100C, max. *

Resistivity at 100C, min. (ohm - cm) *

PCB content *


5.0 TESTS

Artificial Pollution tests shall be performed
on one of the representative bushing. Yes / No


Special Tests to be carried out

PAGE NO. 15 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G

TRANSMISSION MATERIALS STANDARD SPECIFICATION
50-TMSS-02, Rev. 0



6.0 DATA SCHEDULE

CVT APPLICABLE FOR 110 KV TO 380 KV

ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY
SEC:
A.







ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY
BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
B.







OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/
CONTRACTOR:
C.





Actual Manufacturer
of Equipment/Material
Vendor/Supplier/
Contractor

Name of the Company
Location and address



Name and Signature of
authorized
representative

and date


Official Seal/Stamp
of the Company &
Date




PAGE NO. 16 OF 16 50TMSS02R0/J SG
Date of Approval: August 6, 2006 G