STEAM ENGINE GENERATOR CAPACITY CALCULATION

3.9.1

Normal Operation

3.9.1.1 Total Demand Load (KW)


= (1 x 1675.53) + (0.5 x 266.65)
3.9.1.2 Total Demand Load (KVAR)
= (1 x 1082.45) + (0.5 x 197.84)
3.9.1.3 Total Demand Load (KVA)
= (1 x 1997.99) + (0.5 x 332.04)
3.9.1.4 Total Peak Load (KW)
= (1 x 1675.53) + (0.5 x 266.65) + (0.1 x 933.26)
3.9.1.5 Total Peak Load (KVAR)
= (1 x 1082.45) + (0.5 x 197.84) + (0.1 x 572.34)
3.9.1.6 Total Peak Load (KVA)
= (1 x 1997.99) + (0.5 x 332.04) + (0.1 x 1094.95)

3.9.2

1808.86

KW

1181.36

KVAR

2164.01

KVA

1902.18

KW

1238.60

KVAR

2273.51

KVA

Data of the Largest Stand-by Motor

3.9.2.1 Motor Data


- Equipment No.
- Description
- Rated kW
- Rated Voltage
- Power Factor on Full Load
- Starting Power Factor
- Efficiency on Full Load
- Consumption kW
- Consumption kVAR

P-912 C
Cooling Water Recirculation Pump with motor
160.00 KW
380 V
0.85
0.25
0.926
145.79 KW
90.35 KVAR

3.9.2.2 Motor full load current ( IFL)


= ( ( 160.00 x 1000 ) / (0.93 x 0.85 ) ) / ( 1.73 x 380.00 )
3.9.2.3 Motor starting current ( Is) using DS starting type
= 0,33x650 % x 308.85 x 0.33
=
3.9.2.4 Motor starting capacity ( KVAs)
= ( 1.732 x 662.48 x 380.00) / 1000
=
3.9.2.5 The Load before starting
KWB = Total Demand Load (KW)
=
KVARB = Total Demand Load (KVAR)
=
KVAB = Total Demand Load (KVA)
=
3.9.2.6 The Load after starting
KW = Total Demand Load (KW) + KW motor
=
KVAR = Total Demand Load (KVAR) + KVAR motor
=
KVA
=

=308.85

662.48

436.03

KVA

1808.86
1181.36
2164.01

KW
KVAR
KVA

1954.64
1271.72
2331.93

KW
KVAR
KVA

3.9.2.7 Required capacity for permissible voltage dip


KVA1 = ( 436.03+2164.01) x 0.17 x ( 1 - 0.15 ) / 0.15
=
2504.71 KVA
3.9.2.8 Required capacity for permissible overload during starting
KVA2 = ( V ( 1808.86 + 436.03 x 0.25 )2 + ( 1181.36 + 436.03 x 0.97 )2 / 1.50
=
1666.61 KVA
KW2
= ( 1808.86 + 436.03 x 0.25 ) / 1.10
=
1743.51 KW
2

SELECTION OF GENERATOR CAPACITY

2.1
2.1.1

STEAM ENGINE GENERATOR


The selected capacity of Steam turbine generator must be sufficient for each of the calculated value s
The maximum calculated capacity in above section for real and apparent power shall be the minimum
KW :
KW
1,954.64
KVA :
KVA
2,504.71

2.1.2

The selected capacity of Steam turbine generator shall be:


KW G :
KW
5,700
KVAG :
PF
:

2.1.3

2,000
0.80

KVA
Lagging

Conclusion of Steam Engine Generator Capacity


No.
1
2
3
4

Condition

Required Power
kW
Margin (%)
Normal Operation
1,808.86
68.27
Peak Load
1,902.18
66.63
Study of 150 kW Motor Starting (During Starting)
1,743.51
69.41
Study of 150 kW Motor Starting (After Starting)
1,954.64
65.71

According to the results of this study, it is further confirmed that the capacity of generator
is sufficient for normal operation of Bioethanol Plant
3

EMERGENCY DIESEL GENERATOR CALCULATION

4.9.1

Normal Operation

4.9.1.1 Essential Demand Load (KW)


= (1 x 0.00) + (0.5 x 0.00)
4.9.1.2 Essential Demand Load (KVAR)
= (1 x 0.00) + (0.5 x 0.00)
4.9.1.3 Essential Demand Load (KVA)
= (1 x 0.00) + (0.5 x 0.00)

0.00

KW

0.00

KVAR

0.00

KVA

SELECTION OF GENERATOR CAPACITY

2.1
2.1.1

DIESEL ENGINE GENERATOR


The selected capacity of diesel engine generator must be sufficient for each of the calculated value sh

The maximum calculated capacity in above section for real and apparent power shall be the minimum
KW
:
KW
0.00
KVA :
KVA
0.00
2.1.1

The selected capacity of Diesel engine generator shall be:


KW G :
KW
1,000
KVAG :
PF
:

2.1.2

1,250
0.80

KVA
Lagging

Conclusion of Diesel Engine Generator Capacity


No.

Condition

Emergency Operation

Required Power
kW
Margin (%)
0.00
100.00

According to the results of this study, it is further confirmed that the capacity of generator
is sufficient for normal operation of Compressor Station

01
02A
02B
03
04

x=
kW
116.07
359.60
196.53
501.56
501.78

CONTINUOUS
1
KVAR
84.67
220.99
128.18
373.61
274.99

KVA
143.67
422.08
234.63
625.41
572.19

TOTAL

1675.53

1082.45

1997.99

KW
144.79
384.71
206.19
562.49
510.67

NORMAL
KVAR
105.07
239.87
135.43
419.33
281.66

KVA
178.90
453.50
246.72
701.59
583.30

PRETREATMENT
PROCESS 1
PROCESS 2
PEMBANGKITAN
WATER TREATMENT

ulation Pump with motor (Fermentation and Distillation ) C

0.33
6.50
0.97

DF
RED
START
SIN START

GENERATOR DATA
Xd'
0.17
KG
1.50
KE
1.10
V DIP
0.15
PF
0.80

INT

f the calculated value shown on Section 3.9.1.7, 3.9.2.6 , 3.9.2.8 and 3.9.2.9.
r shall be the minimum rating of the Generator

the calculated value shown on Section 2.11.

r shall be the minimum rating of the Generator

y=
kW
57.44
50.22
19.33
121.88
17.78

INTERMITTENT
0.50
KVAR
40.81
37.77
14.50
91.43
13.33

266.65

197.84

KVA
70.46
62.84
24.17
152.36
22.22

z=
kW
57.95
346.55
147.82
174.99
205.95

STAND-BY
0.1
KVAR
38.81
214.59
91.65
109.15
118.15

KVA
69.75
407.61
173.92
206.24
237.43

332.04

933.26

572.34

1094.95

TRAFO CALCULATION
PEAK
KW
KVAR
KVA
150.58
108.95
185.87
419.37
261.33
494.26
220.97
144.60
264.11
579.99
430.24
722.22
531.26
293.48
607.05

CAPACITY
215
544
296
842
700

CON

OPTIMAL
CHOICE Persen to Cap
600
36%
600
91%
600
49%
600
140%
600
117%

01
02A
02B
03
04
TOTAL
SAFE CHOICE
CAPACITY
CHOICE
232
600
618
600
330
600
903
600
759
600

x=
kW
0.00
0.00
0.00
0.00
0.00

CONTINUOUS
1
KVAR
0.00
0.00
0.00
0.00
0.00

0.00

FE CHOICE
Persen to Cap
39%
103%
55%
150%
126%

0.00

178.90
453.50
246.72
701.59
583.30

KVA
0.00
0.00
0.00
0.00
0.00

y=
kW
0.00
0.00
0.00
0.00
0.00

0.00

0.00

INTERMITTENT
0.5
KVAR
0.00
0.00
0.00
0.00
0.00

WORST CHOICE
CHOICE Persen to Cap
600
30%
600
76%
600
41%
600
117%
600
97%

0.00

KVA
0.00
0.00
0.00
0.00
0.00

z=
kW
0.00
0.00
0.00
0.00
0.00

STAND-BY
0.1
KVAR
0.00
0.00
0.00
0.00
0.00

KVA
0.00
0.00
0.00
0.00
0.00

0.00

0.00

0.00

0.00

CLIENT :

REVISION : -

PROJECT NO
:
PROJECT NAME :
LOCATION
:

ELECTRICAL LOAD LIST


MCC FOR SUBSTATION 1
01-MCC-01

1.
2.
3.
4.
5.
6.
7.
8.

System Voltage = 400 V


System Frequency = 50 Hz

Continuous Load = Load that operated continuously during normal operation


Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
Standby Load = Load that does not operate during normal operation
Absorbed Load = Load that is absorbed by the driven equipment
Load Factor = Absorbed load divide by Nameplate Rating
Operating Load (kW) = Absorbed load divide by Efficiency
Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
Power Factor = cos j

PREPARED BY :
APPROVED BY :

Reference Document :

9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)


10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating
Voltage Absorb.

Tag No.

Load Description

Load

Circuit

Load

Type

Type

Status

(M/F)

(Volt)

Load
(KW)

(C/I/S)

Motor
(HP)

(KW)

Others

FLA

Load

(A)

Factor

Power
Eff.

Factor

(KVA)

Continuous

Intermittent

kW

kVAR

18.29

11.33

kW

Stand-by

kVAR

Remarks

kW

kVAR

18.29

11.33

17.44

10.81

PRETREATMENT
ADDITIONAL
01-P-01A

S/S 01 Pump 01A

DOL

380

16.10

18.50

37.58

0.87

88.0%

85.0%

01-P-01 B

S/S 01 Pump 01B

DOL

380

16.10

18.50

37.58

0.87

88.0%

85.0%

01-P-02 A

S/S 01 Pump 02A

DOL

380

15.00

15.0

17.65

31.18

1.00

86.0%

85.0%

01-P-02 B

S/S 01 Pump 02B

DOL

380

15.00

15.0

17.65

31.18

1.00

86.0%

85.0%

01-LP-01

Lighting Panel Area 01 A

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

01-LP-02

Lighting Panel Area 01 B

380

36.00

36.0

45.00

75.97

1.00

90.0%

80.0%

01-WO-01

Welding Outlet

380

20.00

20.0

25.00

42.20

1.00

90.0%

80.0%

00-LP-01

Lighting Panel Area 00 A

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

8.89

6.67

NL

00-LP-02

Lighting Panel Area 00 B

380

24.00

24.0

30.00

50.64

1.00

90.0%

80.0%

26.67

20.00

NL

00-LP-03

Lighting Panel Area 00 C

380

12.00

12.0

15.00

25.32

1.00

90.0%

80.0%

13.33

10.00

NL

00-LP-04

Lighting Panel Area 00 D

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

8.89

6.67

NL

00-LP-05

Lighting Panel Area 00 E

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

8.89

6.67

NL

00-LP-06

Lighting Panel Area 00 F

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

8.89

6.67

NL

00-LP-07

Lighting Panel Area 00 G

380

12.00

12.0

15.00

25.32

1.00

90.0%

80.0%

13.33

10.00

NL

Total

Electrical Load Summary for Boiler


1. Demand Load
Demand Load (kW)
= 1 116.07 + 0.5 57.44
Demand Load (kVA)
= 1 143.67 + 0.5 70.46
2. Peak Load
Peak Load (kW) = 1 116.07 + 0.5 57.44 + 0.1 57.95
Peak Load (kVA) = 1 143.67 + 0.5 70.46 + 0.1 69.75

kVA
Bus No. : 01-MCC-01

= 144.79 kW
= 178.90 kVA
= 150.58 kW
= 185.87 kVA

NL
17.44

8.89

10.81

NL

6.67
30.00

NL
22.22

84.67

NL
NL

40.00

116.07
143.67

NL

57.44
70.46

40.81

57.95
69.75

16.67

38.81

400 V, 3 Phase, 50 Hz

NL

CLIENT :

REVISION :

PROJECT NO
:
PROJECT NAME :
LOCATION
:

ELECTRICAL LOAD LIST


MCC FOR SUBSTATION 02
02-MCC-01

1.
2.
3.
4.
5.
6.
7.
8.

System Voltage = 400 V


System Frequency = 50 Hz

Continuous Load = Load that operated continuously during normal operation


Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
Standby Load = Load that does not operate during normal operation
Absorbed Load = Load that is absorbed by the driven equipment
Load Factor = Absorbed load divide by Nameplate Rating
Operating Load (kW) = Absorbed load divide by Efficiency
Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
Power Factor = cos j

PREPARED BY :
APPROVED BY :

Reference Document :

9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)


10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating

Tag No.

Load Description

Voltage
(Volt)

Absorb.
Load
(KW)

Load
Type
(M/F)

Circuit
Type

Load
Status
(C/I/S)
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
C
C
C
C
C

380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380

58.40
58.40
69.20
69.20
26.10
26.10
2.40
2.40
6.00
6.00
0.20
0.20
0.20
0.20
3.60
3.60
2.27
2.27
11.20
11.20
1.50
47.85

FLA
(A)

Load
Factor

Eff.

Power
Factor

75.00
75.00
90.00
90.00
30.00
30.00
3.00
3.00
7.50
7.50
0.25
0.25
0.25
0.25
5.50
5.50
3.70
3.70
14.00
14.00
1.50
55.00

143.09
143.09
170.60
170.60
59.58
59.58
7.35
7.35
16.35
16.35
0.61
0.61
0.61
0.61
12.90
12.90
8.78
8.78
29.44
29.44
3.67
105.39

0.87
0.87
0.91
0.91
0.87
0.87
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.87

92.6%
92.6%
93.2%
93.2%
90.0%
90.0%
78.5%
78.5%
82.0%
82.0%
78.5%
78.5%
78.5%
78.5%
81.0%
81.0%
80.0%
80.0%
85.0%
85.0%
78.5%
92.2%

86.0%
86.0%
86.0%
86.0%
85.0%
85.0%
79.0%
79.0%
85.0%
85.0%
79.0%
79.0%
79.0%
79.0%
80.0%
80.0%
80.0%
80.0%
85.0%
85.0%
79.0%
86.0%

Motor
(HP)

(KW)

Others
(KVA)

Continuous
kW

kVAR

63.07

37.42

74.25

44.06

29.00

17.97

Intermittent
kW

Stand-by

kVAR

P-2101 A
P-2101 B
P-2102 A
P-2102 B
P-2103 A
P-2103 B
P-2104 A
P-2104 B
P-2105A
P-2105B
P-2106 A
P-2106 B
P-2107 A
P-2107 B
P-2108 A
P-2108 B
P-2109 A
P-2109 B
A-2101
A-2102
A-2103
P-2110 A

PROCESS A
S/S 02A Pump 01A
S/S 02A Pump 01B
S/S 02A Pump 02A
S/S 02A Pump 02B
S/S 02A Pump 03A
S/S 02A Pump 03B
S/S 02A Pump 04A
S/S 02A Pump 04B
S/S 02A Pump 05A
S/S 02A Pump 05B
S/S 02A Pump 06A
S/S 02A Pump 06B
S/S 02A Pump 07A
S/S 02A Pump 07B
S/S 02A Pump 08A
S/S 02A Pump 08B
S/S 02A Pump 09A
S/S 02A Pump 09B
S/S 02A Agitator motor 01
S/S 02A Agitator motor 02
S/S 02A Agitator motor 03
S/S 02A Pump 10A

M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M

DOL
DOL
DS
DS
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL
DOL

P-2110 B

S/S 02A Pump 10B

DOL

380

47.85

55.00

105.39

0.87

92.2%

86.0%

P-2111 A

S/S 02A Pump 11A

DOL

380

47.85

55.00

105.39

0.87

92.2%

86.0%

P-2111 B

S/S 02A Pump 11B

DOL

380

47.85

55.00

105.39

0.87

92.2%

86.0%

P-2112 A

S/S 02A Pump 12A

DOL

380

20.20

30.00

59.58

0.87

90.0%

85.0%

P-2112 B
P-2113 A
P-2113 B
P-2113 C

S/S 02A Pump 12B


S/S 02A Pump 13A
S/S 02A Pump 13B
S/S 02A Pump 13C

M
M
M
M

DOL
DOL
DOL
DOL

S
I
I
I

380
380
380
380

20.20
1.00
1.00
1.00

30.00
1.00
1.00
1.00

59.58
2.45
2.45
2.45

0.87
0.80
0.80
0.80

90.0%
78.5%
78.5%
78.5%

85.0%
79.0%
79.0%
79.0%

1.27
1.27
1.27

0.99
0.99
0.99

3.06

2.37

7.32

4.53

0.25
0.25

kVAR

63.07

37.42

74.25

44.06

29.00

17.97

3.06

2.37

7.32

4.53

0.25

0.20

0.25

0.20

4.44

3.33

51.90

30.79

51.90

30.79

22.44

13.91

0.20
0.20

4.44

3.33

2.84
2.84
13.18
13.18
1.91
51.90

2.13
2.13
8.17
8.17
1.48
30.79

51.90

30.79

22.44

kW

Remarks

NL
NL
NL
NL
NL
NL
NL
NL
NL
NL
NL
NL
EL
EL
EL
EL
EL
EL
EL
EL
EL
NL
NL
NL

13.91

NL
NL
NL
NL
NL
NL

OTHERS
02-LP-01

Lighting Panel Area 02 A

380

20.88

24.00

30.00

50.64

0.87

90.0%

80.0%

23.20

17.40

EL

02-LP-02

Lighting Panel Area 02 B

380

20.88

24.00

30.00

50.64

0.87

90.0%

80.0%

23.20

17.40

NL

02-WO-01

Welding Outlet

380

17.40

20.00

25.00

42.20

0.87

90.0%

80.0%

19.33

14.50

NL

02-WO-02

Welding Outlet

380

17.40

20.00

25.00

42.20

0.87

90.0%

80.0%

19.33

14.50

NL

02-UPS-01

UPS A

380

16.00

32.00

40.00

67.53

0.50

90.0%

80.0%
Total
kVA

Electrical Load Summary for Boiler


1. Demand Load
Demand Load (kW)
= 1 359.60 + 0.5 50.22

Bus No. : 02-MCC-01

= 384.71 kW

17.78

13.33

359.60
220.99
422.08

EL
50.22
62.84

37.77

346.55
214.59
407.61
400 V, 3 Phase, 50 Hz

CLIENT :

REVISION :

PROJECT NO
:
PROJECT NAME :
LOCATION
:

ELECTRICAL LOAD LIST


MCC FOR SUBSTATION 02
02-MCC-01

1.
2.
3.
4.
5.
6.
7.
8.

System Voltage = 400 V


System Frequency = 50 Hz

Continuous Load = Load that operated continuously during normal operation


Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
Standby Load = Load that does not operate during normal operation
Absorbed Load = Load that is absorbed by the driven equipment
Load Factor = Absorbed load divide by Nameplate Rating
Operating Load (kW) = Absorbed load divide by Efficiency
Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
Power Factor = cos j

PREPARED BY :
APPROVED BY :

Reference Document :

9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)


10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating

Tag No.

Load Description

Demand Load (kVA)


= 1 422.08 + 0.5 62.84
2. Peak Load
Peak Load (kW) = 1 359.60 + 0.5 50.22 + 0.1 346.55
Peak Load (kVA) = 1 422.08 + 0.5 62.84 + 0.1 407.61

Load
Type
(M/F)

Circuit
Type

= 453.50 kVA
= 419.37 kW
= 494.26 kVA

Load
Status
(C/I/S)

Voltage
(Volt)

Absorb.
Load
(KW)

Motor
(HP)

(KW)

Others
(KVA)

FLA
(A)

Load
Factor

Eff.

Power
Factor

Continuous
kW

kVAR

Intermittent
kW

kVAR

Stand-by
kW

kVAR

Remarks

CLIENT :

REVISION :

PROJECT NO
:
PROJECT NAME :
LOCATION
:

ELECTRICAL LOAD LIST


MCC FOR SUBSTATION 02
02-MCC-02

1.
2.
3.
4.
5.
6.
7.
8.

System Voltage = 400 V


System Frequency = 50 Hz

Continuous Load = Load that operated continuously during normal operation


Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
Standby Load = Load that does not operate during normal operation
Absorbed Load = Load that is absorbed by the driven equipment
Load Factor = Absorbed load divide by Nameplate Rating
Operating Load (kW) = Absorbed load divide by Efficiency
Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
Power Factor = cos j

PREPARED BY :
APPROVED BY :

Reference Document :
EQUIPMENT LIST

9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)


10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating

Tag No.

Load Description

Load
Type
(M/F)

Voltage Absorb.
Circuit Load
(Volt)
Load
Type Status
(KW)
(C/I/S)

Motor
(HP)

(KW)

Others

FLA
(A)

Load
Factor

Power
Factor

Eff.

(KVA)

P-2201 A

PROCESS B
S/S 02B Pump 01A

DOL

380

26.10

30.00

59.58

0.87

90.0%

85.0%

P-2201 B

S/S 02B Pump 01B

DOL

380

26.10

30.00

59.58

0.87

90.0%

85.0%

P-2202 A

S/S 02B Pump 02A

DOL

380

19.14

22.00

44.43

0.87

88.5%

85.0%

P-2202 B

S/S 02B Pump 02B

DOL

380

19.14

22.00

44.43

0.87

88.5%

85.0%

P-2203 A

S/S 02B Pump 03A

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2203 B

S/S 02B Pump 03B

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2204 A

S/S 02B Pump 04A

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2204 B

S/S 02B Pump 04B

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2205 A

S/S 02B Pump 05A

DOL

380

65.25

75.00

143.09

0.87

92.6%

86.0%

P-2205 B

S/S 02B Pump 05B

DOL

380

65.25

75.00

143.09

0.87

92.6%

86.0%

P-2206 A

S/S 02B Pump 06A

DOL

380

12.00

15.00

31.18

0.80

86.0%

85.0%

P-2206 B

S/S 02B Pump 06B

DOL

380

12.00

15.00

31.18

0.80

86.0%

85.0%

P-2207 A

S/S 02B Pump 07A

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2207 B

S/S 02B Pump 07B

DOL

380

1.20

1.50

3.67

0.80

78.5%

79.0%

P-2208 A

S/S 02B Pump 08A

DOL

380

2.96

3.70

8.78

0.80

80.0%

80.0%

P-2208 B

S/S 02B Pump 08B

DOL

380

2.96

3.70

8.78

0.80

80.0%

80.0%

P-2209 A

S/S 02B Pump 09A

DOL

380

1.76

2.20

5.39

0.80

78.5%

79.0%

P-2209 B

S/S 02B Pump 09B

DOL

380

1.76

2.20

5.39

0.80

78.5%

79.0%

P-2210 A

S/S 02B Pump 10A

DOL

380

1.76

2.20

5.39

0.80

78.5%

79.0%

P-2210 B

S/S 02B Pump 10B

DOL

380

1.76

2.20

5.39

0.80

78.5%

79.0%

Continuous
kW

kVAR

29.00

17.97

21.63
1.53
1.53
70.46
13.95
1.53
3.70
2.24
2.24

Intermittent
kW

Stand-by

kVAR

Remarks

kW

kVAR

29.00

17.97

21.63

13.40

1.53

1.19

1.53

1.19

70.46

41.81

13.95

8.65

1.53

1.19

3.70

2.78

2.24

1.74

2.24

1.74

NL

13.40

NL
NL

1.19

NL
NL

1.19

NL
NL

41.81

NL
NL

8.65

NL
NL

1.19

NL
EL

2.78

EL
EL

1.74

EL
EL

1.74

EL
EL
EL

OTHERS
Lighting Panel Area 02 C

380

27.84

32.00

40.00

67.53

0.87

90.0%

80.0%

30.93

23.20

02-UPS-02

UPS B

380

16.00

32.00

40.00

67.53

0.50

90.0%

80.0%

17.78

13.33

02-UPS-03

UPS C

380

0.00

32.00

40.00

67.53

0.00

90.0%

80.0%

Space Heater

380

17.40

20.00

25.00

42.20

0.87

90.0%

80.0%

02-LP-03

02-SH-1

Total
kVA

Electrical Load Summary for Boiler


1. Demand Load
Demand Load (kW)
= 1 196.53 + 0.5 19.33
Demand Load (kVA)
= 1 234.63 + 0.5 24.17
2. Peak Load
Peak Load (kW) = 1 196.53 + 0.5 19.33 + 0.1 147.82
Peak Load (kVA) = 1 234.63 + 0.5 24.17 + 0.1 173.92

Bus No. : 02-MCC-02

= 206.19 kW
= 246.72 kVA
= 220.97 kW
= 264.11 kVA

EL
EL
0.00
19.33

196.53
128.18
234.63

19.33
24.17

0.00

14.50
14.50

EL
EL

147.82
173.92

91.65

400 V, 3 Phase, 50 Hz

CLIENT :

REVISION :

PROJECT NO

ELECTRICAL LOAD LIST

PREPARED BY :

PROJECT NAME :

MCC FOR SUBSTATION 03

APPROVED BY :

LOCATION

03-MCC-01

1. Continuous Load = Load that operated continuously during normal operation


2. Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
3. Standby Load = Load that does not operate during normal operation
4. Absorbed Load = Load that is absorbed by the driven equipment

System Voltage = 400 V

Reference Document :

5. Load Factor = Absorbed load divide by Nameplate Rating

System Frequency = 50 Hz

EQUIPMENT LIST

6. Operating Load (kW) = Absorbed load divide by Efficiency


7. Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
8. Power Factor = cos j
9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)
10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating
Voltage Absorb.

Tag No.

Load Description

Load

Circuit

Load

Type

Type

Status

(M/F)

(C/I/S)

(Volt)

Load
(KW)

Motor
(HP)

(KW)

Others

FLA

Load

(A)

Factor

Power
Eff.

Factor

(KVA)

Continuous
kW

kVAR

380

290

Intermittent

Stand-by

kW

kVAR

33.33

25.00

kW

Remarks

kVAR

03-MCC-A

Local Panel for Boiler

380

03-MCC-B

Local Panel for STG

380

30.00

30.0

63.31

1.00

90.0%

80.0%

P-301 A

S/S 03 Pump 01A

DS

380

12.00

15.00

31.18

0.80

86.0%

85.0%

13.95

8.65

NL

P-301 B

S/S 03 Pump 01B

DS

380

12.00

15.00

31.18

0.80

86.0%

85.0%

13.95

8.65

NL

P-302 A

S/S 03 Pump 02A

DOL

380

0.60

0.75

1.84

0.80

78.5%

79.0%

P-302 B

S/S 03 Pump 02B

DOL

380

0.60

0.75

1.84

0.80

78.5%

79.0%

0.76

0.59

Local Panel for Coal Handling System

DOL

380

18.00

18.0

37.98

1.00

90.0%

80.0%

03-MCC-C

NL

0.76
20.00

NL

0.59

NL

15.00

NL
EL

ADDITIONAL
P-303 A

S/S 03 Pump 03A

DS

380

81.81

90.00

170.60

0.91

93.2%

86.0%

87.78

52.08

NL

P-303 B

S/S 03 Pump 03B

DOL

380

6.00

7.50

16.35

0.80

82.0%

85.0%

7.32

4.53

NL

S/S 03 Pump 04

DOL

380

26.10

30.00

59.58

0.87

90.0%

85.0%

29.00

17.97

P-305 A

S/S 03 Pump 05A

DOL

380

26.10

30.00

59.58

0.87

90.0%

85.0%

29.00

17.97

P-305 B

S/S 03 Pump 05B

DOL

380

26.10

30.00

59.58

0.87

90.0%

85.0%

P-304

NL
NL
29.00

17.97

NL

Others
17.78

13.33

03-BC-01

Baterry charger

380

16.00

16.00

20.00

33.76

1.00

90.0%

80.0%

03-BC-02

Battery for STG

380

55.00

55.00

70.00

116.06

1.00

90.0%

80.0%

03-BC-03

Battery RCP STG

220

1.60

1.60

2.00

5.83

1.00

90.0%

80.0%

1.78

1.33

EL

03-BC-04

Battery RCP DEG

220

1.60

1.60

2.00

5.83

1.00

90.0%

80.0%

1.78

1.33

EL

03-CP-01

Cathodic Protection

380

4.00

4.00

5.00

8.44

1.00

90.0%

80.0%

4.44

3.33

EL

03-LP-01

Lighting Panel Area 03 A

380

16.00

16.0

20.00

33.76

1.00

90.0%

80.0%

17.78

13.33

03-LP-02
03-WP-01

Lighting Panel Area 03B

380

24.00

24.0

30.00

50.64

1.00

90.0%

80.0%

Welding Outlet

380

20.00

20.0

25.00

42.20

1.00

90.0%

80.0%
Total

Electrical Load Summary for Boiler


1. Demand Load
Demand Load (kW) = 1 501.56 + 0.5 121.88
= 562.49 kW
Demand Load (kVA) = 1 625.41 + 0.5 152.36
= 701.59 kVA
2. Peak Load
Peak Load (kW)
= 1 501.56 + 0.5 121.88 + 0.1 174.99= 579.99 kW
Peak Load (kVA)
= 1 625.41 + 0.5 152.36 + 0.1 206.24= 722.22 kVA

kVA
Bus No. :03-MCC-01

EL
61.11

45.83

EL

EL
26.67

20.00

NL
22.22

501.56
373.61
625.41

121.88
152.36

91.43

16.67

174.99
109.15
206.24
400 V, 3 Phase, 50 Hz

NL

CLIENT :

REVISION :

PROJECT NO

ELECTRICAL LOAD LIST

PREPARED BY :

PROJECT NAME :

MCC FOR SUBSTATION 04

APPROVED BY :

LOCATION

04-MCC-01

1. Continuous Load = Load that operated continuously during normal operation


2. Intermittent Load = Load that does not operate continuously but comes ON and OFF during normal operation
3. Standby Load = Load that does not operate during normal operation
4. Absorbed Load = Load that is absorbed by the driven equipment

System Voltage = 400 V

Reference Document :

5. Load Factor = Absorbed load divide by Nameplate Rating

System Frequency = 50 Hz

EQUIPMENT LIST

6. Operating Load (kW) = Absorbed load divide by Efficiency


7. Operating Load (kVAR) = Operating Load (kW) x tan (arc cos j)
8. Power Factor = cos j
9. Apparent Power (kVA) = SQRT (kW2 + kVAR2)
10. Maximum Load Demand = 1.0 A + 0.5 B + 0.1 C
where A = Continuous Load
B = Intermittent Load
C = Standby Load
Load

Consumed Load
Rating
Voltage Absorb.

Tag No.

Load Description

Load

Circuit

Load

Type

Type

Status

(Volt)

Load
(KW)

Motor
(HP)

(KW)

Others

FLA

Load

(A)

Factor

Power
Eff.

Factor

(KVA)

Continuous

(M/F)

(C/I/S)

Local Panel Water Treatment

380

P-401 A
P-401 B
P-411 A

S/S 04 Pump 01A


S/S 04 Pump 01B
Cooling Water Pump 11 A

M
M
M

DOL
DOL
DS

C
S
C

380
380
380

26.10
26.10
145.44

30.00
30.00
160.00

59.58
59.58
293.88

0.87
0.87
0.91

90.0%
90.0%
94.0%

85.0%
85.0%
88.0%

154.72

83.51

P-411 B

Cooling Water Pump 11 B

DS

380

145.44

160.00

293.88

0.91

94.0%

88.0%

154.72

83.51

P-411 C

Cooling Water Pump 11 C

DS

380

145.44

160.00

293.88

0.91

94.0%

88.0%

04-MCC-A

150

kW

kVAR

150

80

29.00

17.97

Intermittent
kW

Stand-by

kVAR

kW

Remarks

kVAR
NL

29.00

17.97

154.72

83.51

NL
NL
EL
NL
NL

Others
04-LP-01

Lighting Panel Area 05 A

380

8.00

8.0

10.00

16.88

1.00

90.0%

80.0%

04-LP-02

Lighting Panel Area 05 B

380

16.00

16.0

20.00

33.76

1.00

90.0%

80.0%

04-CP-01

Cathodic Protection

380

4.00

4.00

5.00

8.44

1.00

90.0%

80.0%

04-WO-01

Welding Outlet

380

20.00

20.0

25.00

42.20

1.00

90.0%

80.0%
Total

Electrical Load Summary for Boiler


1. Demand Load
Demand Load (kW)
= 1 501.78 + 0.5 17.78
Demand Load (kVA)
= 1 572.19 + 0.5 22.22
2. Peak Load
Peak Load (kW) = 1 501.78 + 0.5 17.78 + 0.1 205.95
Peak Load (kVA) = 1 572.19 + 0.5 22.22 + 0.1 237.43

kVA
Bus No. : 04-MCC-01

= 510.67 kW
= 583.30 kVA
= 531.26 kW
= 607.05 kVA

8.89

6.67

EL
17.78

4.44

13.33

NL

3.33

EL
22.22

501.78
274.99
572.19

17.78
22.22

13.33

16.67

205.95
118.15
237.43
400 V, 3 Phase, 50 Hz

NL

URUTAN NGAJAR
1 drawing single line diagram
2 Rename komponen
3 Masukan rating
4 Load flow
5 masuk ke revision , pengenalan SF, Loading Factor dan PF dan Efisiensi

DATA MOTOR
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
18

pump manufacturer data


EFFICIENCY @POWER
Rating FACTOR @ Rating
RATING
LOAD FACTOR (%)SERVICE FACTOR
100%
100%
0.25
78.5%
79.0%
80.0%
1
0.75
78.5%
79.0%
80.0%
1
1
78.5%
79.0%
80.0%
1
1.5
78.5%
79.0%
80.0%
1
2.2
78.5%
79.0%
80.0%
1
3
78.5%
79.0%
80.0%
1
3.7
80.0%
80.0%
80.0%
1
5.5
81.0%
80.0%
80.0%
1
7.5
82.0%
85.0%
80.0%
1
14
85.0%
85.0%
80.0%
1
15
86.0%
85.0%
80.0%
1
18
88.0%
85.0%
80.0%
1
18.5
88.0%
85.0%
87.0%
1
22
88.5%
85.0%
87.0%
1
30
90.0%
85.0%
87.0%
1
55
92.2%
86.0%
90.9%
1
75
92.6%
86.0%
90.9%
1
90
93.2%
86.0%
90.9%
1
160
94.0%
88.0%
90.9%
1

Potrebbero piacerti anche