Electronic Pressure Measurement

Air Flow Transmitter Type A2G-25


WIKA Datasheet A2G-25

Applications
Measuring the volume flow in ventilation ducts for air and Used for fans and ventilators of various manufacturers Monitoring of air volume flow or pressure directly

non-combustible gases on the air handling unit

For use with fans/blowers from various manufacturers

Special Features
Easy installation User-friendly display Easy-to-read LCD display Temperature compensated Output signals for differential pressure and air volume flow Air flow calculation based on k factor

Air Flow Transmitter model A2G-25

Description
Version In accordance with the CE requirements of EMC Directive 89/336/EEC, ROHS Directive 2002/95/EY Accuracy At 4 InWC and 8 InWC 0.02 InWC: 1.5 % of display At 20 InWC and 28 InWC : 0.03 InWC: 1.5 % of display Display ranges 0 ... 4 InWC, 0 ... 8 InWC, 0 ... 20 InWC or 0 ... 28 InWC Selectable units on the display: LPM, m3/s, m3/h, cfm, l/s, scfh, mbar, mmWC, kPa or Pa Long-term stability At 4 InWC and 8 InWC: 0.03 InWC At 20 InWC and 28 InWC: 0.1 InWC Manual zero adjustment (standard) Automatic zero adjustment (optional): 0.03 InWC Maximum working pressure 100 InWC Operating temperature Ambient: -4...+160F Medium: 23 +122 F Permissible ambient humidity 0 ... 95 % rH, non-condensing Ingress protection NEMA 3 (IP54 per EN 60529 / IEC 529) Weight 5.2 ounces (150 grams )

WIKA Datasheet A2G-25 3/2013

Page 1 of 4
R

Standard features
Process connection Hose barb (ABS) Measuring element Piezo sensor Display Alphanumeric display with menu-driven user interface Case Plastic (ABS) Electrical connection M16 PG-Gland

Output signal V OUT DC 0 10 V, Load R minimum 1 k linear to adjusted output unit, P OUT DC 0 10 V, Load R minimum 1 k linear to adjusted output unit Supply voltage AC 24 V or DC 24 V 10 % Zero point adjustment On the display keyboard Standard accessories 2 mounting screWC 2 plastic duct connectors 3 feet PVC hose, inner diameter 1/8 / 3/16 Options
Automatic zero adjustment

(Long-term stability 1 Pa)

Wiring diagram

V-scale output can be changed (in relation to the selected output unit)

Page 2 of 4

WIKA Datasheet A2G-25 3/2013

Connection diagram

Zero point adjustment


Manual zero adjustment (standard) 1. Both the + and the flow inputs must be disconnected. 2. Press the zero point button until the red LED lights up. 3. Wait until the LED switches off again. Now the instrument can be reconnected. 4. In normal operation, we recommend that a zero adjustment is carried out every 12 months. Automatic zero adjustment (option) The automatic zero adjustment adjusts the zero point from time to time so that a manual zero adjustment is not necessary. During the zero adjustment (3 seconds every 10 minutes), the output signal and the display show the last measured value.

ZERO

Dimensions in inches
2.65 1.69 2.05
40376281.01

3.36

0.47

0.39

0.59

0.75 0.91

WIKA Datasheet A2G-25 3/2013

0.15

2.76 Page 3 of 4

40376281X.01

Menu selections and initialization instructions for installation


If buttons are not pressed within 20 seconds the device returns to the normal measuring mode. 1. 2. 3. Press the Select button for at least 2 seconds to enter the menu. Select the fan manufacturer. Each fan manufacturer has its own specific K-value. Please take the correct K-value from the data sheet: Flkt Woods (k = 0,3 99) Rosenberg (k = 37 800) Nicotra (c = 10 1500) Comefri (k = 10 2000) Ziehl (k = 10 1500) Ebm-Papst (k = 10 1500) Gebhard (k = 50 4700)

4. The following units will be displayed: m3/s, m3/h, cfm, l/s, scfh, lpm, kPa, mbar, mmWC, inchWC or Pa. 5. At 1,000 Pa Pressure output unit (and P OUT scale) At 2,000 Pa 0 ... 2000 Pa 0 ... 2 kPa 0 ... 20 mbar 0 ... 200 mmWC 0 ... 8 inchWC At 5,000 Pa At 7,000 Pa

The maximum value corresponds to an output signal of 10 V

0 ... 1,000 Pa 0 ... 1 kPa 0 ... 10 mbar 0 ... 100 mmWC 0 ... 4 inchWC

0 ... 5000 Pa 0 ... 5 kPa 0 ... 50 mbar 0 ... 500 mmWC 0 ... 20 inchWC

0 ... 7,000 Pa 0 ... 7 kPa 0 ... 70 mbar 0 ... 700 mmWC 0 ... 28 inchWC

6.

Flow output unit for defining the V OUT scale

7. V OUT scale, selectable: m3/s 10 V = 1 50 m3/s m3/h 10 V = 4000 200000 m3/h cfm 10 V = 2000 100000 cfm l/s 10 V = 1000 50000 l/s scfh 10 V = 1000000 6000000 scfh lpm 10 V = 60000 3000000 lpm 8. 9. Stepless response time selection. Press the END button and the instrument returns to the normal measuring mode.

The specifications given in this document represent the state of engineering at the time of publishing. We reserve the right to make modifications to the specifications and materials.