PROJECT: Construction of Expansion of Yashoda Hospital- Phase-1

GRAND SUMMARY S No 1 2 3 4 Item CHILLED WATER AIR CONDITIONING SYSTEM DX SYSTEM VENTILATION SYSTEM BASEMENT VENTILATION SYSTEM TOTAL AMOUNT In Words: Supply Installation Total Remarks

For Employer

Page 1 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No A 1.0 DESCRIPTION CHILLED WATER AIR CONDITIONING SYSTEM Installation of Water Cooled Turbo Chillers of below specified actual cooling capacity with following technical parameters complying with the technical specifications. Evaporator with 54F inlet water and 44F outlet water and fouling factor of 0.0001 FPS units. The chiller shall be with single / twin independent refrigerant circuits, having R-134a / R-407c / R-410A / Eco friendly refrigerant. The scope shall include the complete packaged chiller with hermetic / semi-hermetic compressor, condenser, chiller , refrigerant controls & valves, vibration isolators, refrigerant piping and wiring, accessories as required, automatic and safety controls mounted in central console panel and all mounted on a epoxy coated steel frame with spring isolators complete as per specifications, suitable for outdoor exposed duty conditions and complete assembly mounted on common base frame / skid, painted with anti corrosive paint. Motor shall be suitable for 415+/-10,50 cycles, 3 phase ac supply. Following accessories shall be also included in the scope of supply of chillers. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

i Factory Supplied Electrical starter panel with unit mounted power isolator and BMS ready Microprocessor Panel. ii Chillers starters shall be close transition start delta if only as per manufacturer standard. However, the Chiller should be able to operate from 10 % capacity to 100 % in stepless / infinite steps and this factor should be able to be monitored / controllable from the End User's BMS System for User based HVAC Load Optimisation requirements iii Counter flanges / victaulic couplings for cooler and condenser water piping connections. iv Restrained spring type of Vibration isolators to be provided or as recommended by manufacturer for complete structurual isolation v Acoustic jacketing of the chiller to meet the noise level of less than 70 dB(A) at 3 m from unit 1.0 a 300 TR Capacity Turbocor as per above specifications .

Nos.

3.00

For Employer

Page 2 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 1.0 b DESCRIPTION SITC of Standalone Chiller Plant Manager with Visual Display Console and with complete connectivity to Client's BMS on OPEN protocol to be included(Prior Approval to be taken from BMS Vendor to suite the Protocol, preferably by MODBUS). SITC and handing over of Split coupled Vertical inline type chilled water circulation pump set mechanical seal to deliver the following flow rate with flexible connection inlet & outlet including necessary Pressure Gauges with siphon & cock, insulation etc.,complete. As per Specifications. The pump motor shall suitable for 415 10% volts, 50 cycles, 3 phase AC power supply. Primary chilled water pumps of 720 USGPM at 15 MWC head (2Working+1Stand BY) Secondary chilled water pumps of 720 USGPM at 25 MWC head (with motor suitable to operate on variable frequency drive). (2 Working+1Stand BY) SITC of Stand alone Chilled Water Secondary Pumps logic controller, 2 DP transmitters, 3 nos. individual VFDs for all Secondary pumps with required software and hardware to connect to Client's BMS integration, in an IP 54 enclosure and all related control wiring of 400 RMT length from Controller Panel to DP Transmitters (2No's) in MS conduit along the Chilled Water pipeline and all related control wiring. NOTE: The scope includes Electrical cabling(15 Rmt each ) from the VFD Panel to respective Secondary pumps. Chilled Water Secondary pumps VFD Compatible Panel Incoming : 160A 35KA TP MCCB with Neutral link- 1no Bus bars : 160A TPN Aluminum Bus bars 1Set Outgoings: Bypass star delta starter suitable for 25kw -3 No's for Secondary Pumps (VFD's considered in Secondary pumps) Metering : UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

Nos.

1.00

2.0

2.1 a 2.2 a

Nos. Nos.

3.00 3.00

2.2 b

Lot

1.00

For Employer

Page 3 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION i) 0 - 500V Digital Voltmeter with Selector switch -1set ii) 0 160A Digital Ammeter with Resin cast Cts and selector switch-1set iii) CT operated Multi function Meter with RS 485 connectivity-1set iv) LED type Phase indication lamps with individual MCB control and toggle switches - 1set Condenser cooling water pumps of 1440 USGPM at 45 MWC head. SITC of Single or multiple cell Induced draft cooling towers to suit heat rejection of below specified Chiller heat rejection while working at 95.5 F inlet water and 88 F outlet water designed at an ambient wet bulb temperature of 80 F taking a cooling water flow of 1440 usgpm as per technical specifications. The scope shall include complete FRP casing louvers for intake air with required internal structural supports in galvanized steel, internal piping distribution, axial flow propeller fan with FRP or die pressure die cast aluminum blades, driven by TEFC, IPFF, outdoor application Eff1 motor. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

2.3 a 3.0

Nos.

3.00

3.0 a 4.0

Cooling Tower (Cap: 360 TR) & Flow rate of 1440 USGPM Air Handling Units

Nos.

3.00

For Employer

Page 4 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

4.1 SITC of Ceiling suspended Air Handling Units of below specified duty conditions with Full Face Cooling Coil, DIDW backward curved Fan with Eff1 TEFC IP 55 drive motor, in thermal break profile casing. The Air Handling Unit shall be in double skin casing of 50 mm thick insulated panels with 0.8 mm thick prepainted outer and GS inner skin, Fan & Motor assembly mounted on aluminum frame resting on spring isolators, sized with Full Face AHRI certified 8Row,12 FPI Chilled Water cooling coil with max. 1.50 M/s Coil Face Velocity, and having all round insulated drain pan of 1.0 mm thick SS-304, fire retardant flexible canvas, AHU outlet damper, safety door limit switches, internal belt guard, internal service light, UV light inside AHU etc, all as per specifications and with Noise level below 65 dB levels. The Fan Static shall be 150 MM WG at below specified CFM and the filteration level provided within the AHU shall be MERV 7 + MERV 13 + MERV 17. The AHU shall be designed for 24 Hours operation duty conditions and shall have suitable VFD for the motor.

The scope includes suitable Power & Control Cables of 10 RMT each from floor electrical panel to AHU starter panel then to the respective AHU motor. The AHU shall be designed for 24 Hours operation duty conditions and the AHU Motor shall be VFD Compatible and the AHU shall have controls for the motor's VFD to be controlled through time dependent Air Velocity Settings including hardware & wiring and shall be possible to be monitored / controlled through Client's BMS System. a. 3200 CFM / 6.0 TR (CT OT's) Nos. 2.00

For Employer

Page 5 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

4.2 SITC of Ceiling Suspended Treated Fresh AIr Units of below specified duty conditions with Full Face Cooling Coil, DIDW backward curved Fan with Eff1 TEFC IP 55 drive motor, in thermal break profile casing. The Air Handling Unit shall be in double skin casing of 25 mm thick insulated panels with 0.8 mm thick prepainted outer and GS inner skin, Fan & Motor assembly mounted on aluminum frame resting on spring isolators, sized with Full Face AHRI certified 8 Row 12 FPI Chilled Water cooling coil with max. 2.5 M/s Coil Face Velocity, and having all round insulated drain pan of 1.0 mm thick SS-304, fire retardant flexible canvas, AHU outlet damper, safety door limit switches, internal belt guard, internal service light, UV light inside AHU etc.all as per specifications and with Noise level below 65 dB levels. The Fan Static shall be 75 MM WG at below specified CFM and the filteration level provided within the AHU shall be MERV 7 + MERV 13 + MERV 17.

The scope includes suitable Power & Control Cables of 10 RMT each from floor electrical panel to AHU starter panel then to the respective AHU motor. The AHU shall be designed for 12 - 16 Hours operation duty conditions and the AHU Motor shall be VFD Compatible and the AHU shall have controls for the motor's VFD to be controlled through time dependent Air Velocity Settings including hardware & wiring and shall be possible to be monitored / controlled through Client's BMS System. a. 1200 CFM / 6.0 TR b. 1400 CFM / 7.0 TR c. 1800 CFM / 9.0 TR 5.0 Fan coil units & Chilled Water Cassette Units Sets Sets Sets 1.00 1.00 1.00

For Employer

Page 6 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 5.1 DESCRIPTION SITC of Hide Away Chilled Water Fan Coil Units with inlet & outlet SS Shut off Ball valves,Strainer, Proportional Control Solenoid Valve, 3 speed Fan controller, Wall Mounted Electronic Digital Display Thermostat with BMS connectivity, Canvas connection, Required Control wiring, required power & control cables etc. with Max 40 dB sound level & with cordless remote. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) 5.2

1.0 TR / 400 CFM 1.5 TR / 600 CFM 2.0 TR / 800 CFM 3.0TR / 1200 CFM SITC of Hide Away Chilled Water Ceiling Cassettes with inlet & outlet SS Shut off Ball valves,Strainer, Proportional Control Solenoid Valve, 3 speed Fan controller, Wall Mounted Electronic Digital Display Thermostat with BMS connectivity,Required Control wiring, required power & control cables etc. with Max 40 dB sound level & with cordless remote.

Nos. Nos. Nos. Nos.

R/o 48.00 6.00 R/o

a) b) c) d) d) 6.0

1.0 TR / 400 CFM 1.5 TR / 600 CFM 2.0 TR / 800 CFM 3.0TR / 1200 CFM 4.0TR / 1600 CFM Pressure Monitoring System SITC of Wall Mountable / Standalone Magnehelic Gauges for displaying room differential pressure 0-10 mm with wall mounted / stand alone Gauge Panel in SS & with related sensors and accessories and BMS Compatibility for remote pressure monitoring. Chilled water piping

Nos. Nos. Nos. Nos. Nos.

R/o 106.00 39.00 17.00 R/o

Nos

10.00

7.0

For Employer

Page 7 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 7.1 DESCRIPTION SITC of the following heavy Class "C" MS Pipes and fittings confirmed to IS 1239 & IS 3589 as specifications,cut to required lengths and installed with all welded joints, providing and fixing in position neccessary fittings like bends, elbows, tees, reducers, mating flanges & sockets and insulation with 50 mm thick, 18 kg/cum density TF quality expanded polystyrene pre-formed pipe sections upto 80 mm dia pipes and 75 mm thick insulation for above 80 mm dia pipes finished with air-tight leak-proof alkathene vapour barrier, 22 G GI chicken wire mesh wrapping and 26 G Alm sheet cladding. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) e) f) g) h) i) j) k) l) m) 8.0

300mm dia (minimum 6mm thick ) 250mm dia (minimum 6mm thick ) 200mm dia (minimum 6mm thick ) 150mm dia 125mm dia 100mm dia 80mm dia 65mm dia 50mm dia 40mm dia 32mm dia 25mm dia 20mm dia Condenser water piping SITC of the following heavy Class "C" MS Pipes and fittings confirmed to IS 1239 & IS 3589 as specifications, cut to required lengths and installed with all welded joints, providing and fixing in position neccessary with fittings like bends, elbows, tees, reducers, mating flanges & sockets and approved color 2 coat painting.

Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt Rmt

150.00 R/o 150.00 40.00 10.00 15.00 150.00 470.00 400.00 640.00 860.00 2200.00 R/o

a) 350mm dia b) 300mm dia

Rmt Rmt

140.00 R/o

For Employer

Page 8 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No c) d) e) f) g) h) i) 9.0 DESCRIPTION 250mm dia 200mm dia 150mm dia 125mm dia 100mm dia 80mm dia 50mm dia SITC of Extended stem Butterfly valves of following sizes with extended stem, wafer type / lug type construction, bolts, supports etc as per specifications 2 suitable for 16 Kg/cm pressure. (The valves used in the chilled water pipeline shall be insulated with loose TF quality thermocole for a layer of 50 mm thickness and finished as per similar specifications of chilled water piping insulation). UNIT Rmt Rmt Rmt Rmt Rmt Rmt Rmt QTY 200.00 R/o 20.00 R/o 20.00 R/o 40.00 Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) e) f) g) h)

300mm dia (gear operated) 250mm dia (gear operated) 200mm dia (gear operated) 150mm dia 125mm dia 100mm dia 80mm dia 65mm dia

Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos.

3.00 18.00 23.00 R/o R/o 3.00 8.00 10.00

For Employer

Page 9 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No i) j) k) l) m) 10.0 DESCRIPTION 50mm dia 40mm dia (ball valve) 32mm dia (ball valve) 25mm dia (ball valve) 20mm dia (ball valve) SITC of Manual Balancing valves for following sizes with flanged type construction, bolts, supports etc. as per specifications suitable for 16 Kg/cm 2 pressure. The valves shall be insulated with loose TF quality thermocole for a layer of 50mm thickness. The insulation to be covered by 24 G aluminum sheet box. 300mm dia 250mm dia 200mm dia 150mm dia 125mm dia 100mm dia 80mm dia 65mm dia 50mm dia 40mm dia 32mm dia 25mm dia 20mm dia UNIT Nos. Nos. Nos. Nos. Nos. QTY 7.00 10.00 3.00 R/o R/o Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) e) f) g) h) i) j) k) l) m)

Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos.

R/o 6.00 4.00 R/o R/o R/o 4.00 5.00 R/o 5.00 R/o R/o R/o

For Employer

Page 10 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 11.0 DESCRIPTION SITC of 2-way Modulating Valve with Spring-Return Actuator with Open / Close Feedback signal & BMS connectivity option on Open / MODBus / BACnet protocol & local Wall Mounted Digital Display Thermostats for Mixing Valve Temperature Control and Extended Bracket to clear insulation for Actuator and related control cabling in flexible PVC conduit. (The AHU Starter Panel shall have a 24 V AC/DC supply available for this purpose) for the following line sizes. The valves shall be insulated with loose TF quality thermocole for a layer of 50mm thickness and finished as per chilled water insulation specifications. The scope includes suitable Power cable & control cable of each 10 RMT from AHU starter panel to actuator and BMS connectivity for remote monitoring / controlling. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) e) f) g) 12.0

100mm dia line 80mm dia line 65mm dia line 50mm dia line 40mm dia line 32mm dia line 25mm dia line SITC of Dual plate wafer type Check valves for following sizes with SS / Bronze plate, bolts, supports etc. as per specifications suitable for 16 Kg/cm 2 pressure. The valves shall be insulated with loose TF quality thermocole for a layer of 50mm thickness and finished as per chilled water insulation specifications. 250mm dia 200mm dia 150mm dia 125mm dia

Nos. Nos. Nos. Nos. Nos. Nos. Nos.

R/o R/o R/o R/o 5.00 R/o R/o

a) b) c) d)

Nos. Nos. Nos. Nos.

R/o 6.00 3.00 R/o

For Employer

Page 11 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 13.0 DESCRIPTION SITC of Y type strainers with SS Mesh for following sizes with matching flanges, bolts, supports etc. The strainers shall be insulated with loose TF quality thermocole for a layer of 50mm thickness and finished as per chilled water insulation. a) b) c) d) e) f) g) h) i) j) k) 14.0 250mm dia 200mm dia 150mm dia 100mm dia 80mm dia 65mm dia 50mm dia 40mm dia 32mm dia 25mm dia 20mm dia SITC of Motorized ON/OFF butterfly valves with Actuators with ON / OFF Feedback for following sizes with Extended Stem, matching bolts, supports etc. complete with required 240 / 12 V transformers, control wiring from chillers etc. as per specifications. The valves shall be suitable for BMS integration on Open / MODBus BACnet protocol. The valves shall be insulated with loose TF quality thermocole for a layer of 50mm thickness and finished as per chilled water insulation specifications. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. 3.00 6.00 R/o R/o R/o R/o R/o 5.00 R/o R/o R/o UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) b) c) 15.0 a)

250mm dia 200mm dia 150mm dia 125mm dia SITC of Automatic Air Vents on extended nipples with isolation valves. 1/2 " dia.

Nos. Nos. Nos. Nos. Nos.

6.00 3.00 R/o R/o 50.00

For Employer

Page 12 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 16.0 DESCRIPTION SITC of Rubber expansion joints for following sizes with double bellows, tie rods and MS flanges. The REJs shall be insulated with flexible nitrile rubber insulation of 32 mm thickness in two layers. 250mm dia 200mm dia 150mm dia 125mm dia SITC of Dial type Pressure gauges with siphon and ball valve SITC of Dial type Thermometers with required length of thermowells & immersion stems SITC of Paddle type water flow switches for chiller side DRAIN PIPING: SITC of Condensate drain piping for following sizes of class B GI pipes from AHU drain connections to nearest floor drain complete with fittings, U-traps etc. The insulation shall be similar to that of the chilled water piping. a) b) c) d) e) 21.0 22.0 SITC of digital display Water flow meter suitable for BMS connectivity with necessary accessories in chilled Water Main header Nos 1.00 25mm dia. 32mm dia 40mm dia 50mm dia 65mm dia SITC of insulated 1000 LTRS HDPE Expansion tank with all required connections & valves Sets Sets Sets Sets Sets Sets Sets 12.00 18.00 R/o R/o 456.00 444.00 6.00 UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) 17.0 18.0 19.0 20.0

Rmt Rmt Rmt Rmt Rmt Set

950.00 350.00 250.00 180.00 90.00 1.00

For Employer

Page 13 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 23.0 DESCRIPTION SITC of Air separator on the return water header located at the primary pump suction and suitable for 1440 US GPM water flow, 300 mm dia inlet & outlet. The separator should be complete with high capacity air vent, service valve, non return valve, valve connection for makeup water inlet, flanges etc. SITC of Chemical Dosing Sets & Softner to meet the water quality requirements for Cooling tower Water including a dosing pump, with interconnecting tubing and foot valve, chemical storage tank of 25 liters, ionization sensor and required controls. AIR DISTRIBUTION SITC of Factory fabricated GSS ducting complete with splitters, turning vanes, access doors, supports etc. as per specifications. Factory fabricated ducting to be as per SMACNA standards for the sheet metal thicknesses as given below. 24 G Ducting (upto 750 mm) 22 G Ducting (751 mm to 1500 mm) 20 G Ducting (1501 mm to 2200 mm) 18 G Plenum SITC of Round Flexible duct 100 mm Dia 150 mm Dia m2 m2 m2 2 m m m2
2

Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

BOQ Date: 30-Aug-2013 RATE Supply Installation Supply Rev: R0 AMOUNT Installation

UNIT

QTY

Sets

1.00

24.0

Sets

1.00

25.0 25.1

a) b) c) 25.2 25.3 a) b)

1300.00 150.00 20.00 30.00 R/o R/o

For Employer

Page 14 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT m
2

Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

BOQ Date: 30-Aug-2013 RATE Supply Installation Supply Rev: R0 AMOUNT Installation

QTY 80.00

c) 200 mm Dia 25.4 SITC of Aluminum ducting complete with splitters, turning vanes, access doors, supports etc. as per specifications. a) 18 G ducting b) 20 G ducting 25.5 SITC of Multi blade volume control dampers of opposed blade type in GSS construction with suitable links, levers and quadrants for proper balancing of the air distribution system. 25.6 SITC of Motorized fire and smoke dampers with minimum 90 min fire rating UL 555 listed with fire and smoke sensor and factory wired control panel, having extended sleeve of 450 mm. The damper actuator and total wiring for actuator and control panel shall be rated to withstand 250 deg C for 2 hours. a) Bare fire damper b) Motorized actuator of suitable power rating and torque rating for above dampers along with connectivity for BMS. 25.7 SITC of 4 way supply air square ceiling diffusers in extruded aluminum construction having powder coated finish with integral black painted opposed blade dampers 25.8 SITC of 4 way return air square ceiling diffusers in extruded aluminum construction without dampers 25.9 SITC of Fresh air intake louvers of powder coated extruded aluminum construction with all side flanges having integral insect screen. 25.10 SITC of Supply Air Grill to suit gyp and grid false ceiling with AL extruded black colored collar damper 25.11 SITC of Return Air / Exhaust Air Grill to suit gyp and grid false ceiling with AL extruded black colored collar damper 25.12 SITC of Al. Powder coated Continuous Grill of following sizes a. 4" Continuous Grill b. 6" Continuous Grill

m m2 m
2

R/o R/o 10.00

10.00 30.00 R/o R/o 5.00 20.00 15.00

Nos. m2 m m SMT SMT


2

RMT RMT

R/o 350.00

For Employer

Page 15 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT RMT No's QTY R/o 100.00 Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

c. 8" Continuous Grill 25.13 SITC of Exhaust Air Grill(Round type) to suit gyp and grid false ceiling with AL extruded black colored collar damper for toilets 26.0 26.1 Insulation SITC of Duct thermal insulation with 25 mm thick blanket type fiberglass with 3 factory laminated aluminum foil with density 24 kg/m and edges covered with al tape and then covered with 22 G GI chicken wire mesh as per technical specifications. SITC of Duct thermal insulation with 50 mm thick blanket type fiberglass with 3 factory laminated aluminum foil with density 24 kg/m and edges covered with Al Tape and covered with 22 G GI Chicken wire mesh as per technical specifications SITC of Duct Thermal Insulation applied outside of the duct work with Alm. backed Closed cell nitrile/ Cross linked foam duly fixed with adhesive, 22 G chicken wire mesh. (25 mm Thickness) SITC of Duct acoustic insulation with 12 mm thick rigid board fiberglass of 48 kg/m3 density, and completely covered with RP tissue and 26 G aluminum perforated sheet mechanically bonded with 6 mm fasteners. SITC of Duct Accoustic Insulation applied inside of the duct work with Alm. backed OPEN cell nitrile/ Cross linked foam duly fixed with adhesive and GI nuts & bolts.(19 mm thickness) SITC of Under deck insulation with 50mm thick TF quality expanded polystyrene rigid boards, and bottom completely covered with AL Foil covering and then cross binding with 22 G GI chicken wire mesh, for fixing and brass screws and washers as required. SITC of MS Support structures for chilled water piping, condenser water piping, on terrace, floors, etc. AMC (material & labour) year wise (for 5 years) after the standard 24 month from commissioning warranty period.

m2

650.00

26.2

m2

R/o

26.3

m2

R/o

26.4

m2

250.00

26.5

m2

R/o

26.6

m2

560.00

27.0 28.0

Lot

1.00

For Employer

Page 16 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION SUB TOTLA FOR CHILLED WATER BASED AIR SYSTEM B 1.0 1.1 DX SYSTEM Air Handling Units SITC of Ceiling suspended Air Handling Units of below specified duty conditions with Full Face Cooling Coil, DIDW backward curved Fan with Eff1 TEFC IP 55 drive motor, in thermal break profile casing. The Air Handling Unit shall be in double skin casing of 50 mm thick insulated panels with 0.8 mm thick prepainted outer and GS inner skin, Fan & Motor assembly mounted on aluminum frame resting on spring isolators, sized with Full Face AHRI certified 6 Row 12 FPI Direct expansion cooling coil with max. 2.5 M/s Coil Face Velocity, and having all round insulated drain pan of 1.0 mm thick SS-304, fire retardant flexible canvas, AHU outlet damper, safety door limit switches, internal belt guard, internal service light, UV light inside AHU etc, all as per specifications and with Noise level below 65 dB levels. The Fan Static shall be 75 MM WG at below specified CFM and the filteration level provided within the AHU shall be MERV 7 + MERV 13. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

The scope includes suitable Starter Panel with VFD & Power & Control Cables of 10 RMT each from floor electrical panel to AHU starter panel then to the respective AHU motor. The AHU shall be designed for 12 - 16 Hours operation duty conditions and the AHU Motor shall be VFD Compatible and the AHU shall have controls for the motor's VFD to be controlled through time dependent Air Velocity Settings including hardware & wiring and shall be possible to be monitored / controlled through Client's BMS System. a. 3800 CFM / 8.5 TR (FOR MRI) b. 1600 CFM / 4.0 TR (FOR CTSCAN) Nos. Nos. 1.00 1.00

For Employer

Page 17 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

1.2 SITC of Ceiling suspended Air Handling Units of below specified duty conditions with Full Face Cooling Coil, DIDW backward curved Fan with Eff1 TEFC IP 55 drive motor, in thermal break profile casing. The Air Handling Unit shall be in double skin casing of 50 mm thick insulated panels with 0.8 mm thick prepainted outer and GS inner skin, Fan & Motor assembly mounted on aluminum frame resting on spring isolators, sized with Full Face AHRI certified 8Row,12 FPI Direct expansion cooling coil with max. 1.50 M/s Coil Face Velocity, and having all round insulated drain pan of 1.0 mm thick SS-304, fire retardant flexible canvas, AHU outlet damper, safety door limit switches, internal belt guard, internal service light, UV light inside AHU etc, all as per specifications and with Noise level below 65 dB levels. The Fan Static shall be 150 MM WG at below specified CFM and the filteration level provided within the AHU shall be MERV 7 + MERV 13 + MERV 17. The AHU shall be designed for 24 Hours operation duty conditions and shall have suitable VFD for the motor.

The scope includes suitable Power & Control Cables of 10 RMT each from floor electrical panel to AHU starter panel then to the respective AHU motor & to the Strip heaters and humidifier. The AHU shall be designed for 24 Hours operation duty conditions and the AHU Motor shall be VFD Compatible and the AHU shall have controls for the motor's VFD to be controlled through time dependent Air Velocity Settings including hardware & wiring and shall be possible to be monitored / controlled through Client's BMS System. a. 3200 CFM / 7.0 TR b. 3800 CFM / 8.0 TR Nos. Nos. 3.00 4.00

For Employer

Page 18 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

2.0 SITC of following capacity Condensing Units including refrigerant connections with expansion valves & necessary valves etc., complete a. 8.5 TR Nos b. 5.5 TR Nos 3.0 SITC of the following capacities of 4Way cassette with complete with compressor, condenser, evaporator, Remote, Control cable & Power Cable, supports, etc. as per the specifications. 8.00 1.00

a. b. c. d. e. 4.0 4.1

1.0 TR / 400 CFM 1.5 TR / 600 CFM 2.0 TR / 800 CFM 3.0TR / 1200 CFM 4.0TR / 1600 CFM REFRIGERANT PIPING SITC of 16 SWG hard drawn copper piping for ductable split units of the following sizes including 19mm thick nitrile tube insulation, supports, clamping, fittings, etc.

Nos. Nos. Nos. Nos. Nos.

1.00 3.00 3.00 2.00 R/o

a. b. c. d. c) 1.0

3/8" dia(9.375) 5/8" dia(15.8) 7/8" dia(22.2) 1 1/8 dia(28.6 mm) SUB TOTAL FOR DX SYSTEM VENTILATION SYSTEM SITC of Cabinet type Fresh Air Fan of double single skin insulated casing, DIDW centrifugal backward curved fan, Eff 1 TEFC drive motor, drive set, base frame, vibration isolators, flexible connection following capacities.

RMT RMT RMT RMT

150.00 350.00 20.00 180.00

a) 900 CFM / 25 mmWC b) 1000 CFM / 25mmWC c) 3000 CFM / 25 mmWC

Sets Sets Sets

6.00 4.00 1.00

For Employer

Page 19 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 2.0 DESCRIPTION SITC of Cabinet type Exhaust Air fan of double single skin insulated casing, DIDW centrifugal backward curved fan, Eff 1 TEFC drive motor, drive set, base frame, vibration isolators, flexible connections.for following capacities. UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

a) b) c) d) e) 3.0 a

100 CFM / 25 mmWC 200 CFM / 25 mmWC 300 CFM / 25 mmWC 500 CFM / 25 mmWC 600 CFM / 25 mmWC SITC of Exhaust Fans (Wall Mounted with Mounting Frame & Insect barrier SS mesh) (Max 60 Db) of following capacities for Patient Rooms Toilets. 50 CFM, 6.5 mm WG 100 CFM, 6.5 mm WG 200 CFM, 6.5 mm WG 250 CFM, 6.5 mm WG SUB TOTAL FOR VENTILATION SYSTEM BASEMENT VENTILATION SYSTEM JET FANS Supply,Installation,Testing & Commissioning of Induction 300mm Dia JETVENT fans with as per Technical specifications SMOKESPILL TUBE AXIAL FANS FOR EXHAUST & FRESH AIR Supply erection testing and commissioning & handing over of Long Cased Axial fans for exhaust air of the following capacities, containing DIDW blower along with suitable size motor mounted on a M.S frame fan pulley, motor pulley.with all required supports etc.,complete

Sets Sets Sets Sets Sets

6.00 1.00 6.00 5.00 4.00

a) b) c) d) D) 1 1.1 2

Nos Nos Nos Nos

56.00 2.00 R/o R/o

No's

40.00

2.1

9.43 Cum/Sec or 20,000 CFM @ 25 MM TOTAL STATIC, Motor : 7.5KW, 4pole (FOR FRESH AIR)

No's

4.00

For Employer

Page 20 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No 2.2 DESCRIPTION 11.79 Cum/Sec or 25,000 CFM @ 25 MM TOTAL STATIC, Motor : 7.5KW, 4pole (FOR EXHAUST AIR) Conducting the CFD ( Computerized Fluid Dynamic analysis and submission of Reports and adjusting the Location of Fans as required Supply installation testing and Commissioning of Carbon Monoxide Detector as per the specifications PLC based control panel for CO detectors and control of JET Fans for demand ventilation with a logic Should also enable auto on/off of fans for power saving BASED ON SENSING OF CO LEVEL. Supply,fabrication,installation & testing of sheet metal smoke extraction cum ventilation ducts with 90 mins Fire rated spray Coating / Paint in accordance with the approved shop drawings complete with all accessories like vanes flanges suspension rods anchor bolts GI bolts and nuts,canvas connections etc,complete. 18 gauge galvanized sheet steel Supply,installation,testing and balancing of MS Fire Rated (for 90 mins operation) Backdraught dampers with Fire rated BMS compatible actuaters for Exhasut air duct with all Fire rated Cabling accessories etc,complete. Supply,Installation, Testing & commissioning of Heavy duct Flexible 2mm thick fabric Fire Rated canvas (for 90 mins operation) connection with inspection zip to connect GI Duct MV PANELS Sqm 450.00 UNIT No's QTY 8.00 Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

2.3

LS

1.00

2.4

No's

20.00

2.5

No's

4.00

2.6

2.7

2.8

Sqm

25.00

2.9 3

Sqm

25.00

For Employer

Page 21 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

Supply, installation, Testing and Commissioning of 3 phase and Neutral 415V 4 wire Free Standing Floor mounted MCC made out of 2mm thick CRCA sheet after seven tank process and painting with Epoxy powder coating.

The panel shall consist of suitable rating TPN Aluminium bus bar (at the rating of 0.8A/Sq.mm) supported with DMC/ SMC barriers and color coded with Heat shrinkable sleeves. The Metering shall be provided as specified.

The panel shall have Short circuit withstanding capacity of minimum 50KA and consist of the switchgear as mentioned below. The panel shall be got fabricated from manufacturers with CPRI Test certificate only. The MCC shall have at least two spare cubicles of the maximum rating. The size of all Panel Mounting Meters shall be 96X96mm. The Panels shall be mounted on U channels including supply and fixing of the same. Every ACB shall be provided with ON/OFF /Trip Indication lamps of LED type. All MCCBs shall be with Electronic releases for Overload, Short Circuit and inbuilt earth fault relay. Every motor in MCC shall be provided with required Contactors, Overload relay, On/Off Push buttons, On/Off/trip indications in manual mode and Auto/ manual selector switch. The MCC shall be provided with PLC with suitable Inputs/ outputs, power supply, Relays and fully wired in Auto mode including software and other accessories. The PLC shall also be wired to CO sensors for operation as per specifications 3.1 Blower Room 1 MCCs ( TYPICAL) Incoming : 100A 25KA TP MCCB with Neutral link- 1no Bus bars : 100A 25KA TPN Aluminium Bus bars 1Set Outgoings:

No's
For Employer Page 22 of 25

4.00
For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION 63A 25KA TP MCCB for 7.5 kw Blower , 4 No's. Suitable rating MPCB with Dual speed Controller suitable for 1.1KW Impulse fan Motor along with PLC for control of impulse fans based on co level - 12Nos . Metering : UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

No's

4.00

For Employer

Page 23 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION i) 0 - 500V Digital Voltmeter with Selector switch -1set ii) 0 100A Digital Ammeter with Resin cast Cts and selector switch-1set iii) CT operated Electronic Energy Meter with RS 485 connectivity-1set iv) LED type Phase indication lamps with individual MCB control and toggle switches - 1set MV CABLES Supply and laying dressing and clamping of 1.1KV grade, PVC insulated Aluminium/Copper conductor armoured Underground cables including all fixing accessories such as clamps for fixing the cable or laid in ground including excavation and refilling of earth and providing protection with sand and bricks as per drawing. a. b. c. 5 4C X 2.5 Sq.mm Copper. ( from Blower Panel to 7.5 kw Motor) 2Cx1.5sq.mm ( Control Cable for CO Sensors) 6Cx1.5sq.mm ( Power Cable for Jet Fans) Cable End Terminations Providing end terminations for following size cables including supply of Double Compression type cable gland, lugs, insulation tape and identification tags complete with end termination and earthing of gland. a. b. c. 6 4C x 2.5 Sq.mm copper 2C x 1.5sq.mm 6C x 1.5sq.mm Earthing Supply and laying of following size strips including including all necessary interconnections with earth station and equipments. a. b. 25 X 6mm GI Strip 1C x 6 Sq.mm copper wire SUB TOTAL FOR BASEMENT VENTILATION RMT RMT 600.00 600.00 No's No's No's 24.00 40.00 80.00 RMT RMT RMT 350.00 700.00 850.00 No's UNIT 4.00 QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

For Employer

Page 24 of 25

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No DESCRIPTION GRAND TOTAL UNIT QTY Date: 30-Aug-2013 RATE Supply Installation Supply BOQ Rev: R0 AMOUNT Installation Package: Supply,Installation,Testing and Commissioning of HVAC and Ventilation System

For Employer

Page 25 of 25

For Contractor