HEAT LOAD ESTIMATE

Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 1 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.89 ADP 56 1 Deh. Rise 15.84

6.15 0 0 6.15 0 0 0 0 103.733 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 564.82 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10832.11 541.61 11373.71 284.34

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

568.69 1 27.25 2.4 1.08 70.64 12297.38

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 13759.35

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 15467.80

Tons TR

1.29

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

719 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 2 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 103.733 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9491.37 474.57 9965.94 249.15

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

498.30 1 27.25 2.4 1.08 70.64 10784.02

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12245.99

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 13954.44

Tons TR

1.16

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

630 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 3 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 103.733 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9491.37 474.57 9965.94 249.15

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

498.30 1 27.25 2.4 1.08 70.64 10784.02

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12245.99

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 13954.44

Tons TR

1.16

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

630 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 4 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 103.733 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9491.37 474.57 9965.94 249.15

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

498.30 1 27.25 2.4 1.08 70.64 10784.02

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12245.99

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 13954.44

Tons TR

1.16

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

630 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 5 SECOND FLOOR 270.14 8.59 2320.5026 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

6.15 6.15 0 0 0 0 0 0 160.59 103.733 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 37.88 0.00 0.00 0.00 0.00 0.00 0.00 1342.53 Deh rise 1049.78 Deh cfm 0.90 ESHF

cfm 38.67504333 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 2074.68 2074.68 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 270.14 270.14 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 12279.93 614.00 12893.93 322.35

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

644.70 1 38.68 2.4 1.08 100.25 13961.22

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 38.68 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

63.12 1480.62 15441.83

38.68 38.68

20 73

0.88 0.88

1.08 0.68

735.14 1689.45

RA fan gain Grand Total 17866.42

Tons TR

1.49

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

816 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 6 SECOND FLOOR 169.44 8.59 1455.4896 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 24.25816 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 6.15 0 0 0 0 0 0 0 92.97 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 940.86 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1301.30 1301.30 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 169.44 169.44 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9243.84 462.19 9706.03 242.65

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

485.30 1 24.26 2.4 1.08 62.88 10496.86

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 24.26 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

39.59 1457.09 11953.95

24.26 24.26

20 73

0.88 0.88

1.08 0.68

461.10 1059.67

RA fan gain Grand Total 13474.72

Tons TR

1.12

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

614 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 7 SECOND FLOOR 169.44 8.59 1455.4896 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 24.25816 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 6.15 0 0 0 0 0 0 0 92.97 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 940.86 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1301.30 1301.30 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 169.44 169.44 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9243.84 462.19 9706.03 242.65

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

485.30 1 24.26 2.4 1.08 62.88 10496.86

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 24.26 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

39.59 1457.09 11953.95

24.26 24.26

20 73

0.88 0.88

1.08 0.68

461.10 1059.67

RA fan gain Grand Total 13474.72

Tons TR

1.12

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

614 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 8 SECOND FLOOR 239.15 8.59 2054.2985 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 103.73 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.89 ESHF

cfm 34.23830833 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

958.47 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1836.67 1836.67 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 239.15 239.15 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10339.08 516.95 10856.04 271.40

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

542.80 1 34.24 2.4 1.08 88.75 11758.98

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 34.24 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

55.88 1473.38 13232.36

34.24 34.24

20 73

0.88 0.88

1.08 0.68

650.80 1495.64

RA fan gain Grand Total 15378.80

Tons TR

1.28

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

687 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 9 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 103.733 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

958.49 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9589.54 479.48 10069.02 251.73

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

503.45 1 27.25 2.4 1.08 70.64 10894.83

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12356.81

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 14065.25

Tons TR

1.17

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

637 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 10 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 103.733 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

958.49 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9589.54 479.48 10069.02 251.73

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

503.45 1 27.25 2.4 1.08 70.64 10894.83

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12356.81

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 14065.25

Tons TR

1.17

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

637 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 11 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 103.733 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

958.49 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9589.54 479.48 10069.02 251.73

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

503.45 1 27.25 2.4 1.08 70.64 10894.83

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12356.81

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 14065.25

Tons TR

1.17

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

637 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 12 SECOND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.88 ADP 56 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 103.733 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

958.49 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9589.54 479.48 10069.02 251.73

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

503.45 1 27.25 2.4 1.08 70.64 10894.83

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 12356.81

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 14065.25

Tons TR

1.17

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

637 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 13 SECOND FLOOR 183.199 8.59 1573.67941 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.88 ESHF

cfm 26.22799017 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1406.97 1406.97 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 183.199 183.199 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9817.18 490.86 10308.03 257.70

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

515.40 1 26.23 2.4 1.08 67.98 11149.12

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 26.23 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

42.80 1460.30 12609.42

26.23 26.23

20 73

0.88 0.88

1.08 0.68

498.54 1145.72

RA fan gain Grand Total 14253.69

Tons TR

1.19

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

652 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 14 SECOND FLOOR 159.49 8.59 1370.0191 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 83.58

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.88 ESHF

cfm 22.83365167 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 625.1784 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1224.88 1224.88 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 159.49 159.49 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9302.26 465.11 9767.37 244.18

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

488.37 1 22.83 2.4 1.08 59.18 10559.11

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 22.83 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

37.26 1454.76 12013.88

22.83 22.83

20 73

0.88 0.88

1.08 0.68

434.02 997.45

RA fan gain Grand Total 13445.35

Tons TR

1.12

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

617 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 15 SECOND FLOOR 159.49 8.59 1370.0191 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 83.58

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.88 ESHF

cfm 22.83365167 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 625.1784 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1224.88 1224.88 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 159.49 159.49 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9302.26 465.11 9767.37 244.18

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

488.37 1 22.83 2.4 1.08 59.18 10559.11

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 22.83 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

37.26 1454.76 12013.88

22.83 22.83

20 73

0.88 0.88

1.08 0.68

434.02 997.45

RA fan gain Grand Total 13445.35

Tons TR

1.12

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

617 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 16 SECOND FLOOR 159.49 8.59 1370.0191 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 83.58

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.88 ESHF

cfm 22.83365167 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 625.1784 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1224.88 1224.88 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 159.49 159.49 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9302.26 465.11 9767.37 244.18

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

488.37 1 22.83 2.4 1.08 59.18 10559.11

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 22.83 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

37.26 1454.76 12013.88

22.83 22.83

20 73

0.88 0.88

1.08 0.68

434.02 997.45

RA fan gain Grand Total 13445.35

Tons TR

1.12

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

617 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 17 SECOND FLOOR 174.96 8.59 1502.9064 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 25.04844 ESHF 0.87 ADP 56 1 Deh. Rise 15.84

0 0 0 0 0 0 0 0 0 1.65 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 16.70 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1343.69 1343.69 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 174.96 174.96 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 8366.58 418.33 8784.91 219.62

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

439.25 1 25.05 2.4 1.08 64.93 9508.71

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 25.05 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

40.88 1458.38 10967.09

25.05 25.05

20 73

0.88 0.88

1.08 0.68

476.12 1094.20

RA fan gain Grand Total 12537.40

Tons TR

1.04

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

556 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 18 SECOND FLOOR 174.96 8.59 1502.9064 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 25.04844 ESHF 0.87 ADP 56 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1343.69 1343.69 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 174.96 174.96 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 8914.70 445.74 9360.44 234.01

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

468.02 1 25.05 2.4 1.08 64.93 10127.39

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 25.05 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

40.88 1458.38 11585.77

25.05 25.05

20 73

0.88 0.88

1.08 0.68

476.12 1094.20

RA fan gain Grand Total 13156.09

Tons TR

1.10

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

592 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 19 GROUND FLOOR 89.4 8.59 767.946 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 12.7991 ESHF 0.82 ADP 56 1 Deh. Rise 15.84

0 0 0 0 0 0 0 0 0 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 686.59 686.59 0.00 0.00 560.00

Transmission gain through roof/ ceiling/partitions 0 89.4 89.4 0 0 2 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 2359.43 117.97 2477.41 61.94

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

123.87 1 12.80 2.4 1.08 33.18 2696.39

270

540.00 540.00 27.00 567.00

Room latent heat Fresh Air 1 12.80 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

20.89 587.89 3284.27

12.80 12.80

20 73

0.88 0.88

1.08 0.68

243.29 559.11

RA fan gain Grand Total 4086.67

Tons TR

0.34

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

158 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 20 SECOND FLOOR 115.47 8.59 991.8873 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 16.531455 ESHF 0.84 ADP 56 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 103.02 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 861.25 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 886.81 886.81 0.00 0.00 840.00

Transmission gain through roof/ ceiling/partitions 0 115.47 115.47 0 0 3 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 3939.00 196.95 4135.95 103.40

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

206.80 1 16.53 2.4 1.08 42.85 4489.00

270

810.00 810.00 40.50 850.50

Room latent heat Fresh Air 1 16.53 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

26.98 877.48 5366.48

16.53 16.53

20 73

0.88 0.88

1.08 0.68

314.23 722.15

RA fan gain Grand Total 6402.85

Tons TR

0.53

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

262 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 21 SECOND FLOOR 115.47 8.59 991.8873 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 16.531455 ESHF 0.84 ADP 56 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 103.02 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 861.25 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 886.81 886.81 0.00 0.00 840.00

Transmission gain through roof/ ceiling/partitions 0 115.47 115.47 0 0 3 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 3939.00 196.95 4135.95 103.40

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

206.80 1 16.53 2.4 1.08 42.85 4489.00

270

810.00 810.00 40.50 850.50

Room latent heat Fresh Air 1 16.53 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

26.98 877.48 5366.48

16.53 16.53

20 73

0.88 0.88

1.08 0.68

314.23 722.15

RA fan gain Grand Total 6402.85

Tons TR

0.53

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

262 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 22 SECOND FLOOR 151.37 8.59 1300.2683 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 6.15 0 0 0 0 0 0 0 125.99 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 44.77 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.88 ESHF

cfm 21.67113833 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

1164.15 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1162.52 1162.52 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 151.37 151.37 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9196.46 459.82 9656.29 241.41

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

482.81 1 21.67 2.4 1.08 56.17 10436.68

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 21.67 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

35.37 1452.87 11889.55

21.67 21.67

20 73

0.88 0.88

1.08 0.68

411.92 946.66

RA fan gain Grand Total 13248.14

Tons TR

1.10

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

610 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 23 SECOND FLOOR 125.87 8.59 1081.2233 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 0 0 0 0 0 0 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.90 ESHF

cfm 18.02038833 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 966.68 966.68 0.00 0.00 840.00

Transmission gain through roof/ ceiling/partitions 0 125.87 125.87 0 0 3 1 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 426.25 6609.61 330.48 6940.09 173.50

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

347.00 1 18.02 2.4 1.08 46.71 7507.31

270

810.00 810.00 40.50 850.50

Room latent heat Fresh Air 1 18.02 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

29.41 879.91 8387.22

18.02 18.02

20 73

0.88 0.88

1.08 0.68

342.53 787.19

RA fan gain Grand Total 9516.94

Tons TR

0.79

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

439 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 24 SECOND FLOOR 197.2 8.59 1693.948 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 0 0 6.15 0 0 0 0 0 0 0 69.07

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 0.00 0.00 564.82 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.92 ESHF

cfm 28.23246667 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 516.6436 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1514.50 1514.50 0.00 0.00 840.00

Transmission gain through roof/ ceiling/partitions 0 197.2 197.2 0 0 3 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 9212.95 460.65 9673.60 241.84

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

483.68 1 28.23 2.4 1.08 73.18 10472.30

270

810.00 810.00 40.50 850.50

Room latent heat Fresh Air 1 28.23 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

46.08 896.58 11368.87

28.23 28.23

20 73

0.88 0.88

1.08 0.68

536.64 1233.28

RA fan gain Grand Total 13138.80

Tons TR

1.09

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

612 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 25 SECOND FLOOR 34.85 8.59 299.3615 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 44.56 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 372.52 Deh rise 0.00 Deh cfm 0.79 ESHF

cfm 4.989358333 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 267.65 267.65 0.00 0.00 560.00

Transmission gain through roof/ ceiling/partitions 0 34.85 34.85 0 0 2 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 1931.95 96.60 2028.55 50.71

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

101.43 1 4.99 2.4 1.08 12.93 2193.62

270

540.00 540.00 27.00 567.00

Room latent heat Fresh Air 1 4.99 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

8.14 575.14 2768.77

4.99 4.99

20 73

0.88 0.88

1.08 0.68

94.84 217.95

RA fan gain Grand Total 3081.55

Tons TR

0.26

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

128 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 26 SECOND FLOOR 34.85 8.59 299.3615 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 44.56 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 372.52 Deh rise 0.00 Deh cfm 0.79 ESHF

cfm 4.989358333 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 267.65 267.65 0.00 0.00 560.00

Transmission gain through roof/ ceiling/partitions 0 34.85 34.85 0 0 2 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 1931.95 96.60 2028.55 50.71

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

101.43 1 4.99 2.4 1.08 12.93 2193.62

270

540.00 540.00 27.00 567.00

Room latent heat Fresh Air 1 4.99 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

8.14 575.14 2768.77

4.99 4.99

20 73

0.88 0.88

1.08 0.68

94.84 217.95

RA fan gain Grand Total 3081.55

Tons TR

0.26

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

128 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 27 SECOND FLOOR 47.83 8.59 410.8597 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 63 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 526.68 Deh rise 0.00 Deh cfm 0.82 ESHF

cfm 6.847661667 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 367.33 367.33 0.00 0.00 560.00

Transmission gain through roof/ ceiling/partitions 0 47.83 47.83 0 0 2 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 2285.48 114.27 2399.76 59.99

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

119.99 1 6.85 2.4 1.08 17.75 2597.49

270

540.00 540.00 27.00 567.00

Room latent heat Fresh Air 1 6.85 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

11.18 578.18 3175.66

6.85 6.85

20 73

0.88 0.88

1.08 0.68

130.16 299.13

RA fan gain Grand Total 3604.95

Tons TR

0.30

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

152 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 28 SECOND FLOOR 47.83 8.59 410.8597 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

6.15 0 0 0 0 0 0 0 63 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 526.68 Deh rise 0.00 Deh cfm 0.82 ESHF

cfm 6.847661667 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 367.33 367.33 0.00 0.00 560.00

Transmission gain through roof/ ceiling/partitions 0 47.83 47.83 0 0 2 0 100 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 426.25 2285.48 114.27 2399.76 59.99

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

119.99 1 6.85 2.4 1.08 17.75 2597.49

270

540.00 540.00 27.00 567.00

Room latent heat Fresh Air 1 6.85 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

11.18 578.18 3175.66

6.85 6.85

20 73

0.88 0.88

1.08 0.68

130.16 299.13

RA fan gain Grand Total 3604.95

Tons TR

0.30

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

152 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 29 SECOND FLOOR 151.04 8.59 1297.4336 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 1 Deh. Rise 15.84

0 6.15 0 0 0 0 0 0 0 0 0 0

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

0.00 37.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Deh rise 0.00 Deh cfm 0.84 ESHF

cfm 21.62389333 ADP 56

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 0 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1159.99 1159.99 0.00 0.00 840.00

Transmission gain through roof/ ceiling/partitions 0 151.04 151.04 0 0 3 0 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

0.00 852.50 4050.36 202.52 4252.88 106.32

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

212.64 1 21.62 2.4 1.08 56.05 4627.89

270

810.00 810.00 40.50 850.50

Room latent heat Fresh Air 1 21.62 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

35.29 885.79 5513.68

21.62 21.62

20 73

0.88 0.88

1.08 0.68

411.03 944.60

RA fan gain Grand Total 6869.31

Tons TR

0.57

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

271 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 1 GROUND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.89 ADP 56 1 Deh. Rise 15.84

6.15 0 0 6.15 0 0 0 0 103.733 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 564.82 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10832.11 541.61 11373.71 284.34

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

568.69 1 27.25 2.4 1.08 70.64 12297.38

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 13759.35

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 15467.80

Tons TR

1.29

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

719 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 1 GROUND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.89 ADP 56 1 Deh. Rise 15.84

6.15 0 0 6.15 0 0 0 0 103.733 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 564.82 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10832.11 541.61 11373.71 284.34

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

568.69 1 27.25 2.4 1.08 70.64 12297.38

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 13759.35

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 15467.80

Tons TR

1.29

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

719 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 1 GROUND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.89 ADP 56 1 Deh. Rise 15.84

6.15 0 0 6.15 0 0 0 0 103.733 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 564.82 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10832.11 541.61 11373.71 284.34

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

568.69 1 27.25 2.4 1.08 70.64 12297.38

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 13759.35

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 15467.80

Tons TR

1.29

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

719 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.

HEAT LOAD ESTIMATE


Client Floor lvl Total Area in sqft Height ft Volume cuft SK HOSPITAL Space used : ROOM 1 GROUND FLOOR 190.35 8.59 1635.1065 DB Summer Monsoon Room Diff Item Area sqft Sun gain TD Solar heat gain through glass North East South West North East North West South East South West North East South West North East North West South East South West Roof Ceiling Floor Partition All glass Internal heat gain People Equipment kw Lights watts Subtotal
Safety factor 5%

City : THIRUVANANTHA PURAM Date : 31/03/2010

Latitude Suntime

8.29 16 :00

WB F 95 85 74 21 80 80

RH% 52.5 80.65

DP

Grs./ lb 188 212 100 88

Factor

Btu / hr Summer Outdoor air details Fresh air Fresh air change 27.251775 ESHF 0.89 ADP 56 1 Deh. Rise 15.84

6.15 0 0 6.15 0 0 0 0 103.733 0 0 103.733

11 11 13 164 11 103 11 127 19 23 21 17 16 11 23 19

0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.44 0.44 0.44 0.44 0.44 0.44 0.44 0.36 0.48

37.88 0.00 0.00 564.82 0.00 0.00 0.00 0.00 867.21 Deh rise 0.00 Deh cfm

cfm

Solar heat gain through walls ( 1- BF)* ( RM DB - ADP) ERSH / 1.08 * temp rise

0.00 Supply cfmERSH / 1.08 * DESIRED Td 775.92284 Outlet Td ERSH / 1.08 * De hum CFM 0.00 0.00 0.00 0.00 0.00 1461.89 1461.89 0.00 0.00 1400.00

Transmission gain through roof/ ceiling/partitions 0 190.35 190.35 0 0 5 1 200 16 16 16 21 280 3410 3.41 1.00 1.25 0.48 0.48 0.40 1.10

3410.00 852.50 10832.11 541.61 11373.71 284.34

Room sensible heat SA duct gain 2.5%

SA fan gain 5% Fresh Air Reheat Effective room sensible heat Latent heat People Subtotal
Safety factor 5%

568.69 1 27.25 2.4 1.08 70.64 12297.38

270

1350.00 1350.00 67.50 1417.50

Room latent heat Fresh Air 1 27.25 2.4 0.68 Effective room latent heat Effective room total heat Outdoor Air Heat Fresh Air Sens Fresh air lat
RA gain

44.47 1461.97 13759.35

27.25 27.25

20 73

0.88 0.88

1.08 0.68

518.00 1190.44

RA fan gain Grand Total 15467.80

Tons TR

1.29

NTHA PURAM

Enthalpy Btu/lb 44 44 27.5 16.5

Deh. Cfm

719 1.Plain Glass( cl E) has to be changed from .56 to.1.0 2.Light & Equipmnet load to be taken as per site conditions. 3.Roof facor,as normal building. 4.Roof factor to be filled when the Roof is exposed. 5.Ceiling facor to be filled up in case of Floor on top. 6.Floor facor when ,we have floor below the Space to be airconditioend/\ 7.The caliculation table only for large areas of Above 500 sq ft.