Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Basic structure of
flame safeguard system
The purpose of the FSG is to prevent an explosion.
For this purpose,
the FSG does not allow fuel to accumulate in the furnace (combustion chamber).
The FSG controls the fuel to keep the density below the explosion limit.
Cases of fuel accumulation in the furnace and corrective measures to them
The ame safeguard system limits the operation to within
safe operational ranges using limits and interlocks, and
always monitors combustion conditions by means of a ame
detector. The signal from the ame detector is converted by
burner controller into the signal required for actuators to
operate safety shutoff valves.
If some failure has occurred in the combustion equipment
resulting in an ignition failure or other burner ame failure,
the ame detector detects the abnormal condition of
combustion ame, transmits the signal to the burner
controller to close the safety shutoff valves, and prevents the
ow of fuel into the combustion chamber.
If the ame detector or burner controller has caused a
failure, the system has a safety circuit function to operate
the fuel shutoff valves or not to start the burner.
Stops the burner by automatic or manual operation.
Starts the burner in correct sequence and monitors the
combustion ame during operation.
Protects against abnormal temperatures or pressures.
Controls the combustion quantity of the burner.
Maintains the operation start standby state during burner
stop.
Functions of the Flame Safeguard System
Residual gas remains in furnace.
Safety shutoff valve is opened before
the ignition source is activated
at the time of burner ignition.
Burner is not ignited even though
ignition operation is tried.
Burner has suddenly experienced
a flame failure due to some cause
during operation.
Burner is experiencing incomplete
combustion due to an inappropriate
fuel/air ratio.
Prepurge
Ventilation must be made until fuel density is decreased to the level below the explosion
limit. The ventilation time length must not be shortened even if a failure occurs.
Burner controller, safety shutoff valve (periodical maintenance)
Ignition timing
Shutoff must be made before the density increases to the explosion limit.
Ignition time length must not become longer even in the event of a failure.
Flame detector, burner controller (ignition sequence)
1.
2.
Limit
Flame detector
Burner controller
Interlock
Leakage Standards for Safety Shutoff Valves: List of Safety Shutoff Valve Leakage Standards
European Safety Shutoff Valve Standard (EN161 Group 2): Excerpted summary by Azbil Corp.
Test methods Internal leakage Test methods Standard External leakage
EN161
Europe
UL429
USA
JIS B 2151
Japan *1
ISO 23551 Standard bore
DN < 10
10 DN 25
25 < DN 80
80 < DN 150
150 < DN 250
*1. For cases of connection to a gas pipe with an outer diameter of 35 mm or less, for gas burning appliance automatic valves used in combustion equipment that uses city gas or liquefied petroleum gas at a gas pressure of 3.3 kPa or less.
Group division
Group 1: Shipped in the bracket, no force applied during piping work.
Group 2: Installed inside or outside the bracket, supported only by the pipe.
20 cm
3
/h or less
40 cm
3
/h or less
60 cm
3
/h or less
100 cm
3
/h or less
150 cm
3
/h or less
Standard bore
DN < 10
10 DN 25
25 < DN 80
80 < DN 150
150 < DN 250
20 cm
3
/h or less
40 cm
3
/h or less
60 cm
3
/h or less
60 cm
3
/h or less
60 cm
3
/h or less
200 cm
3
/h or less
30 cm
3
/h or less
Measure at the burette or water column gauge
after applying 60 mm of H2O and a pressure of
1.5 times the maximum usage pressure from
the inlet and outlet.
Measure at the burette or water column gauge
after applying 60 mm of H2O and a pressure of
1.5 times the maximum usage pressure from
the inlet and outlet.
1.5 times the maximum usage pressure for
those with 350 mm of H2O or greater.
235 cm
3
/h or less (when the internal
diameter is greater than 11/2 B, add an
extra 235 cm
3
/h for each B)
Measure with the leakage detector at 4.2 kPa as
well as 0.5 kPa of air pressure from the inlet.
30 cm
3
/h or less (for appliance valves)
300 cm
3
/h or less (for non-appliance valves)
Test at 175 mm of H2O and again at 1.5 times the
maximum usage pressure (but at least 350 mm of H2O).
Measure
Measure the pressure difference at a pressure gauge
upstream from the valve.
Measure at the leakage detector at 4.2 kPa as
well as 0.5 kPa air pressure from the inlet.
After carrying out an internal leakage test at
0.6 kPa, repeat the test using pressures of
either 1.5 times the maximum usage pressure
or 15 kPa, whichever is higher.
However, those using gas at 11.2 kPa or 14.8
kPa should be tested at a minimum of 22 kPa.
After carrying out an internal leakage test at
0.6 kPa, repeat the test using pressures of
either 1.5 times the maximum usage pressure
or 15 kPa, whichever is higher.
However, those using gas at 11.2 kPa or 14.8
kPa should be tested at a minimum of 22 kPa.
Performance Test methods Item
Leakage
Valve closure ability
Durability
Flow
Resistance to gas
Open time
(slow open)
Strength
(torque: kgfcm)
Size
Must be within 95 % of specification. Converted to 15 C atmospheric pressure
With n-pentane must be within 15 % of the volume change ratio.
Must be 20 % of manufacturers specification.
Must meet the above internal leakage standards when pressure is applied from the outlet.
Must meet the operation, leakage, and valve closure pressures in the above test.
External leakage Internal leakage
Size -15 C 20 C
1 or less
1
1
/ 43
Size
Bending torque
Twisting torque
7
3.5
3
/ 8
10.5
5
1
/ 2
22.5
8.5
3
/ 4
34
12.5
1
47.5
16
1
1
/ 4
61
20
1
1
/ 2
110
25
2
160
32.5
2
1
/ 2
240
40
3
25,000 cycles
25,000 cycles
125,000 cycles
50,000 cycles
60 C
50,000 cycles
25,000 cycles
Total
200,000 cycles
100,000 cycles
Measure internal leakage after applying pressure from
the inlet, and external leakage from the inlet and outlet,
using 60 mm of H2O and a pressure of 1.5 times the
maximum usage pressure.
Applied pressure
Class A: 1500 mm H2O
Class B: 500 mm H2O
Class C: 100 mm H2O
Done with the pressure at the maximum allowable
pressure, the flow rate at 10 % or less of the rating, the
voltage at 85 % at 15 C, 85 % and 110 % (half each)
at 20 C, and 110 % at 60 C.
Measure at 40 C after steeping in 23 C n-pentane for
72 hours and then air-drying for 72 hours.
Measure the time taken to reach 80 % of the
specification flow rate at 110 % of rated voltage at 60 C
and 85 % of rated voltage at -15 C.
For each, apply torque for 10 seconds and check for
internal and external leakage.
Standard bore
DN < 10 20 cm
3
/h or less
10 DN 25 40 cm
3
/h or less
25 < DN 80 60 cm
3
/h or less
80 < DN 150 60 cm
3
/h or less
150 < DN 60 cm
3
/h or less
Standard bore
DN < 10 20 cm
3
/h or less
10 DN 25 40 cm
3
/h or less
25 < DN 80 60 cm
3
/h or less
80 < DN 150 100 cm
3
/h or less
150 < DN 150 cm
3
/h or less
DN < 10
10 DN 25
25 < DN 80
80 < DN 150
150 < DN
20 cm
3
/h or less
40 cm
3
/h or less
60 cm
3
/h or less
60 cm
3
/h or less
60 cm
3
/h or less
20 cm
3
/h or less
40 cm
3
/h or less
60 cm
3
/h or less
100 cm
3
/h or less
150 cm
3
/h or less
O
v
e
r
v
i
e
w
8
Introduction to Flame Safeguard System
I
n
t
r
o
d
u
c
t
i
o
n
t
o
F
l
a
m
e
S
a
f
e
g
u
a
r
d
S
y
s
t
e
m
The adjustment mechanism must seal it so that it can be seen that no adjustments have been made that the manufacturer did not intend.
No amount of drift in the adjustment switches or driving mechanism may interfere with normal valve operation.
Performance
The switch is required to indicate the closed position in both of the following situations.
When the ow is 10 % or less of the fully open ow at the same differential pressure.
ISO 12100
JIS B 9700
S
t
a
r
t
-
u
p
i
g
n
i
t
i
o
n
C
o
n
t
r
o
l
i
g
n
i
t
i
o
n
C
o
n
t
r
o
l
e
x
t
i
n
c
t
i
o
n
C
o
n
t
r
o
l
i
g
n
i
t
i
o
n
C
o
n
t
r
o
l
e
x
t
i
n
c
t
i
o
n
I
g
n
i
t
e
Pilot burner
Main burner
Pilot burner
Main burner
14
O
v
e
r
v
i
e
w
G
e
n
e
r
a
l
S
a
f
e
t
y
C
o
d
e
f
o
r
I
n
d
u
s
t
r
i
a
l
C
o
m
b
u
s
t
i
o
n
F
u
r
n
a
c
e
s
:
J
I
S
B
8
4
1
5
:
2
0
0
8
General Safety Code for Industrial Combustion Furnaces: JIS B 8415: 2008
Temperature
controller
SDC35
Excess
temperature
limit
Limit
Interlock
Advanced UV sensor
for main burner
AUD300C
Burner interlock module
Burner control module
Fuel
Blower
PS PG
PS PG
Air pressure
switch
(C6097A)
Pressure
gauge
Pilot safety
shutoff valve
Gas pressure
switch
C6097A
Pressure
gauge
PS PG
Gas pressure
switch
C6097A
Pressure
gauge
3
9
4
4
4
10
4
11 8
11 8
11 8
9 6
1 2
Exhaust
gas
Flue
Igniter
S7200
Ignition
command
Alarm
Limit
5
7
M
Flame shutter
Ignition transformer
Pilot valve
Advanced UV sensor
for pilot burner
AUD300C
Exhaust
damper
interlock
Seismic
sensor
limit
Limit
Precautions for burner control circuit design
Safety control and operation circuits must use an intrinsic safety design method based on risk assessment.
Interlock (including limits) connections must be configured to directly cut off the load (ignition transformer, pilot safety
shutoff valve, main safety shutoff valve, etc.).
All shutoff contacts are to be on the ungrounded. In addition, leakage breakers, double-pole contacts and other
anti-leakage measures are to be taken as necessary.
The safety control circuit must promptly produce an alarm such as a light or buzzer as needed when an abnormal situation
arises.
Precautions for instrumentation and circuit configuration for the intermittent pilot method
(1) The pilot burner and the main burner must have separate flame monitoring (flame detectors, burner controllers).
(2) The flame detector for the main burner must be installed where it will not detect the flame of the pilot burner.
(3) The limit and interlock must be connected to the limit and interlock terminals of the burner controllers for the pilot burner
and the main burner so that they can directly shut off the load (ignition transformer, pilot shutoff valve, main safety shutoff
valve, etc.).
(4) For the startup circuit configuration, the main burner ignition enabled output (pilot flame ignition signal) from the
controller for the pilot burner must always be connected to the interlock input terminal and start-up input terminal on the
controller for the main burner.
(5) When the pilot burner or main burner fails to ignite or goes out, the circuit must stop all burners.
Caution:
Main
safety shutoff valve
Intermittent pilot system instrumentation example
O
v
e
r
v
i
e
w
15
G
e
n
e
r
a
l
S
a
f
e
t
y
C
o
d
e
f
o
r
I
n
d
u
s
t
r
i
a
l
C
o
m
b
u
s
t
i
o
n
F
u
r
n
a
c
e
s
:
J
I
S
B
8
4
1
5
:
2
0
0
8
Even highly reliable control systems with high levels of performance and functionality cannot eliminate the risk of re, since
they can fail and become unable to control combustion. Unfortunately, improvements in controllability have not meant
improvements in safety.
Normally, control and safety instrumentation are separated, so that even if the safety device is relatively inaccurate, one with
reliable operation must be used. The relationship between safety and control must allow control to be performed where safety
is assured, so the control zone must be an area that is included within the safe zone. This zone is where improvements in
control must be made.
Control and safety tend to be thought of as being handled by control devices and safety devices, respectively. However, while
this may usually be the case, they are difcult to achieve solely using these devices. The structure and function of the
combustion equipment, facilities, etc., are also elements that affect control and safety.
In other words, achieving control and safety is possible only once the three elements of (1) control and safety devices, (2)
equipment and facilities, and (3) the location (conditions of installation) are all appropriate. In addition, it is difcult to ensure
safety in the case of all equipment or facilities failing or when the installation conditions are no longer met. When safety cannot
be assured, we naturally wish to eliminate all failures and breakdowns, but even if all scenarios could be considered, it would
still not be possible to absolutely guarantee safety.
With this in mind, it is necessary to carry out regular inspections and maintenance of the equipment to ensure safety. That is,
maintenance is also an important component of safety assurance.
In summary, combustion equipment and facilities are objects for control, but they also must be fundamentally safe. To achieve
this, the control zone needs to be encircled by the safety zone, and that in turn must be encircled by the maintenance zone.
The equipment and facilities, and the control devices (including the ame safeguard control system), and the installation
conditions are each elements of control/safety/maintenance.
bSafety configuration of control system bSpecific example of safety configuration
Controllers
Installation
location
Equipment
bControllers
bLimits
bSensors
bActuators
(valves, damper motors)
bSafety valves
bBurners
bValve trains
bDampers
bPiping
bVentilation
bFlues
Maintenance zone
Safety zone
Safety zone
Control zone
M
a
i
n
v
a
l
v
e
I
g
n
i
t
i
o
n
t
r
a
n
s
f
o
r
m
e
r
P
i
l
o
t
v
a
l
v
e
Power (high electric potential side), HOT
Control zone
Power (ground side), GND
Limit
Burner
controller
ON/OFF control
Control
zone
Safety
zone
Shutoff
valve
Control
valve
Burner
Fuel
O
v
e
r
v
i
e
w
16
C
o
n
c
e
p
t
B
e
h
i
n
d
C
o
m
b
u
s
t
i
o
n
E
q
u
i
p
m
e
n
t
C
o
n
t
r
o
l
a
n
d
S
a
f
e
t
y
Concept Behind Combustion Equipment Control and Safety
Memo
17
O
v
e
r
v
i
e
w
C
o
n
c
e
p
t
B
e
h
i
n
d
C
o
m
b
u
s
t
i
o
n
E
q
u
i
p
m
e
n
t
C
o
n
t
r
o
l
a
n
d
S
a
f
e
t
y
Burner controllers Flame detectors Valves / Actuators
Intermittent operation systems
Continuous operation and intermittent operation systems Continuous operation and intermittent operation systems
Protect relays
Gas shutt-off valves
Gas regulators Motorized gas valves
AUD300
Advanced ultraviolet ame detector
Ultraviolet ame detector *1
Advanced ultraviolet ame detector and socket
AUD100/110 + AUD15
Visible light frame detector
AUD500
Shut-off valve *3
MAX808/5000/7000
C7076D C7076A
AFD110 AFD100
Pressure regulator *4
RV
MAX SAFETY multi protectoglo
with UV tube diagnostic circuit
R4332B (for C7076)
Burner interlock module and
burner control module
RX-L and RX-R
Protect relay
R4424
(for AFD100/110)
R4440
(for AFD100/110)
Intermittent operation systems
Flame relay
FRS100
Advanced UV relay
AUR350
Limit / Interlock switches
Gas pressure switches
Eathquake sensing switches
Gas pressure switch
C6097
Earthquake sensing switch
V-725 VBC7000
Peripheral devices
Analog flame meters
Analog ame meter
FSP136
Flame simulators
Control motors
FSG motorized gas valve
CCM21/CCV20
Buttery valve
V51E
Ignition transformers
Flame
detection
signal
Limit/
interlock
signal
Safety shutoff/
control
Flame simulator
FSP300
Solenoid valve *2
GV-A
Control motor
ECM3000
*1. C7076A and C7076D are products of Honeywell International Inc.
*2. GV-A is a product of Elster GmbH.
*3. MAX808, MAX5000 and MAX7000 are products of Maxon Corporation.
*4. RV is a product of Maxitrol Company.
Ignition transformer
ATN110-A
High power igniter
S7200
Flameproof
explosion-proof
ignition transformer
APN4709
Dynamic self-checking
burner controller
AUR450
O
v
e
r
v
i
e
w
18
Product Line
P
r
o
d
u
c
t
L
i
n
e
Burner controllers Flame detectors Valves / Actuators
Intermittent operation systems
Continuous operation and intermittent operation systems Continuous operation and intermittent operation systems
Protect relays
Gas shutt-off valves
Gas regulators Motorized gas valves
AUD300
Advanced ultraviolet ame detector
Ultraviolet ame detector *1
Advanced ultraviolet ame detector and socket
AUD100/110 + AUD15
Visible light frame detector
AUD500
Shut-off valve *3
MAX808/5000/7000
C7076D C7076A
AFD110 AFD100
Pressure regulator *4
RV
MAX SAFETY multi protectoglo
with UV tube diagnostic circuit
R4332B (for C7076)
Burner interlock module and
burner control module
RX-L and RX-R
Protect relay
R4424
(for AFD100/110)
R4440
(for AFD100/110)
Intermittent operation systems
Flame relay
FRS100
Advanced UV relay
AUR350
Limit / Interlock switches
Gas pressure switches
Eathquake sensing switches
Gas pressure switch
C6097
Earthquake sensing switch
V-725 VBC7000
Peripheral devices
Analog flame meters
Analog ame meter
FSP136
Flame simulators
Control motors
FSG motorized gas valve
CCM21/CCV20
Buttery valve
V51E
Ignition transformers
Flame
detection
signal
Limit/
interlock
signal
Safety shutoff/
control
Flame simulator
FSP300
Solenoid valve *2
GV-A
Control motor
ECM3000
*1. C7076A and C7076D are products of Honeywell International Inc.
*2. GV-A is a product of Elster GmbH.
*3. MAX808, MAX5000 and MAX7000 are products of Maxon Corporation.
*4. RV is a product of Maxitrol Company.
Ignition transformer
ATN110-A
High power igniter
S7200
Flameproof
explosion-proof
ignition transformer
APN4709
Dynamic self-checking
burner controller
AUR450
O
v
e
r
v
i
e
w
19
P
r
o
d
u
c
t
L
i
n
e
For detailed specifcations, or to learn whether a product is available
in a particular country, please contact our sales staff.
Products
Flame
Safeguard
System
: This product is certified as complying with CE marking for use in Europe.
: This product is certified as complying with a U.S. product safety standard.
: This product is certified as complying with a Canadian product safety standard.
: This product is certified as complying with a U.S. product safety standard.
For detailed specifications, or to learn whether a product is
available in a particular country, please contact our sales staff.
v
Burner Controllers
v
Flame detectors
v
Pressure Switch
v
Igniter
v
Peripheral devices
20
Products
Flame
Safeguard
System
: This product is certified as complying with CE marking for use in Europe.
: This product is certified as complying with a U.S. product safety standard.
: This product is certified as complying with a Canadian product safety standard.
: This product is certified as complying with a U.S. product safety standard.
For detailed specifications, or to learn whether a product is
available in a particular country, please contact our sales staff.
v
Burner Controllers
v
Flame detectors
v
Pressure Switch
v
Igniter
v
Peripheral devices
21
Features
Buner Interlock Module (RX-L80/90) Buner Control Module (RX-R40/20)
bProvides combustion safety to meet the specifications of the combustion equipment
Safety features are tailored to equipment specifications by means of the modular structure and wide range of selectable functions.
Provides a variety of preinstalled safety functions, reducing the time spent on safety circuit review and validation.
Functions can be selected and executed via the PC loader, without acquiring or creating special software.
bConservation of space and wiring
Side connectors between modules carry safety signals such as shutoff commands, eliminating the need for external wiring or relays, saving
wiring and space.
bMaintenance support functions
An operation log (number of starts, operating time, alarm history, etc.) is kept automatically without the need for any special settings.
Status can be checked as necessary by connecting the PC loader.
Various monitor outputs tailored to the structure of the combustion equipment are implemented, aiding in understanding the
maintenance/troubleshooting situation and in determining the cause of a problem.
Product status checks: 7-segment LED display
Front panel indicators: Open collector monitor output
Remote status monitoring: RS-485 (standard feature)
The roles of the burner interlock module in
the combustion safety architecture are the
handling of burner interlock
monitoring/processing and of the purge
function. A maximum of 32 burner control
modules can be combined to easily
support multiple burner equipment.
This module is also equipped with the
ability to connect through RS-485 or
Ethernet (only RX-L90) communications,
making remote monitoring possible.
The roles of the burner control module in
the combustion safety architecture are the
ignition, flame monitoring, and safety
shutoff functions. This unit can be
combined with the burner interlock module
to support a variety of combustion
equipment.
b Ignition functions (for the 3 models below)
3
8
.
6
8
8
153.5
13.3
G1
Electric wire mounting conduit 1/2-14NPSM
AUD300CX000
XXXX XXXXX
MADE IN JAPAN
Bushing 1
3/ 4
Packing nut
*1 For applications using coke oven gas, hydrogen, chlorine, ammonia, naphtha, ethylene, etc., in
which the burner structure may impose restrictions on the mounting of the ame detector, it is
necessary to check that ame monitoring is reliable.
*2 Standards approvals are valid only for a combination of AUR450C, AUD300C, and Q241A104
No inspection certificate
Inspection certificate included
Model Selection
Item
Advanced
ultraviolet
flame
detector
Model No.
AUD300C1000
AUD300C100D
AUD300C100T
AUD300C100DT
AUD300C1100
AUD300C110D
AUD300C110T
AUD300C110DT
Lens type
Standard
Condenser
Additional features
None
Inspection certicate provided
None
Inspection certicate provided
None
Inspection certicate provided
None
Inspection certicate provided
Special treatment
None
None
Tropicalization
Tropicalization
None
None
Tropicalization
Tropicalization
P
r
o
d
u
c
t
s
27
F
l
a
m
e
d
e
t
e
c
t
o
r
s
Advanced Ultraviolet Flame Detector
AUD300C1000
The AUD300C1000 Advanced Ultraviolet Flame Detector is de-
signed to detect ultraviolet radiation from an oil or gas burner fame,
for use with both batch and continuous operation.
The AUD300C is used in combination with a dedicated burner con-
troller. By means of the built-in shutter, any malfunction of the UV
flame detector or burner controller is detected by the continuous
self-checking (Dynamic Self-Check) function, ensuring highly reli-
able combustion safety control.
Model Selection
Optional parts (sold separately)
Specifications
Explosion-proof housing
Explosion-protection certified
Applicable types of flame*1
Shutter voltage
Self-checking cycle
Insulation resistance
Dielectric strength
Ambient temperature
Ambient storage temperature
Ambient storage humidity
Vibration resistance
Pressure resistance for mounting part
Protection
Mounting posture
Mounting (on the monitoring pipe)
Accessory cable length
Flame signal wire requirements
and extension distance
Materials
Color
Mass
Expiration date of tube unit and shutter unit
Dimensions
Ex d IIC T4
Product qualied by Technology Institution of Industrial
Safety (TIIS) and National Supervision and Inspection Center
for Explosion Protection and Safety Instrumentation (NEPSI).
City gas, natural gas, propane gas, kerosene, heavy oil, coke oven gas,
hydrogen, chlorine, ammonia. naphtha, ethylene, etc.
Approx. 24 Vdc (supplied from Burner Controller)
Approx. 75 cycles / min
Between ange mounting part and F-terminal (or blue lead wire),
between ange mounting part and G-terminal (or yellow lead wire),
between ange mounting part and S1-terminal (or white lead wire),
between ange mounting part and S2-terminal (or white lead wire):
50 M min. by 500 Vdc megger at each of the above locations.
(However, the tube unit must be removed)
Between ange mounting part and F-terminal (or blue lead wire),
between ange mounting part and G-terminal (or yellow lead wire),
between ange mounting part and S1-terminal (or white lead wire),
between ange mounting part and S2-terminal (or white lead wire):
1500 Vac for 1 min or 1800 Vac for 1 s at each of the above locations.
(However, the tube unit must be removed)
-20 to +60 C
-20 to +70 C
90 % RH at 40 C max. (without condensation)
4.9 m/s
2
max., 10 to 55 Hz for 2 hours each in X, Y and Z directions
690 kPa
IP67
-45 to +90 (in vertical direction)
Flange: Parallel pipe thread G2-1/4, Adapter: Taper pipe thread R1
AWG18 heat-resistant silicone cables (4 cores),
3 or 10 m (depending on the model number)
IV wires with 2.0 mm
2
and max. 200 m in length
Aluminum
Purple (equivalent to DIC257)
Approx. 2.5 kg
3 years
b For further details, please refer to specications sheet No. CP-SS-1873E.
Maintenance parts (sold separately)
Model No. Item
AUD60A1010 AUD Maintenance Kit (includes shutter and tube units)
(Unit: mm)
Body
Bushing
AUD Maintenance Kit
Model No.:AUD60A1010
The AUD60A1010 maintenance kit includes the assembled
shutter unit and tube unit, as well as consumables such as
the AUD500C main unit ange and tight-tting cover O-ring,
expiration label, etc.
t 1:Expiration
date label
Example of
an attached label
GOOD THRU
GOOD THRU
Outside earth screw M4
1
0
3
52.8
1
8
5
2
4
.
5
35
1
0
3
1
2
4
3
2
35
119.2
189
G2-1/4
G 1/2
70
60max
420Vp-p
5.5mA Max.
DC24V
180mA Max.
AMBIENT TEMPERATURE
SENSOR VOLTAGE
SENSOR CURRENT
SHUTTER VOLTAGE
SHUTTER CURRENT
MODEL
AUD500C21
DATE CODE
FLAME PROOF
Ex dIIC T4
FLAME DETECTOR
MADE IN JAPAN
(
)
CAUTIONUse heat resistant conductors of 70 min
SERIAL NO:
Name plate
Cover setscrew
(width across at: 2)
8
0
7
4
75.5
(210) 22
17
9
54
2Rc (for air purge)
Plug with hexagon socket (width across at: 5)
2 points
R1
AUD500
Packing
Adapter
Item
Accessory
cable length
Lens type Model No
Advanced ultraviolet flame detector AUD500C1100__
AUD500C1110__
AUD500C1101__
AUD500C1111__
3 m
10 m
3 m
10 m
Standard
Condenser
1
/ 8
Note: This item is necessary.
Model No. Item
81441151-001 Adapter (G2-
1
/ 4
R1)
*1. For applications using coke oven gas, hydrogen, chlorine, ammonia. naphtha, ethylene, etc., in
which the burner structure may impose restrictions on the mounting of the ame detector, it is
necessary to check that ame monitoring is reliable.
Replace the blank (_ _) in the mobel number with one of the for choices below.
0: Standard product
D: Inspection certicate included
OT: Tropicalization
DT: Inspection certicate + tropicalization
Y: Traceability certicate included
E: Heavy duty coating + inspection certicate
P
r
o
d
u
c
t
s
28
F
l
a
m
e
d
e
t
e
c
t
o
r
s
Advanced Ultraviolet Flame Detector
AUD500C11000
The AUD500C Explosion-Proof Advanced Ultraviolet Flame
Detector (hereafter referred to as the AUD500C) is designed to
detect ultraviolet radiation from an oil or gas burner fame, for use
with both batch and continuous operation.
The AUD500C is used in combination with a dedicated burner
controller. By means of the built-in shutter, any malfunction of
the UV flame detector or burner controller is detected by the
continuous self-checking (Dynamic Self-Check) function, ensuring
highly reliable combustion safety control.
Replace the blank ( _ ) in the mobel number with one of the for choices below.
0 : Standard
D : Inspection certicate
T*: Tropicalization treatment
B*: Inspection certicate + tropicalization treatment
* Only AUD110 Series
*1. AUD15C1000
*2. Seal adapter (model No. 81403159)
Refer to the following dimensions
Specifications
Applicable type of fuel *1
Mass
Materials
Insulation resistance
Dielectric strength
Ambient temperature
Ambient storage
temperature
Ambient humidity
Allowable pressure
Vibration resistance
Protection
Mounting nut
Lead wires
Conduit
Flame signal wire
City gas, natural gas, propane gas, kerosene, heavy oil, coke oven gas, hydrogen, chlorine, ammonia. naphtha, ethylene, etc.
AUD100C
Approx. 120 g
(with the AUD15: approx. 140 g)
Aluminum
50 M min by 500 Vdc megger
(between each lead wire and the metal part of socket when the AUD15 is removed)
1500 Vac for 1 min or 1800 Vac for 1 s
(between each lead wire and the metal part of socket when the AUD15 is removed)
-20 to +120 C
-20 to +70 C
90 % RH at 40 C (without condensation)
35 kPa
5 m/s
2
max. (10 to 60 Hz for 2 hours each in X, Y and Z directions)
IP65 (JIS C 0920/IEC 60529) with pipes and wires connected
G1 (R1 and 1-11BSP are connectable)
AWG #18 (approx. 1.2 mm
2
) ame retardant cross-linked polyethylene insulated cable, approx. 1800 mm long (blue and white) (only AUD100)
G1/2 (1/2-14BSPP is connectable)
Standard: 2.0 mm
2
, 600 Vac cable with PVC insulation ("IV cable"). Max. length: approx. 200 m
AUD110C
Approx. 120 g
(with the AUD15: approx. 140 g)
Socket: Aluminum
Terminal block: Heat-resistant resin (PBT + GF30) (black)
50 M min by 500 Vdc megger
(between each of terminals F and G and the metal part of socket when the AUD15 is removed)
1500 Vac for 1 min or 1800 Vac for 1 s
(between each of terminals F and G and the metal part of socket when the AUD15 is removed)
b For further details, please refer to specications sheet No. CP-SS-1877E.
Model Selection
AUD100C100_
AUD100C1000-A15
AUD110C100_
AUD110C1000-A15
Lead-wire model without the AUD15
Lead-wire model with the AUD15
Terminal block model without the AUD15
Terminal block model with the AUD15
Optional parts (sold separately)
Tube unit (ultraviolet photoelectric tube) *1
Seal adapter *2
Analog flame meter
Flame simulator
Lens unit (focal length: 70 mm)
Lens unit (focal length: 70 mm) with inspection certificate
Lens unit (focal length: 30 mm)
Lens unit (focal length: 30 mm) with inspection certificate
Description
Dimensions
Thermolabel
Light-receiving
glass surface
Product label
Time period label
1
4
.
2
Heat resistant flat plastic cable (black/white)
0.75mm
2
Length 700 mm 25 mm
9
.
5
m
a
x
.
Sensing surface
14.3
Sensing surface
P
r
o
d
u
c
t
s
30
F
l
a
m
e
d
e
t
e
c
t
o
r
s
AFD100A/B
Visible Light Frame Detector
The AFD100A/B visible light fame detector is a batch operation
fame sensor that detects visible light from an oil combustion
burner fame.
There are two different types for different burner constructions,
depending on whether the light is received from the front or
side.
Be sure to combine this product with the burner controller appropriate
for the AFD100.
C554A compatible replacement adapter
Specifications
Model selection
Item Model No.
Visible light flame detector AFD110A0000
Optional Parts (sold separately)
Item Model No.
Replacement sensor AFD100A0035
Dimensions
(Unit: mm)
G3/4
G3/8
F G
117
4
0
6
2
(
8
2
)
Black
White
G
F
1
4
.
2
(12)
(15)
17
20 10 32.7 22
Replacement sensor (AFD100A0035)
9
.
3
m
a
x
Illuminance-current characteristics
(Conditions: VR = 5 V, at 25 C)
Dark characteristics
Dielectric strength
Insulation resistance
Allowable ambient temperature
Storage temperature
Allowable ambient humidity
Vibration resistance
Cable
Protection
Material
Mounting
Compatible burner controllers
Mass
At an illuminance of 10 lx (color temperature of 2,856 K), 30 A or more.
(Measurement conditions: Supply voltage: 5 V, load resistance: 20 k, room temperature/normal humidity)
In total darkness (0 lx), 24 A or lower.
(Measurement conditions: Supply voltage: 5 V, load resistance: 20 k, room temperature/normal humidity)
Commercial frequency 500 Vac, applied for 1 minute with no abnormalities.
(Between lead wires and ange, at room temperature and normal humidity)
With a 500 Vdc megger, 50 M or more.
(Between lead wires and ange, at room temperature and normal humidity)
-20 to +60 C
-20 to +70 C
40 C, 90 % RH or less (without condensation)
Double amplitude 4.9 m/s
2
, 10-55 Hz, 2 hours each in X, Y, Z directions
Heat-resistant at plastic cable, 0.75 mm
2
Black (terminal F), white (terminal G)
IP44 (with conduit and wiring connected)
Aluminum
G3/4 inch ange
R4424 or R4440H series product that supports AFD
Approx. 200 g
M4 connection screw
Terminal block
P
r
o
d
u
c
t
s
31
F
l
a
m
e
d
e
t
e
c
t
o
r
s
Visible Light Flame Detecter
AFD110A
The AFD110A visible light fame detector is a batch operation
fame sensor that detects visible light from an oil combustion
burner fame.
This product must be combined with an AFD-compatible Burner
controller.
Dimensions
(Unit: mm)
Specifications
Model Selection
Wiring
Gas pressure switch C6097A0110
C6097A0210
C6097A0310
C6097A0410
C6097A0510
Optional Parts (sold separately)
Switch operation indicator lamp (100/200 Vac) 81404156
Monitoring pressure gauge port
M4 plug screw, length 6
PBT
Wiring port 22
R 32
Low-pressure port
Rp 1/8
Rp 1/4 high-pressure port
Note: Remove the dust seal before using
Note
3 unthreaded holes for bracket
installation (depth 8)
R 20
45
2
1
3
0
3
2
68.4 68.4
69
38.4
9
69
5
9
8
6
2
6
.
5
1
0
.
5 1
3
1
0
.
5
Housing
Die-cast aluminum
6
1
Applicable fluids
Model
Control action
Setting range
On-off differential
(nominal value)
Maximum Allowable pressure
Setting accuracy
Output
Contact raiting
Insulation resistance
Dielectric strength
Contact resistance
Fluid temperature
Ambient temperature
Durability
Wiring terminal
Installation direction
Protection
Mass
High-pressure gas contacting material
Accessories (sold separately)
Natural gas, liqueed petroleum gas, and air
Low pressure side: when at atmospheric pressure. High pressure side: when pressure is increasing.
SPDT contact output
On pressure down, terminals 1-3 closed, terminals 2-3 open.
On pressure rise, terminals 1-3 open, terminals 2-3 closed.
Resistive load: 250 Vac, 5 A
Inductive load: 250 Vac, 3 A (power factor: 0.6)
Minimum contact operating current and voltage: 50 mA, 24 Vdc
100 M min. between each terminal and non-live metal part with a 500 Vdc megger
Betw. terminals with the same polarity: 1000 Vac, 50/60 Hz for 1 min
Betw. each terminal and non-electrically charged metal parts: 1500 Vac, 50/60 Hz for 1 min
Leakage current of 1 mA or less under these conditions
Initial 100 m max. (measured by voltage drop method at 68 Vdc and 1 A)
-15 to +60 C (without freezing or condensation)
-15 to +60 C (without freezing or condensation)
Over 100,000 operations at the rated contact voltage and current
M3.5 screw terminal
Vertical, or horizontal with the pressure setting dial facing upwards.
IP54
260 g
Die-cast aluminum (housing), NBR/nitrile rubber (diaphragm)
Switch operation indicator lamp (100/200 Vac)
Model No.: 81404156
C6097A0110
ON/OFF
0.1 to 1 kPa
40 Pa (xed)
20 kPa
0.1 0.06 kPa, 1 0.15 kPa
C6097A0210
ON/OFF
0.25 to 5 kPa
60 Pa (xed)
30 kPa
0.25 0.15 kPa, 5 0.75 kPa
C6097A0310
ON/OFF
3 to 15 kPa
280 Pa (xed)
50 kPa
3 0.9 kPa, 15 2.25 kPa
C6097A0510
ON/OFF
10 to 70 kPa
800 Pa (xed)
150 kPa
10 3 kPa, 70 8 kPa
C6097A0410
ON/OFF
10 to 50 kPa
700 Pa (xed)
150 kPa
10 2.4 kPa, 50 7.5 kPa
Loads
Voltage
For a pressure drop:
Terminals 31 closed
Terminals 32 open
For a pressure rise:
Terminals 31 open
Terminals 32 closed
3
1
2
(COM)
(NC)
(NO)
Model No. Item
Model No. Item
Rp 1/4 high-pressure port
with plug ( use 6 mm hex wrench )
Note. Use M4 self-tapping screw or provide the hole with M4 threads before use.
P
r
o
d
u
c
t
s
32
P
r
e
s
s
u
r
e
S
w
i
t
c
h
Gas Pressure Switch
C6097A
The C6097A gas pressure switch is a pressure detector for city
gas, natural gas, LP gas and air.
The external electrical circuit is turned on or off according to
the preset value.
This device can be used in a variety of ways including detection
of maximum/minimum gas/air pressure supplied to the gas
burning device, burner blower interlock, or flter clogging.
As a supplementary part (sold separately), there is a switch-
action display light for switching the gas pressure.
Specifications
Model selection
Item
Gun type oil burner
Power gas burner
Model No.
S7200A100-OHR
S7200A200-OHR
S7200A100-GHR
S7200A200-GHR
Applicable burner
Model
Rated power and voltage
No. of electrodes
Recommended air speed
Time rating
Characteristics
High-voltage side connection
Grounding method
Power consumption
Mass
Operating voltage
High voltage side output voltage
Recommended electrode spacing
Electrical life
Induced lightning surge resistance
Insulation resistance
Dielectric strength
Operating ambient temperature
Operating ambient humidity
Storage ambient temperature
Ground terminal
Recommended high voltage cable
Power cord
Case material
Case color
Mounting
Mounting position
Oil-red gun-type burner
1
10 + 15 m/s
6 min, 20 %
One ground wire
Half-wave
Bullet terminal
Approx. 650 g
2
10 + 15 m/s
60 min, 50 % *1
Neutral ground
S7200A100OHR
100 Vac 5060 Hz
70 VA
S7200A200OHR
200 Vac 5060 Hz
75 VA
Note: The percentage gure is the allowable usage rate for continuous ignition. For example, 6 min, 20 % means that 1.2 min is the max. continuous discharge time (4.8 min rest).
S7200A100GHR
100 Vac 5060 Hz
55 VA
S7200A200GHR
200 Vac 5060 Hz
65 VA
Gas-red power burner
*1. This is the value when used in an ambient temperature of less than 40 C and is 60 min. and 33 % when used in an ambient temperature between 40 C and 60 C.
*2. For the rated voltage, room temperature, normal humidity and 20 pF voltage divider input capacity.
*Models with number S7200A-G for gas-fired power burners have only one terminal output
and therefore there is no bullet terminal on this side.
Optional Parts (sold separately)
Item
High voltage cable (10 units)
Model No.
YS7200A300-S2
YS7200A500-S2
YS7200A1000-S2
YS7200A2000-S2
Cable length
30 cm
50 cm
1 m
2 m
Dimensions
(Unit: mm)
-15 % to +10 % of rated supply voltage
Approx. 20 kV
o-p
*2
3.5 0.5 mm
100,000 operations or 10 years under standard conditions (rated supply voltage, air speed between electrodes, room temperature, normal humidity)
10 kV or more between wires and between wires and ground (1.2/50 s, 100 or more)
Between ground terminal and input terminals using a 500 Vdc megger, 50 M or more (excluding high voltage terminals)
Between ground terminal and input terminals, 1800 Vac, 1 s without abnormalities (excluding high voltage terminals)
-20 to +60 C
90 % RH or less at 40 C (no leak discharge due to condensation between the secondary terminals and the secondary terminal and ground)
-20 to +60 C
If there is poor electrical contact between the ground terminal and the burner main unit, high frequency noise will occur and create electrical interference in other
equipment, radios, TVs, etc. Be sure to remove the paint from the point of contact on the burner so that there is a good connection.
Standards
/Dimensions
Pullout strength
500 30 mm (plastic cabtyre cable, 2 cores / VCTFK, JIS3306 / 0.75 mm
2
, 30/0.18 diameter 4.4 6.8 black)
Polycarbonate
Black
Mounted on metal plate (1 mm thick or more)
Mounted such that ground terminal makes contact with metal plate.
Approx. 16 kV
o-p
*2
2.5 0.5 mm
High-voltage AIRN (JIS3405) cable for use in vehicles or neon light wiring, 300 mm (standard) to 2000 mm (maximum) in length.
(However, if the wire is longer than 600 mm, use an insulator to raise it by at least 50 mm. Separate the cables by at least 3 cm.)
More than 290 kPa. AIRN cable (JIS3405) must be used to prevent the cable from pulling out during transport or under use conditions.
Power cord
Plastic cabtyre cable, 2 cores
VCTFK JIS C 3306
0.75 mm
2
, 30/0.18, dia. 4.4 6.8, black
1
9
72
51
5.2
0.8
5
7
3
8
3
9
4
.
5
7
3
Ground terminal
5.2 hole
High voltage terminal
Dia. 6.4 bullet terminal
(free-machined brass rod) (2)
6010
50030
59
29
4
*
P
r
o
d
u
c
t
s
33
I
g
n
i
t
e
r
High Power Igniter
S7200A
The S7200A igniter is a solid-state, high performance ignition
transformer used with business and industrial oil-fred gun-type
burners and gas-fred power burners.
Compared with our other products, this unit has twice the
ignition energy, equivalent to the amount of a coil ignition
transformer, therefore making it possible to use this transformer
with burners that previously could be ignited only by using a
coil ignition transformer.
Compared to the S720, the high-voltage cable can be extended
to 2 meters, and at that length the power does not drop.
Dimensions Specifications
(Unit: mm)
AUR300C/350C, AUR450C, RA890F/G, R4750, R4780,
FRS100B/C, FRL100/101,.etc
Moving coil
0 to 40 C
80% RH max. at 40 C
(no condensation allowed)
Vertical (unit has a strap on top)
2.5 % FS
Black
Approx. 450 g
7.5V
7.5V
SPL 15UA
OFF
TAUT BAND
A V
1
8
0
100 105 25
6
0
Strap
*: discontinued model
Model Selection
Analog flame meter FSP136A100
+ 9 9
8
K3
7 7
8
6
K1
K2
5 5
6
4
3 3
4
F
G
S
S
Relay terminal
FSP300C RX-R40
SB9
SA9
GA7
FB6
*Attach the FSP300C100 to the relay terminals. *Attach the FSP300C to terminals 11 through 14.
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
RX-L80 RX-R40C
F
G
FSP300C RX-R20
GA7
FB6
*Attach the FSP300C100 to the relay terminals.
RX-L80
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
RX-R20C
POWER
FLAME
FRS100 FLAME RELAY
G
F
(G)
6
5
(F)
*Attach the FSP300C100 to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
G
F
2K
G
F
*Attach the FSP300C100 to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
G
G
F
F
*Attach the FSP300C100
to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
G
F
G
F
*Attach the FSP300C100 to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
G
F
(G)
24
23
(F)
*Attach the FSP300C100 to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
F1 F2
F3
F4 G
Flme detectory relay
G
F
*Attach the FSP300C100
to the relay terminals.
Relay terminal
FSP300C100 SHUTTER
SHUTTER
UV
SENSOR
LINE CHECK
FLAME
MODE
LED1
LED2
SW1
S2
S1
G
F
SYNC
OFF
ON
P
r
o
d
u
c
t
s
36
P
e
r
i
p
h
e
r
a
l
d
e
v
i
c
e
s
FSP300C100
Flame Simulator
37
Application Examples
(RX Series)
Flame
Safeguard
System
v
Selecting an RX Series
Combustion Safety Controller
v
Boiler
v
Deodorizing Furnace
v
Small Holding Furnace
v
Small Melting and Holding Furnace
v
Large Melting Furnace
v
Heating Furnace 1 to 4
v
Heating Furnace
(Regenerative Burner)
v
Settings Tables
Various configurations and specifications exist for combustion equipment depending on the amount of combustion, ignition method, combustion
control method, and specific equipment specifications.
The versatile RX Series can be used for a variety of combustion equipment, from small batch furnaces to large-scale steel plant combustion
furnaces, and its functions can be easily switched using a PC loader.
To select the appropriate RX Series device, please refer to the pipe trains, sequence charts, or other relevant material in this document.
This is a system that controls a single burner using a series of devices such as a blower, combustion gas pressure switch, combustion
air pressure switch, and safety shutoff valve.
This is a facility with many burners in a single combustion furnace. The following diagram shows a multiburner furnace where equipment
such as blowers, pressure switches, safety shutoff valves, etc. are shared.
Note: A single facility with multiple combustion furnaces is called a multi-zone facility.
Single burner
Multiple burners
APL : Low air pressure switch
GPL : Low gas pressure switch
GPH : High gas pressure switch
FD : Flame detector
IG : Ignition transformer
PV : Pilot safety shutoff valve
MV : Main safety shutoff valve
CM : Control motor
APL : Low air pressure switch
GPL : Low gas
pressure switch
GPH : High gas
pressure switch
FD : Flame detector
IG : Ignition transformer
PV : Pilot safety shutoff valve
MV : Main safety shutoff valve
CM : Control motor
IG2
FD
Fuel
MV GPL GPL GPH
GPL GPL GPH
APL Blower
APL blower
PV
CM
IG
FD1
Fuel
MV
PV
CM
IG1
FD2
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
38
S
e
l
e
c
t
i
n
g
a
n
R
X
S
e
r
i
e
s
C
o
m
b
u
s
t
i
o
n
S
a
f
e
t
y
C
o
n
t
r
o
l
l
e
r
Selecting an RX Series Combustion Safety Controller
b ON/OFF control
The amount of combustion is controlled by igniting and extinguishing the burner. This method is frequently adopted by small
combustion furnaces, and the combustion furnace equipment conguration can be made quite simple.
Also, the time-proportional ON/OFF control method uses repeated short intervals of combustion in order to reach the desired amount of
heat. In this case, it is necessary to periodically inspect and replace equipment in consideration of the service life of the safety shutoff
valve and control device.
(Models RX-R22/46 allow driving of the load and ensuring of safety by using the RX-R external relay. These models make highly frequent
ON/OFF control possible without relying on the service life of the RX Series internal relay.)
b Hi-Lo-Off Control
The amount of combustion is controlled in small increments by ON/OFF control. This is used in small to medium sized combustion
furnaces.
b Proportional control
Proportional control is able to continuously control the amount of combustion and is widely adopted in combustion furnaces that require
exact control of the combustion process. This is generally used in large combustion furnaces to continuously maintain a desired amount
of combustion between minimum and maximum. However, this method requires a variety of equipment, such as control motors,
equalizing valves, etc., which makes its conguration and adjustment complicated in comparison to ON/OFF control.
Synchronous ignition is when multiple burners are ignited in sync (simultaneously) in a multi-burner setup. Because multiple burners
share safety shutoff valves, the conguration can be made simpler by reduction of the number of safety shutoff valves. However, if there
is a ame failure in one burner, then multiple burners must be shut off because the safety shutoff valve is shared.
Asynchronous ignition is when multiple burners are ignited asynchronously (at different times) in a multi-burner system. Because safety
shutoff valves are not shared, if there is a ame failure in one burner, the burners gas supply can be shut off without affecting other
burners. Also, since burners are individually ignited and extinguished, thinned-out operation and the stopping of burners when a
malfunction occurs is possible.
Ignition method
Burner Pilot
Interrupted pilot
Direct ignition
Interrupted pilot
Continuous pilot
Continuous pilot
Direct ignition
Continuous pilot
Control method
Main combustion
facility
Reference page Setup
Asynchronous
ignition
Asynchronous
ignition
Asynchronous
ignition
Asynchronous
ignition
Asynchronous
ignition
Asynchronous
ignition
Asynchronous
ignition
Hi-Lo-OFF
ON/OFF
(time proportional)
Proportional control
Proportional control
ON/OFF
(time proportional)
ON/OFF
(time proportional)
ON/OFF
(time proportional)
Small melting
holding furnace
Large melting
furnace
Heating furnace 1
Heating furnace 2
Heating furnace 3
Heating furnace 4
Heating furnace
(regenerative burner)
pages 46 and 47
pages 48 and 49
pages 50 and 51
pages 52 and 53
pages 54 and 55
pages 56 and 57
pages 58 and 59
pages 62 and 63
pages 64 and 65
pages 64 and 65
pages 66 and 67
pages 66 and 67
pages 68 and 69
pages 68 and 69
b Multiple burners
Ignition method
Pilot
Control method Reference page Setup
Interrupted pilot
Interrupted pilot
Continuous pilot
Proportional control
Proportional control
ON/OFF
No.
1
2
3
4
5
6
7
No.
1
2
3
Boiler
Deodorizing furnace
Small holding furnace
pages 40 and 41
pages 42 and 43
pages 44 and 45
page 60
page 60
pages 62 and 63
b Single burner
Application Examples
AC power source
Lamp
No. 2 ignition
Sequence chart
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
48
L
a
r
g
e
M
e
l
t
i
n
g
F
u
r
n
a
c
e
Large Melting Furnace
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
No. * ignition: Ignition of burner No. *
SSR: Solid state relay
(No.3, No.4)
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower
Burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Prepurge
Prepurge
cancellation
Prepurge
cancellation
Postpurge
Power ON
Burner
ignition Burner extinction
AC power source
Lamp
No. 2 ignition
Sequence chart
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
49
L
a
r
g
e
M
e
l
t
i
n
g
F
u
r
n
a
c
e
bThe blower, control valve and main gas valve are driven by the external control circuit. The Hi/Lo position of each control valve is input
into the zone RX-L and monitoring of the control valve opening is performed during the purge and ignition process. (Note: The CM1 and
CM2 control motors are controlled by a connected host device.)
bIf there is an ignition failure or flame failure, only the affected burner will be stopped, and it will restart by an ignition command from the
RX-R once the operation has been reset.
bWhen restarting a burner that has accidentally gone out, the CM1 and CM2 control valves must be closed when igniting and confirmation
of closure must be received.
bIf ignition failure or flame failure occurs in all of the burners
within a certain zone, operation will restart from prepurge.
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
CN7 CN7
RX-L80/90
Multiple burners: Interrupted pilot ignition - Proportional control
FD2 FD1
IG2
Fuel
Master valve
MV1
MV2
CM2
PV1
APL
GPL GPH
Blower
PV2
CM1
IG1
RX-L80
/90
RX-L80
/90
RX-R20
/40
RX-R20
/40
RX-L80
/90
Zone No. 1 Shared
interlock
Other zones
RX-R20
/40
RX-R20
/40
Master valve: Main gas valve
APL: Air pressure low switch
GPL: Gas pressure low switch
GPH: Gas pressure high switch
FD: Flame detector
IG: Ignition transformer
PV: Pilot safety shutoff valve
MV: Main safety shutoff valve
CM: Control motor
Piping train
Wiring
RX conguration
Lamp
CM 1 and 2 closed
CM1 and 2 open
Error
Reset
Start
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
bPlease refer to pages 64 and 65 for the settings table.
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
*1
A-B6
A-A7
A-A9
A-B9
FD
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
Shared
Zone No. 1
Prepurge Postpurge
Steady
combustion
Power ON
Burner
ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Start 1
Control motor (CM1)
CM1 open output (externally driven)
CM1 closed output (externally driven)
CM1 control output (externally driven)
Control motor (CM2)
CM2 open output (externally driven)
CM2 closed output (externally driven)
CM2 control output (externally driven)
Error
CM1 and 2 open
CM1 and 2 closed
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PV1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PV2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Sequence chart
AC power source
Lamp
No. 2 ignition
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
52
H
e
a
t
i
n
g
F
u
r
n
a
c
e
2
Heating Furnace 2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R44 H G
FD21
No. * ignition: Ignition of main burner No. *
Prepurge Postpurge
Steady
combustion
Power ON
Burner
ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Start 1
Error
CM1 and 2 open
CM1 and 2 closed
Control motor (CM1)
CM1 open output (externally driven)
CM1 closed output (externally driven)
CM1 control output (externally driven)
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PV1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 11 (FD11)
Flame detector No. 12 (FD12)
Control motor (CM2)
CM2 open output (externally driven)
CM2 closed output (externally driven)
CM2 control output (externally driven)
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PV2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 21 (FD21)
Flame detector No. 22 (FD22)
Shared
Zone No. 1
Sequence chart
AC power source
Lamp
No. 2 ignition
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
53
H
e
a
t
i
n
g
F
u
r
n
a
c
e
2
24 V
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
FD2 FD3 FD4
FD1
IG1 IG2 IG3 IG4
MV2
MV3
MV4
PV2
PV3
PV4
PV1
Master valve
Fuel
MV1
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD1
CN7 CN7
bThe blower and main gas valve are driven by an external control circuit.
bThe burners are started by individual RX-Ls. When the RX-L of each burner starts, they proceed to the prepurge
and then pilot ignition.
The main burner ignition for each zone is input according to the call-for-heat and the main burner is activated.
If the activation frequency of the main burner is taken into account, a circuit controlled externally is added (see fig. on the right).
bIf there is an ignition failure or flame failure, only the affected burner will be stopped, and after the operation is reset, the burner will be restarted from prepurge
by reentry of the RX-L start command.
Burner No. 1 Burner No. 2 Burner No. 3 Burner No. 4
RX-L80
/90
RX-L80
/90
Burner No. 1 Burner No. 2 Burner No. 3 Burner No. 4
RX-R20
/40
RX-L80
/90
RX-R20
/40
RX-L80
/90
RX-R20
/40
RX-L80
/90
RX-R20
/40
bPlease refer to pages 66 and 67 for the settings tables.
APL
GPL GPH
Blower
Master valve: Main gas valve
APL: Low air pressure switch
GPL: Low gas pressure switch
GPH: High gas pressure switch
FD: Flame detector
IG: Ignition transformer
PV: Pilot safety shutoff valve
MV: main safety shutoff valve
IG
PV
MV
SSR
MB control
command
(TP control)
Fig. 1
Piping train
Wiring
RX conguration
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 1 ignition
Lamp
DC power source
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
Multiple burners: Continuous pilot ignition - Time proportional control (individual ignition)
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
CN7
No. *: Ignition of main burner No. *
Burner No.*
Prepurge Postpurge
Power ON
Burner
ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (Externally driven)
Main gas valve (master valve) (externally driven)
Start 1
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PVB1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Start 2
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PVB2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Sequence chart
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
Lamp
Error
Reset
Start 2
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
54
H
e
a
t
i
n
g
F
u
r
n
a
c
e
3
Heating Furnace 3
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
CN7
No. *: Ignition of main burner No. *
Burner No.*
Prepurge Postpurge
Power ON
Burner
ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (Externally driven)
Main gas valve (master valve) (externally driven)
Start 1
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PVB1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Start 2
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PVB2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Sequence chart
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
Lamp
Error
Reset
Start 2
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
55
H
e
a
t
i
n
g
F
u
r
n
a
c
e
3
bThe blower and main gas valve are driven by an external control circuit.
bAfter the RX-L is started one of the RX-Rs starts, and operation proceeds through prepurge, pilot ignition and main ignition.
bIf there is an ignition failure or flame failure, only the affected burner will be stopped, and it will be restarted by an ignition command from the RX-R
once the operation has been reset.
bIf all of the burners within a certain zone experience ignition failure or flame failure, the operation will restart from prepurge.
bIf all of the start requests (ignition commands) end for all RX-Rs and the next call-for-heat (ignition command) is within the allowable time, then the
furnace can restart with a prepurge.
Whether or not a prepurge is implemented depends on the prepurge conditions (B-12) at the RX-L restart time and cancellation within the allotted
time. The allowable time is managed by the reignition wait time (D-8). If the allowable time is exceeded, the furnace will be restarted with a prepurge.
bA direct ignition model is incorporated because the number of times the burners start and stop increases.
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
FD2 FD1
IG1 IG2
Fuel
Master valve
MV1
MV2
Multiple burners: Continuous direct ignition - Time proportional control
CN7 CN7
RX-L80
/90
RX-L80
/90
RX-R22 RX-R22
Zone 1
Zone*
bPlease see pages 68 and 69 for the settings table.
APL
GPL GPH
Blower
Master valve: Main gas valve
APL: Air pressure low switch
GPL: Gas pressure low switch
GPH: Gas pressure high switch
FD: Flame detector
IG: Ignition transformer
MV: Main safety shutoff valve
Piping train
Wiring
RX conguration
DC power source
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
Lamp
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR11
SSR12
SSR11
SSR12 MV1
IG1
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
Prepurge
Cancel
prepurge
Postpurge
Power ON
Burner
ignition
Burner
extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Main gas valve (master valve) (externally driven)
Start 1
Error
Main burner No. 1 ignition (No. 1 ignition)
Solid state relay 11 (SSR11)
Solid state relay 12 (SSR12)
Ignition transformer No. 1 (IG1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Main burner No. 2 ignition (No. 2 ignition)
Solid state relay 21 (SSR21)
Solid state relay 22 (SSR22)
Ignition transformer No. 2 (IG2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Shared
Zone No. 1
Lamp
No. 2 ignition
AC power source AC power source
Lamp
No. 1 ignition
Sequence chart
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
56
H
e
a
t
i
n
g
F
u
r
n
a
c
e
4
Heating Furnace 4
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR11
SSR12
SSR11
SSR12 MV1
IG1
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
Prepurge
Cancel
prepurge
Postpurge
Power ON
Burner
ignition
Burner
extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Main gas valve (master valve) (externally driven)
Start 1
Error
Main burner No. 1 ignition (No. 1 ignition)
Solid state relay 11 (SSR11)
Solid state relay 12 (SSR12)
Ignition transformer No. 1 (IG1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 1 (FD1)
Main burner No. 2 ignition (No. 2 ignition)
Solid state relay 21 (SSR21)
Solid state relay 22 (SSR22)
Ignition transformer No. 2 (IG2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 2 (FD2)
Shared
Zone No. 1
Lamp
No. 2 ignition
AC power source AC power source
Lamp
No. 1 ignition
Sequence chart
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
57
H
e
a
t
i
n
g
F
u
r
n
a
c
e
4
bThe blower and main gas valve are driven by an external control circuit.
bEach pair of burners is started by the RX-L.
The pilot burners are activated once the RX-L is started, the main burner ignition for each RX-R is input according to the main request which activates
the main burner.
An externally controlled circuit is added because the burner is more frequently activated.
bWhen an ignition failure or flame failure occurs, the pair is stopped, and after it is reset, it restarts operation once the RX-L ignition command is given.
bThe air supply and exhaust switchover valve are controlled by an external circuit, but the necessary interlock information is monitored by the
corresponding RX-L.
Fuel
Master valve
FD11
MV1
PV1 IG1
IG2
PV2
Switchover valve 21
Switchover valve 22
Switchover valve 11
Switchover valve 12
MV2
FD12
FD21
FD22
Multiple burners: Continuous pilot ignition - Time proportional control
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
FD11
SSR1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46
IG1
PV1
SSR1 MV1
CN7 CN7
RX-L80
/90
Piping train
Wiring
RX conguration
RX-L80
/90
RX-R46 RX-R40 RX-R46 RX-R40
bPlease refer to pages 68 and 69 for the settings table.
APL
GPL GPH
Blower
Master valve: Main gas valve
APL: Low air pressure switch
GPL: Low gas pressure switch
GPH: High gas pressure switch
FD11/21: Pilot burner flame detector
FD12/22: Main burner flame detector
IG: Ignition transformer
PV: Pilot safety shutoff valve
MV: Main safety shutoff valve
Lamp
No. 1 ignition
Lamp
24 V
DC power source
Switchover valve monitor
Error
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
H G
AC power source
Lamp
Piping train
A-A8
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD21
SSR2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46 H G
IG2
PV2
SSR2 MV2
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
Prepurge Postpurge Steady combustion
Burner ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Start 1
Error
Switchover valve monitor
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PV1)
Solid state relay 1 (SSR1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 11 (FD11)
Flame detector No. 12 (FD12)
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PV2)
Solid state relay 2 (SSR2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 21 (FD21)
Flame detector No. 22 (FD22)
Shared
Zone No. 1
Sequence chart
Lamp
AC power source
Lamp
No. 2 ignition
Lamp
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
58
H
e
a
t
i
n
g
F
u
r
n
a
c
e
(
R
e
g
e
n
e
r
a
t
i
v
e
B
u
r
n
e
r
)
Heating Furnace (Regenerative Burner)
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD21
SSR2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46 H G
IG2
PV2
SSR2 MV2
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
Prepurge Postpurge Steady combustion
Burner ignition Burner extinction
Start
Error
Gas pressure high (GPH)
Gas pressure low (GPL)
Air pressure low (APL)
Blower sync
Blower (externally driven)
Start 1
Error
Switchover valve monitor
Main burner No. 1 ignition (No. 1 ignition)
Ignition transformer No. 1 (IG1)
Pilot shutoff valve No. 1 (PV1)
Solid state relay 1 (SSR1)
Main shutoff valve No. 1 (MV1)
Flame detector No. 11 (FD11)
Flame detector No. 12 (FD12)
Main burner No. 2 ignition (No. 2 ignition)
Ignition transformer No. 2 (IG2)
Pilot shutoff valve No. 2 (PV2)
Solid state relay 2 (SSR2)
Main shutoff valve No. 2 (MV2)
Flame detector No. 21 (FD21)
Flame detector No. 22 (FD22)
Shared
Zone No. 1
Sequence chart
Lamp
AC power source
Lamp
No. 2 ignition
Lamp
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
59
H
e
a
t
i
n
g
F
u
r
n
a
c
e
(
R
e
g
e
n
e
r
a
t
i
v
e
B
u
r
n
e
r
)
bSingle burner 1: interrupted pilot Proportional control (Boiler)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Single zone
Enabled
Linked 1
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Enabled
Enabled
Internal
Internal
1
IN3
IN4
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
0
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
bSingle burner 2: Interrupted pilot Proportional control (Deodorizing furnace)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
RX-L type
Air switch check use
Startup type:
760 C mode use
Air switch check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Damper output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
bRX-L bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91s
RX-L linked
RX-L linked
0.0
20.0
0.0
0.0
1
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-B8
A-B9
A-BA
A-A0
A-A9
TB1
TB2
B-A0
BSV
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90 H G
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG
PV
MV
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD
*1
A-B6
A-A7
A-A9
A-B9
FD
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-B8
A-B9
A-BA
A-A0
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-A1
A-A2
A-A3
H G
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG
PV
MV
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD
*1
A-B6
A-A7
A-A9
A-B9
FD
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
MV open
Lamp
CM control output
CM closed
CM open
Blower
AC power source
DC power source
Proportional control
Other error
Steam pressure error
Low water level shutoff
Air pressure low
Gas pressure low
Gas pressure high
CM closed
CM open
Chimney damper open
Seismoscope
Reset
Start + Call for heat
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp Lamp
CM control output
CM closed output
CM open output
Blower
Master valve
AC power source
DC power source
Proportional control
Air pressure low
Gas pressure low
Gas pressure high
CM closed
CM open
Main valve open
Error
Reset
Start
Single zone
Enabled
Linked 1
Disabled
When RX-L start switch OFF
Start switch input
Enabled
Enabled
Enabled
Enabled
Internal
Internal
1
IN3
IN4
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
0
Settings table
Wiring
Wiring
Settings table
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
60
S
e
t
t
i
n
g
s
T
a
b
l
e
s
Settings Tables
Memo
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
61
S
e
t
t
i
n
g
s
T
a
b
l
e
s
bMulti-burner 1: Asynchronous ignition, Interrupted pilot Hi-Lo-Off Control (Small melting holding furnace)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Single zone
Enabled
Individual
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Enabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
0
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
Settings table
bSingle burner 3: Continuous pilot ON/OFF control (Small holding furnace)
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90 H G
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Single zone
Enabled
Linked 2
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Enabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
0
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual monitoring
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG
PV
MV
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R44 H G
FD11
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90 H G
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
Lo-MV1
Hi-MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD1
Wiring
Settings table
Wiring
AC power source
Lamp
M ignition
Lamp
Blower
AC power source
DC power source
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
Hi 1 ignition
Lo 1 ignition
Lamp
Blower
AC power source
DC power source
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD12
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
M ignition: Main burner ignition
*1
A-B6
A-A7
A-A9
A-B9
FD
IG2
Lo-MV2
Hi-MV2
H G
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40
FD2
*2. For RX-R20
*1. For RX-R40
AC power source
Hi 2 ignition
Lo 2 ignition
Lo * ignition: Low fire ignition of burner No. *
Hi * ignition: High fire ignition of burner No. *
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
62
S
e
t
t
i
n
g
s
T
a
b
l
e
s
Settings Tables
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD12
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
M ignition: Main burner ignition
*1
A-B6
A-A7
A-A9
A-B9
FD
IG2
Lo-MV2
Hi-MV2
H G
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40
FD2
*2. For RX-R20
*1. For RX-R40
AC power source
Hi 2 ignition
Lo 2 ignition
Lo * ignition: Low fire ignition of burner No. *
Hi * ignition: High fire ignition of burner No. *
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
63
S
e
t
t
i
n
g
s
T
a
b
l
e
s
bMulti-burner 3: Asynchronous ignition, Interrupted pilot Proportional control (Heating furnace 1)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Low fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Shared
Enabled
Individual
Disabled
Blower sync OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Input
Internal
1
None
None
Lockout
Enabled
Disab
1
None
Disabled
Lockout
0
bRX-L
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Low fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disabled
Linked 2
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
IN2
IN3
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
1
bRX-L
bMulti-burner 2: Asynchronous ignition, Direct ignition ON/OFF (Time proportional) control (Large melting furnace)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Low fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Single zone
Enabled
Individual
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Enabled
Disabled
Internal
Internal
1
None
None
Lockout
Cancellation within the allotted time
Disabled
1
Lockout
Disabled
Lockout
0
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90 H G
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR11
SSR12
SSR11
SSR12 MV1
IG1
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
CN7 CN7
RX-L80/90
Settings table
Wiring
Settings table
Wiring
AC power source
Lamp
No. 1 ignition
Lamp
Blower
AC power source
DC power source
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
Lamp
CM 1 and 2 closed
CM 1 and 2 open
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
No. * ignition: Ignition of burner No. *
SSR: Solid state relay
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
*1
A-B6
A-A7
A-A9
A-B9
FD
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
No. * ignition: Ignition of main burner No. *
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 1 ignition
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
64
S
e
t
t
i
n
g
s
T
a
b
l
e
s
Settings Tables
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Interrupted pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
No. * ignition: Ignition of burner No. *
SSR: Solid state relay
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
*1
A-B6
A-A7
A-A9
A-B9
FD
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
No. * ignition: Ignition of main burner No. *
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 1 ignition
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
65
S
e
t
t
i
n
g
s
T
a
b
l
e
s
bMulti-burner 5: Asynchronous ignition, Continuous pilot ON/OFF (Time proportional) control (Heating Furnace 3)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Shared
Enabled
Individual
Disabled
Blower sync OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Input
Internal
2
None
None
Lockout
Enabled
Disabled
2
None
Disabled
Lockout
0
bRX-L
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Single zone
Disabled
Linked 2
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
1
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
9 1 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
bMulti-burner 4: Asynchronous ignition, Continuous pilot Proportional control (Heating furnace 2)
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A6
A-A7
A-A8
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R44 H G
FD11
CN7 CN7
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge us
(Not used)
RX-L communication error handling
RX-L device address
Shared
Enabled
Individual
Disabled
Blower sync OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Input
Internal
1
None
None
Lockout
Enabled
Disabled
1
None
Disabled
Lockout
0
bRX-L
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disabled
Linked 2
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
IN2
IN3
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
1
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
9 1 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
24 V
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG1
PV1
MV1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD1
CN7 CN7
AC power source
Lamp
No. 1 ignition
Lamp
CM 1 and 2 closed
CM 1 and 2 open
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 1 ignition
Lamp
DC power source
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
Settings table
Wiring
Settings table
Wiring
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disable
Linked 2
Disable
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
Lockout
1
Disabled
Lockout
2
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R44 H G
FD21
No. *: Ignition of main burner No. *
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
9 1 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
3
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.5 0.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
4
bRX-R
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
CN7
No. *: Ignition of main burner No. *
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
Lamp
Error
Reset
Start 2
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
66
S
e
t
t
i
n
g
s
T
a
b
l
e
s
Settings Tables
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disable
Linked 2
Disable
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
Lockout
1
Disabled
Lockout
2
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Continuous pilot
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R44 H G
FD21
No. *: Ignition of main burner No. *
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
9 1 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
3
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.5 0.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
4
bRX-R
A-B0
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
*1
A-B6
A-A7
A-A9
A-B9
FD
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B1
A-B2
IG2
PV2
MV2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R20/40 H G
FD2
CN7
No. *: Ignition of main burner No. *
AC power source
Lamp
No. 2 ignition
*2. For RX-R20
*1. For RX-R40
AC power source
Lamp
No. 2 ignition
Lamp
Error
Reset
Start 2
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
67
S
e
t
t
i
n
g
s
T
a
b
l
e
s
bMulti-burner 6: Asynchronous ignition, Direct ignition ON/OFF (Time proportional) control (Heating furnace 4)
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
CN7 CN7
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Shared
Enabled
Individual
Disabled
Blower sync OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Input
Internal
1
None
None
Lockout
Enabled
Disabled
1
None
Disabled
Lockout
0
bRX-L
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disabled
Individual
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
1
bRX-L
bMulti-burner 7: Asynchronous ignition, Continuous pilot ON/OFF (Time proportional) control (Heating furnace/ regenerative burner)
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Shared
Enabled
Individual
Disabled
Blower sync OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Input
Internal
1
None
None
Lockout
Enabled
Disabled
1
None
Disabled
Lockout
0
bRX-L
A-1
A-2
A-3
A-4
A-5
B-1
B-2
B-3
B-4
B-5
B-6
B-7
B-8
B-9
B-10
B-11
B-12
B-13
B-14
B-15
B-16
B-17
B-18
B-19
Shared/zone
Air switch check use
Startup type:
760 C mode use
Air switch start check result clear
RX-L start method
Prepurge use
Relay output
Blower output
Control motor output
Blower sync signal source
Purge count start signal source
Number of locked-out RX-Ls
High fire position input
Light fire position input
Process timeout handling
Prepurge after RX-R restart
Low fire stop
RX-L connectable units
Postpurge for residual flame
RX-R prepurge use
(Not used)
RX-L communication error handling
RX-L device address
Zone
Disabled
Linked 2
Disabled
When RX-L start switch OFF
Start switch input
Prepurge and postpurge enabled
Disabled
Disabled
Disabled
Internal
Internal
1
None
None
Lockout
Enabled
Disabled
1
Lockout
Disabled
Lockout
1
bRX-L
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
bRX-R
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
TB1
TB2
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
A-B8
A-B0
24 V
A-B1
A-B2
A-B3
A-B4
A-B5
A-B6
A-B7
A-A9
A-A8
A-A7
A-A6
TB1
TB2
B-A0
B-B0
B-A3
B-B3
B-A7
B-B7
B-A9
B-B9
B-AA
B-BA
39
1
26
38
RX-L80/90
FD11
SSR1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46 H G
IG1
PV1
SSR1 MV1
CN7 CN7
Settings table
Wiring
Settings table
Wiring
Lamp
DC power source
Error
Reset
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start
AC power source
Lamp
No. 1 ignition
Lamp
DC power source
Switchover valve monitor
Error
Start 1
Lamp
DC power source
Blower sync
Air pressure low
Gas pressure low
Gas pressure high
Error
Reset
Start B-A0
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR11
SSR12
SSR11
SSR12 MV1
IG1
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
RX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
3
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
4
bRX-R
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD21
SSR2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46 H G
IG2
PV2
SSR2 MV2
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
No. * ignition: Ignition
of main burner No. *
SSR: Solid state relay
AC power source
Lamp
No. 2 ignition
AC power source
Lamp
No. 1 ignition
Lamp
AC power source
Lamp
No. 2 ignition
Lamp
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
68
S
e
t
t
i
n
g
s
T
a
b
l
e
s
Settings Tables
FD1
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR11
SSR12
SSR11
SSR12 MV1
IG1
FD2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-A9
B-AA
TB1
TB2
A-A0
A-A2
A-B0
A-B2
A-A4
A-B4
A-B6
A-A7
RX-R22 H G
SSR21
SSR22
SSR21
SSR22 MV2
IG2
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
1
RX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Direct
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
2
bRX-R
No. * ignition: Ignition of main burner No. *
SSR: Solid state relay
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
2
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Individual
Disabled
91 s
RX-L linked
RX-L linked
0.0
0.0
0.0
0.0
3
bRX-R
1-1
1-2
1-3
1-4
2-1
2-2
2-3
2-4
2-5
2-6
4-1
Switch combustion mode
RX-R prepurge use
Pilot ignition time
(Not used)
Start conditions
Reset conditions
Restore error wait time
Startup delay time
Control air valve OFF delay time
Air OFF confirmation timeout time
RX-R device address
Flame relay
Disabled
4.50.5 s
RX-L linked
RX-L linked
0.0
0.0
0.0
20.0
4
bRX-R
FD12
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
FD21
SSR2
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-A2
A-B1
A-B2
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R46 H G
IG2
PV2
SSR2 MV2
FD22
B-B0
B-B1
B-B2
B-B3
B-B4
B-B5
B-B6
B-B7
B-B8
B-B9
B-BA
B-A0
B-AA
TB1
TB2
A-A0
A-B0
A-B2
A-B1
A-A4
A-B4
A-B6
A-A7
A-A9
A-B9
RX-R40
No. * ignition: Ignition
of main burner No. *
SSR: Solid state relay
AC power source
Lamp
No. 2 ignition
AC power source
Lamp
No. 1 ignition
Lamp
AC power source
Lamp
No. 2 ignition
Lamp
A
p
p
l
i
c
a
t
i
o
n
E
x
a
m
p
l
e
s
69
S
e
t
t
i
n
g
s
T
a
b
l
e
s
CP-PC-1420E
Based on its core principle of human-centered automation,
Azbil Corporation offers combustion equipment
that provides safety and peace of mind.
Flame Safeguard System Selection Guide
Please read the "Terms and Conditions" from the following URL before
ordering or use:
http://www.azbil.com/products/bi/order.html
1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan
URL: http://www.azbil.com
1st Edition : Issued in Oct. 2004-PP
4th Edition : Issued in Sep. 2012-ED CP-PC-1420E
[Notice] Specifications are subject to change without notice.
No part of this publication may be reproduced or duplicated
without the prior written permission of Azbil Corporation.
Yamatake Corporation changed its name to Azbil Corporation on April 1, 2012.
Other product names, model numbers and company names may be trademarks of the respective company.
(10)
FSG, SDC and AUD are registered trademarks of Azbil Corporation in Japan.
F
l
a
m
e
S
a
f
e
g
u
a
r
d
S
y
s
t
e
m
S
e
l
e
c
t
i
o
n
G
u
i
d
e