Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CONTENTS
Introduction to Glands............................................................................. 12:2 I.P Ratings for Cable Glands....................................................................12:4 A1/A2 Brass Gland with Outer Seal........................................................ 12:6 CX Brass Gland with Outer Seal..............................................................12:7 CXT Brass Gland with Outer Seal .......................................................... 12:8 Ultech Nylon Gland................................................................................... 12:9 LSF Standard Cable Gand for Non Armoured Cable............................. 12:11 Technical Data........................................................................................... 12:12 Index EMC Nickel Plated Gland for Braid Screened Cable................... 12:13 CW Brass Gland with Outer Seal............................................................. 12:14 BW Brass Gland........................................................................................ 12:16 E1W Brass Gland with Inner & Outer Seal.............................................. 12:17 Low Smoke & Fume Gland Kits............................................................... 12:18 BW Brass Gland LSF............................................................................. 12:19 CW Brass Gland with Outer LSF Seal..................................................... 12:20 Selecting Glands for Hazardous Areas................................................... 12:21 A2F Flameproof Gland with Outer Seal.................................................. 12:22 E1WF Flameproof Gland with Inner & Outer Seal.................................. 12:23 E1XF Flameproof Gland with Inner & Outer Seal................................... 12:24 Excelplus Deluge Proof Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................... 12:25 Universal Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................................................. 12:26 E2WF (RTLF) Flameproof Gland with Inner & Outer Seal..................... 12:27 Universal Explosion Proof Barrier Glands............................................. 12:28 Brass Earth Tags...................................................................................... 12:29 High Performance Sealing Washers....................................................... 12:30 Glavanised Serrated Washers................................................................. 12:30 Steel, Brass & Aluminium Locknuts....................................................... 12:31 PCP/PVC Shrouds........................................................................ ............ 12:32 Lugs........................................................................................................... 12:33 Telcleats - Black Polythene & Grey LSF................................................. 12:36 PUJ Straight Cable Joints..................................................................... 12:37 Claw & Two Bolts Cleats - Aluminium Alloy........................................... 12:38 Cable Tiles & Warning Tapes...................................................... .............12:39 11kV Indoor Termination Kits...................................................................12:40 3M Inline (Straight) Barrier Boot - MB63................................................. 12:42 3M Pre-Moulded Right Angle Barrier Boot..............................................12:43 Heat Shrinkable Tubing............................................................................ 12:44
ACCESSORIES
Glands
Cable glands are designed to provide some or all of the following functions in a cabling system: Mechanical connection: Locate and anchor cable. Earth continuity: Armour termination. Ingress Protection: Protect against dust and liquids. Hazardous area: Flameproof protection.
The design of cable glands are covered by BS6121, which covers size, finish, materials, performance, etc. The gland designs are basically a combination of compatibility with cable and installation requirements. GLAND TYPES There are several distinct gland types covered in BS6121 Part 1; A Type B Type C Type D1 Type E1 Type D2 Type E2 Type Suffixes are used to identify the type of armour on a cable: W = single wire armour X = wire braid armour Y = aluminium wire armour Z = steel tape armoured Hence, CW would be a single wire armour, whereas CX would be for a braid armour. The only difference is in the armour lock which caters for the physical size of the armour.
12
12:2
ACCESSORIES
Gland Type A1/A2 BW CW Application/Use Indoor/outdoor brass gland for use with unarmoured cable. Indoor, low-cost, two-part brass gland for use with single wire armoured cable. Indoor/outdoor brass glands for use with single wire armoured cable. Provides seal on outer sheath of cable and separate armour locking ring. NB: Aluminium gland available for aluminium wire armoured cable. CX Indoor/outdoor brass gland for use with braid armoured cables. Provides seal on outer sheath of cable and separate armour locking ring. Indoor/outdoor brass gland for use with single wire armour cable. Provides seal on inner and outer sheaths of cable, and has separate armour locking ring.
E1W
LSF Glands BW Indoor, low cost, two-part brass gland for use with LSF single wire armoured cables. Indoor/outdoor brass gland for use with LSF single wire armoured cables. Provides LSF seal onto outer sheath of cable and separate armour locking ring.
CW
Glands for Hazardous Areas A2F Indoor/outdoor brass gland for use with unarmoured cables. For use with flameproof or increased safety equipment (E.Exd or E.Exe) Indoor/outdoor brass gland for use with single wire armoured cable. Provides seal on inner and outer sheaths of cable, and has separate locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe) Indoor/outdoor brass gland for use with braid armoured cable. Provides seal on inner and outer sheaths of cable, and has separate armour locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe). Indoor/outdoor brass gland for use with single wire armoured and lead sheathed cables (eg. EEMUA types, BS5308 PT1/Type 3). Provides seal onto outer sheath of cable. Inner seal grips and provides earth continuity to lead sheath. Design has separate armour locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe). Indoor/outdoor brass barrier gland for use with a braid armoured cable. Provides seal on outer sheath of cable, and solid setting compound squeezed into the interstices of cable when installed to prevent escape of gases through centre of cable. For use with explosion proof equipment.
E1WF
E1XF
E2WF
BARR-X
12
12:3
ACCESSORIES
12
12:4
ACCESSORIES
12
12:5
ACCESSORIES
To BS6121: Part 1. Suitable for unarmoured, plastic or rubber sheathed cables. Suitable for most indoor and outdoor applications. Seal rated to IP66
12
Glands are supplied in kit form, complete with locknuts and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit
12:6
ACCESSORIES
BS6121: Part 1 Suitable for wire braid armoured, plastic or rubber sheathed cables. Outer seal grips sheath of cable. Weatherproof and water proof. Seal rated to IP66. Design has separate armour locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface
20SS 20S 20 25 32 40
Glands are supplied in kit form, complete with locknuts, earthtags and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit
12
12:7
ACCESSORIES
20S 20 25 32 40
Glands are supplied in kit form, complete with locknuts, earthtags and shrouds. Up to size 32:- 2 per kit Size 40 and above:- 1 per kit
12
12:8
ACCESSORIES
Suitable for unarmoured, plastic or rubber sheathed cables. Polyamide 6 nylon gland with neoprene seal. Compact skin-top design Quick and easy assembly Halogen free and UL94-V2 flammability rated. Seal rated IP68 at 5 bar. Temperature range: -30C to +80C Grey RAL 7001 colour ISOMETRIC thread. 10mm thread length for gland sizes 16-25, 18mm for gland size 32. Ultech is a registered trade name of Elkay International
16 20S 20 25 32
Glands are supplied in kit form, complete with nylon washer and locknut. All sizes: 2 per kit. NB: Mini-size polyamide 6.6 standard nylon gland is also available for IP66 rated nitrile seal for small diameter cable. Details as follows:-
12
12:9
ACCESSORIES
Mini - Gland
Halogen free and UL94-V2 flammability rated. -20C to +90C temperature range. Grey RAL 7001 colour. ISOMETRIC thread. 8mm thread length.
Glands are supplied in kit form with nylon washer and locknut 2 per kit.
12
12:10
ACCESSORIES
Suitable for unarmoured plastic or rubber sheathed cables. Polyamide 6.6 nylon gland with nitrile rubber seal. Quick and easy assembly. Halogen free and UL94-V2 flammability rated. Seal rated at IP66. -20C to +90C temperature range. Black RAL 9005 colour. ISO METRIC thread. 11mm thread length LSF glands meet following standards:- BS6853 App B5.1, BS7878, BS2782 M141, IEC 60754-1, IEC 60754-2, BS6425, NES713/Iss 3.
12
Glands are supplied in kit form, complete with washer and locknut.
12:11
ACCESSORIES
TECHNICAL DATA
APPLICABLE TO NYLON GLANDS - CHEMICAL RESISTANCE Listed below is the general chemical resistance information for the materials used to manufacture the majority of products in this catalogue. S = Suitable L = Limited suitability U = Unsuitable
Chemical Agent ASTM Oil No. 2 Acetaldehyde Acetic acid (10%) Acetic acid (glacial) Acetone Ammonium Hydroxide (35%) Benzene Benzyl Alcohol Bromine (liquid) Butyl Alcohol Butyl Acetate Butylamine Carbon Tetrachloride Chlorine Gas Citric acid (10%) Cresols Cyclohexane Diesel oil Diethyl ether Ethanol Ethylamine Ethylene glycol Formaldehyde Hexane Hydrochloric acid (10%) Hydrochloric acid (conc) Hydrogen peroxide (35%) Nylon S L L L S S S L U S S S S U S U S S S S L S S S U U L Chemical Agent Hydrogen sulphide (gas) Iso-octane Iso-propanol Lubricating oil Methanol Nitric acid (10%) Nitric acid (conc) Ozone (gas) Paraffin oil Petrol Phenol Silicone oils Sodium hydroxide (60%) Sodium hypochlorite (bleach) Styrene Sulphur dioxide (gas) Sulphuric acid (10%) Sulphuric acid (70%) Toluene Transformer oil Trichloroethylene Tricresyl phosphate (SKYDROL) Turps White spirit Xylene Zinc chloride Nylon S S S S L U U L S S U S S L S U U U S S L S S S S U
12
12:12
ACCESSORIES
Index EMC Nickel Plated Brass Gland for Braid Screened Cable
1 2 1 4 1 3 1 5 1 6 1
FEATURES. 1. Compression Nut 2. Santoprene Seal 3. Endless Spring 4. Tapered Ring 5. O Ring 6. Gland Body
For use with braid screened cable to connect screen to the enclosure system. Two tapered rings applying force onto an endless spring washer ensure positive and intimate contact for efficient screening. Screen can continue into enclosure. Suitable for systems conforming to EN50082. Nickel plated brass gland body with santoprene rubber seal. Seal rated IP68 at 1 bar. -40 to +135C temperature range. ISO METRIC thread with exception of gland for 4-6mm diameter cable which has P.G.7 thread to DIN40430.
Anixter Part No. Gland Manf. E1AH-EMC-7 E1AH-EMC-16 E1AH-EMC-20 E1AH-EMC-25SS E1AH-EMC-25S E1AH-EMC-25 E1AH-EMC-32S E1AH-EMC-32 Elkay Elkay Elkay Elkay Elkay Elkay Elkay Elkay Gland No. 261-1000 260-1000 260-1250 260-1400 260-1450 260-1500 260-1600 260-1650 260-1700 Gland Cable Dimensions Accommodated (mm) Over Screen Min. 1.5 3.0 4.0 6.5 8.0 8.0 12.5 15.0 15.0 Max. 4.0 7.0 8.5 10.0 12.0 12.0 17.5 21.0 21.0 Cable Diameter Min. 4.0 6.0 8.0 10.0 11.0 14.0 17.0 19.0 22.0 Max. 6.0 8.0 10.5 11.5 14.0 16.6 20.0 23.0 27.0
Manf. Part Size PG7 M16 M20 M25 M25 M25 M25 M32 M32
E1AH-EMC-25SSS Elkay
12
Glands are supplied in kit form complete with locknut. All sizes: 2 per kit.
12:13
ACCESSORIES
BS6121: Part 1 Suitable for wire armoured, plastic or rubber sheathed cables. Outer seal grips sheath of cable. Weatherproof and water proof. Seal rated to IP66. Design has separate armour locking ring (Pirelli glands only). Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface
Brass glands are provided with steel locknuts and aluminium glands are provided with aluminium locknuts. For more corrosive environments brass locknuts may be supplied. Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli CMP Up to size 25: - 2 per kit Size 32 and above:- 1 per kit Up to size 32:- 2 per kit Size 40 and above:- 1 per kit
12
12:14
ACCESSORIES
CABLE & GLAND DETAILS
Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 8.6 8.6 11.6 11.6 13.9 13.9 19.9 19.9 26.2 26.2 32.1 32.1 38.1 38.1 44.0 44.0 50.0 55.9 55.9 67.9 67.9 19.9 26.2 32.1 38.1 44.0 8.0 8.0 8.0 13.2 13.4 15.8
E1AG-CW-20SSC E1AG-CW-20SS E1AG-CW-20SC E1AG-CW-20S E1AG-CW-20C E1AG-CW-20 E1AG-CW-25C E1AG-CW-25 E1AG-CW-32C E1AG-CW-32 E1AG-CW-40C E1AG-CW-40 E1AG-CW-50SC E1AG-CW-50S E1AG-CW-50C E1AG-CW-50 E1AG-CW-63S E1AG-CW-63C E1AG-CW-63 E1AG-CW-75C E1AG-CW-75 E1DN-CW-25 E1DN-CW-32 E1DN-CW-40 E1DN-CW-50SC E1DN-CW-50
Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP CMP Pirelli CMP Pirelli CMP Pirelli Pirelli Pirelli CMP Pirelli
11.4 15.9 12.9 20.8 15.0 20.9 17.0 27.2 20.3 27.4 23.5 33.5 26.0 33.9 29.0 39.9 31.0 40.4 38.0 46.2 36.5 46.7 39.5 52.6 43.0 53.1 48.9 59.4 51.3 65.3 58.0 65.9 62.5 78.0 64.9 78.5 17.0 27.2 23.5 33.5 29.0 39.9 36.5 46.7 39.5 52.6
NB Pirelli glands have separate armour locking rings. CMP glands have integral knurled armour lock. * Also known as 20/16 (CMP only),
12
12:15
ACCESSORIES
BW Brass Gland
BS6121: Part 1 Suitable for single wire armoured, plastic or rubber sheathed cables. For use in dry, indoor situations. Low-cost two-part design. IP54 Shroud may be used for additional ingress protection
E1AJ-BW-20SC E1AJ-BW-20S E1AJ-BW-20C E1AJ-BW-20 E1AJ-BW-25C E1AJ-BW-25 E1AJ-BW-32C E1AJ-BW-32 E1AJ-BW-40C E1AJ-BW-40 E1AJ-BW-50S E1AJ-BW-50C E1AJ-BW-50 E1AJ-BW-63C E1AJ-BW-63 E1AJ-BW-75C E1AJ-BW-75
Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP CMP Pirelli CMP Pirelli CMP Pirelli CMP
12
Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kit CMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kit
12:16
ACCESSORIES
E1BA-E1W-20S E1BA-E1W-20SC E1BA-E1W-20 E1BA-E1W-20C E1BA-E1W-25 E1BA-E1W-25C E1BA-E1W-32 E1BA-E1W-32C E1BA-E1W-40 E1BA-E1W-40C E1BA-E1W-50S E1BA-E1W-50SC E1BA-E1W-50 E1BA-E1W-50C E1BA-E1W-63 E1BA-E1W-63C E1BA-E1W-75S
Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli
11.7 13.9 12.9 20.8 13.0 19.9 17.0 27.2 11.1 19.9 20.3 27.4 20.0 26.2 23.5 33.5 17.0 26.2 26.0 33.9 26.3 32.1 29.0 39.9 22.0 32.1 31.0 40.4 32.2 38.1 38.0 46.2 29.5 38.1 36.5 46.7 38.2 44.0 39.5 52.6 35.6 44.0 43.0 53.1 50.1 55.9 51.3 65.3 47.2 55.9 58.0 65.9 56.0 61.9 62.0 71.6
Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kit CMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kit NB Pirelli glands have separate armour locking rings. CMP glands have integral knurled armour lock.
12
12:17
ACCESSORIES
NOTE: The materials utilised in these kits are noted for the absence of smoke generating constituents, particularly halogens (flourine, bromine and chlorine) thus avoiding the hazards of highly irritant and toxic fumes emitted by standard materials such as PCP and PVC when exposed to flame.
12
12:18
ACCESSORIES
To BS6121: Part 1. Suitable for single wire armoured, plastic or rubber sheathed cables. For use in dry, indoor situations. Low cost two-part design. IP54. LSF shroud may be used for additional ingress protection.
Glands are supplied in kit form, complete with locknuts and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit
20S 20 25 32 40 50 63 75
12
12:19
ACCESSORIES
To BS6121: Part 1. Suitable for single wire armoured, plastic or rubber sheathed cables. Outer LSF seal grips sheath of cable. Weatherproof and waterproof. Seal rated to IP66 Design has separate armour locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.
Glands are supplied in kit form, complete with locknuts and LSF shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit
E1AG-CW-20SSLSF E1AG-CW-20SLSF E1AG-CW-20LSF E1AG-CW-25LSF E1AG-CW-32LSF E1AG-CW-40LSF E1AG-CW-50SLSF E1AG-CW-50LSF E1AG-CW-63LSF E1AG-CW-75LSF
Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli
13.9 12.9 20.8 19.9 17.0 27.2 26.2 23.5 33.5 32.1 29.0 39.9 38.1 38.0 46.2 44.0 39.5 52.6 55.9 51.3 65.3 67.9 62.5 78.0
12
12:20
ACCESSORIES
12
12:21
ACCESSORIES
Max
8.0 8.5 11.5 11.9 13.5 14.3 16.5 19.5 20.2 25.5 26.5 32.0 32.5 37.0 43.0 44.4 50.0 56.3
12
12:22
ACCESSORIES
Suitable for single wire armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment. Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications. Pirelli glands are supplied in kit form completPirellie with locknuts, earthtags and shrouds. Up to size 25: - 2 per kit Size 32 and above:- 1 per kit
20SS 20S 20 25 32 40 50 63
26.55 32.42 29.0 39.9 38.39 44.33 39.5 52.6 50.27 56.24 51.3 65.3
12
12:23
ACCESSORIES
Suitable for wire braid armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications. Pirelli glands are supplied in kit form complete with locknuts, earthtags and shrouds. Up to size 25: - 2 per kit Size 32 and above:- 1 per kit
Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli
11.79 14.15 12.9 20.8 20.12 17.0 27.2 26.55 23.5 33.5
12
26.55 32.42 29.0 39.9 32.42 38.39 38.0 46.2 38.39 44.33 39.5 52.6 44.33 50.27 50.0 58.9
12:24
ACCESSORIES
Excelplus Deluge Proof Flameproof & Increased Safety Gland with Inner & Outer Seals
Suitable for wire braid and single wire armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof, waterproof and deluge proof. Inner and outer seal rated to IP67. Design has separate armour locking ring and additional locking ring to ensure integrity of armour lock under vibrating conditions. Gland rated to IP67 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Dual certified. Complies with group II C hazardous atmospheres EN50014, EN50018 and EN50019 (BS5501 Part 1, Part 5 and Part 6). BASEEFA Approved. Zone 1 and Zone 2 applications. Supplied as gland only.
20S 20 25 32 40 50 63 75
11.5 21.0 18.5 27.5 21.0 34.0 31.0 41.5 36.0 52.5 50.0 65.5 59.0 78.0
12
12:25
ACCESSORIES
Universal Flameproof & Increased Safety Gland with Inner & Outer Seals
Suitable for wire braid, single wire, steel tape and strip armoured plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Complies with group II C hazardous atmospheres EN50014, EN50018 and EN50019 (BS5501 Part 1, Part 5 and Part 6). BASEEFA Approved. Zone 1 and Zone 2 applications. Incorporates external boot seal which offers protection against moisture ingress to the armour. Glands are supplied in kit form complete with locknut, earthtag, shroud, nylon washer and serrated washers. All sizes: 1 per kit
20S 20 25 32 40 50 63 75
12
12:26
ACCESSORIES
Suitable for SWA, plastic or rubber oversheathed, lead inner sheath cables. Outer seal grips sheath of cable. Inner seal grips and provides earth continuity to lead sheath. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. RTLF for use with flameproof equipment or increased safety equipment. Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications.
12
12:27
ACCESSORIES
For plastic or rubber insulated cables with wire braid, single wire, steel tape or strip armour, having extruded or taped bedding. Solid setting compound is squeezed into the interstices of the cable when gland is installed. Compound forms a barrier around individual cores so preventing escape of gases through centre of cable. Sealing arrangements are rated to IP66. Weatherproof and waterproof. For use with explosion proof equipment in Zone 1 hazardous areas. Complies with group II C qualifies the gland for use under the most onerous conditions. BASEEFA Approved. Approved to EN50014 and EN50018 (BS5501 Part 1 and Part 5)
20S 20 25 32 40 50
12
12:28
ACCESSORIES
Ensure earth continuity is maintained between the gland and the equipment. Aluminium earth tags should be used with aluminium glands. NOTE: Earth bond connections are specified in IEE wiring regulations and relevant Codes of Practice.
TAG DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Bolt Hole Diameter (mm)
20 25 32 40 50 63 75
12
12:29
ACCESSORIES
WASHER DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Washer Material
SEALING WASHER
E1DS-20R E1DS-25R E1DS-32R E1DS-40R E1DS-50R E1DS-63R E1DS-75R E1DT-20 E1DT-25 E1DT-32 E1DT-40 E1DT-50 E1DT-63 E1DT-75
20 25 32 40 50 63 75 20 25 32 40 50 63 75
NYLON NYLON NYLON NYLON NYLON NYLON NYLON FIBRE FIBRE FIBRE FIIBRE FIBRE FIBRE FIBRE
WASHER DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm)
12
20 25 32 40 50
12:30
ACCESSORIES
Used to secure gland body to the equipment where entry hole is not tapped. Brass backnuts recommended for most corrosive environments. Aluminium backnuts should be used with aluminium glands. Steel backnuts are primarily for dry, low humidity environments.
LOCKNUT DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Locknut Material
20 25 32 40 50 63 75
12
12:31
ACCESSORIES
PC P/PVC Shrouds
For fitting over cable glands where additional protection against onerous weather conditions and corrosion is required. Provide an effective seal onto both gland and cable oversheath. PCP shrouds are particularly recommended for outdoor and the most hostile conditions and are not affected by ultravoilet rays contained in sunlight. PVC shrouds for use in dry indoor and most outdoor situations.
SHROUD DETAILS
Anixter Part No. To Suit Gland Size (mm) Shroud Material
12
E1BF-20SH E1BF-20H E1BF-25H E1BF-32H E1BF-40H E1BF-50H E1BF-63H E1BF-75H E1DR-20SH E1DR-20H E1DR-25H E1DR-32H E1DR-40H E1DR-50H E1DR-63H E1DR-75H
20S 20 25 32 40 50 63 75 20S 20 25 32 40 50 63 75
PCP PCP PCP PCP PCP PCP PCP PCP PVC PVC PVC PVC PVC PVC PVC PVC
12:32
ACCESSORIES
These compression lugs are based on the standard tin plated connectors manufactured by Pirelli, and are suitable for indoor and outdoor applications. Connections are manufactured from thickwall copper tubing and incorporate single hole palm. The base of the compression barrel is effectively waterblocked via incorporation of a waterproof seal during manufacture.
LUG DETAILS
Anixter Part No. To Suit Conductor Size (mm2) Stud Size (mm)
12 16 16 16 16 20
12
12:33
ACCESSORIES
Lugs
The use of compression lugs for securing conductors to terminals has long been recognised as offering the optimum combination of electrical integrity, reliability and speedy installation. Single hole, two hole and four hole palm lugs available. The compression system ensures a high level of termination when used in association with tooling supplied by the same manufacturer ensuring that the completed installation complies with the standards laid down in BS4579 Part 1 (Compression joints in copper conductors). Anixter stocks uninsulated compression lugs, manufactured by Pirelli Components, produced from high conductivity electrolytic copper having a tin plated finish for operating temperatures up to 1500C and also to prevent corrosion.
12
12:34
ACCESSORIES
Anixter Part No. To Suit Conductor Size (mm2) Flex Str. Stud Size (mm) Anixter Part No. To Suit Conductor Size (mm2) Flex Str. Stud Size (mm)
Single Hole Palm E1AE-BT-6-C5 E1AE-BT-6-C6 E1AE-BT-6-C8 E1AE-BT-6-C10 E1AE-BT-10-C5 E1AE-BT-10-C6 E1AE-BT-10-C8 E1AE-BT-10-C10 E1AE-BT-10-C12 E1AE-BT-16-C5 E1AE-BT-16-C6 E1AE-BT-16-C8 E1AE-BT-16-C10 E1AE-BT-16-C12 E1AE-BT-25-C6 E1AE-BT-25-C8 E1AE-BT-25-C10 E1AE-BT-25-C12 E1AE-BT-35-C6 E1AE-BT-35-C8 E1AE-BT-35-C10 E1AE-BT-35-C12 E1AE-BT-50-C6 E1AE-BT-50-C8 E1AE-BT-50-C10 E1AE-BT-50-C12 E1AE-BT-70-C8 E1AE-BT-70-C10 E1AE-BT-70-C12 E1AE-BT-70-C16 E1AE-BT-95-C10 E1AE-BT-95-C12 E1AE-BT-95-C16 E1AE-BT-120-C10 E1AE-BT-120-C12 E1AE-BT-120-C16 E1AE-BT-120-C20 E1AE-BT-150-C10
4.0 to 6.0 10
10
16
16
25
25
35
35
50
50
70
70
95
95
120
5 6 8 10 5 6 8 10 12 5 6 8 10 12 6 8 10 12 6 8 10 12 6 8 10 12 8 10 12 16 10 12 16 10 12 16 20 10
E1AE-BT-150-C12 E1AE-BT-150-C16 E1AE-BT-185-C10 E1AE-BT-185-C12 E1AE-BT-185-C16 E1AE-BT-185-C20 E1AE-BT-240-C12 E1AE-BT-240-C16 E1AE-BT-240-C20 E1AE-BT-300-C12 E1AE-BT-300-C16 E1AE-BT-300-C20 E1AE-BT-400-C16 E1AE-BT-500-C20 E1AE-BT-630-C20 Two Hole Palm E1AE-BT-150-C12B2 E1AE-BT-185-C12B2 E1AE-BT-240-C12B2 E1AE-BT-300-C12B2 E1AE-BT-400-C12B2 E1AE-BT-500-C12B2 Four Hole Palm E1AE-BT-300-C8B4 E1AE-BT-400-C8B4 E1AE-BT-500-C8B4 E1AE-BT-630-C8B4
120
150
150
185
185 240
240 300
300 400 500 120 150 185 240 300 400 240 300 400 500
400 500 630 150 185 240 300 400 500 300 400 500 630
12 16 10 12 16 20 12 16 20 12 16 20 16 20 20 12 12 12 12 12 12 8 8 8 8
12
12:35
ACCESSORIES
CLEAT DETAILS
Anixter Part No. Cable Dimensions Accomodated Min (mm) Max (mm)
Black Polythene E1D-A01 E1D-A02 E1D-A03 E1D-A04 E1D-A05 E1D-A06 E1D-A07 E1D-A08 Grey LSF E1D-A01LSF E1D-A02LSF E1D-A03LSF E1D-A04LSF E1D-A05LSF E1D-A06LSF E1D-A07LSF E1D-A08LSF 10 12 15 18 22 26 32 39 10 12 15 18 22 26 32 39 15 17 20 24 29 34 42 51 15 17 20 24 29 34 42 51
12
12:36
ACCESSORIES
To Suit Conductor Size Two Core (mm2) Three Core (mm2) Four Core (mm2)
1.5 to 4.0 6.0 to 25.0 35, 50 70, 95 120, 150, 185 240, 300 400
1.5 to 4.0 6.0, 10.0 16, 25 35, 50 70, 95, 120 150, 185, 240 300, 400
1.5, 2.5 4.0 to 10.0 16 25, 35, 50 70, 95, 120 150, 185 240, 300, 400
14.0 - 22.0 14.0 - 30.0 20.0 - 37.0 25.0 - 42.0 33.0 - 55.0 45.0 - 74.0 50.0 - 90.0
12
12:37
ACCESSORIES
Claw cleats for cable dimensions up to 51mm diameter. Two bolt cleats for cable dimensions 51mm and above.
CLEAT DETAILS
Anixter Part No. Cable Dimensions Accomodated Min (mm) Max (mm)
Claw Cleats E1B-BA01 E1B-BA02 E1B-BA03 E1B-BA04 E1B-BA05 E1B-BA06 E1B-BA07 E1B-BA08 E1B-BA09 Two Bolt Cleats E1B-BA10 E1B-BA11 E1B-BA12 E1B-BA13 E1B-BA14 E1B-BA15 51 57 64 70 76 83 57 64 70 76 83 89 10 13 16 19 22 25 32 38 44 13 16 19 22 25 32 38 44 51
12
12:38
ACCESSORIES
515319
12
12:39
ACCESSORIES
3M Part No.
E1DW-MT16
MT16
70-400
3.5
12
12:40
ACCESSORIES
12
12:41
ACCESSORIES
* For dimensions greater than these no boots are required. NB: 3 barrier boots are provided in each kit.
3M Part No.
E1DW-MB63
MB63
Up to 630
0.8
12
12:42
ACCESSORIES
"B"
"A"
"C"
No heating required 11kV rated voltage (95kV BIL) Track resistant EPDM material For use in conductor sizes 35 - 300mm2
"D" "E"
Circular Bushing
Elliptical Bushing
Dimensions of cable box and bushing dimensions should meet the following criteria: Dimension A B C D E Min (mm) Phase - Earth clearance 30 Phase - Phase clearance 70 Bushing length 110 Bushing diameter at length C (circular bushing) 45** Bushing circumference at length C 140** (eliptical bushing) Description Max (mm) 76* 127* 127* 50 157
* For dimensions greater than these no boots are required. ** Bushings below these minumum dimensions can be catered for using 3Ms MB64/S supplementary kit(s) in conjunction with the standard MB 64 kit. NB: 3 barrier boots are provided in each kit.
Anixter Part No. 3M Part No. Suitable for Conductor Sizes (mm2) Approx. Kit Weight (kg)
12
E1DW-MB64
MB64
35 - 300
1.05
12:43
Anixter Part No. E1CUCTW127-02 CTW127-06 CTW254-02 CTW254-06 CTW380-02 CTW380-06 CTW510-02 CTW510-02
Colour
Min. Expanded Diameter (D) mm 12.7 12.7 25.4 25.4 38.0 38.0 51.0 51.0
Max. Recovered Diameter (d) mm 6.4 6.4 12.7 12.7 19.1 19.1 25.4 25.4
Nominal Wall Thickness mm 0.64 0.64 0.89 0.89 1.02 1.02 1.14 1.14
To suit standard LV core size mm2 25 - 35 25 - 35 50 150 50 150 185 300 185 300 400 630 400 630
12
12:44