ACCESSORIES

CONTENTS
Introduction to Glands............................................................................. 12:2 I.P Ratings for Cable Glands....................................................................12:4 A1/A2 Brass Gland with Outer Seal........................................................ 12:6 CX Brass Gland with Outer Seal..............................................................12:7 CXT Brass Gland with Outer Seal .......................................................... 12:8 Ultech Nylon Gland................................................................................... 12:9 LSF Standard Cable Gand for Non Armoured Cable............................. 12:11 Technical Data........................................................................................... 12:12 Index EMC Nickel Plated Gland for Braid Screened Cable................... 12:13 CW Brass Gland with Outer Seal............................................................. 12:14 BW Brass Gland........................................................................................ 12:16 E1W Brass Gland with Inner & Outer Seal.............................................. 12:17 Low Smoke & Fume Gland Kits............................................................... 12:18 BW Brass Gland LSF............................................................................. 12:19 CW Brass Gland with Outer LSF Seal..................................................... 12:20 Selecting Glands for Hazardous Areas................................................... 12:21 A2F Flameproof Gland with Outer Seal.................................................. 12:22 E1WF Flameproof Gland with Inner & Outer Seal.................................. 12:23 E1XF Flameproof Gland with Inner & Outer Seal................................... 12:24 Excelplus Deluge Proof Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................... 12:25 Universal Flameproof & Increased Safety Gland with Inner & Outer Seals............................................................................................. 12:26 E2WF (RTLF) Flameproof Gland with Inner & Outer Seal..................... 12:27 Universal Explosion Proof Barrier Glands............................................. 12:28 Brass Earth Tags...................................................................................... 12:29 High Performance Sealing Washers....................................................... 12:30 Glavanised Serrated Washers................................................................. 12:30 Steel, Brass & Aluminium Locknuts....................................................... 12:31 PCP/PVC Shrouds........................................................................ ............ 12:32 Lugs........................................................................................................... 12:33 Telcleats - Black Polythene & Grey LSF................................................. 12:36 PUJ Straight Cable Joints..................................................................... 12:37 Claw & Two Bolts Cleats - Aluminium Alloy........................................... 12:38 Cable Tiles & Warning Tapes...................................................... .............12:39 11kV Indoor Termination Kits...................................................................12:40 3M Inline (Straight) Barrier Boot - MB63................................................. 12:42 3M Pre-Moulded Right Angle Barrier Boot..............................................12:43 Heat Shrinkable Tubing............................................................................ 12:44

ACCESSORIES

Glands
Cable glands are designed to provide some or all of the following functions in a cabling system: Mechanical connection: Locate and anchor cable. Earth continuity: Armour termination. Ingress Protection: Protect against dust and liquids. Hazardous area: Flameproof protection.

The design of cable glands are covered by BS6121, which covers size, finish, materials, performance, etc. The gland designs are basically a combination of compatibility with cable and installation requirements. GLAND TYPES There are several distinct gland types covered in BS6121 Part 1; A Type B Type C Type D1 Type E1 Type D2 Type E2 Type Suffixes are used to identify the type of armour on a cable: W = single wire armour X = wire braid armour Y = aluminium wire armour Z = steel tape armoured Hence, CW would be a single wire armour, whereas CX would be for a braid armour. The only difference is in the armour lock which caters for the physical size of the armour.

12

12:2

ACCESSORIES
Gland Type A1/A2 BW CW Application/Use Indoor/outdoor brass gland for use with unarmoured cable. Indoor, low-cost, two-part brass gland for use with single wire armoured cable. Indoor/outdoor brass glands for use with single wire armoured cable. Provides seal on outer sheath of cable and separate armour locking ring. NB: Aluminium gland available for aluminium wire armoured cable. CX Indoor/outdoor brass gland for use with braid armoured cables. Provides seal on outer sheath of cable and separate armour locking ring. Indoor/outdoor brass gland for use with single wire armour cable. Provides seal on inner and outer sheaths of cable, and has separate armour locking ring.

E1W

LSF Glands BW Indoor, low cost, two-part brass gland for use with LSF single wire armoured cables. Indoor/outdoor brass gland for use with LSF single wire armoured cables. Provides LSF seal onto outer sheath of cable and separate armour locking ring.

CW

Glands for Hazardous Areas A2F Indoor/outdoor brass gland for use with unarmoured cables. For use with flameproof or increased safety equipment (E.Exd or E.Exe) Indoor/outdoor brass gland for use with single wire armoured cable. Provides seal on inner and outer sheaths of cable, and has separate locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe) Indoor/outdoor brass gland for use with braid armoured cable. Provides seal on inner and outer sheaths of cable, and has separate armour locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe). Indoor/outdoor brass gland for use with single wire armoured and lead sheathed cables (eg. EEMUA types, BS5308 PT1/Type 3). Provides seal onto outer sheath of cable. Inner seal grips and provides earth continuity to lead sheath. Design has separate armour locking ring. For use with flameproof or increased safety equipment (E.Exd or E.Exe). Indoor/outdoor brass barrier gland for use with a braid armoured cable. Provides seal on outer sheath of cable, and solid setting compound squeezed into the interstices of cable when installed to prevent escape of gases through centre of cable. For use with explosion proof equipment.

E1WF

E1XF

E2WF

BARR-X

12

12:3

ACCESSORIES

I.P Ratings for Cable Glands


I.P. (Ingress Protection) Ratings detail the degree of protection against solid bodies and liquids, and is tested against IEC 144. Generally any seal has a rating of IP66. However, since they are tested in isolation, when they are in conjunction with a piece of equipment this needs to be taken into consideration. Generally the following can be taken:1. Gland used in Plain Entry with Backnut - IP54. 2. Gland used in Plain Entry with sealing washer between gland and equipment interface - IP66. 3. Gland used in Tapped Entry - IP65. 4. These can be uprated by the use of Sealing washers and Thread Sealants. 5. Special designs of Gland are available which can achieve an IP Rating of IP68. (NB. Interface with equipment then becomes critical.)

12

12:4

ACCESSORIES

Degree of Protection IEC 144 I.P. Ratings


First Digit 0 1 2 3 4 5 6 Second Digit 0 1 2 3 4 5 6 7 8 Protection (Against solid bodies) No protection Protected against solid bodies larger than 50mm, eg, accidental contact with hand. Protected against solid bodies larger than 12mm, eg, finger. Protected against solid bodies larger than 2.5mm, eg, tools and wires. Protected against solid bodies larger than 1.0mm, eg, fine tools and small wires. Protected against dust (no harmful deposits). Completely protected against dust. Protection (Against Liquids) No protection. Protected against vertically falling drops of water (condensation). Protected against drops of water falling at up to 150 from the vertical. Protected against rain falling at 600 from vertical. Protected against splashes of water from all directions. Protected against jets of water from all directions. Protected against jets of water of similar force to heavy seas. Protected against the effects of temporary immersion. Protected against prolonged effects of immersion under pressure.

12

12:5

ACCESSORIES

A1/A2 Brass Gland with Outer Seal

To BS6121: Part 1. Suitable for unarmoured, plastic or rubber sheathed cables. Suitable for most indoor and outdoor applications. Seal rated to IP66

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Overall diameter Min Max 3.5 8.0 11.0 13.0 19.0 25.0 31.5 36.5 42.5 8.5 11.5 13.5 19.5 25.5 32.0 37.0 43.0 50.0

E1AW-A1/A2-20SS E1AW-A1/A2-20S E1AW-A1/A2-20 E1AW-A1/A2-25 E1AW-A1/A2-32 E1AW-A1/A2-40 E1AW-A1/A2-50S E1AW-A1/A2-50 E1AW-A1/A2-63S

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20SS 20S 20 25 32 40 50S 50 63S

12

Glands are supplied in kit form, complete with locknuts and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit

12:6

ACCESSORIES

CX Brass Gland with Outer Seal

BS6121: Part 1 Suitable for wire braid armoured, plastic or rubber sheathed cables. Outer seal grips sheath of cable. Weatherproof and water proof. Seal rated to IP66. Design has separate armour locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 8.6 11.6 13.9 19.9 26.2 32.1 8.0 8.0 13.2 15.8

E1AH-CX-20SS E1AH-CX-20S E1AH-CX-20 E1AH-CX-25 E1AH-CX-32 E1AH-CX-40

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20SS 20S 20 25 32 40

12.9 20.8 17.0 27.2 23.5 33.5 29.0 39.9

Glands are supplied in kit form, complete with locknuts, earthtags and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit

12

12:7

ACCESSORIES

CXT Brass Gland with Outer Seal


Gland reference not specified in BS6121:Part 1. However, gland complies in all other respects with the design and test requirements of Type A2 cable glands. Suitable for wire braid armoured/screened, plastic or rubber sheathed cables. Outer seal grips sheath of cable. Weatherproof and water proof. Seal rated to IP66. Integral knurled armour lock. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Overall Min Max 6.1 6.5 11.1 17.0 22.0 11.6 13.9 19.9 26.2 32.1

E1AH-CXT-20S E1AH-CXT-20 E1AH-CXT-25 E1AH-CXT-32 E1AH-CXT-40

CMP CMP CMP CMP CMP

20S 20 25 32 40

Glands are supplied in kit form, complete with locknuts, earthtags and shrouds. Up to size 32:- 2 per kit Size 40 and above:- 1 per kit

12

12:8

ACCESSORIES

Ultech Nylon Gland with Outer Seal


For non-armoured cable

Suitable for unarmoured, plastic or rubber sheathed cables. Polyamide 6 nylon gland with neoprene seal. Compact skin-top design Quick and easy assembly Halogen free and UL94-V2 flammability rated. Seal rated IP68 at 5 bar. Temperature range: -30C to +80C Grey RAL 7001 colour ISOMETRIC thread. 10mm thread length for gland sizes 16-25, 18mm for gland size 32. Ultech is a registered trade name of Elkay International

CABLE & GLAND DETAILS


Anixter Part Number Gland Manf. Gland Manf. Part Number Gland Size Cable Dimensions accommodated (mm) Overall diameter Minimum Maximum 5.0 6.0 10.0 13.0 18.0 10.0 12.0 14.0 18.0 25.0

E1AV-ULT-16 E1AV-ULT-20S E1AV-ULT-20 E1AV-ULT-25 E1AV-ULT-32

Elkay Elkay Elkay Elkay Elkay

270-8011 270-8021 270-8031 270-8061 270-8071

16 20S 20 25 32

Glands are supplied in kit form, complete with nylon washer and locknut. All sizes: 2 per kit. NB: Mini-size polyamide 6.6 standard nylon gland is also available for IP66 rated nitrile seal for small diameter cable. Details as follows:-

12

12:9

ACCESSORIES

Mini - Gland

Halogen free and UL94-V2 flammability rated. -20C to +90C temperature range. Grey RAL 7001 colour. ISOMETRIC thread. 8mm thread length.

CABLE & GLAND DETAILS


Anixter Part Number Gland Manf. Gland Manf. Part Number Gland Size Cable Dimensions accommodated (mm) Overall diameter Minimum E1AV-MINI-13 Elkay 239-B M13 2.0 Maximum 5.0

Glands are supplied in kit form with nylon washer and locknut 2 per kit.

12

12:10

ACCESSORIES

LSF Standard Cable Gland for Non-Armoured Cable

Suitable for unarmoured plastic or rubber sheathed cables. Polyamide 6.6 nylon gland with nitrile rubber seal. Quick and easy assembly. Halogen free and UL94-V2 flammability rated. Seal rated at IP66. -20C to +90C temperature range. Black RAL 9005 colour. ISO METRIC thread. 11mm thread length LSF glands meet following standards:- BS6853 App B5.1, BS7878, BS2782 M141, IEC 60754-1, IEC 60754-2, BS6425, NES713/Iss 3.

CABLE & GLAND DETAILS


Anixter Part Number Gland Manf. Gland Manf. Part Number Gland Size Cable Dimensions accommodated (mm) Overall diameter Minimum E1AV-LSF-20SS E1AV-LSF-20S E1AV-LSF-20 Elkay Elkay Elkay 249-LSF 251-LSF 252-LSF 20SS 20S 20 4.0 7.0 8.0 Maximum 6.0 10.0 13.0

12
Glands are supplied in kit form, complete with washer and locknut.

12:11

ACCESSORIES
TECHNICAL DATA
APPLICABLE TO NYLON GLANDS - CHEMICAL RESISTANCE Listed below is the general chemical resistance information for the materials used to manufacture the majority of products in this catalogue. S = Suitable L = Limited suitability U = Unsuitable
Chemical Agent ASTM Oil No. 2 Acetaldehyde Acetic acid (10%) Acetic acid (glacial) Acetone Ammonium Hydroxide (35%) Benzene Benzyl Alcohol Bromine (liquid) Butyl Alcohol Butyl Acetate Butylamine Carbon Tetrachloride Chlorine Gas Citric acid (10%) Cresols Cyclohexane Diesel oil Diethyl ether Ethanol Ethylamine Ethylene glycol Formaldehyde Hexane Hydrochloric acid (10%) Hydrochloric acid (conc) Hydrogen peroxide (35%) Nylon S L L L S S S L U S S S S U S U S S S S L S S S U U L Chemical Agent Hydrogen sulphide (gas) Iso-octane Iso-propanol Lubricating oil Methanol Nitric acid (10%) Nitric acid (conc) Ozone (gas) Paraffin oil Petrol Phenol Silicone oils Sodium hydroxide (60%) Sodium hypochlorite (bleach) Styrene Sulphur dioxide (gas) Sulphuric acid (10%) Sulphuric acid (70%) Toluene Transformer oil Trichloroethylene Tricresyl phosphate (SKYDROL) Turps White spirit Xylene Zinc chloride Nylon S S S S L U U L S S U S S L S U U U S S L S S S S U

12

12:12

ACCESSORIES

Index EMC Nickel Plated Brass Gland for Braid Screened Cable
1 2 1 4 1 3 1 5 1 6 1

FEATURES. 1. Compression Nut 2. Santoprene Seal 3. Endless Spring 4. Tapered Ring 5. O Ring 6. Gland Body

For use with braid screened cable to connect screen to the enclosure system. Two tapered rings applying force onto an endless spring washer ensure positive and intimate contact for efficient screening. Screen can continue into enclosure. Suitable for systems conforming to EN50082. Nickel plated brass gland body with santoprene rubber seal. Seal rated IP68 at 1 bar. -40 to +135C temperature range. ISO METRIC thread with exception of gland for 4-6mm diameter cable which has P.G.7 thread to DIN40430.
Anixter Part No. Gland Manf. E1AH-EMC-7 E1AH-EMC-16 E1AH-EMC-20 E1AH-EMC-25SS E1AH-EMC-25S E1AH-EMC-25 E1AH-EMC-32S E1AH-EMC-32 Elkay Elkay Elkay Elkay Elkay Elkay Elkay Elkay Gland No. 261-1000 260-1000 260-1250 260-1400 260-1450 260-1500 260-1600 260-1650 260-1700 Gland Cable Dimensions Accommodated (mm) Over Screen Min. 1.5 3.0 4.0 6.5 8.0 8.0 12.5 15.0 15.0 Max. 4.0 7.0 8.5 10.0 12.0 12.0 17.5 21.0 21.0 Cable Diameter Min. 4.0 6.0 8.0 10.0 11.0 14.0 17.0 19.0 22.0 Max. 6.0 8.0 10.5 11.5 14.0 16.6 20.0 23.0 27.0

Manf. Part Size PG7 M16 M20 M25 M25 M25 M25 M32 M32

E1AH-EMC-25SSS Elkay

12

Glands are supplied in kit form complete with locknut. All sizes: 2 per kit.

12:13

ACCESSORIES

CW Brass Gland with Outer Seal

BS6121: Part 1 Suitable for wire armoured, plastic or rubber sheathed cables. Outer seal grips sheath of cable. Weatherproof and water proof. Seal rated to IP66. Design has separate armour locking ring (Pirelli glands only). Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface

Brass glands are provided with steel locknuts and aluminium glands are provided with aluminium locknuts. For more corrosive environments brass locknuts may be supplied. Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli CMP Up to size 25: - 2 per kit Size 32 and above:- 1 per kit Up to size 32:- 2 per kit Size 40 and above:- 1 per kit

12

12:14

ACCESSORIES
CABLE & GLAND DETAILS
Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 8.6 8.6 11.6 11.6 13.9 13.9 19.9 19.9 26.2 26.2 32.1 32.1 38.1 38.1 44.0 44.0 50.0 55.9 55.9 67.9 67.9 19.9 26.2 32.1 38.1 44.0 8.0 8.0 8.0 13.2 13.4 15.8

E1AG-CW-20SSC E1AG-CW-20SS E1AG-CW-20SC E1AG-CW-20S E1AG-CW-20C E1AG-CW-20 E1AG-CW-25C E1AG-CW-25 E1AG-CW-32C E1AG-CW-32 E1AG-CW-40C E1AG-CW-40 E1AG-CW-50SC E1AG-CW-50S E1AG-CW-50C E1AG-CW-50 E1AG-CW-63S E1AG-CW-63C E1AG-CW-63 E1AG-CW-75C E1AG-CW-75 E1DN-CW-25 E1DN-CW-32 E1DN-CW-40 E1DN-CW-50SC E1DN-CW-50

Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP CMP Pirelli CMP Pirelli CMP Pirelli Pirelli Pirelli CMP Pirelli

20SS 20SS* 20S 20S 20 20 25 25 32 32 40 40 50S 50S 50 50 63S 63 63 75 75 25 32 40 50S 50

11.4 15.9 12.9 20.8 15.0 20.9 17.0 27.2 20.3 27.4 23.5 33.5 26.0 33.9 29.0 39.9 31.0 40.4 38.0 46.2 36.5 46.7 39.5 52.6 43.0 53.1 48.9 59.4 51.3 65.3 58.0 65.9 62.5 78.0 64.9 78.5 17.0 27.2 23.5 33.5 29.0 39.9 36.5 46.7 39.5 52.6

Aluminium CW glands for aluminium wire armoured cable

NB Pirelli glands have separate armour locking rings. CMP glands have integral knurled armour lock. * Also known as 20/16 (CMP only),

12

12:15

ACCESSORIES

BW Brass Gland
BS6121: Part 1 Suitable for single wire armoured, plastic or rubber sheathed cables. For use in dry, indoor situations. Low-cost two-part design. IP54 Shroud may be used for additional ingress protection

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 11.6 11.6 13.9 13.9 19.9 19.9 26.2 26.2 32.1 32.1 38.1 44.0 44.0 55.9 55.9 67.9 67.9 15.8 16.1 20.8 21.1 27.2 27.4 33.5 34.4 39.9 42.4 50.1 52.6 55.7 65.3 68.2 78.0 82.9

E1AJ-BW-20SC E1AJ-BW-20S E1AJ-BW-20C E1AJ-BW-20 E1AJ-BW-25C E1AJ-BW-25 E1AJ-BW-32C E1AJ-BW-32 E1AJ-BW-40C E1AJ-BW-40 E1AJ-BW-50S E1AJ-BW-50C E1AJ-BW-50 E1AJ-BW-63C E1AJ-BW-63 E1AJ-BW-75C E1AJ-BW-75

Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP CMP Pirelli CMP Pirelli CMP Pirelli CMP

20S 20S 20 20 25 25 32 32 40 40 50S 50 50 63 63 75 75

12

Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kit CMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kit

12:16

ACCESSORIES

E1W Brass Gland with Inner and Outer Seals


BS6121: Part 1 Suitable for single wire armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 8.7 6.1 6.5 11.6 8.0 15.8 11.6 11.4 15.9 13.9 15.0 20.9

E1BA-E1W-20S E1BA-E1W-20SC E1BA-E1W-20 E1BA-E1W-20C E1BA-E1W-25 E1BA-E1W-25C E1BA-E1W-32 E1BA-E1W-32C E1BA-E1W-40 E1BA-E1W-40C E1BA-E1W-50S E1BA-E1W-50SC E1BA-E1W-50 E1BA-E1W-50C E1BA-E1W-63 E1BA-E1W-63C E1BA-E1W-75S

Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli CMP Pirelli

20S 20S 20 20 25 25 32 32 40 40 50S 50S 50 50 63 63 75S

11.7 13.9 12.9 20.8 13.0 19.9 17.0 27.2 11.1 19.9 20.3 27.4 20.0 26.2 23.5 33.5 17.0 26.2 26.0 33.9 26.3 32.1 29.0 39.9 22.0 32.1 31.0 40.4 32.2 38.1 38.0 46.2 29.5 38.1 36.5 46.7 38.2 44.0 39.5 52.6 35.6 44.0 43.0 53.1 50.1 55.9 51.3 65.3 47.2 55.9 58.0 65.9 56.0 61.9 62.0 71.6

Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Pirelli Up to size 25: - 2 per kit Size 32 and above:- 1 per kit CMP Up to size 32:- 2 per kit Size 40 and above:- 1 per kit NB Pirelli glands have separate armour locking rings. CMP glands have integral knurled armour lock.

12

12:17

ACCESSORIES

Low Smoke and Fume Gland Kits


Convenient ready to use kits. Contain everything necessary to terminate an LSF cable run - gland(s) with LSF seal(s), backnuts(s), earth tag(s) and LSF shroud(s). Zero halogen. Complies with the test criteria of BS6724, BS6853 category 1. Continuous operating temperature of -500C to 1500C Resists most chemicals, solvents, acids, alkalis, oils, moisture, steam and UV light. Excellent tear resistance.

NOTE: The materials utilised in these kits are noted for the absence of smoke generating constituents, particularly halogens (flourine, bromine and chlorine) thus avoiding the hazards of highly irritant and toxic fumes emitted by standard materials such as PCP and PVC when exposed to flame.

12

12:18

ACCESSORIES

BW Brass Gland - LSF

To BS6121: Part 1. Suitable for single wire armoured, plastic or rubber sheathed cables. For use in dry, indoor situations. Low cost two-part design. IP54. LSF shroud may be used for additional ingress protection.

Glands are supplied in kit form, complete with locknuts and shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 11.6 13.9 19.9 26.2 32.1 44.0 55.9 67.9 15.8 20.8 27.2 33.5 39.9 52.6 65.3 78.0

E1AJ-BW-20SLSF E1AJ-BW-20LSF E1AJ-BW-25LSF E1AJ-BW-32LSF E1AJ-BW-40LSF E1AJ-BW-50LSF E1AJ-BW-63LSF E1AJ-BW-75LSF

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20S 20 25 32 40 50 63 75

12

12:19

ACCESSORIES

CW Brass Gland with Outer LSF Seal

To BS6121: Part 1. Suitable for single wire armoured, plastic or rubber sheathed cables. Outer LSF seal grips sheath of cable. Weatherproof and waterproof. Seal rated to IP66 Design has separate armour locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface.

Glands are supplied in kit form, complete with locknuts and LSF shrouds. Up to size 25:- 2 per kit Size 32 and above:- 1 per kit

CABLE & GLAND DETAILS


Anixter Part No. Gland Gland Manu Size Cable dimensions accomodated Under armour Overall Min Max Min Max 8.6 11.6 8.0 13.2 8.0 15.8

E1AG-CW-20SSLSF E1AG-CW-20SLSF E1AG-CW-20LSF E1AG-CW-25LSF E1AG-CW-32LSF E1AG-CW-40LSF E1AG-CW-50SLSF E1AG-CW-50LSF E1AG-CW-63LSF E1AG-CW-75LSF

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20SS 20S 20 25 32 40 50S 50 63 75

13.9 12.9 20.8 19.9 17.0 27.2 26.2 23.5 33.5 32.1 29.0 39.9 38.1 38.0 46.2 44.0 39.5 52.6 55.9 51.3 65.3 67.9 62.5 78.0

12

12:20

ACCESSORIES

Selecting Glands for Hazardous Areas


ZONE CLASSIFICATION
Zone 0 (Division 0) Explosive gas/air mixture is continuously present or for long periods. No equipment should be terminated in this zone. Zone 1 (Division 1) Explosive gas/air mixture is likely to occur in normal operation. Zone 2 (Division 2) Explosive gas/air mixture is not likely to occur and if so, only for a short period of time. Increased Safety Glands(E.Exe) For use in hazardous environments and comply with EN50014 and EN 50019 (BS5501 Part 1 and Part 6). These glands can only be used where no parts of the electrical equipment can produce sparks/arcing or exceeds the gas ignition temperature. E.Exe glands are normally recommended for Zone 2 applications but can be used in Zone 1, i.e. indirect entry situations. Flameproof (E.Exd) Glands For use in hazardous environments and comply with EN50014 and EN50018 (BS5501 Part 1 and Part 5). These glands are approved for direct entry applications in Zone 1 areas, IIA, IIB or IIC gas groups with the exception of A2F glands which are for IIA and IIB groupings - may also be used in Zone 2 areas. Explosion Proof Barrier Glands For use in hazardous environments and comply with EN50014 and EN 50018 (BS5501 Part 1 and Part 5). These glands are approved for direct entry applications in Zone 1 areas, IIA, IIB, or more commonly IIC gas groups. Selecting Barrier Glands as opposed to Conventional Flameproof Glands The main applications for the specification of barrier glands in accordance with the relevant codes of practice, can be summarised as follows: with enclosures containing an ignition source and installed in Group IIC gas areas with an enclosure containing an ignition source and in a Zone 1 area where the volume of the enclosure exceeds 2 litres with cables other than those specified in BS5308, BS5467, BS6116, BS6346 and 6883 where 'cold flow' of cable installation is considered a possibility to prevent gas migration from one area to another to prevent moisture migration in cables where the user assessment considers a barrier gland essential for safety

12

12:21

ACCESSORIES

A2F Flameproof Gland with Outer Seal


Suitable for unarmoured, plastic or rubber sheathed cables. Suitable for most indoor and outdoor applications. Seal rated to IP66. Complies with IIB hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). Zone 1 and Zone 2 applications. For use with flameproof or increased safety equipment (E.Exd or E.Exe) BASEEFA Approved. Glands are supplied in kit form complete with locknuts, earthtags and shrouds. Up to size 25: - 2 per kit Size 32 and above:- 1 per kit Hawke glands are supplied as gland only

CABLE & GLAND DETAILS


Anixter Part No. Gland Gland Manu Size Cable dimensions accomodated Overall Min
E1AT-A2F-16H-A E1AT-A2F-20SS E1AT-A2F-20S E1AT-A2F-20SH-A E1AT-A2F-20 E1AT-A2F-20H-A E1AT-A2F-25S E1AT-A2F-25 E1AT-A2F-25H-A E1AT-A2F-32 E1AT-A2F-32H-A E1AT-A2F-40 E1AT-A2F-40H-A E1AT-A2F-50S HAWKE Pirelli Pirelli HAWKE Pirelli HAWKE Pirelli Pirelli HAWKE Pirelli HAWKE Pirelli HAWKE Pirelli Pirelli HAWKE Pirelli HAWKE 16 20SS 20S 20S 20 20 25S 25 25 32 32 40 40 50S 50 50 63S 63 3.0 3.5 8.0 7.5 11.0 11.0 13.0 16.0 13.0 19.0 19.0 25.0 25.0 31.5 36.5 31.5 42.5 42.5

Max
8.0 8.5 11.5 11.9 13.5 14.3 16.5 19.5 20.2 25.5 26.5 32.0 32.5 37.0 43.0 44.4 50.0 56.3

12

E1AT-A2F-50 E1AT-A2F-50H-A E1AT-A2F-63S E1AT-A2F-63H-A

12:22

ACCESSORIES

E1WF Flameproof Gland with Inner & Outer Seals

Suitable for single wire armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment. Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications. Pirelli glands are supplied in kit form completPirellie with locknuts, earthtags and shrouds. Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 3.81 8.0 14.0 19.7 8.74 8.0 13.2 11.79 8.0 15.8 20.12 17.0 27.2 26.55 23.5 33.5

E1BN-E1WF-20SS E1BN-E1WF-20S E1BN-E1WF-20 E1BN-E1WF-25 E1BN-E1WF-32 E1BN-E1WF-40 E1BN-E1WF-50 E1BN-E1WF-63

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20SS 20S 20 25 32 40 50 63

11.79 14.15 12.9 20.8

26.55 32.42 29.0 39.9 38.39 44.33 39.5 52.6 50.27 56.24 51.3 65.3

12

12:23

ACCESSORIES

E1XF Flameproof Gland with Inner & Outer Seals

Suitable for wire braid armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications. Pirelli glands are supplied in kit form complete with locknuts, earthtags and shrouds. Up to size 25: - 2 per kit Size 32 and above:- 1 per kit

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 3.81 3.81 8.0 14.0 19.7 8.74 8.74 11.79 8.0 8.0 8.0 13.2 13.2 15.8

E1BP-E1XF-16 E1BP-E1XF-20SS E1BP-E1XF-20S E1BP-E1XF-20 E1BP-E1XF-25 E1BP-E1XF-32

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

16 20SS 20S 20 25 32 40 50S 50 63S

11.79 14.15 12.9 20.8 20.12 17.0 27.2 26.55 23.5 33.5

12

E1BP-E1XF-40 E1BP-E1XF-50S E1BP-E1XF-50 E1BP-E1XF-63S

26.55 32.42 29.0 39.9 32.42 38.39 38.0 46.2 38.39 44.33 39.5 52.6 44.33 50.27 50.0 58.9

12:24

ACCESSORIES

Excelplus Deluge Proof Flameproof & Increased Safety Gland with Inner & Outer Seals
Suitable for wire braid and single wire armoured, plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof, waterproof and deluge proof. Inner and outer seal rated to IP67. Design has separate armour locking ring and additional locking ring to ensure integrity of armour lock under vibrating conditions. Gland rated to IP67 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Dual certified. Complies with group II C hazardous atmospheres EN50014, EN50018 and EN50019 (BS5501 Part 1, Part 5 and Part 6). BASEEFA Approved. Zone 1 and Zone 2 applications. Supplied as gland only.

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 7.0 8.0 10.5 15.5 23.0 28.5 44.0 53.0 12.0 14.4 20.2 26.5 32.5 44.5 56.5 68.5 9.0 16.0

E1BP-EXC-20S-A E1BP-EXC-20-A E1BP-EXC-25-A E1BP-EXC-32-A E1BP-EXC-40-A E1BP-EXC-50-A E1BP-EXC-63-A E1BP-EXC-75-A

Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli Pirelli

20S 20 25 32 40 50 63 75

11.5 21.0 18.5 27.5 21.0 34.0 31.0 41.5 36.0 52.5 50.0 65.5 59.0 78.0

12

12:25

ACCESSORIES

Universal Flameproof & Increased Safety Gland with Inner & Outer Seals
Suitable for wire braid, single wire, steel tape and strip armoured plastic or rubber sheathed, extruded bedded cables. Outer seal grips sheath of cable. Inner seal grips bedded layer of cable. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface. For use with flameproof equipment or increased safety equipment (E.Exd or E.Exe). Complies with group II C hazardous atmospheres EN50014, EN50018 and EN50019 (BS5501 Part 1, Part 5 and Part 6). BASEEFA Approved. Zone 1 and Zone 2 applications. Incorporates external boot seal which offers protection against moisture ingress to the armour. Glands are supplied in kit form complete with locknut, earthtag, shroud, nylon washer and serrated washers. All sizes: 1 per kit

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 7.5 9.4 12.1 17.6 23.1 28.9 39.9 50.5 11.9 14.3 20.2 26.5 32.5 44.4 56.3 68.2 9.5 16.0 12.5 20.5 16.9 26.0 22.0 33.0 28.0 41.0 36.0 52.6 46.0 65.3 57.0 78.0

E1DZ-UNI-20S E1DZ-UNI-20 E1DZ-UNI-25 E1DZ-UNI-32

HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE

20S 20 25 32 40 50 63 75

12

E1DZ-UNI-40 E1DZ-UNI-50 E1DZ-UNI-63 E1DZ-UNI-75

12:26

ACCESSORIES

E2WF (RTLF) Flameproof Gland with Inner & Outer Seals

Suitable for SWA, plastic or rubber oversheathed, lead inner sheath cables. Outer seal grips sheath of cable. Inner seal grips and provides earth continuity to lead sheath. Weatherproof and waterproof. Inner and outer seal rated to IP66 Design has separate outer locking ring. RTLF for use with flameproof equipment or increased safety equipment. Complies with group II C hazardous atmospheres EN50014 and EN50018 (BS5501 Part 1 and Part 5). BASEEFA Approved. Zone 1 and Zone 2 applications.

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Over lead sheath Overall Min Max Min Max
7.0 8.0 11.5 15.0 18.0 20.0 23.0 29.0 34.0 9.6 12.0 17.0 19.0 23.0 25.0 29.0 35.0 40.0 10.5 12.9 17.0 25.0 25.0 33.0 33.0 39.5 39.5 16.0 20.9 27.1 33.3 33.3 42.9 42.9 52.6 52.6

E1CF-RTLF-20SH-A E1CF-RTLF-20H-A E1CF-RTLF-25H-A E1CF-RTLF-32SH-A E1CF-RTLF-32H-A E1CF-RTLF-40SH-A E1CF-RTLF-40H-A E1CF-RTLF-50SH-A E1CF-RTLF-50H-A

HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE

20S 20 25 32S 32 40S 40 50S 50

12

Glands are supplied as gland only.

12:27

ACCESSORIES

Universal Explosion Proof Barrier Glands

For plastic or rubber insulated cables with wire braid, single wire, steel tape or strip armour, having extruded or taped bedding. Solid setting compound is squeezed into the interstices of the cable when gland is installed. Compound forms a barrier around individual cores so preventing escape of gases through centre of cable. Sealing arrangements are rated to IP66. Weatherproof and waterproof. For use with explosion proof equipment in Zone 1 hazardous areas. Complies with group II C qualifies the gland for use under the most onerous conditions. BASEEFA Approved. Approved to EN50014 and EN50018 (BS5501 Part 1 and Part 5)

CABLE & GLAND DETAILS


Anixter Part No. Gland Manu Gland Size Cable dimensions accomodated Under armour Overall Min Max Min Max 10.0 12.5 18.4 24.7 29.7 41.7 9.5 16.0 12.5 20.5 16.9 26.0 22.0 33.0 28.0 41.0 36.0 52.6

E1BS-UNI-20S-A E1BS-UNI-20-A E1BS-UNI-25-A E1BS-UNI-32-A E1BS-UNI-40H-A E1BS-UNI-50H-A

HAWKE HAWKE HAWKE HAWKE HAWKE HAWKE

20S 20 25 32 40 50

12

Glands are supplied body only with 2 compound mixes.

12:28

ACCESSORIES

Brass Earth Tags

Ensure earth continuity is maintained between the gland and the equipment. Aluminium earth tags should be used with aluminium glands. NOTE: Earth bond connections are specified in IEE wiring regulations and relevant Codes of Practice.

TAG DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Bolt Hole Diameter (mm)

E1BG-20R E1BG-25R E1BG-32R E1BG-40R E1BG-50R E1BG-63R E1BG-75R

20 25 32 40 50 63 75

7.2 10.3 11.9 13.5 13.5 13.5 13.5

12

12:29

ACCESSORIES

High Performance Sealing Washers


Improve the IP rating between the gland and the equipment i.e. IP66. Fibre or Nylon available according to customer preference.
EQUIPMENT INTERFACE

WASHER DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Washer Material

SEALING WASHER

E1DS-20R E1DS-25R E1DS-32R E1DS-40R E1DS-50R E1DS-63R E1DS-75R E1DT-20 E1DT-25 E1DT-32 E1DT-40 E1DT-50 E1DT-63 E1DT-75

20 25 32 40 50 63 75 20 25 32 40 50 63 75

NYLON NYLON NYLON NYLON NYLON NYLON NYLON FIBRE FIBRE FIBRE FIIBRE FIBRE FIBRE FIBRE

Galvanised Serrated Washers


Used to prevent loosening of locknut Mild steel zinc plated

WASHER DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm)

12

E1DY-20 E1DY-25 E1DY-32 E1DY-40 E1DY-50

20 25 32 40 50

12:30

ACCESSORIES

Steel, Brass & Aluminium Locknuts

Used to secure gland body to the equipment where entry hole is not tapped. Brass backnuts recommended for most corrosive environments. Aluminium backnuts should be used with aluminium glands. Steel backnuts are primarily for dry, low humidity environments.

LOCKNUT DETAILS
Anixter Part No. ISO Entry Thread Diameter (mm) Locknut Material

E1BK-20R E1BK-25R E1BK-32R E1BK-40R E1BK-50R E1BK-63R E1BK-75R

20 25 32 40 50 63 75

BRASS BRASS BRASS BRASS BRASS BRASS BRASS

Steel and aluminium locknuts are available when required.

12

12:31

ACCESSORIES

PC P/PVC Shrouds

For fitting over cable glands where additional protection against onerous weather conditions and corrosion is required. Provide an effective seal onto both gland and cable oversheath. PCP shrouds are particularly recommended for outdoor and the most hostile conditions and are not affected by ultravoilet rays contained in sunlight. PVC shrouds for use in dry indoor and most outdoor situations.

SHROUD DETAILS
Anixter Part No. To Suit Gland Size (mm) Shroud Material

12

E1BF-20SH E1BF-20H E1BF-25H E1BF-32H E1BF-40H E1BF-50H E1BF-63H E1BF-75H E1DR-20SH E1DR-20H E1DR-25H E1DR-32H E1DR-40H E1DR-50H E1DR-63H E1DR-75H

20S 20 25 32 40 50 63 75 20S 20 25 32 40 50 63 75

PCP PCP PCP PCP PCP PCP PCP PCP PVC PVC PVC PVC PVC PVC PVC PVC

12:32

ACCESSORIES

Lugs for Medium Voltage Cables

These compression lugs are based on the standard tin plated connectors manufactured by Pirelli, and are suitable for indoor and outdoor applications. Connections are manufactured from thickwall copper tubing and incorporate single hole palm. The base of the compression barrel is effectively waterblocked via incorporation of a waterproof seal during manufacture.

LUG DETAILS
Anixter Part No. To Suit Conductor Size (mm2) Stud Size (mm)

E1AE-BTHW-70-C12 E1AE-BTHW-95-C16 E1AE-BTHW-120-C16 E1AE-BTHW-150-C16 E1AE-BTHW-185-C16 E1AE-BTHW-240-C20

70 95 120 150 185 240

12 16 16 16 16 20

12

12:33

ACCESSORIES

Lugs
The use of compression lugs for securing conductors to terminals has long been recognised as offering the optimum combination of electrical integrity, reliability and speedy installation. Single hole, two hole and four hole palm lugs available. The compression system ensures a high level of termination when used in association with tooling supplied by the same manufacturer ensuring that the completed installation complies with the standards laid down in BS4579 Part 1 (Compression joints in copper conductors). Anixter stocks uninsulated compression lugs, manufactured by Pirelli Components, produced from high conductivity electrolytic copper having a tin plated finish for operating temperatures up to 1500C and also to prevent corrosion.

12

12:34

ACCESSORIES
Anixter Part No. To Suit Conductor Size (mm2) Flex Str. Stud Size (mm) Anixter Part No. To Suit Conductor Size (mm2) Flex Str. Stud Size (mm)

Single Hole Palm E1AE-BT-6-C5 E1AE-BT-6-C6 E1AE-BT-6-C8 E1AE-BT-6-C10 E1AE-BT-10-C5 E1AE-BT-10-C6 E1AE-BT-10-C8 E1AE-BT-10-C10 E1AE-BT-10-C12 E1AE-BT-16-C5 E1AE-BT-16-C6 E1AE-BT-16-C8 E1AE-BT-16-C10 E1AE-BT-16-C12 E1AE-BT-25-C6 E1AE-BT-25-C8 E1AE-BT-25-C10 E1AE-BT-25-C12 E1AE-BT-35-C6 E1AE-BT-35-C8 E1AE-BT-35-C10 E1AE-BT-35-C12 E1AE-BT-50-C6 E1AE-BT-50-C8 E1AE-BT-50-C10 E1AE-BT-50-C12 E1AE-BT-70-C8 E1AE-BT-70-C10 E1AE-BT-70-C12 E1AE-BT-70-C16 E1AE-BT-95-C10 E1AE-BT-95-C12 E1AE-BT-95-C16 E1AE-BT-120-C10 E1AE-BT-120-C12 E1AE-BT-120-C16 E1AE-BT-120-C20 E1AE-BT-150-C10

4.0 to 6.0 10

10

16

16

25

25

35

35

50

50

70

70

95

95

120

5 6 8 10 5 6 8 10 12 5 6 8 10 12 6 8 10 12 6 8 10 12 6 8 10 12 8 10 12 16 10 12 16 10 12 16 20 10

E1AE-BT-150-C12 E1AE-BT-150-C16 E1AE-BT-185-C10 E1AE-BT-185-C12 E1AE-BT-185-C16 E1AE-BT-185-C20 E1AE-BT-240-C12 E1AE-BT-240-C16 E1AE-BT-240-C20 E1AE-BT-300-C12 E1AE-BT-300-C16 E1AE-BT-300-C20 E1AE-BT-400-C16 E1AE-BT-500-C20 E1AE-BT-630-C20 Two Hole Palm E1AE-BT-150-C12B2 E1AE-BT-185-C12B2 E1AE-BT-240-C12B2 E1AE-BT-300-C12B2 E1AE-BT-400-C12B2 E1AE-BT-500-C12B2 Four Hole Palm E1AE-BT-300-C8B4 E1AE-BT-400-C8B4 E1AE-BT-500-C8B4 E1AE-BT-630-C8B4

120

150

150

185

185 240

240 300

300 400 500 120 150 185 240 300 400 240 300 400 500

400 500 630 150 185 240 300 400 500 300 400 500 630

12 16 10 12 16 20 12 16 20 12 16 20 16 20 20 12 12 12 12 12 12 8 8 8 8

12

12:35

ACCESSORIES

Telcleats - Black Polythene & Grey LSF


Range taking and self adjusting Just 8 sizes cover from 10mm to 51mm diameter Ultraviolet and weather resistant Low cost Versatile One piece Single fixing LSF cleats are low smoke and fume emission and zero halogen Coloured grey to distinguish from black coloured Telcleat Meets requirements of BS6853 and LUL specification E1042 with regards to temperature index, smoke emission and toxicity ratings.

CLEAT DETAILS
Anixter Part No. Cable Dimensions Accomodated Min (mm) Max (mm)

Black Polythene E1D-A01 E1D-A02 E1D-A03 E1D-A04 E1D-A05 E1D-A06 E1D-A07 E1D-A08 Grey LSF E1D-A01LSF E1D-A02LSF E1D-A03LSF E1D-A04LSF E1D-A05LSF E1D-A06LSF E1D-A07LSF E1D-A08LSF 10 12 15 18 22 26 32 39 10 12 15 18 22 26 32 39 15 17 20 24 29 34 42 51 15 17 20 24 29 34 42 51

12

12:36

ACCESSORIES

Straight Cable Joints


Polyurethane Resin Encapsulation Suitable for 2, 3, 4 core XLPE/PVC SWA Copper Conductor Cables
Joints comply with BS6910 Part 1. Transparent shell to allow inspection of joint before application of resin. Joints utilise Two-Part Polyurethane resin to encapsulate, insulate and protect the jointed conductors. Resin and hardener are separated by a centre peelable seal in Twin Pack Laminated Sachet (completely enclosed mixing). Unmixed ingredients have shelf life of 24 months based on average UK temperature. Compression connectors for relevant conductor size are SJK1, SJK2, SJK3 and SJK4 kits. Armour bonds included in all kits. Simple to use - no special tools required. Supplied in resealable box.

Anixter Part No.

To Suit Conductor Size Two Core (mm2) Three Core (mm2) Four Core (mm2)

Shell Length (mm)

Internal Diameter (mm)

To Suit Cable Diameter (mm)

SJK1 SJK2 SJK3 SJK4 SJK5 SJK6 SJK7

1.5 to 4.0 6.0 to 25.0 35, 50 70, 95 120, 150, 185 240, 300 400

1.5 to 4.0 6.0, 10.0 16, 25 35, 50 70, 95, 120 150, 185, 240 300, 400

1.5, 2.5 4.0 to 10.0 16 25, 35, 50 70, 95, 120 150, 185 240, 300, 400

190 260 360 400 530 705 900

36 47 55 70 100 125 150

14.0 - 22.0 14.0 - 30.0 20.0 - 37.0 25.0 - 42.0 33.0 - 55.0 45.0 - 74.0 50.0 - 90.0

12

12:37

ACCESSORIES

Claw & Two Bolt Cleats Aluminium Alloy

Claw cleats for cable dimensions up to 51mm diameter. Two bolt cleats for cable dimensions 51mm and above.

CLEAT DETAILS
Anixter Part No. Cable Dimensions Accomodated Min (mm) Max (mm)

Claw Cleats E1B-BA01 E1B-BA02 E1B-BA03 E1B-BA04 E1B-BA05 E1B-BA06 E1B-BA07 E1B-BA08 E1B-BA09 Two Bolt Cleats E1B-BA10 E1B-BA11 E1B-BA12 E1B-BA13 E1B-BA14 E1B-BA15 51 57 64 70 76 83 57 64 70 76 83 89 10 13 16 19 22 25 32 38 44 13 16 19 22 25 32 38 44 51

12

12:38

ACCESSORIES

Cable Tiles & Warning Tapes


Plastic warning cable tiles and warning tapes for buried cables and have the following warning legend:

CAUTION CAUTION ELECTRIC CABLE BELOW

CABLE TILE DETAILS


Anixter Part No. Tile Dimensions (mm)

500315 500314 500313

1000 x 152 x 12 1000 x 244 x 12 1000 x 300 x 12

WARNING TAPE DETAILS


Anixter Part No. Tile Dimensions (mm)

515319

150mm wide x 100 microns thick (365m roll)

12

12:39

ACCESSORIES

11kV Indoor Termination Kits for 3 Core PILC/PICAS Cables


Scotchcast termination kits for use on 11kV indoor terminations for 3 core paper insulated, belted, lead sheath and corrugated aluminium sheath cables. Inorganic cold shrink silicone insulator. Cold pour Scotchcast resin to insulate and fill crotch area. Light weight assembly No special tools necessary Cold shrink technology, no heating required 11kV rated voltage 95kV nominal impluse withstand voltage 700C maximum operating temperature (accelerated ageing test to VDE0278) 1600C overload temperature (accelerated ageing test to VDE0278) Track resistance on silicone insulator as per ASTM 2303-68 @2.5kV - 30 hours @3.5kV - 10 hours Contents list of kit: - EPDM rubber pre-stretched tubes - Silicone Glove - Silicone pre-stretched tubes - Polyetherurethane resin - Self amalgamating tapes: - Stress control tape - EPR rubber tape - Silicone tape - Core separator - Cable cleaner - Gloves - Drawing instructions

Anixter Part No.

3M Part No.

Suitable for Conductor Sizes (mm2)

Approx. Kit Weight (kg)

E1DW-MT16

MT16

70-400

3.5

12

Scotchcast is a registered Trade Mark of 3M.

12:40

ACCESSORIES

11kV Indoor Termination Kits for 3 Core Polymeric Cables


Scotchcast termination kits for use on 11kV indoor terminations for 3 cores XLPE or EPR insulated cables. Inorganic cold shrink silicone insulator. Light weight assembly No special tools necessary Cold shrink technology, no heating required 11kV rated voltage 95kV nominal impluse withstand voltage 950C maximum operating temperature (accelerated ageing test to VDE0278) 2500C overload temperature (accelerated ageing test to VDE0278) Track resistance on EPDM insulator as per ASTM 2303-68 @2.5kV - 5 hours Contents list of kit: - EPDM rubber pre-stretched tubes - EPDM Rubber Glove - Self amalgamating tapes: - Semi-conducting tape - EPR rubber tape - Copper earth braid with integral lug - Constant force springs - Cable cleaner - Drawing instructions
Anixter Part No. 3M Part No. Suitable for Conductor Sizes (mm2) Approx. Kit Weight (kg)

Scotchcast is a registered Trade Mark of 3M.


E1DW-MT46 E1DW-MT47 E1DW-MT48 MT46 MT47 MT48

35-70 95-185 240-400

3.0 2.5 3.0

12

12:41

ACCESSORIES

3M Inline (Straight) Barrier Boot - MB63


Installation of cable termination to bushing connections in switchgear and cable end boxes for straight (in-line) applications. Suitable for paper or polymeric cables No special tools necessary Quick and simple installation Cold shrink technology, no heating required 11kV rated voltage (75kV BIL) Track resistant EPDM material For use on conductor sizes up to 630mm2 Dimensions of cable box and bushing dimensions should meet the following criteria: Dimension A B C D Description Phase - Earth clearance Phase - Phase clearance Bushing diameter 50mm up bushing Bushing length Min (mm) 18 36 24 50 Max (mm) 76* 127* 66 127*

* For dimensions greater than these no boots are required. NB: 3 barrier boots are provided in each kit.

Anixter Part No.

3M Part No.

Suitable for Conductor Sizes (mm2)

Approx. Kit Weight (kg)

"C" "D" "B" "A"

E1DW-MB63

MB63

Up to 630

0.8

12

12:42

ACCESSORIES

3M Pre-Moulded Right Angle Barrier Boot


Installation of cable termination to bushing connections in switchgear and cable end boxes for right angle applications. Consists of one large tubular opening to fit a porcelain bushing, and a smaller stepped tubular opening to cover the cable lugs and fit over the cable terminations. A sealing cover is also included which allows the connection bolts to be accessed after barrier boot has been slipped onto the bushing and termination. The sealing cover guarantees an electrical sealing of the live parts and is re-enterable. Suitable for paper or polymeric cables No special tools necessary Quick and simple installation Re-enterable design
Section XX X

"B"

"A"

"C"

No heating required 11kV rated voltage (95kV BIL) Track resistant EPDM material For use in conductor sizes 35 - 300mm2
"D" "E"

Circular Bushing

Elliptical Bushing

Dimensions of cable box and bushing dimensions should meet the following criteria: Dimension A B C D E Min (mm) Phase - Earth clearance 30 Phase - Phase clearance 70 Bushing length 110 Bushing diameter at length C (circular bushing) 45** Bushing circumference at length C 140** (eliptical bushing) Description Max (mm) 76* 127* 127* 50 157

* For dimensions greater than these no boots are required. ** Bushings below these minumum dimensions can be catered for using 3Ms MB64/S supplementary kit(s) in conjunction with the standard MB 64 kit. NB: 3 barrier boots are provided in each kit.
Anixter Part No. 3M Part No. Suitable for Conductor Sizes (mm2) Approx. Kit Weight (kg)

12

E1DW-MB64

MB64

35 - 300

1.05

12:43

ACCESSORIES Heat Shrinkable Tubing


(PICTURE UNAVAILABLE) General purpose heat-shrinkable polyolefin tubing. To identify and insulate cable cores on LV power cables. 55 to +120C operating temperature. 120C minimum shrink temperature. 20 kV/mm dielectric strength as per IEC60243 Standard 2:1 shrink ratio Flame retardant Good resistance to chemicals

Anixter Part No. E1CUCTW127-02 CTW127-06 CTW254-02 CTW254-06 CTW380-02 CTW380-06 CTW510-02 CTW510-02

Colour

Black Blue Black Blue Black Blue Black Black

Min. Expanded Diameter (D) mm 12.7 12.7 25.4 25.4 38.0 38.0 51.0 51.0

Max. Recovered Diameter (d) mm 6.4 6.4 12.7 12.7 19.1 19.1 25.4 25.4

Nominal Wall Thickness mm 0.64 0.64 0.89 0.89 1.02 1.02 1.14 1.14

To suit standard LV core size mm2 25 - 35 25 - 35 50 150 50 150 185 300 185 300 400 630 400 630

12

12:44