Easy-to-order temperature sensor assemblies to fit a variety of applications RTDs, thermocouples, and transmitters Fittings, connection heads, and thermowells included Tip-sensitive, high temperature, explosionproof, and flameproof options
To specify custom assemblies see: Probes Accessories Transmitters Section 3 Section 4 Section 5
Tip-sensitive spring loaded.........................................2-2 to 2-3 Direct immersion ............................................................2-4 to 2-5 Tip-sensitive with thermowells..................................2-6 to 2-7 High temp. with thermowells ....................................2-8 to 2-9 Explosionproof/Flameproof...................................2-10 to 2-15 Flameproof...................................................................2-16 to 2-21 Eurostyle........................................................................2-22 to 2-23 Specifying custom assemblies .............................................2-24
Page 2-1
Temperature Transmitters
CONDUIT THREAD
Overview
Fast and accurate readings from bearings, blocks, and other solids. Mincos spring-loaded holder ensures solid contact in drilled holes and has a built-in oil seal. The sensing probe features a copper alloy tip for quick response to temperature changes. Tip-sensitive RTD probe for use to 260C (500F) Spring-loaded holder with fluid seal Cast iron, stainless steel, or aluminum connection head
Mincos Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications. Special high-accuracy calibration: For high system accuracy, specify transmitters with matched calibration. Calibration data traceable to NIST will also be provided. Get more information on page 5-22.
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Holder: Stainless steel with Viton O-ring. Connection head: Cast iron, aluminum, or stainless steel. Pressure rating: 50 psi (3.4 bar). Insulation resistance: 100 megohms minimum at 100 VDC, leads to case. Connection: Terminal block for wires to AWG 14. Time constant: Typical value in moving water: Single element: 1.5 seconds. Dual element: 3.0 seconds.
Sensing Elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.5% at 0C Copper (0.00427 TCR) 10 0.2% at 25C (dual) 10 0.5% at 25C Nickel (0.00672 TCR) 120 0.5% at 0C Code PA PD PE CA CC NA
Page 2-2
14 NPT
CONDUIT THREAD
Overview
Fast and accurate readings from bearings, blocks, and other solids. Mincos spring-loaded holder ensures solid contact in drilled holes and has a built-in oil seal. The sensing probe features a copper alloy tip for quick response to temperature changes. Tip-sensitive Thermocouple for use to 260C (500F) Spring-loaded holder with fluid seal Cast iron, stainless steel, or aluminum connection head
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Holder: Stainless steel with Viton O-ring. Connection head: Cast iron, aluminum, or stainless steel. Pressure rating: 50 psi (3.4 bar). Insulation resistance: 10 megohms minimum at 100 VDC, leads to case. Ungrounded junctions only. Connection: Terminal block for wires to AWG 14. Time constant: Typical value in moving water: Grounded junction: 1.5 seconds. Ungrounded junction: 7 seconds
133 P 1
Temperature Transmitters
Mincos Temptran thermocouple transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
Conduit thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT C Connection head: C = Cast iron A = Aluminum S = Stainless steel To order sensor assembly, stop here. To order with transmitter, add: 190 Temptran transmitter model: 190 = TT190: Fixed Range, Hockey Puck 205 = TT205: Fixed Range, Miniature 520 = TT520: Programmable, Hockey Puck 521 = TT521: HART Programmable, Hockey Puck A Temperature range codes starting on page 5-20 or at www.minco.com/rangecode/ AS5192EU133P1C190A = Sample part number
Page 2-3
ASSEMBLIES
Temperature Transmitters
Minco's Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications. Special high-accuracy calibration: For high system accuracy, specify transmitters with matched calibration. Calibration data traceable to NIST will also be provided. Get more information on page 5-22.
Overview
Mount sensors directly in fluid flow for fast response. Probes are rated to 100 psi (6.9 bar). For use in non-corrosive fluids only. RTD probe for use to 260C (500F) Adjustable fluid seal fitting Cast iron, stainless steel, or aluminum connection head
Sensing elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) Copper (0.00427 TCR) (dual) Nickel (0.00672 TCR) 100 0.5% at 0C 10 0.2% at 25C 10 0.5% at 25C 120 0.5% at 0C Code PA PD PE CA CC NA
Page 2-4
14 NPT
CONDUIT THREAD
Overview
Mount sensors directly in fluid flow for fast response. Probes are rated to 100 psi (6.9 bar). For use in non-corrosive fluids only. Thermocouple for use to 260C (500F) Adjustable fluid seal fitting Cast iron, stainless steel, or aluminum connection head
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Fitting: Stainless steel, silicone rubber O-ring. Connection head: Cast iron, aluminum, or stainless steel. Pressure rating: 100 psi (6.9 bar). Insulation resistance: 10 megohms minimum at 100 VDC, leads to case. Ungrounded junctions only. Connection: Terminal block for wires to AWG 14. Time constant: Typical value in moving water: Grounded junction: 1.5 seconds. Ungrounded junction: 7 seconds.
215 P 1
Temperature Transmitters
Mincos Temptran thermocouple transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
Conduit thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT C Connection head: C = Cast iron A = Aluminum S = Stainless steel To order sensor assembly, stop here. To order with transmitter, add: 190 Temptran transmitter model: 190 = TT190: Fixed Range, Hockey Puck 205 = TT205: Fixed Range, Miniature 520 = TT520: Programmable, Hockey Puck 521 = TT521: HART Programmable, Hockey Puck A Temperature range codes starting on page 5-20 or at www.minco.com/rangecode/ AS5205EU215P1C190A = Sample part number
Page 2-5
ASSEMBLIES
Temperature Transmitters
Minco's Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications. Special high-accuracy calibration: For high system accuracy, specify transmitters with matched calibration. Calibration data traceable to NIST will also be provided. Get more information on page 5-22.
0.5" (12.7 mm) DIAMETER DIAMETER: 14 NPT THREAD: 0.625" (15.9 mm) 14 NPT THREAD: 0.750" (19.0 mm)
Overview
Thermowells protect sensors from the effects of fluid flow and pressure. These assemblies are spring-loaded for positive probe contact against the bottom of the thermowell. The probes copper alloy tip provides superior time response and reduces error from stem conduction. 316 stainless steel thermowell Tip-sensitive RTD probe for use to 260C (500F) Spring-loaded probe Cast iron, stainless steel, or aluminum connection head
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Connection head: Cast iron, aluminum, or stainless steel. Thermowell: 316 stainless steel. Extension: Stainless steel. Pressure rating: 7000 psi (483 bar) at 21C, reducing to 6300 psi (433 bar) at 260C. Standard U dimensions: 2.5, 4.5, 6.0, 7.5, 8.0, 10.5, 13.5, 16.5, and 22.5". Insulation resistance: 100 megohms minimum at 100 VDC, leads to case. Connection: Terminal block for wires to AWG 14. Time constant: 17 seconds typical in moving water.
Sensing elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.5% at 0C Copper (0.00427 TCR) 10 0.2% at 25C (dual) 10 0.5% at 25C Nickel (0.00672 TCR) 120 0.5% at 0C Code PA PD PE CA CC NA
Page 2-6
DIAMETER: 14 NPT THREAD: 0.625" (15.9 mm) 14 NPT THREAD: 0.750" (19.0 mm)
Overview
Thermowells protect sensors from the effects of fluid flow and pressure. These assemblies are spring-loaded for positive probe contact against the bottom of the thermowell. The probes copper alloy tip provides superior time response and reduces error from stem conduction. 316 stainless steel thermowell Tip-sensitive thermocouple for use to 260C (500F) Spring-loaded probe Cast iron, stainless steel, or aluminum connection head 135 U
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Connection head: Cast iron, aluminum, or stainless steel. Thermowell: 316 stainless steel. Extension: Stainless steel. Pressure rating: 7000 psi (483 bar) at 21C, reducing to 6300 psi (433 bar) at 260C. Standard U dimensions: 2.5, 4.5, 6.0, 7.5, 8.0, 10.5, 13.5, 16.5, and 22.5". Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Ungrounded junctions only. Connection: Terminal block for wires to AWG 14. Time constant: Typical value in moving water. Grounded junction: 17 seconds. Ungrounded junction: 22 seconds. P 1
Temperature Transmitters
Mincos Temptran thermocouple transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
Connection head: C = Cast iron A = Aluminum S = Stainless steel 1 Thermowell process thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT U Extension option: P = Coupling/nipple extension N = No extension U = Union/Nipple extension To order sensor assembly, stop here. To order with transmitter, add: 190 Temptran transmitter model: 190 = TT190: Fixed Range, Hockey Puck 205 = TT205: Fixed Range, Miniature 520 = TT520: Programmable, Hockey Puck 521 = TT521: HART Programmable, Hockey Puck A Temperature range codes starting on page 5-20 or at www.minco.com/rangecode/ AS5145EU135P1C1U190A = Sample part number
Page 2-7
ASSEMBLIES
DIAMETER: 14 NPT THREAD: 0.625" (15.9 mm) 14 NPT THREAD: 0.750" (19.0 mm)
Temperature Transmitters
Mincos Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications. Special high-accuracy calibration: For high system accuracy, specify transmitters with matched calibration. Calibration data traceable to NIST will also be provided. Get more information on page 5-22.
Overview
Sense temperature in high-pressure fluids and gases. These assemblies are spring-loaded for positive probe contact against the bottom of the thermowell. 316 stainless steel thermowell RTD probe for use to 550C (1022F) Spring-loaded probe Cast iron, stainless steel, or aluminum connection head
Note: For temperatures less than 260C (500F), assemblies using tip-sensitive sensors are recommended.
Specifications
Temperature range: Thermowell and sensor: -100 to 550C (-148 to 1022F). Connection head: Cast iron: 260C (500F) max. Aluminum: 316C (600F) max. Stainless steel: 121C (250F) max. Material: Probe: 316 stainless steel. Connection head: Cast iron, aluminum, or stainless steel. Thermowell: 316 stainless steel. Extension: Stainless steel. Pressure rating: 7000 psi (483 bar) at 21C, reducing to 2500 psi (172 bar) at 550C. Standard U dimensions: 2.5, 4.5, 6.0, 7.5, 8.0, 10.5, 13.5, 16.5, and 22.5". Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Connection: Terminal block for wires to 14 AWG. Time constant: 23 seconds typical in moving water.
Sensing elements
Element Platinum (0.00391 TCR) 100 0.1% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Code PB PD
Page 2-8
DIAMETER: 14 NPT THREAD: 0.625" (15.9 mm) 14 NPT THREAD: 0.750" (19.0 mm)
Overview
Sense temperature in high-pressure fluids and gases. These assemblies are spring-loaded for positive probe contact against the bottom of the thermowell.
Note: For temperatures less than 260C (500F), assemblies using tip-sensitive sensors are recommended.
Temperature Transmitters
Mincos Temptran thermocouple transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
316 stainless steel thermowell Thermocouple probe for use to 550C (1022F) Spring-loaded probe Cast iron, aluminum or stainless steel connection head
Specifications
Temperature range: Thermowell and sensor: -100 to 550C (-148 to 1022F). Connection head: Cast iron: 260C (500F) max. Aluminum: 316C (600F) max. Stainless steel: 121C (250F) max. Material: Probe: 316 stainless steel. Connection head: Cast iron, aluminum, or stainless steel. Thermowell: 316 stainless steel. Extension: Stainless steel. Pressure rating: 7000 psi (483 bar) at 21C, reducing to 2500 psi (172 bar) at 550C. Standard U dimensions: 2.5, 4.5, 6.0, 7.5, 8.0, 10.5, 13.5, 16.5, and 22.5". Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Ungrounded junctions only. Connection: Terminal block for wires to 14 AWG. Time constant: 60 seconds typical in moving water.
135 P 1
Conduit thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT C Connection head: C = Cast iron A = Aluminum S = Stainless steel 1 Thermowell process thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT U Extension option: P = Coupling/nipple extension N = No extension U = Union/Nipple extension To order sensor assembly, stop here. To order with transmitter, add: 190 Temptran transmitter model: 190 = TT190: Fixed Range, Hockey Puck 205 = TT205: Fixed Range, Miniature 520 = TT520: Programmable, Hockey Puck 521 = TT521: HART Programmable, Hockey Puck A Temperature range codes starting on page 5-20 or at www.minco.com/rangecode/ AS5165KU135P1C1U190A = Sample part number
Page 2-9
L REF.
CONDUIT THREAD
Overview
Explosionproof and flameproof rating for hazardous areas where accurate temperature sensing is critical. Tip sensitive, all stainless or MgO filled probes available Hazardous area rated High temp process temperature options (600C) available. Contact Minco for more information.
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel (tip sensitive models have copper alloy tip). Holder: Stainless steel. Connection head: Copper free aluminum alloy (CH104) 316L stainless steel (CH106). Pressure rating: See table on next page. Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Connection: Terminal block for wires to 14 AWG. Time constant: Typical value in moving water. Tip sensitive: Single element 1.5 seconds. Dual element 5 seconds. All stainless and MgO filled: 10 seconds.
Explosionproof and flameproof ratings: National and Canadian Electrical Code: Class I, Divisions 1 and 2, Groups B, C, and D, Class II, Groups E, F, and G, T6 (Ta = 40C), T2 (Ta = 260C). Ta limited to 160C for CSA Class II locations. National Electrical Code (Article 505): Class I, Zones 1 and 2, AEx d IIC, T6 (Ta =40C), T2 (Ta = 260C). Canadian Electrical Code (IEC 60079): Zones 1 and 2, Ex d IIC, T6 (Ta = 40C), T2 (Ta = 260C).
Page 2-10
Probe diameters Number of elements Tip-sensitive All stainless MgO filled (platinum only)
0.236" (6.0 mm) Single Dual AS700 AS701 AS702 AS703 AS704
0.250" (6.4 mm) Single Dual AS720 AS721 AS722 AS723 AS724 AS725
Pressure Rating 200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) None None
L REF.
Head
Code
4.4" (112 mm) CH104 0* 4.2" (106 mm) CH106 1* G 1/2 4.2" (107 mm) CH104 2* G 1/2 4.0" (101 mm) CH106 3* 1/ - 14 NPT 5.7" (144 mm) CH104 4 2 1/ - 14 NPT 5.4" (138 mm) CH106 5 2 G 1/2 5.7" (144 mm) CH104 6 G 1/2 5.4" (138 mm) CH106 7 1/ - 14 NPT 4.4" (112 mm) CH104 8** 2 1/ - 14 NPT 4.2" (106 mm) CH106 9** 2 * 0.250 diameter only for all stainless and MgO probes (not available in tip-sensitive, 0.215" diameter or 0.236" diameter probes).
** 0.236 and 0.250 diameters only for fixed spring-loaded fittings. Note: Connection head dimensions are found on pages 4-2 to 4-3.
- 14 NPT - 14 NPT
Sensing elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Code Single Dual PA PD PM PE PW CA NA NB CCCC NANA NBNB PAPA PDPD PMPM PEPE PWPW
Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.06% at 0C (Meets EN60751, Class A) Platinum (0.00385 TCR) Platinum (0.00375 TCR) Copper (0.00427 TCR) (dual) Nickel (0.00672 TCR) Nickel (0.00618 TCR) 100 0.5% at 0C 1000 0.12% at 0C 10 0.2% at 25C 10 0.5% at 25C 120 0.5% at 0C 100 0.22% at 0C
Page 2-11
ASSEMBLIES
Assembly numbers
CONDUIT THREAD
Overview
Explosionproof and flameproof rating for hazardous areas where accurate temperature sensing is critical. Tip sensitive, MgO filled probes available Hazardous area rated
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel (tip sensitive models have copper alloy tip). Holder: Stainless steel. Connection head: Copper free aluminum alloy (CH104) 316L stainless steel (CH106). Pressure rating: See table on next page. Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Ungrounded junctions only. Connection: Terminal block for wires to 14 AWG. Time constant: Typical value in moving water. Tip sensitive: Grounded 1.5 seconds. Ungrounded 7 seconds. MgO filled: Grounded: 1.5 seconds. Ungrounded: 5.0 seconds.
Explosionproof and flameproof ratings: National and Canadian Electrical Code: Class I, Divisions 1 and 2, Groups B, C, and D, Class II, Groups E, F, and G, T6 (Ta = 40C), T2 (Ta = 260C). Ta limited to 160C for CSA Class II locations. National Electrical Code (Article 505): Class I, Zones 1 and 2, AEx d IIC, T6 (Ta =40C), T2 (Ta = 260C). Canadian Electrical Code (IEC 60079): Zones 1 and 2, Ex d IIC, T6 (Ta = 40C), T2 (Ta = 260C).
Temperature Transmitters
Minco's Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
Contact Minco if transmitter is required
Page 2-12
CH104: Aluminum IP65, Type 3 and 4. CH106: 316L stainless steel IP66, Type 3, 4, and 4X. Fitting Welded Welded Welded Welded Adjustable spring-loaded Adjustable spring-loaded Adjustable spring-loaded Adjustable spring-loaded Fixed spring-loaded Fixed spring-loaded Process thread
1/ 2 1/ 2
Pressure Rating 200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) None None
L REF. 4.4" (112 mm) 4.2" (106 mm) 4.2" (107 mm) 4.0" (101 mm) 5.7" (144 mm) 5.4" (138 mm) 5.7" (144 mm) 5.4" (138 mm) 4.4" (112 mm) 4.2" (106 mm)
Head CH104 CH106 CH104 CH106 CH104 CH106 CH104 CH106 CH104 CH106
- 14 NPT - 14 NPT
* Welded fitting only available with 0.250 Mg0 filled probes [minimum insertion (2.5 63mm)] ** 0.236 and 0.250 diameters only for fixed spring-loaded fittings. Note: Connection head dimensions are found on pages 4-2 to 4-3.
Assembly numbers
Probe diameters Number of elements Tip-sensitive MgO filled 0.215" (5.5 mm) 0.236" (6.0 mm) Single Dual Single Dual AS766 AS767 AS706 AS707 AS708 AS709 0.250" (6.4 mm) Single Dual AS726 AS727 AS728 AS729
Junction types
Thermocouple Junction Chromel-Constantan Iron-Constantan Chromel-Alumel Copper-Constantan Code Single Dual E J K T EE JJ KK TT
100 P 3
Page 2-13
ASSEMBLIES
Temperature Transmitters
CONDUIT THREAD
Mincos Temptran RTD transmitters provide a 4 to 20 mA or HART Protocol signal that can be sent over long distances with a simple 2-wire system. Leadwires: 2-lead RTD: TT211, TT520, TT521 3-lead RTD: TT176, TT520, TT521 4-lead RTD: TT520, TT521 Physical: Epoxy potted for moisture resistance. See Section 5 for complete temperature transmitter specifications.
Overview
Tip sensitive, all stainless or MgO filled RTD probe Temptran transmitter for long signal path
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel (tip sensitive models have copper alloy tip). Holder: Stainless steel. Connection head: Copper free aluminum alloy (CH104) 316L stainless steel (CH106). Pressure rating: See table on next page. Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Connection: Terminal block for wires to 14 AWG. Time constant: Typical value in moving water. Tip sensitive: Single element 1.5 seconds. Dual element 5 seconds. All stainless and MgO filled: 10 seconds. Explosionproof and flameproof ratings: National and Canadian Electrical Code: Class I, Divisions 1 and 2, Groups B, C, and D, Class II, Groups E, F, and G, T6 (Ta = 40C), T2 (Ta = 260C). Ta limited to 160C for CSA Class II locations. National Electrical Code (Article 505): Class I, Zones 1 and 2, AEx d IIC, T6 (Ta =40C), T2 (Ta = 260C). Canadian Electrical Code (IEC 60079): Zones 1 and 2, Ex d IIC, T6 (Ta = 40C), T2 (Ta = 260C).
Page 2-14
CH104: Aluminum IP65, Type 3 and 4. CH106: 316L stainless steel IP66, Type 3, 4, and 4X. Fitting Process thread Pressure Rating L REF. Head Code Minimum Insertion Depth (mm) 0* 47 1* 47 2* 47 3* 47 4 27 27 27 27 27 27
Welded Welded Welded Welded Adjustable spring-loaded Adjustable spring-loaded Adjustable spring-loaded Adjustable spring-loaded Fixed spring-loaded Fixed spring-loaded
1/ 2 1/ 2
- 14 NPT - 14 NPT
200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 200 psi (13.8 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) 50 psi (3.4 bar) None None
4.4" (112 mm) 4.2" (106 mm) 4.2" (107 mm) 4.0" (101 mm) 5.7" (144 mm)
- 14 NPT
5.4" (138 mm) CH106 5 5.7" (144 mm) CH104 6 5.4" (138 mm) CH106 7 4.4" (112 mm) CH104 8** 4.2" (106 mm) CH106 9**
G 1/2 G 1/2
1/ 2
- 14 NPT - 14 NPT
1/ 2
* 0.250 diameter only for all stainless and MgO probes. (not available in tip-sensitive, 0.215" diameter or 0.236" diameter probes) ** 0.236 and 0.250 diameters only for fixed spring-loaded fittings. Note: Connection head dimensions are found on page 4-2.
Sensing elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.06% at 0C (Meets EN60751, Class A) Platinum (0.00385 TCR) 100 0.5% at 0C Platinum (0.00375 TCR) 1000 0.12% at 0C Copper (0.00427 TCR) 10 0.2% at 25C Nickel (0.00672 TCR) 120 0.5% at 0C Nickel (0.00618 TCR) 100 0.22% at 0C
Specifications subject to change
Code: Single PA PD PM PE PW CA NA NB
Page 2-15
0344
PROCESS THREAD: - 14 NPT (SHOWN) OR ISO 228/1-G PROBE
II 2 G Ex e II
ATEX
CONDUIT THREAD
Overview
Flameproof sensors are designed to contain an explosion as well as prevent the transmission of an explosion to the surrounding atmosphere. These sensors are suitable for use in Zone 1 or Zone 2. Approved for use in hazardous locations defined by IEC/EN 60079-0 and IEC/EN 60079-1, ATEX directive 94/9/EC (KEMA 03 ATEX 2389 X), and II 2 G Ex d IIC T6 Features tip-sensitive, all stainless or MgO filled RTD probe for fast response Spring-loaded holder ensures good probe contact U.S. or metric threads
Pressure rating: Spring-loaded holder: 50 psi (3.4 bar). Fluid seal fitting: 100 psi (6.9 bar). Insulation resistance: 100 megohms min. at 100 VDC, leads to probe case. Connection: Terminal block for wires up to AWG 14. Time constant: Typical value in moving water. Tip sensitive: Single element 1.5 seconds. Dual element 7 seconds. All stainless and MgO filled: 10 seconds.
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Tip-sensitive probe: Stainless steel with copper alloy tip. All stainless RTD: Stainless steel. MgO filled RTD: Inconel. Fittings: Stainless steel. Connection head: CH356: 316L stainless steel IP66, Type 3, 4, and 4X. CH357: Aluminum alloy IP65, Type 3 and 4. CH358: Epoxy coated aluminum alloy IP66, Type 3, 4, and 4X.
Page 2-16
Fitting options
Fitting Fluid Seal Fluid Seal Set screw spring-loaded Set screw spring-loaded Fixed spring-loaded Welded Welded Release knob spring-loaded Release knob spring-loaded
ASSEMBLIES
Process Thread
1/ 2
L REF. CH356 4.3" (108mm) 4.1" (103 mm) 5.3" (135 mm) 5.0" (128mm) 4.5" (115 mm) 4.2"(107 mm) 4.0" (101 mm) 5.4" (137 mm) 5.2" (132 mm) CH357/CH358 4.6" (116 mm) 4.4" (111 mm) 5.6" (143 mm) 5.4" (136 mm) N/A 4.5" (115 mm) 4.3" (109 mm) 5.7" (145 mm) 5.5" (140 mm)
- 14 NPT
1/ 2
G
1/ 2
- 14 NPT
1/ 2
G
1/ 2 1/ 2
G 1/2
1/ 2
* Not available with CH356 stainless steel connection head. ** 0.250" (6.4mm) for all stainless and MgO only (not available in tip-sensitive or 0.236" diameter models).
Notes: CH356: 316L stainless steel IP66, Type 3, 4, and 4X. CH357: Aluminum alloy IP65, Type 3 and 4. CH358: Epoxy coated aluminum alloy IP66, Type 3, 4, and 4X. Get more information on connection heads on pages 4-2 to 4-3.
Sensing elements
Element Platinum (0.00392 TCR) 100 0.5% at 0C Code Single Dual PA PD PM PE PW CA NA NB CCCC NANA NBNB PAPA PDPD PMPM PEPE PWPW
Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.06% at 0C (Meets EN60751, Class A) Platinum (0.00385 TCR) Platinum (0.00375 TCR) Copper (0.00427 TCR) (dual) Nickel (0.00672 TCR) Nickel (0.00618 TCR) 100 0.5% at 0C 1000 0.12% at 0C 10 0.2% at 25C 10 0.5% at 25C 120 0.5% at 0C 100 0.22% at 0C
Conduit thread: 3 = 1/2 - 14 NPT 4 = 3/4 - 14 NPT 5 = M20 x 1.5 AS8004PD100X3 = Sample part number
Specifications subject to change
Page 2-17
0344
PROCESS THREAD: - 14 NPT (SHOWN) OR ISO 228/1-G PROBE
II 2 G Ex e II
ATEX
CONDUIT THREAD
Overview
Flameproof sensors are designed to contain an explosion as well as prevent the transmission of an explosion to the surrounding atmosphere. These sensors are suitable for use in Zone 1 or Zone 2. Approved for use in hazardous locations defined by IEC/EN 60079-0 and IEC/EN 60079-1, ATEX directive 94/9/EC (KEMA 03 ATEX 2389 X), and II 2 G Ex d IIC T6 Features tip-sensitive or MgO filled thermocouple probe for fast response Spring-loaded holder ensures good probe contact U.S. or metric threads
Time constant: Typical value in moving water. Tip sensitive: Single element 1.5 seconds. Dual element 7 seconds. All stainless and MgO filled: 10 seconds.
Temperature Transmitters
Mincos Temptran thermocouple transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications.
Contact Minco if transmitter is required.
Refer to Mincos Application Aid #19 entitled Specifying Temperature Sensors for Hazardous Areas for more information on how to classify a hazardous area, methods of protection, and the various standards and agencies (including FM, CSA, CENELEC and ATEX). Application Aid #19 is available at www.minco.com/sensoraid/.
Page 2-18
Fitting options
Fitting Fluid Seal Fluid Seal Set screw spring-loaded Set screw spring-loaded Fixed spring-loaded Welded Welded Release knob spring-loaded Release knob spring-loaded Process Thread
1/ 2
- 14 NPT
1/ 2
G
1/ 2
0* 1* 2 3 4 6** 7** 8 9
- 14 NPT
1/ 2
5.3" (135 mm) 5.0" (128mm) 4.5" (115 mm) 4.2"(107 mm) 4.0" (101 mm) 5.4" (137 mm) 5.2" (132 mm)
5.6" (143 mm) 5.4" (136 mm) N/A 4.5" (115 mm) 4.3" (109 mm) 5.7" (145 mm) 5.5" (140 mm)
G
1/ 2 1/ 2
- 14 NPT - 14 NPT
G 1/2
1/ 2
- 14 NPT
G 1/2
* Not available with CH356 stainless steel connection head. ** 0.250" (6.4mm) for MgO only (not available in tip-sensitive or 0.236" diameter models).
Notes: CH356: 316L stainless steel IP66, Type 3, 4, and 4X. CH357: Aluminum alloy IP65, Type 3 and 4. CH358: Epoxy coated aluminum alloy IP66, Type 3, 4, and 4X. Get more information on connection heads on pages 4-2 to 4-3.
Junction types
Thermocouple Junction Chromel-Constantan Iron-Constantan Chromel-Alumel Copper-Constantan Code Single Dual E J K T EE JJ KK TT
450 P 3
Conduit thread: 3 = 1/2 - 14 NPT 4 = 3/4 - 14 NPT 5 = M20 x 1.5 AS8064EEU450P3 = Sample part number
Specifications subject to change
Page 2-19
ASSEMBLIES
Code
0344
II 2 G Ex e II
PROBE
ATEX
Overview
Flameproof sensors are designed to contain an explosion as well as prevent the transmission of an explosion to the surrounding atmosphere. These sensors are suitable for use in Zone 1 or Zone 2. Approved for use in hazardous locations defined by IEC/EN 60079-0 and IEC/EN 60079-1, ATEX directive 94/9/EC (KEMA 03 ATEX 2389 X), and II 2 G Ex d IIC T6
CONDUIT THREAD
Temperature Transmitters
Mincos Temptran RTD transmitters provide a 4 to 20 mA or HART Protocol signal that can be sent over long distances with a simple 2-wire system. Leadwires: 2-lead RTD: TT211, TT520, TT521 3-lead RTD: TT176, TT520, TT521 4-lead RTD: TT520, TT521 Physical: Epoxy potted for moisture resistance. See Section 5 for complete temperature transmitter specifications.
Features tip-sensitive, all stainless or MgO filled RTD probe for fast response Spring-loaded holder ensures good probe contact U.S. or metric threads
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Tip-sensitive probe: Stainless steel with copper alloy tip. All stainless RTD: Stainless steel. MgO filled RTD: Inconel. Fittings: Stainless steel. Connection head: CH356: 316L stainless steel IP66, Type 3, 4, and 4X. CH357: Aluminum alloy IP65, Type 3 and 4. CH358: Epoxy coated aluminum alloy IP66, Type 3, 4, and 4X. Pressure rating: Spring-loaded holder: 50 psi (3.4 bar). Fluid seal fitting: 100 psi (6.9 bar). Insulation resistance: 100 megohms min. at 100 VDC, leads to probe case. Connection: Terminal block for wires to 14 AWG. Time constant: Typical value in moving water. Tip sensitive: Single element 1.5 seconds. All stainless and MgO filled: 10 seconds.
Page 2-20
Fitting options
Fitting Fluid Seal Fluid Seal Set screw spring-loaded Set screw spring-loaded Fixed spring-loaded Welded Welded Release knob spring-loaded Release knob spring-loaded Process Thread - 14 NPT G 1/2 1/ - 14 NPT 2 G 1/2 1/ - 14 NPT 2 1/ - 14 NPT 2 G 1/2 1/ - 14 NPT 2 G 1/2
1/ 2
L REF. CH356 4.3" (108mm) 4.1" (103 mm) 5.3" (135 mm) 5.0" (128mm) 4.5" (115 mm) 4.2"(107 mm) 4.0" (101 mm) 5.4" (137 mm) 5.2" (132 mm)
CH357/CH358 4.6" (116 mm) 4.4" (111 mm) 5.6" (143 mm) 5.4" (136 mm) N/A 4.5" (115 mm) 4.3" (109 mm) 5.7" (145 mm) 5.5" (140 mm)
** 0.250" (6.4mm) for all stainless and MgO only (not available in tip-sensitive or 0.236" diameter models).
CH357 Aluminum 0.236" (6.0mm) 0.250" (6.4mm) Single Single AS830 AS840 AS832 AS842 AS834 AS844
CH358 Epoxy Coated 0.236" (6.0mm) 0.250" (6.4mm) Single Single AS860 AS870 AS862 AS872 AS864 AS874
Notes: CH356: 316L stainless steel IP66, Type 3, 4, and 4X. CH357: Aluminum alloy IP65, Type 3 and 4. CH358: Epoxy coated aluminum alloy IP66, Type 3, 4, and 4X. Get more information on connection heads on pages 4-2 to 4-3.
Sensing elements
RTD sensing element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) 100 0.5% at 0C Code PA PD PE
Page 2-21
Eurostyle Sensors
THERMOWELL LENGTH U
Overview
These low priced assemblies come complete with thermowells, spring-loaded probes, and connection heads. They provide accurate sensing and quick response in liquid or air streams. Specify U.S. or metric thread for global compatibility. Compact, economical RTD or thermocouple assembly Metric straight thread or U.S. tapered thread Tip-sensitive probe for use to 260C (500F) Optional European Form B connection head to DIN 43729 Stainless steel thermowell
Specifications
Temperature range: -50 to 260C (-58 to 500F). Material: Probe: Stainless steel with copper alloy tip. Connection head: Cast aluminum. Thermowell: 300 series stainless steel. Pressure rating: 2755 psi (190 bar) at 25C, reducing to 493 psi (34 bar) at 600C. Insulation resistance: 10 megohms min. at 100 VDC, leads to case. Ungrounded junctions only on thermocouples. Connection: Terminal block for wires to 14 AWG.
Temperature Transmitters
Mincos Temptran RTD transmitters provide a 4 to 20 mA signal or HART Protocol that can be sent over long distances with a simple 2-wire system. See Section 5 for complete temperature transmitter specifications. Special high-accuracy calibration: For high system accuracy, specify transmitters with matched calibration. Calibration data traceable to NIST will also be provided. Get more information on page 5-22.
Page 2-22
RTD sensing element Platinum (0.00392 TCR) 100 0.5% at 0C Platinum (0.00385 TCR) 100 0.1% at 0C (Meets EN60751, Class B) Platinum (0.00385 TCR) Copper (dual) (0.00427 TCR) Nickel (0.00672 TCR) 100 0.5% at 0C 10 0.2% at 25C 10 0.5% at 25C 120 0.5% at 0C
Code PA PD PE CA CC NA
AS5245
135
Assembly number: AS5245: Single junction TC AS5246: Dual junction TC Junction type: E = Chromel-Constantan J = Iron-Constantan K = Chromel-Alumel T = Copper-Constantan Junction grounding: G = Grounded U = Ungrounded TW length U in 0.1" increments Specify in 0.1" increments [Ex: 135 = 13.5 inches (343 mm)]
Conduit thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT 3 = PG cable gland (Eurostyle only) E Connection head: A = Standard aluminum head E = Eurostyle aluminum head 3 TW process thread: 1 = 1/2 - 14 NPT 2 = 3/4 - 14 NPT 3 = ISO 228/1 - G 1/2 To order sensor assembly, stop here. To order with transmitters, add: TT190 Temptran model: 190 = TT190: Fixed Range, Hockey Puck 520 = TT520: Programmable, Hockey Puck 521 = TT521: HART Programmable, Hockey Puck A Temperature range codes starting on page 5-20 or at www.minco.com/rangecode/ AS5245EG135P3E3190A = Sample part number
Page 2-23
ASSEMBLIES
Sensing elements
The standard assemblies in this section will fit a wide variety of installations. However, for more versatility you can create new assemblies from the probes, accessories, and transmitters in the pages listed.
Temperature rating Correct pipe threads for fitting and conduit Number of terminals or wire nuts Hazardous area requirements
5. Install a transmitter
Transmitters convert sensor output to a 4 to 20 mA current signal, immune to leadwire resistance. See Section 5 for RTD and thermocouple transmitters. Factors to consider are:
2. Add a fitting
See Section 4 for probe mounting fittings. Adjustable fittings, combined with cut-to-length probes, allow instant fabrication of assemblies to any length required. Included are spring-loaded holders, pressure fittings, and bayonet-style fittings. Factors to consider are: Temperature rating Probe diameter Correct NPT threads Pressure ratings Compatibility with environment
Transmitter accepts sensor input Transmitter fits connection head Ambient temperature range acceptable
3. Select a thermowell
Thermowells protect sensors from the effects of fluid flow and pressure. See Section 4 for a variety of well styles and materials. Factors to consider are: Pressure rating Compatibility with fluid media Insertion depth Correct NPT thread
Thermowell drawings show an adder to convert thermowell length U to insertion depth D. Then use D plus the fitting adder A to find total probe length L.
THERMOWELL LENGTH U
ADDER A
Page 2-24