SECTION 16521 EXTERIOR LIGHTING PART 1 - GENERAL

Read and conform to all electrical sections of these specifications,the general instructions for electrical division, section 16010, apply to and form part of all electrical sections. These shall be read in conjunction with design drawings.

1.01

RELATED DOCUMENTS

A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 16 Specification Sections, apply to this Section. B. Refer section 16511-Interior Lighting C. Refer External, Landscape, Faade & Electrical lighting layouts.

1.02

SUMMARY

A. This Section includes only power supply, installation, testing & commissioning of exterior lighting comprising of external, landscape and faade lighting. Refer separate specifications (by specialist) for Light fixtures, lamps, ballasts, poles and accessories required to meet a complete system. B. Refer Electrical lighting layout drawings. C. Provide 5% spare lamps for all of fixtures (minimum 2 Nos. for each type). D. Refer section 16511-Interior Lighting for all relevant Standards & Codes. E. CODES AND STANDARDS CIBSE BS 7671 BS 7430 BS 6141 Lighting Guides Requirements for electrical installation. Earthing system Insulated cables and flexible cords for use in high temperature zones.

WB4733 Al Ghurair City Expansion Phase II

16521 April 2008 Rev - 0

Exterior Lighting Page 1 of 8

1.03

SUBMITTALS

A. General: Submit the following in accordance with Conditions of Contract and Division 1 Specification Sections. B. Product data describing fixtures, lamps, ballasts, and emergency lighting units. Arrange product data for fixtures in order of fixture designation. Include data on features and accessories and the following information: 1. Outline drawings of fixtures indicating dimensions and principal features. 1.04 QUALITY ASSURANCE Design, manufacture, testing and method of installation of all apparatus and materials furnished under requirement of these specification shall conform to latest publications or standard rules of the following: a) DEWA regulations for electrical installation works b) Regulations for Electrical equipment of building IEE, BS London c) British Standards. A. The Quality Control/Quality Assurance duties shall be performed by the Contractor. The system of quality control verification shall be in accordance with ISO 9000 standards of quality assurance.

B. Manufacturers Qualifications: Firms experienced in manufacturing fixtures that are similar to those indicated for this Project and that have a record of successful in-service performance. C. Lamps Manufacturers : 1. General Electric 2. Osram 3. Philips USA Germany Holland

Lamps of one type to be supplied from one manufacturer and from the same production run.

PART 2 - PRODUCTS Note: Refer section 16511-Interior Lighting for all relevant Standards,
WB4733 Al Ghurair City Expansion Phase II 16521 April 2008 Rev - 0 Exterior Lighting Page 2 of 8

Codes and Data unless specified otherwise or recommended by approved manufacturer.. 2.01 FIXTURES:

A. Lighting fixtures schedule shall be as shown on Luminaires schedule/ specifications issued separately by ID, Facade & Land scape designer . B. All luminaires shall carry approved certification as appropriate. C. All luminaries shall be fully compliant with relevant codes, related reports and codes of practices prevalent in the industry. D. Luminaires enclosures shall generally be IP 65 (Weather proof) when located in external out door location, however if instructed otherwise to suit any specific requirement it shall be binding on the contractor to comply accordingly. E. All external luminaire must be suitable to operate at 50C ambient and must be anti- corrosive. F. Pertaining to specific requirements on flame propogation & flammability of transluscent covers, contractor shall be liable to provide material test certificates adhering to BS 2782. G. Skirted porcelain type lamp holders suiting to screw cap lamps shall be used unless other wise instructed or recommended by the approved manufacturer for their specific fixture.. H. Luminaires with & without ballasts or transformers shall generally be suitable for direct mounting on normally flammable surfaces unless instructed other wise. I. Reflectors, diffusers, covers & outer finishes shall be clean at the time of completion. J. Ballasts for fluorescent lamps shall be high power factor and compliant to relevant codes & standards. 2.02 LUMINAIRES SCHEDULES

A. Refer light fittings schedule issued by specialist lighting designers. B. General Description: 1. EXTERNAL LUMIAIRES All external luminaries compliant to their specific data sheets / specifications in line with the schedule shall be supplied & installed. 2. WATER PROOF LUMINAIRES

WB4733 Al Ghurair City Expansion Phase II

16521 April 2008 Rev - 0

Exterior Lighting Page 3 of 8

Light fittings exposed to weather conditions or other notified specific compliance areas shall be IP 65/67 or as instructed other wise by consultant or recommended by approved manufacturer. 3. DISCHARGE LUMINAIRES a. Contractor to supply & install luminaries in line with the lay out, schedule & specifications. b. Luminaires should be complete in all respect i.e control gear, lamps, diffusers, mounting brackets, columns (if applicable) and any other accessories deemed necessary for an appropriate installation. c. One or more lamps as per the requirement of the approved luminaire of the type as appropriate MBF,MBI,MH etc. shall be provided. 4. FLAME PROOF LUMINAIRES All flame proof luminaries in hazardous areas or as specified/instructed shall be fully compliant to AUJ, BS 229, BS889 & any other applicable relevant standard. Minimum rated for IP65 2.03 COLUMNS & BOLLARDS a.Appropriate approved columns, bollards as specified by specialist designer shall be installed in line with manufacturers recommendations and Engineers acceptance complete with their bases and all other related accessories. b. Bond metal parts of columns & bollards to earthing terminal. c. Generally earthing conductor same size as live conductors shall be provided to connect luminaire to earthing terminal for proper protection.

2.04

AIRCRAFT WARNING LUMINAIRES: Note: Lights shall have to be Civil Aviation Authority compliant and the contractor shall be responsible to obtain necessary approvals prior to installation.

A. B.

Aircraft warning light shall be supplied, installed and commissioned by MEP Contractor in Compliance with Civil Aviation requirements. The system consist of high intensity strobe light on roof, medium intensity white light along the elevation as shown on drawings, and lighting control panels. System shall be integrated to BMS. Medium Intensity White Lighting System
16521 April 2008 Rev - 0 Exterior Lighting Page 4 of 8

C.

WB4733 Al Ghurair City Expansion Phase II

.1

Applicable specifications Certified to: FAA Advisory Circular AC 150/5345-43E Compliant: ICAO Annex 14 Transport Canada TP 382E DGAC of Mexico

.2

System Description The Medium Intensity White Lighting System shall utilize a white strobe light for daytime and nighttime marking. The flash head shall be powered and controlled by a power supply that can be mounted remotely at the base of the structure. The power supply shall constantly monitor the operation of the system, and provides alarm contact closure upon any failure. The system shall automatically switches between day and night intensities by use of a calibrated photocell. The flash heads shall incorporate a light blocking strip that minimizes ground scatter light, resulting in a community friendly lighting system.

.3 .4

Flash head Internally triggered Xenon strobe tubes shall be utilized for long-life and maximum efficiency, without creating corrosive ozone Parabolic reflector/linear strobe tubes optics combination provides very precise optics and blocks ground scatter light in both red and white operation Safety interlock switch included No moving parts High temperature, UV resistant acrylic used for flash head lens Photometric Performance: a. Day- 200,000 +/- 25% effective candelas b. Twilight- 20,000 +/-25% effective candelas c. Night- 2,000 +/-25% effective candelas d. Night/ICAO- 4,000 +/-25% effective candelas e. Photometric control shall be by means of two photo cells with the following sensitivities: i. Twilight range of 350-650 lux ii. Night range of 20-50 lux f. 120 deg. Horizontal beam coverage g. 3 deg. Vertical beam width

.5

Power Supply Provides power electronics, timing circuitry, and monitoring for lighting
16521 April 2008 Rev - 0 Exterior Lighting Page 5 of 8

WB4733 Al Ghurair City Expansion Phase II

D. .1

system Automatic day/night intensity control Manual intensity override Easily accessible components Plug-in circuit cards Fail safe monitoring system with three remote alarm contacts Low power consumption Lighting Control Compliance Applicable FAA and ICAO Standards

.2

Technical Data Lighting controls shall combine digital circuitry with rugged electromechanical hardware to yield the industrys most comprehensive obstruction lighting controls. The system shall be modular design allows for custom controls for almost any combination of flashing red beacons and sidelights. The panel shall have outdoor housing and a calibrated photocell for automotive day/night switching. A photocell override switch shall be provided, facilitating troubleshooting or maintenance. All controls shall provide comprehensive status indicators and alarm contacts for easy connection to remote monitoring systems.

.3

Features Controls for multiple beacons flash all beacons simultaneously per FAA and ICAO specifications Lightning protection provided by: Circuit breaker protection to all tower lighting circuits MOV surge suppressors on all inputs, outputs, and photocell lines Torroidal current sensors isolate tower lines from monitoring circuitry Load balance resistor capability Boost Transformer(s) capability shall be provided to reduce wire gauge required to power beacons

.4

Alarm Contacts/Control Status Individual alarm contacts and control status shall be provided for: Control power failure Day/night mode status
16521 April 2008 Rev - 0 Exterior Lighting Page 6 of 8

WB4733 Al Ghurair City Expansion Phase II

Each flashing red beacon Each level of steady burning obstruction lights Flasher By-Pass alarm/status for each beacon

Number of lamps being monitored can easily be changed by setting dip-switches Control cables shall be capable of running the whole distance between the control panel and the luminaries. Bi-color red/green LED status indicators provide instant indication of alarm and control status Normally open and normally closed alarm contracts are both available Primary and auxiliary alarm contacts shall be provided.

PART 3 - EXECUTION 3.01 INSTALLATION

A. Submit method statement for installation & testing of light fittings.


WB4733 Al Ghurair City Expansion Phase II 16521 April 2008 Rev - 0 Exterior Lighting Page 7 of 8

B. Submit complete details of lighting controls and respective interfaces of approved fittings. C. Furnish and install external lighting fittings of the types specified and in the positions indicated on the drawings. Check all requirements regarding conduit runs and positions and the casting in of conduit. D. The contractor shall also be responsible for the installation and wiring of the external lighting installation as shown on the drawing and in accordance with the schedule of light fittings. E. Each mounting bracket pole shall be fitted with a fuse unit of approved manufacturer connecting to the lighting units mounted on the bracket. F. Lighting installation shall be complete in all respect including but not limited to the following: Light fittings, Lamps, Control gear, ducting/conduiting, conduit boxes/terminal boxes, Cabling/wiring, switching accessories & protective circuiting etc.

3.02

FIELD QUALITY CONTROL Replace damaged fixtures and

A. Inspect each installed fixture for damage. components. 3.03 ADJUSTING AND CLEANING

A. Clean fixtures upon completion of installation. Use methods and materials recommended by manufacturer. B. Adjust amiable fixtures to provide required light intensities.

END OF SECTION

WB4733 Al Ghurair City Expansion Phase II

16521 April 2008 Rev - 0

Exterior Lighting Page 8 of 8