ST-1 & 2
CLASS A SYSTEM
Case-1 ; Considering only leakage through the Door at the ST-1 area
Double Door area ( only at Ground floor)
Height-H/(m)
=
Width-D/(m)
=
Total No of Door =
Total Area
=
Leakage factor for Double Door is , K
Air Flow rate Q , as per BS 5588
Q=0.83xAxP^0.5
Q=0.83x(1X0.03)x50^0.5
2.2
2.2
1
4.84
0.03
m
m
Nos
m2
Q1
0.18 m /s
Single Door Area (all the floor apart from Ground Floor )
Height-H/(m)
=
2.2 m
Width-D/(m)
=
1.1 m
Total No of Door =
29 Nos
2
Total Area
=
70.18 m
Leakage factor for single Door is ,
K
0.01
Air Flow rate Q , as per BS 5588
Q=0.83xAxP^0.5
Q=0.83x(29X0.01)x50^0.5
3
Q2
1.70 m /s
Total Air Flow rate for ST-01
Q3
=
Q1+Q2
m3/s
Q3
=
0.18+1.7
3
1.88 m /s
3,980.66 cfm
3
Increase by 50%
2.82 m /s
Q3
=
5,970.99 cfm
Case-2 ; Considering one single door is opened (Class A system)
Single Door Area
Height-H/(m)
Width-D/(m)
=
=
Total area A
=
From the BS5588 ,velocity is to be 0.75m/s
2.2 m
1.1 m
2.42 sqm
V =
0.75
Q4= AV
Q4= 2.42X0.75
Q4=
1.815
3,846.97
m/s
m3/s
m3/s
cfm
9,817.96 cfm
3
0.69 m /s
1,472.69 cfm
3
Total Volume Flow Rate of the Fan should be
5.33 m /s
11,290.65 cfm
According to the BS 5588 Staircase pressurization fan is to be single speed 1hr fire rating @300C
a) To calculate pressure required in stairwell to exhaust 1.815 m3/s to atmosphere via fire floor
Area of single leaf door=2.2X1.1=2.42 sq.m
Area of exhaust vent = 1.815/2.5 =0.726 sq.m
A.E = (1/A1^2+1/A2^2)^-0.5
= (1/2.42^2+1/0.726^2)^-0.5
=
0.70 sq.m
P1=(Q/(0.83XA.E))^2
= (1.815/(0.83X0.7))^2
=
9.758902835 Pa
This is more than covered by 50 Pa
b) To calculate area of pressure relief
Quantity of air to be wasted = 5.33 - 2.82
3
=
2.51 m /s
Area of pressure relief = Q/(0.83XP^0.5)
= 2.51 / (0.83X50^0.5)
=
0.428 sq.m
Let Height of Pressure relief damper = 0.7 m
then Width will be = 0.428 / 0.7 = 0.62 m, say 0.65m
Width/(mm)
1600
1550
1500
1450
1400
1350
1300
1250
1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
500
350
Height/(mm)
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
200
200
Volume flow
Rate/(cfm)
11,310.00
10,933.00
10,556.00
10,179.00
9,802.00
9,425.00
9,048.00
8,671.00
8,294.00
7,917.00
7,540.00
7,163.00
6,786.00
6,409.00
6,032.00
5,655.00
5,278.00
4,901.00
4,524.00
4,147.00
3,770.00
3,393.00
3,016.00
2,639.00
2,262.00
1,885.00
1,508.00
1,131.00
754.00
377.00
Length(m)
10
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
10
8
54
Fittings
Size
Elbow 1600x500
Reducer
Qty
2
29
Eq.
Diameter(De)
m
0.939
0.926
0.913
0.900
0.886
0.872
0.857
0.843
0.827
0.812
0.795
0.779
0.762
0.744
0.726
0.706
0.687
0.666
0.644
0.622
0.598
0.573
0.547
0.518
0.488
0.455
0.420
0.381
0.337
0.286
SAT(sound attonuator)
VAV
Flexible duct
0
0
0
0.3inch/100ft
sub total
70
0
0.00
89.14
VCD Size
Various
Qty
grilles
Various
Qty
197.20 Pa
39.44 Pa
237 pa
^0.126 ln(0.33R/W)]
Friction loss
pa/m
inch/100ft
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.57
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
0.07
TOTAL
Total
Friction
Loss(Pa)
5.740
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
2.296
5.740
4.592
78.064
=
=
Total area A
=
From the BS5588 ,velocity is to be 0.75m/s
2.2 m
1.1 m
2.42 sqm
V =
0.75
Q4= AV
Q4= 2.42X0.75
Q4=
1.815
3846.97
m/s
m3/s
m3/s
cfm
Q= Q3+Q4
Q= 0.62+1.815
Q=
2.607
Q=
5,526
5,526.31
0.39
828.95
m3/s
m3/s
cfm
cfm
m3/s
cfm
3.00 m /s
6,355.26 cfm
According to the BS 5588 Staircase pressurization fan is to be single speed 1hr fire rating @300C
Total Volume Flow Rate of the Fan should be
a) To calculate pressure required in stairwell to exhaust 1.815 m3/s to atmosphere via fire floor
Area of single leaf door=2.2X1.1=2.42 sq.m
Area of exhaust vent = 1.815/2.5 =0.726 sq.m
A.E = (1/A1^2+1/A2^2)^-0.5
= (1/2.42^2+1/0.726^2)^-0.5
=
0.70 sq.m
P1=(Q/(0.83XA.E))^2
= (1.815/(0.83X0.7))^2
=
9.758902835 Pa
This is more than covered by 50 Pa
b) To calculate area of pressure relief
Quantity of air to be wasted = 2.80 - 0.62
3
=
2.18 m /s
Area of pressure relief = Q/(0.83XP^0.5)
= 2.18 / (0.83X50^0.5)
=
0.371 sq.m
Let Height of Pressure relief damper = 0.5 m
then Width will be = 0.371 / 0.5 = 0.742 m, say 0.75m
Width/(mm)
750
650
650
550
450
350
350
Volume flow
Rate/(cfm)
Height/(mm)
650
650
550
550
550
550
350
Length(m)
10
4
4
4
4
4
4
34
6,356.00
5,448.00
4,540.00
3,632.00
2,724.00
1,816.00
908.00
Eq.
Diameter(De)
m
0.763
0.711
0.653
0.601
0.543
0.477
0.383
Fittings
Size
Elbow 2100x1100
Reducer
Qty
2
6
SAT(sound attonuator)
VAV
Flexible duct
0
0
0
0.3inch/100ft
sub total
70
0
0.00
73.96
VCD Size
Various
Qty
grilles
Various
Qty
123.48 Pa
24.70 Pa
148 pa
Friction loss
pa/m
0.57
0.57
0.57
0.57
0.57
0.57
0.57
TOTAL
inch/100ft
0.07
0.07
0.07
0.07
0.07
0.07
0.07
Total
Friction
Loss(Pa)
5.740
2.296
2.296
2.296
2.296
2.296
2.296
19.516