Sei sulla pagina 1di 26

OPERATION AND INSTALLATION MANUAL OTC, OTR and OTM SERIES

MODELS .25A, .33A, .5A, .75A, 1.0A, 1.5A, 2.0A, 3.0A, 5.0A, 7.5A & 10A

MODELS 15A, 20A, 25A & 30A

MANUAL #O002168 Prepared August 23, 2007 P.O. BOX 5246 TRAVERSE CITY, MICHIGAN 49696 231.946.2931 www.optitemp.com

TABLE OF CONTENTS
INTRODUCTION Unpacking Service/Support SECTION I - Safety Warnings SECTION II - General Information Description Specifications Cooling Capacity Pump Capacity SECTION III Installation & Connection Installation and Connection Electrical Connecting to the Process Drain-back prevention Reservoir SECTION IV - Operation Operating Temperature Range Limits Corrosion Protection Fluid Quality Starting the Unit Refrigeration System Setting the Temperature Controller Setting the PID Parameters SECTION V - Troubleshooting Troubleshooting Guide Preventative Maintenance Checklist SECTION VI - Optional Equipment WARRANTY CERTIFICATION (S) APPENDIX A - Supplemental Information Dew Point/Temperature Chart Filtration General System Specifications Control Parameters General Install Schematic (If Applicable) Electrical Schematic Equipment Options Control Parameter Manual 2 2

4 4 4 4

5 5 6 7 7

8 8 8 9 10 10 11

12 15 16 17 18 19 20 21 24 25 26 27 Inside Manual Back Cover

OPTI TEMP INC

PAGE 1

INTRODUCTION
Thank you for choosing OPTI TEMP for your heat transfer needs. OPTI TEMP welcomes your comments and feedback. Please feel free to contact us with any questions, comments, concerns, or feedback you may have regarding the OPTI TEMP unit or this manual. Unpacking Before accepting the unit from the freight company, visually inspect the unit for any shipping damage. If there is any indication that the package was mishandled, further inspection should be done immediately in front of the delivery driver. Note all visual damage on the delivery receipt prior to acceptance. Remove the unit from the package and again inspect for any damage that could have occurred during shipment. If damage is noted, be sure to file a claim IMMEDIATELY with the carrier. Remove any packing materials and support materials from the unit. NOTICE IN ORDER TO PROTECT THE UNIT FROM FREEZING WHEN SHIPPED DURING THE WINTER SEASON (GENERALLY BETWEEN OCTOBER 1st and APRIL 30th), THE UNIT MAY BE SHIPPED WITH A SMALL AMOUNT OF ANTIFREEZE IN THE RESERVOIR AND PUMP. YOU MAY WANT TO FLUSH THIS ANTIFREEZE OUT OF THE SYSTEM BEFORE CONNECTING TO YOUR SYSTEM. The amount of anti-freeze used is very small. Contact OPTI TEMP at 231.946.2931 with disposal concerns. If the unit is not equipped with casters, there may be rubber pads or feet in a plastic bag attached to the electrical cord. If provided, you should install the feet on the four corners of the unit, using the double-sided tape that is included in the plastic bag for this purpose, If the unit must be lifted, utilize a forklift. Place the forks evenly across the bottom for proper support and balance. Service/Support Opti Temp is committed to customer service both during and after the sale. If you have questions concerning the unit operation, please contact our Service Department at 231.946.2931. OPTI TEMP systems are built to provide years of trouble free service. All systems are tested prior to shipping to insure you receive the highest quality product. In the unlikely event you experience problems, rest assured our technical service staff will be available to assist you resolve any problems quickly. If your unit fails to operate properly, or if you have questions concerning spare parts or Service, contact our Service Department at 231.946.2931. Before calling, please refer to the serial number tag to obtain the serial number: -Unit Serial Number ___________________________________
OPTI TEMP INC PAGE 2

SECTION 1: SAFETY
Warnings

Warnings can be found throughout the manual. These warnings are designated by an exclamation mark inside a yellow triangle and text highlighted in bold. Failure to observe these instructions can result in permanent damage to the unit, significant property damage, or personal injury or death. Make sure you read and understand all instructions and safety precautions listed in this manual before installing or operating your unit. If you have any questions concerning the operation of your unit or the information in this manual, please contact our Sales Department (see service/support). 1. 2. 3. For safety reasons power supplies must be properly grounded. All Federal, state, and local codes should be followed. Never use flammable or corrosive fluids with this unit. Do not use automobile anti-freeze. Automotive anti-freeze often contains silicates or other components that can damage your system. Only an un-inhibited ethylene glycol should be used. Use of automobile anti-freeze will void the manufacturers warranty. Never place the unit in a location where excessive heat, moisture, or corrosive materials are present. Do not modify or seal reservoir in any way. Performance of installation, operation, or maintenance procedures other than described in this manual may result in a hazardous situation and may void the manufacturers warranty. Transport the unit with care. Sudden jolts or drops can damage internal components. Observe all warning labels. Never remove warning labels. Never operate damaged or leaking equipment. Never operate the unit without heat transfer fluid in the reservoir. Always disconnect power to the unit before opening the control box. Always empty the reservoir before moving the unit. Never operate equipment with damaged power cords. Refer service and repairs to a qualified technician.

4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15.

This manual assumes the OPERATOR is non-technical with limited training and the RESPONSIBLE BODY is technical and fully trained. Your equipment contains refrigerant within its cooling system. The refrigerant is designated as a florinated greenhouse gas. The specific type and quantity of refrigerant contained within the refrigeration system is listed on the units serial tag. The Global Warming Potential (GWP) of the refrigerants used by Opti Temp is:
OPTI TEMP INC PAGE 3

Refrigerant R-134A R-22 R-404A

GWP 1300 1700 3260

SECTION II: GENERAL INFORMATION


Description The OPTI TEMP refrigerated heat exchanger (chiller) is a re-circulating system designed to provide a continuous supply of heat transfer fluid (usually water) at a constant temperature and flow rate. The OPTI TEMP system consists of a refrigeration system, fluid pump, fluid reservoir, and a Proportional Integral Derivative (P.I.D.) controller. The OPTI TEMP system features our patented refrigeration circuitry. This circuitry allows the unit to provide zero to full load capacity control. It also allows the OPTI TEMP chiller to provide very tight temperature control over a very wide temperature range. See operating temperature range limits in section IV for more information about the operating range of your system. The revolutionary refrigeration circuitry adjusts and controls the flow of refrigerant in response to the system load. The circuitry provides only the needed cooling capacity. Because of this innovative circuitry, the refrigeration system (compressor) will operate when the unit is on regardless of whether or not the process calls for cooling. This is normal and is not a cause for concern. Continuous compressor operation reduces wear and tear associated with frequent cycling which can lead to pre-mature compressor failure. Specifications Please see appendix A for complete system specifications. Cooling Capacity Please see appendix A for complete system specifications. Pump Capacity Please see appendix A for Pump capacities.

The following Operation Manual Information is based on Standard Opti Temp Inc. units. For custom units, please refer to the appendix for special instruction sheets.

OPTI TEMP INC

PAGE 4

SECTION III: INSTALLATION


Installation and Connection Locating the System: The OPTI TEMP units utilize air-cooled refrigeration systems. Air is drawn and/or discharged through the front, rear, side and top panels of the unit. The unit must be located so the intake and discharged is not restricted. A minimum clearance of one width of the unit is suggested on all vented sides for adequate ventilation. Failure to provide adequate ventilation may cause a reduction in cooling capacity and/or pre-mature failure. Excessively dusty or oily areas should be avoided. The unit should be periodically cleaned to insure optimum performance. A regular maintenance schedule based on operating conditions is recommended. Please note that oil, dust, and/or other airborne agents can build up on air-cooled condensers resulting in a decrease in performance or system failure. Never place the unit in a location where excessive heat, moisture, airborne oils, or corrosive materials are present.

Operating/Ambient Conditions: i. Operating Temperature Range: 7 to +40oC (+45 to 104oF). ii. Storage Temperature: -10 to +55oC (+14 to 131oF) iii. Operating Ambient Humidity Conditions: 0 to 90 % relative humidity up to 40oC (non-condensing), 10 to 50% relative humidity from 40 to 55oC (non-condensing). Electrical

CAUTION (REFER TO ACCOMPANYING DOCUMENTS) CAUTION: RISK OF ELECTRICAL SHOCK. DISCONNECT SWITCH REQUIRED TO DE-ENERGIZE THE EQUIPMENT BEFORE SERVICING. Refer to the section II, Specifications, Appendix A, and the serial number tag for the specific electrical requirements of your unit. Bring adequate electrical power to the unit. Ensure the voltage of the power source meets the specified voltage, +/- 10%. This power must be through a circuit breaker or a switch-able fused disconnect that is in close proximity to the unit and within easy reach of the operator. Be sure that the unit is grounded, (and the disconnect does not remove the ground). See specifications for 50 Hz operation.

OPTI TEMP INC

PAGE 5

OPTI TEMP systems are equipped with a compressor crankcase heater. The heater warms the oil in the compressor and will separate refrigerant mixed with the oil. Before starting the unit in a cold environment, be sure that power is applied to the unit for a minimum of 12 hours or serious system damage may result. Connecting to the Process Standard stainless steel fittings are provided on the OPTI TEMP unit for connecting TO and FROM process lines. NOTE: All fittings are a male NPT nipple. Run next size larger hose (see data sheet) to and from your process. It is suggested that a valve be installed on the TO PROCESS line and FROM PROCESS line at the OPTI TEMP unit, to be used as balancing valves to balance the flow to the process or as an isolation valve should maintenance be required on the unit. CAUTION: THE FITTINGS ARE CONNECTED TO A MANIFOLD PLATE ATTACHED TO THE UNIT. DO NOT OVERTIGHTEN FITTINGS SUCH THAT YOU BREAK THE FITTINGS FROM THE MANIFOLD PLATE

Never connect the fittings to your building water supply or any pressurized water source.

OPTI TEMP INC

PAGE 6

Drain Back Prevention Depending on the length of hoses and thus the amount of fluid contained in the system, some fluid may drain back causing the reservoir to overflow when the unit is turned off during shut down periods. The drain back would normally be minimal unless there is a leak in the system. If this occurs and provision cannot be made in the reservoir to handle the drain back, the problem can be eliminated by locating the unit so the reservoir is at the same level or above the system; or a check valve can be installed in the process supply line and a solenoid valve installed in the process return line to prevent drain back. Call the factory if this is a problem, or for further information. Reservoir

The OPTI TEMP system is designed as an open system with the top of the reservoir at atmospheric pressure. Do not connect any fittings to the cover of the reservoir or pressurize the reservoir in any way or damage to the system and or personal injury could result. The reservoir is designed to be filled manually.

OPTI TEMP INC

PAGE 7

SECTION IV: OPERATION


Operating Temperature Range Limits

OPTI TEMP systems are designed to operate within a certain specified temperature range. All systems are not designed to operate over the same range. It is important that you do not operate the system outside of this intended range. Please refer to the specifications in APPENDIX A for the operating range of your system.
If this is a low temperature unit, DO NOT OPERATE ABOVE 110oF (40oC). If this is a high temperature unit, DO NOT OPERATE ABOVE 190oF (90oC).

DO NOT OPERATE UNIT ABOVE this temperature range. System damage and/or personal injury may result. Corrosion Protection / Fluid Quality Generally, OPTI TEMP recommends the use of distilled or de-ionized water with its systems instead of tap water because tap water can have a high level of total ionized solids, which can accelerate corrosion. These contaminants function as electrolytes, which increase the potential for galvanic corrosion. Tap water in the US averages 175 ppm (NaCl). The recommended level is between 0.5 to 5 ppm. Normally OPTI TEMP recommends that systems, which require a fluid conductivity below 240 microsiemans/cm, utilize stainless steel construction. Systems where conductivities are permitted to be above 240 microsiemans/cm may use OPTISHIELD corrosion inhibitor to control corrosion and extend system life. OPTI TEMP provides a corrosion inhibitor called OPTISHIELD, which provides protection from corrosion resulting from the presence of dissimilar metals in the cooling circuit. You may wish to use OPTISHIELD Corrosion Inhibitor to protect the OPTI TEMP unit and your process from corrosion. Check with the engineers at OPTI TEMP INC and your machinery supplier for further information. Contact OPTI TEMP or your Process Manufacturer for more information regarding system water quality and corrosion inhibitors.

OPTI TEMP INC

PAGE 8

Starting the Unit Fill the reservoir to within 2 (50mm) from the top of the reservoir or fill port (OR AS NOTED ON THE SIGHT GLASS IF PROVIDED) with the proper heat transfer fluid. Turn on the unit and press the START button. There is a float switch in the unit that will turn on the PUMP ALARM light and stop the unit if the fluid level falls below a safe level. If this happens, turn the unit off and fill the unit again with clean fluid. Repeat this procedure until the system is filled. NOTE: Check pump rotation on 3 phase units at this time. Follow the instructions on the power cord tag. It is recommended that the unit be allowed to run for a few minutes before the reservoir is completely filled. This allows the air to bleed from the lines more easily. Vent the air out of the system. It is helpful to open a valve or a fitting at the system high point (while the system is running) and bleed the air until fluid starts to flow, then close the valve or retighten the fitting. There is an automatic pressure actuated bypass valve in the unit to bypass fluid around the process and back into the Opti Temp reservoir if flow to the process is interrupted for any reason. It is normally factory set at 80 PSI (60 PSI on 2-30A). Adjustment at your facility may be necessary depending on the process requirements. Adjust the bypass valve by: 1. 2. 3. 4. 5. Remove cap (if applicable) Loosening the locking ring with pliers. Lower the pressure by turning the adjustment knob counter-clockwise. Tighten the locking ring with pliers so that it cannot be turned by hand. Replace cap (if applicable)

PLEASE CONTACT OPTI TEMP IF YOUR PROCESS IS EQUIPPED WITH A VALVE, WHICH MAY OR PERODICALLY INTERRUPT FLOW TO THE PROCESS. BYPASS SETTINGS MAY BE CRITICAL TO PROTECT THE SYSTEM FROM DAMAGE! It is recommended that the valve in the supply line to the process be throttled (closed slowly) until the bypass valve just starts to feed. By putting your hand on the valve and bypass line you will be able to feel when the valve starts to open. This allows the air to be cleared from the bypass line. Again check to be sure the fluid in the reservoir is at the proper level. The float switches should be floating. The fluid level in the unit should be checked at least once a week to insure there is adequate fluid in the unit. NOTE: IF THE UNIT IS USED IN A MANNER NOT SPECIFIED BY OPTI TEMP INC., THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED

OPTI TEMP INC

PAGE 9

Refrigeration System Your OPTI TEMP unit uses refrigerant components including compressors, expansion valves and heat exchangers to cool the process supply fluid. WHEN THE OPTI TEMP UNIT IS STARTED COMPRESSOR WILL AUTOMATICALLY START. THE REFRIGERATION

The system is designed such that the compressor will continue to run at all times during the OPTI TEMP units operation. The controller will modulate the quantity of refrigerant used for cooling dependent on the process cooling load. Setting the Temperature Controller This section will discuss the basic control operation and the basic settings. For more complete instruction on the operation of the controller and available options, please read the Instruction Manual for the controller included with this manual. There are two digital display windows on the temperature controller. The upper window displays the actual temperature of the fluid going to the process or the PROCESS VALUE. The lower window displays the SET VALUE of the controller. To the Left of the Upper window there is a small SP1 that will light if the unit is in the cooling mode (the TXV solenoid valve is in the open position). There are several lights over the PROCESS VALUE window on the controller. For CHILLERS (OTC) the AL light stands for alarm and is the freeze alarm for the unit. This has been set at the factory to light if the process temperature falls too low (see Control Parameter Settings Sheet in the Appendix). It will also light the larger freeze alarm light on the panel and shut off the refrigeration system (the compressor and fans). The pump will remain in operation. It will sound the audible alarm (if provided with the unit). If you wish to run at a temperature below the normal setting, see the Trouble Shooting Section Unit Shuts Off---Freeze Alarm Light Is On. On CHEATERS (OTR) the AL light stands for alarm and is the LIV set point for the unit. This has been set at the factory to activate if the process temperature falls to the AL1 set point (see Control Parameters page). To change the temperature set value, it is necessary to touch INDEX (the keypad on the far left) once. SP1 will appear in the lower window and the current set point will appear in the upper window. Touch the UP ARROW to raise the set point, or the DOWN ARROW to lower the set point to the desired set point temperature. When the desired temperature appears in the upper window, press ENTER (the keypad to the far right) to store the new temperature.

OPTI TEMP INC

PAGE 10

IT IS NECESSARY TO TOUCH THE ENTER KEYPAD TO INPUT THE NEW TEMPERATURE. Touch the INDEX keypad again and SP2 will appear in the lower window, and its setting (see Control Parameter Settings Sheet in the Appendix) will appear in the upper window. Touch the INDEX keypad again to return to the operating mode with the Set Point in the lower window and the Process Value in the upper window. Setting the PID Parameters This temperature controller is arranged to provide PID temperature control. PID stands for Proportional-Integral-Derivative control, and for most load situations will give the process more stable temperature control than On/Off control. Under PID control, the temperature controller anticipates cooling and heating requirements and will institute these control activities in anticipation of the load requirements to give more stable temperature control to the process. This temperature controllers PID constants are preset at the factory. This is described on page 22 of the manual. This temperature controller is equipped with Fuzzy Logic. Fuzzy Logic maintains better temperature stability under changing load conditions and allows the unit to come to temperature stability faster after temperature changes. It is important to note that THE FUZZY LOGIC FEATURE OF THIS CONTROLLER IS ENGAGED, AND WE RECOMMEND THAT IT REMAIN ENGAGED. With the fuzzy logic, the unit will provide better temperature stability than when it is not engaged. For more information on these features, please see the Temperature Controller manual in Appendix A. If the optional audible alarm is purchased with the unit, it will be mounted on the control box and both the red light will light and the alarm will sound if a low fluid level condition occurs. The unit will now run and cool the laser, or process.

OPTI TEMP INC

PAGE 11

Section V: Troubleshooting

CAUTION:

RISK OF ELECTRICAL SHOCK. DISCONNECT SWITCH REQUIRED TO DE-ENERGIZE THE EQUIPMENT BEFORE SERVICING. ALWAYS DISCONNECT POWER TO THE UNIT BEFORE OPENING CONTROL BOX. The following Troubleshooting guide is based on Standard Opti Temp Inc. units. For custom units, please refer to the appendix for special instruction sheets. UNIT SHUTS OFF The unit will go off on alarm and the RED alarm light will come on if the reservoir fluid level drops too low. Turn the unit off, remove the fill port cap and check the fluid level. If it is too low, add fluid (as described above), turn on the unit. If the unit still does not start, and you have verified that the unit has adequate fluid in the reservoir and is within the proper range, contact OPTI TEMP INC. at the number located in the Service/Support Section II. LOSS OF CAPACITY NOTE: IF THE UNIT EXHIBITS A LOSS IN CAPACITY, CHECK THE CONDENSER (THE FINNED TUBE COIL) FOR CLEANLINESS. VACUUM OR USE COMPRESSED AIR TO BLOW OUT THIS COIL OR A POWER WASHER TO CLEAN THE COIL. IF A POWER WASHER IS USED, BE SURE TO PROTECT THE ELECTRICAL COMPONENTS FROM WATER. If the OPTI TEMP unit still exhibits a loss in capacity; you observe the compressor is not running or any other refrigeration related problem occurs, we suggest calling a refrigeration service technician. The unit is equipped with sight-glass and access ports to enhance quick troubleshooting and minimize any potential down time. Of course OPTI TEMP is available to assist with trouble you may have. See Service/Support in Section II. UNIT NOT HOLDING SET TEMPERATURE (TEMPERATURE GOES TOO HIGH) Check the load on the unit compared to the cooling capacity of the unit. If the unit is over loaded it will not hold the temperature setting. Check to be sure that the cooling solenoid valve is functioning properly. When cooling is required, the SP1 light will light on the temperature controller and you will hear a definite click when the solenoid valve opens and closes. If you do not hear this click when the unit calls for cooling, the solenoid is either not getting power to open (an electrical fault) or the solenoid is faulty.
OPTI TEMP INC PAGE 12

If the unit still does not function properly, contact OPTI TEMP INC. at 231.946.2931. UNIT NOT HOLDING TEMPERATURE (TEMPERATURE GOES TOO LOW) Have the RESPONSIBLE BODY check to be sure the cooling solenoid is not stuck open allowing refrigerant to enter the refrigerant / cooling water heat exchanger. The expansion valve after the solenoid should be cool to the touch but not cooler than the supply water to the chiller. If the expansion valve is cold and a vibration or noise (rushing liquid) can be heard at the solenoid and expansion valve, ensure there is no electrical power going to the solenoid. If there is no voltage at the solenoid electrical coil, then the valve is stuck open and a refrigeration service technician should be called to replace the valve. If you need additional help, contact OPTI TEMP INC. at 231.946.2931. TEMPERATURE OF THE RESERVOIR IS NOT THE SAME AS INDICATED ON THE CONTROLLER There will always be a slight difference between the controller indicated temperature and the temperature measured in the reservoir. Also, one must be sure that the thermometer used to measure the reservoir temperature is accurate. One should use two thermometers that read the same to confirm the accuracy of the thermometers used. One must also measure the reservoir temperature as close to the end of the thermocouple that is in the reservoir as possible. If the temperature difference seems too high, the controller is probably out of calibration or the unit has a faulty thermocouple. The controller can be calibrated by adjusting the InPC (or InC1) function on the secondary menu of the controller. See the temperature controller manual or contact the factory for further details. You can reach OPTI TEMP INC. at the number located in the Service/Support Section II. TEMPERATURE CONTROLLER IS READING OPEn InP or OPEn This generally indicates a sensor failure. Have the RESPONSIBLE BODY turn off the unit and unplug the unit. Open the control panel door and check to be sure that the red thermocouple lead is connected tightly to terminal 3 of the controller and the white (or yellow) thermocouple lead is connected tightly to terminal 1 of the controller (see the electrical schematic in this control manual). Plug the unit in and start the unit. If this does not correct the problem, contact OPTI TEMP INC. at the number located in the Service/Support Section II.

OPTI TEMP INC

PAGE 13

COMPRESSOR SHUTS OFFFREEZE ALARM LIGHT IS ON AND CONTACTS OPEN The standard freeze alarm setting is 45oF (7oC). It will light the (optional) freeze alarm light on the panel and shut off the refrigeration system (the compressor and fans). The pump will remain in operation. It will sound the audible alarm (if provided with the unit). This is done so that someone wont inadvertently set the temperature below freezing without adding antifreeze to the system. If you wish to run below 45oF (7oC), ADD AN INDUSTRIAL ETHYLENE GLYCOL OR PROPYLENE GLYCOL TO THE SYSTEM. DO NOT USE AUTOMOTIVE ANTIFREEZE. Use the glycol manufacturers recommended concentration for 6oC BELOW your desired operating temperature and install this percentage of glycol into the system. Please keep in mind that glycols reduce the heat transfer efficiency of the heat exchange components in the system. Your unit will have less capacity when using glycols . BE SURE YOU INSTALL ENOUGH ANTIFREEZE TO PROTECT TO 6oC BELOW YOUR DESIRED OPERATING TEMPERATURE. DAMAGE TO YOUR OPTI TEMP CHILLER DUE TO FREEZING FOR ANY REASON IS NOT COVERED BY WARRANTY! If you wish to operate unit below 7oC(45oF), contact OPTI TEMP INC. at 231.946.2931. If the F2 control fuse blows, have a qualified electrician or the responsible party inspect for problems. The replacement fuse for F2 is a Amp (2.5 Amp on 15A30A Units), type F fuse.

OPTI TEMP INC

PAGE 14

484 W. Welch Ct, Traverse City, MI 49686

Ph 231-946-2931 Fax 231-946-0128

PREVENTATIVE MAINTENANCE CHECKLIST WEEKLY CHECKS: Confirm the proper fluid level in the tank and add fluid if necessary. (OPERATOR) QUARTERLY CHECKS: Check the condenser and fan blades and clean if necessary. (RESPONSIBLE BODY)

Change the fluid filter. (OPERATOR)

YEARLY CHECKS: (RESPONSIBLE BODY)


Oil the pump motor (if required) and the condenser fan motors. Change coolant ONCE PER YEAR. Check for fluid leaks in the temperature control unit. Check the fluid bypass valve setting and correct the setting if necessary. Observe the temperature stability under load. If necessary adjust the PID parameters of the units temperature controller. Check safeties (Float Switch, High Temperature Cut Out, Flow Switch).

YEARLY CHECKS (QUALIFIED REFRIGERATION TECHNICIANS ONLY): (RESPONSIBLE BODY)


Leak test refrigeration components with a certified refrigerant leak detector Test refrigeration safeties for proper set point and operation (High and Low Pressure Cut out). General check of the refrigeration system. Check Sight Glass for bubbles during full load operation. Check lines for vibration or rubbing. Look for signs of oil residue.

Date Maintenance Performed Service Company Maintenance Performed By: Model # Notes:

Serial #

OPTI TEMP INC

PAGE 15

Section VI: Optional Equipment


Heaters Often it is desirable to provide heat in the system. For example, it may be desirable to pre-heat the coolant to a particular temperature, above the dew point, to prevent condensation on start up. In other cases the process may be such that heating is required for a part of the process and cooling is required for another part of the process. OPTI TEMP chillers can be equipped with optional heater packages. When so equipped the system will provide heating or cooling automatically with instantaneous changeover. If the temperature of the fluid in the process system falls in temperature, an electric heater (if the optional heater is purchased) in the reservoir activates and heats up the fluid. OPTI TEMP offers a variety of add on heater packages. Contact the factory for more details. If your system is equipped with heat, refer to the specifications in Appendix A for more details. Pumps OPTI TEMP offers a wide variety of pumps to meet specific application needs. Contact the factory for details on available pump options. For details regarding performance specifications of your systems pump, please refer to pump specifications in appendix A. OPTI TEMP offers two types of de-ionization polishing options to maintain process fluid quality. Contact the factory for more information. If your system is equipped with de-ionizing water quality system, please refer to the Appendix for information about the operation, care, and use of this equipment. OPTI TEMP offers a full range of filtration systems for use with OPTI TEMP equipment as well as other process equipment. Contact the factory for more information about filtration. If your system is equipped with filtration, please refer to the Appendix for information about the operation, care, and use of this equipment. Flow Control OPTI TEMP offers a variety of flow control devices such as flow switches, flow meters, pressure transducers, pressure gauges, etc. Contact the factory for more information on optional equipment. If your system is equipped with optional flow control devices, please refer to the Appendix for information about the operation, care, and use of this equipment.
OPTI TEMP INC PAGE 16

De-Ionization

Filtration

Warranty
STANDARD LIMITED WARRANTY
COVERING PARTS, LABOR AND SERVICE
WARRANTY PERFORMANCE: The manufacturer warrants all equipment manufactured by it to be free from defects in workmanship and material when installed and operated in accordance with OPTI TEMP installation and operating guidelines. It shall be the Companys obligation to repair or replace, at its option, any parts and/or materials found to be defective during the warranty period. Performance shall include materials and any labor costs relative to the work as more fully described below. All warranty determinations will be made at OPTI TEMP headquarters. Materials returned to the factory for warranty service shall require prior written authorization. Freight for returns to the factory must be F.O.B. factory and will be at buyers expense. Freight for components returned to buyer under the warranty claim process shall be determined by, and paid for by, the factory. Each party thereby shares in freight costs. Note: Extended warranties and/or Service Agreements are available from the factory. OPTI TEMPs responsibility for systems that qualify for field service or repair, is limited to the component parts necessary for the repair and the labor that is required on site to perform the repair. Any travel labor, mileage charges, incidentals, or other labor required as a consequence of or in conjunction with repairs are the responsibility of the buyer. PARTS: The manufacturers obligation is limited to the repair or replacement of any parts which are returned to the factory, freight prepaid, during the warranty period within one year of equipment shipment to the original purchaser. Warranty is limited to the manufacturers warranty on the components but in no case will it be less than one year. All components are subject to inspection at the manufacturers factory. The warranty is limited only to those components, which in the manufacturers sole opinion are determined to be defective. The warranty does not cover components, which have been repaired or altered without the manufacturers express, written authorization. The manufacturer is not liable for any parts not furnished as a part of its manufactured equipment. Defective parts become the property of the warrantor and must be returned. Replacement parts assume the used portion of this warranty. SERVICE: The company will provide for the service of materials and/or parts found to be covered by this warranty at an authorized service center, or the consumers location, at the companies sole discretion. Service shall be performed only by OPTI TEMP INC. or such authorized representatives and/or service organizations as determined by the company and approved in advance. OPTI TEMP must be notified in writing and a claim initiated under this warranty before service shall be covered under this warranty. Under no circumstances will the company be liable for unauthorized service work. OPTI TEMPs liability does not include any labor charges for replacement parts, adjustments, repairs, or any other work done outside its factories and its liability does not include any resulting damage to persons, property, equipment, goods or merchandize arising out of any defect in or failure of its equipment. FINANCIAL OBLIGATIONS: The Company considers performance under this warranty as its obligation to the buyer as part of the buyers purchase of the Companys products. This implies, however, that the buyer also has satisfied its financial obligation to the seller in the purchase transaction by making full payment for the products by the Companys terms, and settlement of appropriate past due items. Warranty performance may be voided or withheld if buyer fails to perform its payment obligations to seller. No claim of breech of warranty shall be cause for cancellation or rescission of the contract of sale for any system. OPERATIONAL PERFORMANCE: OPTI TEMP INC warrants its products to operate at the designed capacity when installed and operated in accordance with company provided instructions. The performance of the system is affected by the methods of installation, piping, valving, location of components, and the like, and therefore when these criteria are not in conformance with established practice and instruction, the OPTI TEMP INC warranty may be reduced or void. NORMAL OR ROUTINE MAINTENANCE: Such as instrument calibration, changing of compressor oil, condenser and evaporator cleaning, lubrication of bearings, filter cleaning, de-scaling, repairs due to corrosion and other similar events are NOT considered defects and therefore and NOT covered by this warranty. Repairs required due to freezing, regardless of reason or source, are NOT covered by this warranty. OTHER LIMITATIONS: OPTI TEMPs obligation to repair or replace shall not apply to any equipment which has been repaired or altered outside the factory in any way, or which has been subject to negligence, freezing, misuse, or to operational conditions outside OPTI TEMP recommendations. Under no circumstances will the company be responsible for any other direct or consequential damages arising from defective equipment, including but not limited to lost profits, lost income, labor charges, delays in production, idle production, which damages are caused by any defects in material and/or workmanship in its products, and/or damage or delays in shipment. This warranty is in lieu of any other express or implied warranty including any warranty of merchantability or fitness, and of other obligation on the part of the seller. Assignment: None of the customers rights under any order or agreement shall be assigned by the customer to any other person, whether by operation of law or otherwise, without sellers prior written approval. OPTI TEMP does not assume or authorize anyone to assume for it any other obligation. The Company shall not be liable for failure to perform any obligation with respect to buyer resulting directly or indirectly from, or contributed to, by Acts of GOD; Acts of Buyer; Civil or Military Authority; Fires; Strikes or other Labor Disputes; Accidents; Floods; Epidemics; War; Riots; Delays in Transportation; Inability to Obtain Raw Materials, Components, Labor, Fuel or Supplies; Or Any Other Circumstance beyond the sellers reasonable control whether similar or dissimilar to the foregoing.

OPTI TEMP INC

PAGE 17

Certification
OPTI TEMP systems tested and found to be in compliance, with the requirements defined in the EMC standards, defined by 89/336/EEC, as well as Low Voltage Directive (LVD) 73/23/EEC can be identified by the CE label on the rear of the unit. The testing has demonstrated compliance with the following directives: LVD, 73/23/EEC EN61010-1 Complies with UL 3101-1:93 EMC 89/336/EEC EN55011, Class A Verification

For any additional information refer to the Declaration of Conformity that shipped with the unit.

OPTI TEMP INC

PAGE 18

RECOMMENDED OPTI TEMP TEMPERATURE SETTINGS BASED ON OUTSIDE TEMPERATURE AND RELATIVE HUMIDITY CONDITIONS

Outside Temp Degrees F C 70 21

75

24

80

27

85

29

90

32

95

35

100

38

Outside Relative Humidity F C 70 21 80 27 90 32 60 16 70 21 80 27 90 32 50 10 60 16 70 21 80 27 90 32 50 10 60 16 70 21 80 27 90 32 40 4 50 10 60 16 70 21 30 -1 40 4 50 10 60 16 70 21 30 -1 40 4 50 10 60 16 70 21

Dewpoint Temp Degrees F C 59 15 63 17 67 19 61 16 64 18 69 21 72 22 59 15 65 18 69 21 73 23 77 25 65 18 69 21 75 24 79 26 81 27 63 17 68 20 74 23 79 26 59 15 67 19 71 22 79 26 83 28 63 17 72 22 78 26 83 28 89 32

Temperature to Laser Degrees F C 61 16 65 18 69 21 63 17 66 19 71 22 74 23 61 16 67 19 71 22 75 24 79 26 67 19 71 22 77 25 81 27 83 28 65 18 70 21 76 24 81 27 61 16 69 21 73 23 81 27 85 29 65 18 74 23 80 27 85 29 91 33

OPTI TEMP INC

PAGE 19

OPTIFILTER OPTI TEMP INC. introduces the OPTIFLOW filters, which are used to filter fluid being circulated to lasers, welders, injection molds and other machinery and laboratory equipment. The filters are normally installed in the return line of the OPTI TEMP heat transfer units or chillers to filter the fluid returning to the system. This will keep the residue from settling out in the reservoir. The standard filters offered will filter particles down to 30 microns in size. Other filter sizes are available. The OPTIFILTER is highly recommended for use when OPTISHIELD or other corrosion inhibitors are used in the system. When corrosion inhibitors such as OPTISHIELD are added to a system, they dislodge the corrosion particles into the fluid stream where the OPTIFILTER removes this residue before it can do damage to pumps, and other components in the system.
WATER FILTERS FILTERS DESIGNED FOR MAXIMUM PRESSURES OF 125 PSI & 125F MODEL MODEL 5 SLIM Housing/Bracket/Wrench/Filter CARTRIDGES MODEL 10 SLIM Housing/Bracket/Wrench/Filter CARTRIDGES MODEL 10 STANDARD Housing/Bracket/Wrench/Filter CARTRIDGES PIPE SIZE 1/2 MICRON FILTER 30 M 1/2 30 M 3/4 30 M HEIGHT 7 5 12-1/8 9-3/4 12-5/8 9-3/4 10 5 MAX GPM 5 DIAMETER 4-1/2 2-3/4 4-5/8 2-3/4 5-1/8 2-3/4 MODEL NUMBER OTF Model 5Slim OTF-R30-5 OTF Model 10 Slim OTF-R30-10 OTF Model 10 Standard OTF-R30-10

WATER FILTERS FILTERS DESIGNED FOR MAXIMUM PRESSURES OF 100 PSI & 100F MODEL MODEL 12 Housing/Bracket/Wrench/Filter CARTRIDGES MODEL 20 Housing/Bracket/Wrench/Filter CARTRIDGES PIPE SIZE 1 MICRON FILTER 30 M 5M 1-1/2 30 M HEIGHT 13-1/4 9-3/4 9-3/4 23-3/4 20 40 MAX GPM 20 DIAMETER 7-1/4 4-1/2 4-1/2 7-1/8 4-1/2 MODEL NUMBER OTF Model 12 OTF-R30-BB OTF-CP5-BB OTF MODEL 20 OTF-S1-20BB

HIGH TEMPERATURE PRESSURE FILTERS FILTERS DESIGNED FOR MAXIMUM PRESSURE OF 200 PSI & 200F MODEL MODEL ST 1 Housing/Bracket/Wrench/Filter CARTRIDGES PIPE SIZE 3/4 MICRON FILTER 30 M HEIGHT 14 9-3/4 MAX GPM 15 DIAMETER 4 2-5/8 MODEL NUMBER OTF-ST 1 OTF10BCF-30

OPTI TEMP INC

PAGE 20

REFRIGERATED RE-CIRCULATING FLUID CHILLERS

OTC Series - Portable Air Cooled


For Laser, Semiconductor, Medical, X-Ray & Laboratory Applications
Options:

Models OTC-.25A to 10A

Controls / Interlocks PLC controller RS232 and RS485 communication Ethernet ready controller Remote start/stop Audible alarm with silence Visual alarm beacon Remote control Fluid monitoring and control devices Electrical NEMA 4 (outdoor) controls 24V control systems Phase monitor Power cord extension CE compliance NRTL certifications Mechanical Specialty wetted construction materials Multiple pump upgrades Anti-drain back prevention Particle filters UV filters Immersion heaters Remote temp sensing Fluid circuit insulation Manifolds Drain kits Extended warranty Other Fluid conductivity control systems Automatic fluid pH control systems OPTISHIELD corrosion inhibitors

Model OTC-.25A to .5A shown

Features::

0.25 to 10 tons (0.6 to 35 KW) of cooling capacity OPTI TEMP patented advanced refrigeration control (ARC) circuitry standard Micro-processor based PID auto tuning controller with digital display Programmable high temp or high/low temp alarm Temp output in C or F Dual frequency compatible Operating temperature ranges up to 90 C Non-ferrous wetted construction standard Rugged powder coated steel cabinetry Stainless steel MNPT process connections Swivel casters standard Removable cover and side access panels NEMA 1 electrical enclosure standard S.S. brazed plate evaporator Power cord provided One year limited warranty

Contact Information:

OPTI TEMP Inc. 484 W. Welch Ct. Traverse City, MI 49686 P: 231-946-2931 F: 231-946-0128 E: information@optitemp.com

Please contact our sales & applications department for a more complete list of available options.

REFRIGERATED RE-CIRCULATING FLUID CHILLERS

Specifications(1):
Description Standard Flow (2) Rating Max Available (3) Flow Range Pump (Standard) Connection Capacity
(4)

OTC GPM at PSI GPM HP Code MPT KW BTU/hr tons HP Type 115/1/60 100/1/50 230/1/60 230/1/50 230/3/60 460/3/60 Height Width Depth lbs. Gallon F Type

.25A 2.3 65 3.2 0.33 P1 0.5 0.6 2000 0.25 0.25 H 12.8 12

.33A 2.3 65 3.2 0.33 P1 0.5 0.8 2800 0.33 0.33 H 14 13.1 6.9 6.5

.5A 2.3 65 3.2 0.33 P1 0.5 1.3 4570 0.4 0.5 H 19 17.8 9 8.4

.75A 4 65 5.5 0.33 P3 0.5 2.3 7940 0.7 0.75 H 23 20 13 12.2

1.0A 4 65 5.5 0.33 P3 0.5 2.8 9550 0.8 1 H

1.5A 4 65 5.5 0.33 P3 0.5 5 17000 1.4 1.5 H

2.0A 5 47 26 1 C2 1 6 20700 1.7 2 H

3.0A 7 55 26 1.5 C3 1 10.5 36100 3 3.5 S

5.0A 12 53 38 1.5 C3 1 16 54400 4.5 5 H

7.5A 18 61 48 2 C4 1.25 24 82000 6.8 7.5 S

10A 24 58 48 2 C4 1.5 35 120000 10 12 S

Compressor

Full Load (5) Amps

Dimensions

(6)

Weight Internal Reservoir Temp Stability Refrigerant

22.5 15 23 130 0.75 0.2 R134A

22.5 15 23 130 0.75 0.2 R134A

22.5 15 23 155 0.75 0.2 R134A

22.5 24 24.5 205 1 0.2 R134A

15 14 12 6 27.5 28 25 205 2.5 0.2 R134A

22 20 16 8 27.5 28 25 215 2.5 0.2 R134A

29 26 17 10 26.5 36 36 350 2.5 0.2 R134A

46 42 31 15 26.5 36 36 455 2.5 0.2 R134A

48 44 36 14 34.5 31 46 505 2.5 0.5 R22

57 23 45 34.5 46 690 9 0.5 R22

60 35 45 34.5 46 715 9 0.5 R22

(1) As a result of continuous improvement efforts, specifications are subject to change without notice or liability. (2) Pump pressures at pump discharge. (3) Max flow rating with optional pumps. (4) Capacity based on 55 F LWT and 95 F ambient air temperature. Capacities may be 5% as reserved by compressor manufacturer. (5) Full load amps for models with standard pumps. Consult applications engineering for models with optional pumps. Full load amps must be used for sizing disconnects and supply wiring. Contact factory for 50 Hz applications engineering. (6) Dimensions are approximate and do not include filters or castors.

Pump Curves:
Positive Displacement Pump(s)
Flow (LPM)

Centrifugal Pump(s)
Flow (LPM)

0 100 90 80 70 60
Pressure 50 (PSI)

10

15

20

0.0 80
6

50.0

100.0

150.0

200.0 5.00

70 60 50
Pressure (BAR)

P1 &2 60 Hz

P3&4 60 Hz P5&6 60 Hz

5 4 3

4.00

Pressure (PSI) 40 30 C4 50 Hz

3.00 C4 60 Hz C3 60 Hz C3 50 Hz C2 60 Hz C2 50 Hz 1.00 2.00

Pressure (bar)

40 30 20 10 0 0 1

P1 &2 50 Hz

P3&4 50 Hz

P5&6 50 Hz

2 1 0

20 10 0 0 10 20 30

0.00 40 50 60 Flow (GPM)

3
Flow (GPM)

Standard pumps shown, other optional pumps available

LOVE CONTROL PARAMETERS


LOW TEMP WITH NO HEAT F C ITEM SP1 SP2 A1Lo Out1 Out2 SP2D TunE Pb1 Pb2 res rte Pid2 ArUP ArtE Fint Fbnd FrTE PEA VAL PctO InPC FiLt Lpbr SECr InP Unit dPt InPt SEnC SCAL SCAH SPL SPH Sp10 S1St S1OL S1OH S1LP S2t S2St S2OL S2OH S2rE S2Pi S2iH S2LP AL1 A1t A1rE A1Pi A1iH A1St A1LP A1Lb Setting 75 0 45 4tp onof -4 Pid 8 0.3 0.03 OFF OFF OFF 50 4 0.03 OFF 0 4 OFF 4 JIC F 0.0 OFF OFF -328 1607 45 110 OutA Dir 0 100 Oon Abs Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF Setting 25 0 7 4tp onof -2 Pid 4 0.3 0.03 OFF OFF OFF 50 2 0.03 OFF 0 4 OFF 4 JIC C 0.0 OFF OFF -73 871 7 40 OutA Dir 0 100 Oon Abs Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF 75 0 45 4tp onof -4 Pid 8 0.3 0.03 OFF OFF OFF 50 4 0.03 OFF 0 4 OFF 4 JIC F 0.0 OFF OFF -100 1600 45 110 OutA Dir 0 100 Oon Dev Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF 25 0 7 4tp onof -2 Pid 4 0.3 0.03 OFF OFF OFF 50 2 0.03 OFF 0 4 OFF 4 JIC C 0.0 OFF OFF -73 871 7 40 OutA Dir 0 100 Oon Dev Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF 125 0 80 4tp onof -4 Pid 8 0.3 0.03 OFF OFF OFF 50 4 0.03 OFF 0 4 OFF 4 JIC F 0.0 OFF OFF -100 1600 45 190 OutA Dir 0 100 Oon Dev Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF 50 0 Secondary Menu 27 4tp onof -2 Pid 4 0.3 0.03 OFF OFF OFF 50 2 0.03 OFF 0 4 OFF Secure Menu 4 JIC C 0.0 OFF OFF -73 871 7 90 OutA Dir 0 100 Oon Dev Re 0 100 Onof OFF OFF Oon Lo Abs Onof OFF OFF Open Ooff OFF Temperature set point Deviation from SP1 LOW TEMP WITH HEAT F C HIGH TEMP WITH HEAT F C COMMENTS

X002354

Alarm Low Output Selection: OnOf, 1tp,or 1PuL Output Selection: OnOf, 1tp, or 1PuL Set Point 2 Deviaton Tuning Choice: Self, Pid, SLO, nor, FASt PID Parameters PID Parameters PID Parameters PID Parameters Don't Change Approach Rate Fuzzy intensity Set @ Half of PB1 Set same as rte Highest peak since last on/off Lowest valley since last on/off Don't Change Input Correction Use 2 for 0 and 4 for 0.0 Don't Change Don't Change 1P38 FOR RTD F or C Decimal Point Positioning 0 or 0.0 Don't Change Don't Change -200 FOR RTD 875 FOR RTD Set point Low Set point High Don't Change Output State; dir (cool) or rE(heat) Don't Change Don't Change Lamp Type; AbSolute or DEviation from SP1 Output State; dir (cool) or rE(heat) Don't Change Don't Change Reset , Automatic Power Interrupt Inhibit till first cycle Lamp Function: OFF, LO, Hi. HiLo, Evnt Type; AbSolute or DEviation from SP1 Reset , Automatic Power Interrupt Inhibit till first cycle Output State Lamp Loop Break

Performance Curves 60 Hz, 3500 RPM Curvas de Funcionamiento 60 Hz, 3500 RPM
Model NPE / 1ST Size (Tamao) 1 x 114-6 RPM 3500 Curve (Curva) CN0231R01
NPSH R FEET (PIES) 50
TOTAL DYNAMIC HEAD (CARGA DINAMICA TOTAL) H

METERS METROS

FEET PIES

Impeller Selections for ODP & TEFC Motors Selecciones del Impulsor para Motores ODP & TEFC
NOTE: Not recommended for operation beyond printed H-Q curve. NOTA: No se recomienda para funcionamiento superior al impreso en la curva H-Q.

Ordering Standard Code, HP Rating, Imp. Cdigo Estndar HP Dia. de Pedido Potencia

160
140

E D C

1 1 2

4716 4 5316 5 618

5' A 618" DIA. B 534" 45 48 50

6'

8' 10'

40
120 100 80

51 52 51 53 50

12' 48 EFF %

B A

C 5316" D 434" E 4716"

30

HP

20

2H 1H
1 2

60 40

1 12

NOTE: Although not recommended, the pump may pass a 116 sphere. NOTA: Si bien no se recomienda, la bomba puede pasar una esfera de 116.

HP

10
20

HP

3 4

HP

0 0

10

20 5

30
CAPACITY (CAPACIDAD) Q

40 10

50

60 U.S. GPM
m3 hr

METERS METROS 50

FEET PIES

Model NPE / 1ST Size (Tamao) 1 x 114-6 Impeller Selections for Exp. Proof Motors Selecciones del Impulsor para Motores Exp. Proof RPM 3500 Curve (Curva) CN0231R01
NOTE: Not recommended for operation beyond printed H-Q curve. NOTA: No se recomienda para funcionamiento superior al impreso en la curva H-Q.

Ordering Standard Code, HP Rating, Imp. Cdigo Estndar HP Dia. de Pedido Potencia

160

NPSH R FEET (PIES)

F E

1 1 2 3

5'
A 618" DIA.

4116 spec. 4716 4 5316 5 618

TOTAL DYNAMIC HEAD (CARGA DINAMICA TOTAL) H

140
40

45 48

6' 50 51 52

8' 10' 51 12' 48 EFF % 3H P

D C B A

B 534"
120 100 80

C 5316" D 434" E 4716"

53

50

30

20

2H
1 1
P
2

60 40

F 4 16" Spec.
1

8' 10' 12'


1 2

1H
H P
3 4

HP

NOTE: Although not recommended, the pump may pass a 116 sphere. NOTA: Si bien no se recomienda, la bomba puede pasar una esfera de 116.

10

20
0

HP

10

20 5

30

40 10

50

60 U.S. GPM
m3 hr

CAPACITY (CAPACIDAD) Q

15 16
CRANK CASE HEATER(S)

#7
FUSED POWER ENTRY

17

M1

M1

M1

C1

C1

C1

5
M1 CIRCULATION PUMP C1 COMPRESSOR

M1 AUX 4 (21) (22) 6

LEGEND: PANEL WIRING FIELD WIRING

CONDENSING FAN(S) ON-OFF

H1

H4 2 L2 CONTROL TRANSFORMER 240/480-120 VAC. 50 VA (8) 8

F-2 1/2 AMP

L1

TERMINAL IN PANEL COMPONENT TERMINAL WIRE NUMBER

ITEMS IN RED FOR HEATED UNITS ONLY ITEMS IN BLUE ARE OPTIONAL ITEMS IN GREEN ARE FOR 3-PHASE PUMPS. DELETE FOR SINGLE PHASE (PROCON) PUMPS

START

M-1
M1 AUX 8 (33) (34) FLOAT 7

MOTOR STARTER CIRCULATION PUMP (AB 100-M/C NC) SYSTEM RUN INDICATOR

PM
T1 T2

12 9 12 6 11 15 16 10

LOW PRES.

HI PRES.

CR-2
29 9

PM
M1 M2

PROTECTION MODULE (OPTIONAL) (SHORT M1 & M2 WHEN NOT USED) FREEZE WARNING RELAY (LY-2) OPTIONAL: AB SERIES WITH N.C. CONTACT. (REPLACE C-1 & CR-2) COMPRESSOR CONTACTOR DPA 33534 (IN COMPRESSOR ELECTRICAL BOX) HOT GAS BYPASS SOL VALVE (OTC-10 ONLY)

C-1
SOL

11

SOL

852-7514 SNUBBER LIQUID SOLENOID

17 13

18 14 1 3 (WHT) T.C. LOVE CONTROL 16A2133 THERMOCOUPLE (TYPE "J")

OPTI TEMP INC.


TRAVERSE CITY, MICHIGAN
SUBJECT CHILLER SCHEMATIC 1-10 HP 230/460-3-60 W / LOVE CONTROL SPECIAL DRAWN BY
JOB NUMBER

CR-2 (21) M1 AUX (21)

13 (22) 14 (22)

R R

FREEZE WARNING INDICATOR PUMP ALARM INDICATOR

WITH HEATER OPTION AND ANTI DRAIN BK JAC


DATE

8-7-07

SCALE

DRAWING NUMBER

E002061

R1 C1

Potrebbero piacerti anche