Sei sulla pagina 1di 3

HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN

ABB LIMITED

Doc Ref.No. 3VYN591602

SIZING CALCULATION FOR UPS

Sheet 1 of 3

SIZING CALCULATION FOR UPS

OWNER:

HINDUSTAN ZINC LIMITED. ZAWAR MINES, RAJASTHAN.

MAIN CONTRACTOR

TATA PROJECTS LTD. HYDERABAD.

e-BOP CONTRACTOR:

ABB LIMITED. FARIDABAD.

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB eBoP.

HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN


ABB LIMITED

Doc Ref.No. 3VYN591602

SIZING CALCULATION FOR UPS

Sheet 2 of 3

REVISION STATUS SHEET

REV. NO.

DATE 10.07.2007

DESCRIPTION FOR REFERENCE ONLY

R0

Rev. No. R0

Date 10.07.2007

KK Prepared by

AB Reviewed by

For Reference Remarks

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB eBoP.

HINDUSTAN ZINC LTD 1 X 80MW, ZAWAR CPP ZAWAR MINES, RAJASTHAN


ABB LIMITED

Doc Ref.No. 3VYN591602

SIZING CALCULATION FOR UPS

Sheet 3 of 3

S.No. A 1

FEEDER/LOAD DESCRIPITION BTG LOADS SG/TG DCS

LOAD IN REMARKS kVA 12 Reference has been taken from UPS sizing calculation of HZL, Phase-I, Unit-1. Vide Doc. No: TCE.4221A-EL-CAL-580-01, R1, Dated 08-09-2004

2 3 4 5 6 7 8 9 10 11 12 13 14 15 B 1 C

BOP DCS HMI & MAXNET FOR UNIT # 1

6.5 10 6.5

MAX DNA BMS PANELS (SOLENOIDS) LEVEL SWITCH VMS EWLI COAL FLOW DETECTOR ESP IOS LIGHT OIL FLOW METER PD TYPE SPARE FEEDERS CONTROL PANEL (FOR TRANSDUCERS & RECORDERS) TSI MONITORING SYSTEM VMS SYSTEM WORK STN & PRINTER BOP LOADS SWAS & GAS ANALYSERS TOTAL KVA LOADING FACTOR OF 25% AS PER CONTRACT UPS RATING (STANDARD RATING)

4.0 1.0 0.75 1.20 0.60 2.0 0.2 1.5 0.55 0.25 1.5

Feeder Description not enlisted in the TPL document. However, load has been retained.

2.00 50.55 63.18 65 KVA As per the standard rating.

CONCLUSION Selected UPS Rating Voltage Rating No. of UPS per Unit in line with HZL, phase-1 & 2. : : : 65 kVA 110V AC 1 No., parallel redundant type