Sei sulla pagina 1di 61

CIGNA-Bloomfield CT

Location/Tag
AC-11-1 R-12-1 AC-12-1 AC-12-2 R-12-2 R-11-1 R-12-3 AC-12-3 R-10-2 R-9-2 AC-9-2 AC-9-3 AC-10-1 AC-9-1 R-10-1 R-9-1 AC-10-2 R-4-2 AH-4-2 R-4-1 AH-4-1-S R-3-4 AH-3-4 R-3-2 AH-3-2 R-3-1 AC-3-1 R-2-1 AH-2-1 AH-1-1-S AC-5-1-S R-5-1 AH5-2-S R-5-2 AH-5-3-S R-5-3 AH-6-1-S R-6-1 AH-6-2-S AH-7-1-S R-7-1 AH-8-1-S R-8-1 AH-1-1(R1-1) R-6-2 HWP-1&2

Model #
ACH501-015-4-00P2 ACH501-005-4-00P2 ACH501-010-4-00P2 ACH501-005-4-00P2 ACH501-003-4-00P2 ACH501-007-4-00P2 ACH501-007-4-00P2 ACH501-020-4-00P2 ACH501-003-4-00P2 ACH501-010-4-00P2 ACH501-030-4-00P2 ACH501-025-4-00P2 ACH501-040-4-00P2 ACH501-060-4-00P2 ACH501-010-4-00P2 ACH501-020-4-00P2 ACH501-015-4-00P2 ACH501-015-4-00P2 ACH501-040-4-00P2 ACH501-020-4-00P2 ACH501-040-4-00P2 ACH501-007-4-00P2 ACH501-015-4-00P2 ACH501-020-4-00P2 ACH501-060-4-00P2 ACH501-020-4-00P2 ACH501-060-4-00P2 ACH501-020-4-00P2 ACH501-040-4-00P2 ACH501-075-4-00P2 ACH501-060-4-00P2 ACH501-020-4-00P2 ACH501-075-4-00P2 ACH501-025-4-00P2 ACH501-050-4-00P2 ACH501-020-4-00P2 ACH501-040-4-00P2 ACH501-015-4-00P2 ACH501-040-4-00P2 ACH501-075-4-00P2 ACH501-025-4-00P2 ACH501-075-4-00P2 ACH501-025-4-00P2 ACH501-025-4-00P2 ACH501-015-4-00P2 ACH501-075-4-00P2

Serial #
159256 159445 158766 159446 159392 158559 158558 159352 159391 159255 159280 159484 159066 159289 159254 159353 159368 177821 177766 179038 177765 177811 177820 A188524 177758 179037 177756 179036 177767 148443 177757 178994 178446 178511 177770 178993 177768 177822 177769 178444-B 178509 178444-A 178512 148620 177819 131096

HP
15 5 10 5 3 7 7 20 3 10 30 25 40 60 10 20 15 15 40 20 40 7 15 20 60 20 60 20 40 75 60 20 75 25 50 20 40 15 40 75 25 75 25 25 15 75

Equipment Inventory as of 12/12/2013

1 of 61

CIGNA-Bloomfield CT

Location/Tag
CT-1 CT-2 CT-3 CT-4 P4 P3 WILDE-EDP P-1 WILDE-EDP P-2 WILDE-CHWP-1 WILDE-CHWP-2 Blr Rm MAU Chiller CWP2 Chiller CWP4 Chiller SCHP1 Chiller SCHP3 Chiller SCHP2 Cell 3 Cell 3 CT 1 CT 2 CT 3 CT 4 CT 5

Model #
ACH501-040-4-00P2 ACH501-040-4-00P2 ACH501-030-4-00P2 ACH501-040-4-00P2 ACH401-601132 ACH401-601132 ACH401604132 ACH401604132 ACH401612032 ACH401612032 ACH401600932 ACH550UH044A4 ACH550UH044A4 ACH550BD124A4 ACH550BD124A4 ACH550BD124A4 ACH550BD077A4 ACH550BD077A4 ACH401601132 ACH401601132 ACH401601132 ACH401601132 ACH401601132

Serial #
160374 160468 160238 159067 2023100173 2023100170 2031700696 2031700697 2031700299 2031700304 2040600001 2042600457 2042600517 2042600493 2042800138 2042700164 2043400170 2043400629 2034700104 2034700105 2034700103 2034700107 2034700106

HP
40 40 30 40

Equipment Inventory as of 12/12/2013

2 of 61

Location
MER 5 R5-1

Tag
The cooling fan capacitor needs to be replaced.

Problem

Date Corrected

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 80 Deg. F 97 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC11-1
ABB ACH501-015-4-00P2 CRH03H 0

7/6/10
Storage 01A-119 159256 64880 0

Main Fuses: Amp-Trap AJT 30 VFD I-Limit Setting: 19.44 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 473 380 4 7.2 Vac Vac Amps Amps C-A: C-A: C: C: 473 380 4.2 7 1.6 Vac Vac Amps Amps Vac

/ Data X

X 50 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 380 4.3 7.2 Vac Vac Amps Amps 630 B-C: B-C: B: B: Vdc

Display 383 Vac Display 6.8 Amps 632 0 649 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 645 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.5 129 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-12-1
ABB ACH501-005-4-00P ACH1-005-4-SEL CRH03H 0

12/14/12
Chiller Rm. 159445 M3060 61160h 0

VFD Fuses: BUSSMANN FWH 16A6F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 73 Deg. F 84 Deg. F X X X X

Main Fuses: AMP-TRAP AJT-10 VFD I-Limit Setting: 6.68 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 489 455 2.6 3 Vac Vac Amps Amps C-A: C-A: C: C: 488 455 2.5 3.5 1.3 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 455 2.7 3.6 Vac Vac Amps Amps 652 B-C: B-C: B: B: Vdc

Display 460 Vac Display 3.8 Amps 655 0 675 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 668 9.90 23.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.4 mVac 132 n/a n/a Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-12-1
ABB ACH501-010-4-00P ACH1-010-4-SEL CRH03H 0

12/14/12
Chiller Rm. 158766 M3060 53979h 0

VFD Fuses: BUSSMANN FWC-30A 10F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 65 Deg. F 86 Deg. F X X X X

Main Fuses: AMP-TRAP AJT-20 VFD I-Limit Setting: 15.44 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 456 5.9 7.6 Vac Vac Amps Amps C-A: C-A: C: C: 485 456 5.2 7.5 1.1 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 456 5.9 7.6 Vac Vac Amps Amps 648 B-C: B-C: B: B: Vdc

Display 460 Vac Display 7 Amps 653 0 671 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 668 10 26.2 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.5 132 N/A N/A Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-12-2
ABB ACH550-UH-08A8-4 ACH1-005-4-SEL CRH03H 0

12/6/12
Chiller Rm. 2101100995 M3060 0h 0

VFD Fuses: Bussmann FWH 16A6F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 65 Deg. F 27 Deg. C X X X X

Main Fuses: AMP-TRAP AJT-10 VFD I-Limit Setting: 12.4 VFD Freq Limits: 12 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 104 .4 1.6 Vac Vac Amps Amps C-A: C-A: C: C: 487 104 .3 1.7 n/a Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 20 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 104 .3 1.6 Vac Vac Amps Amps 660 B-C: B-C: B: B: Vdc

Display 107 Vac Display 1.6 Amps 661 0 669 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 668 9.97 23.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: n/a 3 19 132 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: n/a VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 65 Deg. F 28 Deg. C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-12-2
ABB ACH550-UH-06A9-4 ACH1-003-4-SE 312B 0

12/14/12
Chiller Rm. 2081402675 M3060 7.70kh 0

Main Fuses: AMP-TRAP AJT-8 VFD I-Limit Setting: 9.7 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 388 1.2 1.9 Vac Vac Amps Amps C-A: C-A: C: C: 487 389 1.3 1.8 n/a Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 59 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 388 1.2 1.8 Vac Vac Amps Amps 653 B-C: B-C: B: B: Vdc

Display 405 Vac Display 2 Amps 657 0 673 n/a n/a n/a n/a n/a Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 669 9.98 23.78 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: n/a 3.4 12 132 n/a n/a Vac mVac mVac Vac mVac mVac

I noticed that the hours haven't change from last years P.M.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 115% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 80 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-11-1
ABB ACH501-007-4-00P2 CRH03H 0

7/6/10
Storage 01A-119 158559 2698 0

Main Fuses: Amp-Trap AJT 15 VFD I-Limit Setting: 10.10 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 473 379 7.3 9.7 Vac Vac Amps Amps C-A: C-A: C: C: 473 379 7.3 9.6 1.8 Vac Vac Amps Amps Vac

/ Data X

VFD Temp at Check-out (Display) 117 Deg. F

X 50 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 379 7.3 9.8 Vac Vac Amps Amps 623 B-C: B-C: B: B: Vdc

Display 383 Vac Display 9.5 Amps 630 0 653 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 647 10 25.7 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.5 129 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-12-3
ABB ACH501-007-4-00P ACH1-007-4-SEL CRH03H 0

12/6/12
Chiller Rm. 158558 M3060 54237h 0

VFD Fuses: BUSSMANN FWH 16A6F VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 65 Deg. F 81 Deg. F X X X X

Main Fuses: AMP-TRAP AJT-15 VFD I-Limit Setting: 9 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 127 .8 4.2 Vac Vac Amps Amps C-A: C-A: C: C: 488 127 .8 4.2 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 17 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 127 .7 4.2 Vac Vac Amps Amps B-C: B-C: B: B: Vdc

Display 134 Vac Display 4.2 Amps 660 0 675 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: N/A N/A Vdc Vdc DC Level: DC Level: DC Level: 10 25.89 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 1 10 132 N/A N/A Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-12-3
ABB ACH501-020-4-00P2 ACH1-020-4-SEL3 CRH03H 8Overcurrent.

12/6/12
Chiller Rm. 159352 M3062 54642h 0

VFD Fuses: Bussman FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 65 Deg. F 70 Deg. F X X X X

Main Fuses: Amp Trap AJT40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 244 2.6 9.4 Vac Vac Amps Amps C-A: C-A: C: C: 485 244 2.6 9 1.4 Vac Vac Amps Amps Vac

/ Data X .47uF .460uF n/a X X n/a X 32 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 245 2.8 9.2 Vac Vac Amps Amps 650 B-C: B-C: B: B: Vdc

Display 248 Vac Display 7.2 Amps 658 0 671 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 666 10 25.97 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.5 mVac 132 n/a n/a Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 75 Deg. F 91 Deg.F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-10-2
ABB ACH501-003-4-00P2 CRH03H 0

7/6/10
MER 10 159391 50214 0

Main Fuses: Amp-Trap AJT 8 VFD I-Limit Setting: 5.26 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 472 454 3 3.5 Vac Vac Amps Amps C-A: C-A: C: C: 472 455 3 3.4 3 Vac Vac Amps Amps Vac

/ Data X

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 472 455 3 3.5 Vac Vac Amps Amps 626 B-C: B-C: B: B: Vdc

Display 460 Vac Display 3.2 Amps 631 0 650 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 646 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8 129 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-9-2
ABB ACH501-010-4-00P2 CRH03H 0

7/1/10
MER 9 159255 6049 0

VFD Fuses: Bussmann FWC 30A10F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 68 Deg. F 82 Deg. F X X X X

Main Fuses: Amp-Trap AJT 20 VFD I-Limit Setting: 14.12 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 482 230 1.5 4.7 Vac Vac Amps Amps C-A: C-A: C: C: 482 231 1.4 4.8 <1 Vac Vac Amps Amps Vac

/ Data X N/A N/A

X 30 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 482 230 1.5 4.8 Vac Vac Amps Amps 646 B-C: B-C: B: B: Vdc

Display 233 Vac Display 4 Amps 649 0 661 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 659 10 25.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.6 mVac 131 Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-9-2
ABB ACH501-030-4-00P2 CRH03H 0

2/12/13
MER 9 159280 12557 0

VFD Fuses: Bussmann FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 86 Deg. F X X X X

Main Fuses: Amp-Trap AJT 60 VFD I-Limit Setting: 39.52 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 480 377 Vac Vac C-A: C-A: C: C: 482 377 Vac Vac

/ Data X 1uF 1.033uF n/a X X n/a X 49 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 483 377 Vac Vac B-C: B-C: B: B: Vdc

Display 383 Vac Display 20 Amps 648 0 667 Vdc Hz

15.7 Amps 22 Amps 642

15 Amps 22.9 Amps

15 Amps 22.9 Amps 1.2 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 663 10 25.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.7 129 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-9-3
ABB ACH501-025-4-00P2 CRH03H 0

2/12/13
MER 9 159484 14922 0

VFD Fuses: Bussmann FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 82 Deg. F X X X X

Main Fuses: Amp-Trap AJT 50 VFD I-Limit Setting: 32.86 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 483 276 7.4 14 Vac Vac Amps Amps C-A: C-A: C: C: 483 276 7 14 1.4 Vac Vac Amps Amps Vac

/ Data X .47uF .466uF n/a X X n/a X 36 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 276 Vac Vac B-C: B-C: B: B: Vdc

Display 283 Vac Display 12.7 Amps 649 0 665 Vdc Hz

7.2 Amps 14.4 Amps 644

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 663 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.7 130 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC-10-1
ABB ACH501-040-4-00P2 CRH03H 0

7/6/10
MER 10 159066 47179 0

VFD Fuses: Bussmann FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 75 Deg. F 88 Deg. F X X X X

Main Fuses: Amp-Trap AJT 60 VFD I-Limit Setting: 57.34 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 476 378 Vac Vac C-A: C-A: C: C: 476 378 Vac Vac

/ Data X 1uF 1.034uF

X 50 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 476 382 Vac Vac B-C: B-C: B: B: Vdc

Display 383 Vac Display 23 Amps 634 0 653 Vdc Hz

16 Amps 25.6 Amps 630

16 Amps 25.3 Amps

15.8 Amps 26 Amps 1.2 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 650 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 128 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: n/a VFD I-Limit Setting: 77.52 VFD Freq Limits: / Data n/a n/a 72 Deg. F 84 Deg. F X X X X 20 TO 60 Hz

AC-9-1
ABB ACH501-060-4-00P2 CRH03H 0

2/12/13
MER 9 159289 60464 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 482 263 14 30 Vac Vac Amps Amps C-A: C-A: C: C: 484 267 14 30 2 Vac Vac Amps Amps Vac

/ Data X 1uF 1.037uF n/a X X n/a X 36 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 269 15 30 Vac Vac Amps Amps 646 B-C: B-C: B: B: Vdc

Display 277 Vac Display 29 Amps 654 0 670 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 665 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 7.7 126 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 75 Deg. F 86 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-10-1
ABB ACH501-010-4-00P2 CRH03H 0

7/6/10
MER 10 159254 46843 0

Main Fuses: Amp-Trap AJT 20 VFD I-Limit Setting: 12.94 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 476 304 3 6 Vac Vac Amps Amps C-A: C-A: C: C: 477 304 2.8 6 1 Vac Vac Amps Amps Vac

/ Data X

X 40 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 476 304 2.8 6 Vac Vac Amps Amps 632 B-C: B-C: B: B: Vdc

Display 307 Vac Display 5 Amps 637 0 652 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 649 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 10 129 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-9-1
ABB ACH501-020-4-00P2 CRH03H 0

2/12/13
MER 9 159353 60760 0

VFD Fuses: Bussmann FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 77 Deg. F X X X X

Main Fuses: Amp-Trap AJT 40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 259 3.5 9.8 Vac Vac Amps Amps C-A: C-A: C: C: 482 261 3.6 9.6 1 Vac Vac Amps Amps Vac

/ Data X .5uF .498uF n/a X X n/a X 32 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 259 3.5 10 Vac Vac Amps Amps 646 B-C: B-C: B: B: Vdc

Display 253 Vac Display 8 Amps 650 0 665 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 662 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.5 mVac 131 n/a n/a Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 75 Deg. F 95 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AC10-2
ABB ACH501-015-4-00P2 CRH03H 0

7/6/10
MER 10 159368 50032 0

Main Fuses: Amp-Trap AJT 30 VFD I-Limit Setting: 23.04 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 470 458 6.9 8.5 Vac Vac Amps Amps C-A: C-A: C: C: 471 458 6.9 9 1.5 Vac Vac Amps Amps Vac

/ Data X

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 471 457 6.5 8.5 Vac Vac Amps Amps 624 B-C: B-C: B: B: Vdc

Display 459 Vac Display 8 Amps 629 0 649 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 644 10 25.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 10 129 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R4-2
ABB ACH501-015-4-00P2 CRH03H 0

5/14/10
MER 4 177821 47913h 0

VFD Fuses: Bussman FWC 30A10F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 70 Deg. F 84 Deg. F X X X X

Main Fuses: Littelfuse JTD 30 VFD I-Limit Setting: 20.52 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 482 173 1.4 7 Vac Vac Amps Amps C-A: C-A: C: C: 482 173 1.2 7 <1 Vac Vac Amps Amps Vac

/ Data X

X 23 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 173 1.2 7 Vac Vac Amps Amps 653 B-C: B-C: B: B: Vdc

Display 176 Vac Display 5 Amps 660 0 671 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 663 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 208 131 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH4-2
ABB ACH501-040-4-00P2 CRH03H 0

5/14/10
MER 4 177766 48395h 0

VFD Fuses: Bussman FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 70 Deg. F 81 Deg. F X X X X

Main Fuses: Littelfuse JTD 80 VFD I-Limit Setting: 53.10 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 261 6 18 Vac Vac Amps Amps C-A: C-A: C: C: 484 262 6.2 18 1.2 Vac Vac Amps Amps Vac

/ Data X 1uF .864uF

X 35 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 261 Vac Vac B-C: B-C: B: B: Vdc

Display 267 Vac Display 15 Amps 654 0 670 Vdc Hz

6 Amps 18.4 Amps 646

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 664 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 129 Vac mVac mVac Vac mVac mVac

Need to replace cooling fan capacitor.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 74 Deg. F 83 Deg.F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R-4-1
ABB ACH501-020-4-00P2

12/7/13
MER 4 179038 60625h 0

Main Fuses: Littelfuse JTD40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 500 189 1.2 8.3 Vac Vac Amps Amps C-A: C-A: C: C: 500 189 1.2 8.1 1.1 Vac Vac Amps Amps Vac

/ Data X .5uF .304uF X X n/a n/a X 25 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 498 189 1.3 8.4 Vac Vac Amps Amps 684 B-C: B-C: B: B: Vdc

Display 192 Vac Display 5.3 Amps 691 0 699 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 692 10.1 25.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 <1 9.5 136 Vac mVac mVac Vac mVac mVac

Fan capacitor reading low.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH4-1
ABB ACH501-040-4-00P2 CRH03H 0

12/7/13
MER 4 177765 60400h 0

VFD Fuses: Bussman FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 70 Deg. F 77 Deg. F X X X X

Main Fuses: Littelfuse JTD 80 VFD I-Limit Setting: 53.10 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 499 211 34 40 Vac Vac Amps Amps C-A: C-A: C: C: 500 211 33 41 .9 Vac Vac Amps Amps Vac

/ Data X 1uF .776uF X X X 28.57 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 499 211 Vac Vac B-C: B-C: B: B: Vdc

Display 219 Vac Display 11.7 Amps 687 0 670 Vdc Hz

33.4 Amps 40 Amps 680

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 664 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.5 129 Vac mVac mVac Vac mVac mVac

Need to replace cooling fan capacitor.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R3-4
ABB ACH501-007-4-00P2 ACH1-007-4-SEL3 CRH03H 0

12/21/12
MER 3 177811 M3632 53904h 0

VFD Fuses: Bussmann FWH16A6F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 74 Deg. F 79 Deg. F X X X X

Main Fuses: Littelfuse JTD 15 VFD I-Limit Setting: 10.10 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 153 .4 1 Vac Vac Amps Amps C-A: C-A: C: C: 484 153 .4 1 n/a Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 22 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 153 .4 1 Vac Vac Amps Amps n/a B-C: B-C: B: B: Vdc

Display 147 Vac Display 2.4 Amps 665 0 675 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: n/a 10 25.8 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: n/a 1 16 133 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH3-4
ABB ACH501-015-4-00P2 ACH1-015-4-SEL3 CRH03H 0

12/21/12
MER 3 177820 M3632 52957 0

VFD Fuses: Bussmann FWC 30A10F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 73 Deg. F 93 Deg. F X X X X

Main Fuses: Littelfuse JTD 30 VFD I-Limit Setting: 20.52 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 304 3.6 8.4 Vac Vac Amps Amps C-A: C-A: C: C: 484 304 3.4 8.4 1.2 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 40 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 304 3.6 8.3 Vac Vac Amps Amps 647 B-C: B-C: B: B: Vdc

Display 308 Vac Display 7.6 Amps 654 0 669 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 663 10 25.8 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 132 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R3-2
ABB ACH501-020-4-00P2 ACH1-020-4-SEL3 CRH03J 0

12/26/12
MER 3 A188524 M3632 50509h 0

VFD Fuses: Bussmann FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 75 Deg. F 75 Deg. F X X X X

Main Fuses: Littelfuse JTD 40 VFD I-Limit Setting: 27.36 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 113 .9 8.3 Vac Vac Amps Amps C-A: C-A: C: C: 484 113 .8 8.3 <1 Vac Vac Amps Amps Vac

/ Data X .5uF .437uF n/a X X n/a X 15 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 113 .7 8.3 Vac Vac Amps Amps 655 B-C: B-C: B: B: Vdc

Display 115 Vac Display 4 Amps 659 0 664 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 660 10 25.7 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 131 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 77.52 VFD Freq Limits: / Data n/a n/a 75 Deg. F 86 Deg. F X X X X 20 TO 60 Hz

AH3-2
ABB ACH501-060-4-00P2 ACH1-060-4-SELBL3 CRH03H 0

12/26/12
MER 3 177758 M3632 56937h 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 482 305 Vac Vac C-A: C-A: C: C: 482 313 Vac Vac

/ Data X 1uF .972uF n/a X X n/a X 42 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 481 306 Vac Vac B-C: B-C: B: B: Vdc

Display 322 Vac Display 28 Amps 651 0 667 Vdc Hz

15.6 Amps 30 Amps 641

14.8 Amps 30 Amps

15.7 Amps 29 Amps 1.9 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: n/a n/a Vac mVac mVac Vac mVac mVac

I did not take readings with the drive at 0Hz, because it started to make unusual sounds and smell bad until I turned it off.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R3-1
ABB ACH501-020-4-00P2 ACH1-020-4-SEL3 0

12/21/12
MER 3 179037 M3632 57906h 0

VFD Fuses: Bussmann FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 74 Deg. F 77 Deg. F X X X X

Main Fuses: Littlefuse JTD 40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 143 1 8.4 Vac Vac Amps Amps C-A: C-A: C: C: 486 143 1 8.3 1.2 Vac Vac Amps Amps Vac

/ Data X .5uF .454uF n/a X X n/a X 25 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 143 1 8 Vac Vac Amps Amps 650 B-C: B-C: B: B: Vdc

Display 230 Vac Display 6.2 Amps 660 0 662 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 658 10 25.98 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1.5 13 132 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 77.52 VFD Freq Limits: / Data n/a n/a 73 Deg. F 82 Deg. F X X X X 20 TO 60 Hz

AH3-1
ABB ACH501-060-4-00P2 ACH1-060-4-SELBL3 CRH03H 0

12/21/12
MER 3 177756 M3632 57883h 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 299 Vac Vac C-A: C-A: C: C: 483 300 Vac Vac

/ Data X 1uF .88uF n/a X X n/a X 40 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 296 14 30 Vac Vac Amps Amps 647 B-C: B-C: B: B: Vdc

Display 308 Vac Display 27 Amps 653 0 667 Vdc Hz

14.6 Amps 30 Amps

14.4 Amps 29 Amps 1.8 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 664 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.2 126 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R2-1
ABB ACH501-020-4-00P2

12/7/13
MER 2 179036 65343 0

VFD Fuses: Bussmann 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 71 Deg. F 73 Deg. F X X X X

Main Fuses: Littelfuse JTD 40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 499 190 1.4 8.4 Vac Vac Amps Amps C-A: C-A: C: C: 499 190 1.4 8.4 .8 Vac Vac Amps Amps Vac

/ Data X .5uF .307uF X X n/a N/a X 25 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 497 190 1.4 8.3 Vac Vac Amps Amps 683 B-C: B-C: B: B: Vdc

Display 192 Vac Display 5.5 Amps 687 0 696 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 693 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 7.3 135 Vac mVac mVac Vac mVac mVac

Reading from fan capacitor low, needs replacement

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH2-1
ABB ACH501-040-4-00P2 D3632A 0

12/7/13
MER 2 177767 D-Tech Cabinet 62467h 0

VFD Fuses: Bussmann FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 70 Deg. F 75 Deg. F X X X X

Main Fuses: Littelfuse JTD 80 VFD I-Limit Setting: 53.10 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 497 242 Vac Vac C-A: C-A: C: C: 498 242 4.8 17 1.3 Vac Vac Amps Amps Vac

/ Data X 1uF .776uF

X 33.31 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 497 243 4.1 17 Vac Vac Amps Amps 676 B-C: B-C: B: B: Vdc

Display 248 Vac Display 13.6 Amps 684 0 675 Vdc Hz

4.9 Amps 17.3 Amps

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 670 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

11.3 mVac 130 Vac mVac mVac

Need to replace cooling fan capacitor. -also need a replacement XFMR fuse, I put a temporary fuse in place(2A), need an littlefuse FLM 1 1/4A

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 77.52 VFD Freq Limits: / Data n/a n/a 72 Deg. F 81 Deg. F X X X X 20 TO 60 Hz

AC5-1
ABB ACH501-060-4-00P2 ACH1-060-4-SELBL3 CRH03H 0

12/17/12
MER 5 177757 M3632 60583 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 245 10 26 Vac Vac Amps Amps C-A: C-A: C: C: 486 243 Vac Vac

/ Data X 1uF .858uF n/a X X n/a X 33 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 246 9.9 26 Vac Vac Amps Amps 651 B-C: B-C: B: B: Vdc

Display 259 Vac Display 23 Amps 660 0 675 Vdc Hz

10.5 Amps 26 Amps 1.5 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 666 10 25.5 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8 126 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R5-1
ABB ACH501-020-4-00P2 ACH1-020-4-SEL3 CRH03H 0

12/17/12
MER 5 178994 M3632 60487h 0

VFD Fuses: Bussmann FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 73 Deg. F X X X X

Main Fuses: Littelfuse JTD 40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 116 1 9.8 Vac Vac Amps Amps C-A: C-A: C: C: 485 116 1 9.8 <1 Vac Vac Amps Amps Vac

/ Data X .5uF .23uF n/a X X n/a X 15 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 116 1.2 10 Vac Vac Amps Amps 658 B-C: B-C: B: B: Vdc

Display 122 Vac Display 5.5 Amps 666 0 670 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 665 10 26.2 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.6 mVac 132 n/a n/a Vac mVac mVac

The cooling fan capacitor needs to be replaced.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 98.97 VFD Freq Limits: / Data n/a n/a 72 Deg. F 97 Deg. F X X X X 20 TO 60 Hz

AH5-2
ABB ACH501-075-4-00P2 AHU1-075-4SELBC3 CRH03H 0

12/17/12
MER 5 178446 M3632 54955h 0

VFD Fuses: Bussman 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 300 20 39 Vac Vac Amps Amps C-A: C-A: C: C: 485 300 Vac Vac

/ Data X 1uF .966uF n/a X X n/a X 40 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 297 19 40 Vac Vac Amps Amps 640 B-C: B-C: B: B: Vdc

Display 316 Vac Display 34 Amps 656 0 672 Vdc Hz

20 Amps 39.5 Amps 2.4 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 666 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 126 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R5-2
ABB ACH501-025-4-00P2 ACH1-025-4-SEL3 CRH03H 0

12/17/12
MER 5 178511 M3632 56727h 0

VFD Fuses: Bussmann FWP5014F VFD O.L. Config: 115% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg.F 75 Deg. F X X X X

Main Fuses: Littelfuse JTD 50 VFD I-Limit Setting: 32.86 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 113 1 9 Vac Vac Amps Amps C-A: C-A: C: C: 486 113 1 9 <1 Vac Vac Amps Amps Vac

/ Data X .5uF .443uF n/a X X n/a X 15 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 486 113 1 9 Vac Vac Amps Amps 659 B-C: B-C: B: B: Vdc

Display 115 Vac Display 5.6 Amps 664 0 669 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 665 10 25.8 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 128 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH5-3
ABB ACH501-050-4-00P2 ACH1-050-4-SEL3 CRH03H 0

12/17/12
MER 5 177770 M3632 29829 0

VFD Fuses: Bussmann FWP 100A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 91 Deg. F X X X X

Main Fuses: Littelfues JTD 100 VFD I-Limit Setting: 66.96 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 313 Vac Vac C-A: C-A: C: C: 482 313 Vac Vac

/ Data X 1uF .23uF n/a X X n/a X 41 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 484 312 Vac Vac B-C: B-C: B: B: Vdc

Display 315 Vac Display 22 Amps 658 0 674 Vdc Hz

10.8 Amps 26.8 Amps 646

12 Amps 26.7 Amps

11.6 Amps 27 Amps 1.2 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 664 10 25.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.6 130 n/a n/a Vac mVac mVac Vac mVac mVac

I replaced the cooling fan capacitor because the readings were so low.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R5-3
ABB ACH501-020-4-00P2 ACH1-020-4-SEL3 CRH03H 0

12/17/12
MER 5 178993 M3632 29523 0

VFD Fuses: Bussmann FWP 5014F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 Deg. F 75 Deg.F X X X X

Main Fuses: Littelfuse JTD 40 VFD I-Limit Setting: 26.88 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 162 2 9 Vac Vac Amps Amps C-A: C-A: C: C: 482 162 1.8 9 <1 Vac Vac Amps Amps Vac

/ Data X .5uF .426uF n/a X X n/a X 21 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 162 2 9 Vac Vac Amps Amps 654 B-C: B-C: B: B: Vdc

Display 164 Vac Display 6.5 Amps 658 0 669 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 663 10 25.8 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.6 mVac 131 n/a n/a Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH6-1
ABB ACH501-040-4-00P2 D3632A CRH03H 0

12/7/13
MER 6 177768 D-Tech Cabinet 58897 0

VFD Fuses: Bussmann FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 69 Deg. F 70 Deg. F X X X X

Main Fuses: Littelfuse JTD 80 VFD I-Limit Setting: 53.10 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 500 227 Vac Vac C-A: C-A: C: C: 500 227 Vac Vac

/ Data X 1uF .377uF n/a X X n/a X 30 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 499 227 Vac Vac B-C: B-C: B: B: Vdc

Display 230 Vac Display 11.7 Amps 691 0 678 Vdc Hz

3 Amps 15.7 Amps 682

3.3 Amps 16.4 Amps

3.5 Amps 16.7 Amps 1 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 671 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 130 n/a n/a Vac mVac mVac Vac mVac mVac

Fan capacitor needs to be replaced 1uF: 12/07/2013

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R6-1
ABB ACH501-015-4-00P2 CRH03H 0

2/21/13
MER 6 177822 56537 0

VFD Fuses: Bussman FWC 30A10F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 69 Deg. F 82 Deg. F X X X X

Main Fuses: Littelfuse JTD 30 VFD I-Limit Setting: 20.52 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 187 1.8 6.8 Vac Vac Amps Amps C-A: C-A: C: C: 485 187 1.6 6.8 1.2 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 24 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 483 187 1.6 7 Vac Vac Amps Amps 656 B-C: B-C: B: B: Vdc

Display 187 Vac Display 5 Amps 660 0 675 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 669 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.5 132 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 98.78 VFD Freq Limits: / Data N/A N/A 74 Deg. F 79 Deg. F X X X X 20 TO 60 Hz

AH8-1
ABB ACH501-075-4-00P2 D3632A CRH03H 0

12/7/13
MER 8 178444 D-Tech Cabinet 575.3 mwh 0

VFD Fuses: Bussman 170M1369 160 VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 498 130 Vac Vac C-A: C-A: C: C: 497 130 Vac Vac

/ Data X 1uF .950uF

X 20 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 498 130 Vac Vac B-C: B-C: B: B: Vdc

Display 153 Vac Display 16 Amps 693 0 700 Vdc Hz

3 Amps 28.5 Amps 686

3.3 Amps 28.7 Amps

2.8 Amps 27.4 Amps .8 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 693 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.4 130 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

AH6-2
ABB ACH501-040-4-00P2 CRH03H 0

2/21/13
MER 6 177769 60023 0

VFD Fuses: Bussman FWP 80A22F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 69 Deg. F 82 Deg. F X X X X

Main Fuses: Littelfuse JTD 80 VFD I-Limit Setting: 53.10 VFD Freq Limits: 20 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 246 Vac Vac C-A: C-A: C: C: 485 245 Vac Vac

/ Data X 1uF .778uF n/a X X n/a X 32 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 246 Vac Vac B-C: B-C: B: B: Vdc

Display 248 Vac Display 15 Amps 659 0 677 Vdc Hz

6.3 Amps 19.3 Amps 652

6.6 Amps 19.8 Amps

6.4 Amps 19.3 Amps 1.4 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 664 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 7.6 130 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: VFD I-Limit Setting: 98.78 VFD Freq Limits: / Data N/A N/A 78 Deg. F 95 Deg. F X X X X 15 TO 60 Hz

AH7-1
ABB ACH501-075-4-00P2 CRH03H 0

7/1/10
MER-7 178448 46176 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 284 17 37 Vac Vac Amps Amps C-A: C-A: C: C: 486 282 Vac Vac

/ Data X 1uF .872uF

X 38 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 282 Vac Vac B-C: B-C: B: B: Vdc

Display 291 Vac Display 32 Amps 648 0 668 Vdc Hz

17 Amps 37.5 Amps 645

17 Amps 37.5 Amps 2.3 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 664 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 8.3 126 Vac mVac mVac Vac mVac mVac

Need to replace cooling fan capacitor. I replaced power indicator lamp.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R7-1
ABB ACH501-025-4-00P2 CRH03H 0

7/1/10
MER-7 178509 47407 0

VFD Fuses: Bussmann FWP50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 78 Deg. F 88 Deg. F X X X X

Main Fuses: Littelfuse JTD 50 VFD I-Limit Setting: 32.86 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 486 315 9 17 Vac Vac Amps Amps C-A: C-A: C: C: 486 316 Vac Vac

/ Data X .5uF .357uF

X 42 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 486 316 9.5 17 Vac Vac Amps Amps 647 B-C: B-C: B: B: Vdc

Display 322 Vac Display 15 Amps 653 0 671 Vdc Hz

9 Amps 16.7 Amps 1.4 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 665 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.2 mVac 131 Vac mVac mVac

Need to replace cooling fan capacitor.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R8-1
ABB ACH501-025-4-00P2 D3632A CRH03H 0

12/7/13
MER 8 178512 D-Tech Cabinet 54348h GRD FAULT

VFD Fuses: Bussman FWP 50A14F VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 74 Deg. F 73 Deg. F X X X X

Main Fuses: Littelfuse JTD 50 VFD I-Limit Setting: 32.54 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 498 111 .9 8.6 Vac Vac Amps Amps C-A: C-A: C: C: 498 111 .8 8.9 .6 Vac Vac Amps Amps Vac

/ Data X .5uF .443uF X X X 15 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 496 111 1.2 7.6 Vac Vac Amps Amps 683 B-C: B-C: B: B: Vdc

Display 115 Vac Display 5.6 Amps 696 0 695 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 690 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 6.6 134 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

R1-1
ABB ACH501-025-4-00P2 ACH1-025-4-SEL3 CRHO3J 0

12/21/12
MER 1 148620 M3632 57402 0

VFD Fuses: Bussmann FWP-50A14Fa VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 72 75 F X X X X

Main Fuses: Littelfuse JTD 50 VFD I-Limit Setting: 31.62 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 188 Vac Vac C-A: C-A: C: C: 486 189 Vac Vac

/ Data X >5uF .45uF n/a X X n/a X 29 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 188 Vac Vac B-C: B-C: B: B: Vdc

Display 209 Vac Display 9.3 Amps 655 0 668 Vdc Hz

2.6 Amps 10.5 Amps 649

3 Amps 10.7 Amps

2.9 Amps 10.8 Amps 1.8 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 664 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9 130 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: n/a VFD O.L. Config: 100% Bypass O.L. Config: Thermal VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 72 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 106.7 VFD Freq Limits: 15 TO 60 Hz

AH1-1
ABB ACH550-UH-097A-4 ACH1-075-4-SELB3 311A 0

12/21/12
MER 1 2074000504 M3632 17.26kh 0

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 485 198 Vac Vac C-A: C-A: C: C: 484 198 Vac Vac

/ Data X n/a n/a n/a X X n/a X 34 Hz

VFD Temp at Check-out (Display) 36.3 Deg. C

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 485 198 Vac Vac B-C: B-C: B: B: Vdc

Display 206 Vac Display 30 Amps 653 0 670 Vdc Hz

10.5 Amps 29.4 Amps 650

10.8 Amps 29.4 Amps

10.4 Amps 29.7 Amps 1.3 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 666 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 7 127 n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 9Overvolt.

R6-2
ABB ACH501-015-4-00P2 CRH03H 19In Comms.

2/21/13
MER 6 177819 65107 19In Comms.

VFD Fuses: Bussman FWC 30A10F VFD O.L. Config: 120% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data n/a n/a 69 Deg. F 82 Deg. F X X X X

Main Fuses: Littelfuse JTD 30 VFD I-Limit Setting: 20.52 VFD Freq Limits: 15 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 166 1.7 7.7 Vac Vac Amps Amps C-A: C-A: C: C: 486 166 1.7 7.7 1 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 21 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 166 1.8 7.9 Vac Vac Amps Amps 657 B-C: B-C: B: B: Vdc

Display 167 Vac Display 5.8 Amps 665 0 675 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 669 10 25.8 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

12.6 mVac 132 n/a n/a Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 98.78 VFD Freq Limits: / Data n/a n/a 73 Deg. F 82 Deg. F X X X X 30 TO 60 Hz

P1+P2
ABB ACH501-075-4-00P ACH1-075-4-SECBCS CRH03E 0

12/14/12
CHILLER ROOM 131096 M3130 9793h 0

VFD Fuses: Bussmann 170M1369 160A VFD O.L. Config: 115% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 281 Vac Vac C-A: C-A: C: C: 488 281 Vac Vac

/ Data X 1uF .825uF n/a X X n/a X 38 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 285 Vac Vac B-C: B-C: B: B: Vdc

Display 295 Vac Display 38 Amps 667 0 677 Vdc Hz

21.4 Amps 40 Amps 666

20.7 Amps 40 Amps

20.9 Amps 40 Amps 3.5 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 673 10 25.5 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 Vac mVac

10.2 mVac 127 n/a n/a Vac mVac mVac

I replaced the output aux contact that keeps the bypass contactor from comeing on at the same time as the drive output contactor because it was broken.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 61 Deg. F 48 Deg. C X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 1Overcurrent. Main Fuses: Amp-Trap AJT60 VFD I-Limit Setting: 35.7 VFD Freq Limits: 12 TO 60 Hz

CT-1
ABB ACH550-UH-059A-4

10/8/10
Outside 2081502881 8.03kh

1Overcurrent.

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 472 452 32 34 Vac Vac Amps Amps C-A: C-A: C: C: 472 452 32 34 4 Vac Vac Amps Amps Vac

/ Data X

X 59.9 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 471 452 31 34 Vac Vac Amps Amps 633 B-C: B-C: B: B: Vdc

Display 459 Vac Display 34 Amps 639 0 669 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 665 10 22.5 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 19 127 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

CT-2
ABB ACH501-040-4-00P2 CRH03H 0

10/8/10
Outside 160468 27071 0

VFD Fuses: Bussmann FWP80A22F VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 64 Deg. F 82 Deg. F X X X X

Main Fuses: Amp-Trap AJT60 VFD I-Limit Setting: 37.60 VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 473 454 Vac Vac C-A: C-A: C: C: 474 456 31 34 4 Vac Vac Amps Amps Vac

/ Data X 1uF 1.12uF

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 453 Vac Vac B-C: B-C: B: B: Vdc

Display 459 Vac Display 32 Amps 641 0 668 Vdc Hz

31 Amps 33.5 Amps 634

30 Amps 33.5 Amps

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 663 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 9.6 127 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

CT-3
ABB ACH501-030-4-00P2 CRH03H 0

10/8/10
Outside 160238 29639 0

VFD Fuses: Bussmann FWP80A22F VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 64 Deg. F 74 Deg. F X X X X

Main Fuses: Buss LPJ-60SPI VFD I-Limit Setting: 38 VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 470 456 31 36 Vac Vac Amps Amps C-A: C-A: C: C: 471 457 32 35 1.8 Vac Vac Amps Amps Vac

/ Data X 1uF .667uF

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 470 456 32 36 Vac Vac Amps Amps 631 B-C: B-C: B: B: Vdc

Display 459 Vac Display 34 Amps 635 0 664 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 659 10 26 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 11 127 Vac mVac mVac Vac mVac mVac

I replaced cooling fan with an R5 kit because fan was making a lot of noise and the capacitor needed to be replaced.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0

CT-4
ABB ACH501-040-4-00P2 CRH03H 0

10/8/10
Outside 159067 34413 0

VFD Fuses: Bussmann FWP80A22F VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Yes System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data N/A N/A 64 Deg. F 77 Deg. F X X X X

Main Fuses: Amp-Trap AJT60 VFD I-Limit Setting: 38.06 VFD Freq Limits: 0 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 474 458 28 32 Vac Vac Amps Amps C-A: C-A: C: C: 474 457 31 33 2.8 Vac Vac Amps Amps Vac

/ Data X

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 455 29 34 Vac Vac Amps Amps 635 B-C: B-C: B: B: Vdc

Display 459 Vac Display 31.5 Amps 641 0 665 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 663 10 25.7 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 12 128 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: N/A VFD I-Limit Setting: 25.3 VFD Freq Limits: / Data n/a X 65 Deg. F 87 Deg. F X X X X 20 TO 60 Hz

P4
ABB ACH401601132 10A0000 1.1.3.7 6DC Undervolt.

12/14/12
Chiller Rm. 2023100173 N/A 17.19kh 0

VFD Fuses: Limitron KTK-R-30 VFD O.L. Config: 105% Bypass O.L. Config: VFD U.V. Config: Disable System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 153 2.3 6.1 Vac Vac Amps Amps C-A: C-A: C: C: 487 260 2.4 6.1 1.3 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 34 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 486 260 2.2 5.8 Vac Vac Amps Amps 667 B-C: 260 B: B: Vdc

Display 260 Vac Display 5.9 Amps 648 0 658 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 669 10 23.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 3.8 172 n/a n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: N/A VFD I-Limit Setting: 25.3 VFD Freq Limits: / Data N/A X 65 Deg. F 86 Deg. F X X X X 20 TO 60 Hz

P3
ABB ACH401601132 10A00000 1.1.3.7 6DC Undervolts.

12/14/12
CHILLER ROOM 2023001530 2023100170 20.13kh 0

VFD Fuses: LIMITRON KTK-R-30 VFD O.L. Config: 105% Bypass O.L. Config: VFD U.V. Config: Disable System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 252 2.3 5.8 Vac Vac Amps Amps C-A: C-A: C: C: 487 253 2.6 5.8 1.4 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 33 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 486 253 2.7 5.7 Vac Vac Amps Amps 658 B-C: B-C: B: B: Vdc

Display 255 Vac Display 6.1 Amps 655 0 671 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: n/a n/a Vdc Vdc DC Level: DC Level: DC Level: 673 10 24.2 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 3.8 64 n/a n/a n/a Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: VFD O.L. Config: Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 61 Deg. F X X X X www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours

CWP2
ABB ACH550-UH-044A-4 300F 16...Earth Fault.

10/8/10
Outside 2062701077 11.23kh

Main Fuses: VFD I-Limit Setting: 48.4 VFD Freq Limits: 12 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 474 456 32 34 Vac Vac Amps Amps C-A: C-A: C: C: 475 456 32 34 6 Vac Vac Amps Amps Vac

/ Data X

VFD Temp at Check-out (Display) 37.6 Deg. C

X 59.8 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 474 456 32 34 Vac Vac Amps Amps 637 B-C: B-C: B: B: Vdc

Display 459 Vac Display 34 Amps 635 0 663 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 664 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 15 124 Vac mVac mVac Vac mVac mVac

Need to replace bulb on VFD indicator light.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 16Earth Fault. Main Fuses: VFD I-Limit Setting: 48.4 VFD Freq Limits: / Data X X 58 Deg. F X X X X 12 TO 60 Hz

CWP-4
ABB ACH550-UH-044A-4 300F 6DC Undervolt.

10/8/10
Outside 2042600517 5.47kh 16Earth Fault.

VFD Fuses: VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 474 460 Vac Vac C-A: C-A: C: C: 475 458 Vac Vac

/ Data X

VFD Temp at Check-out (Display) 39.2 Deg. C

X 60 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 473 460 Vac Vac B-C: B-C: B: B: Vdc

Display 460 Vac Display 34.6 Amps 635 0 661 Vdc Hz

31.7 Amps 34.7 Amps 637

32 Amps 35.3 Amps

32.7 Amps 34.9 Amps 5 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 663 9.98 26.4 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 12 125 Vac mVac mVac Vac mVac mVac

Need to replace bulbs on VFD and Fault indicator lights.

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 6DC Undervolt. Main Fuses: N/A VFD I-Limit Setting: 14.5 VFD Freq Limits: / Data N/A X 65 Deg. F X X X X 12 TO 60 Hz

BOILER MAU
ABB ACH401600932 AOAE0000 1.1.3.7 6DC Undervolt.

5/13/10
Chiller Rm. 2040500696 2040600001 49.51kh 0

VFD Fuses: Limitron KTK-R-20 VFD O.L. Config: 110% Bypass O.L. Config: VFD U.V. Config: Disabled System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 490 90 .5 6.5 Vac Vac Amps Amps C-A: C-A: C: C: 490 90 .6 6.2 <1 Vac Vac Amps Amps Vac

/ Data X

VFD Temp at Check-out (Display) 74.5 Deg. F

X 12 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 489 90 .5 6.5 Vac Vac Amps Amps 669 B-C: B-C: B: B: Vdc

Display 91.8 Vac Display 4.5 Amps 669 0 673 Vdc Hz

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: 7.83 24.85 Vdc Vdc DC Level: DC Level: DC Level: 674 9.98 24 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 5 63 N/A 1 1 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 6DC Undervolt.

SCHP-1
ABB ACH550-BD-124A-4 201D 1Overcurrent.

12/6/12
Chiller Rm. 2042600493 42.95kh 6DC Undervolt.

VFD Fuses: Bussmann 170M1369 160 VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 65 Deg. F 27 Deg. C X X X X

Main Fuses: Breaker VFD I-Limit Setting: 136.4 VFD Freq Limits: 12 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 45 Vac Vac C-A: C-A: C: C: 489 45 Vac Vac

/ Data X n/a n/a n/a X X n/a X 12 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 488 45 Vac Vac B-C: B-C: B: B: Vdc

Display 46 Vac Display 12 Amps 664 0 662 Vdc Hz

1.4 Amps 12.7 Amps 666

1.4 Amps 12.9 Amps

1.5 Amps 12.9 Amps <1 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: 7.76 24.36 Vdc Vdc DC Level: DC Level: DC Level: 666 10 25 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 2 4 125 2 9.5 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 6DC Undervolt.

SCHP-2
ABB ACH550-BD-124A-4 201D 1Overcurrent.

12/6/12
Chiller Rm. 2042700164 15.54kh 6DC Undervolt.

VFD Fuses: Bussman 170M1369 160 VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 65 Deg. F 23 Deg. C X X X X

Main Fuses: Breaker VFD I-Limit Setting: 136.4 VFD Freq Limits: 12 TO 60 Hz

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 487 44 Vac Vac C-A: C-A: C: C: 488 44 1.6 12 <1 Vac Vac Amps Amps Vac

/ Data X n/a n/a n/a X X n/a X 12 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 44 1.4 12 Vac Vac Amps Amps 669 B-C: B-C: B: B: Vdc

Display 46 Vac Display 11.9 Amps 671 0 669 Vdc Hz

1.4 Amps 12.2 Amps

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: 7.74 24.27 Vdc Vdc DC Level: DC Level: DC Level: 667 9.99 24.9 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 3.6 126 2 10 Vac mVac mVac Vac mVac mVac

Metlife
Bloomfield, CT
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours 0 Main Fuses: Breaker VFD I-Limit Setting: 136.4 VFD Freq Limits: / Data X X 65 Deg. F 32 Deg. C X X X X 12 TO 60 Hz

SCHP-3
ABB ACH550-BD-124A-4 203B 0

12/6/12
Chiller Rm. 2042800138 20.54kh 0

VFD Fuses: Bussman 170M1369 160 VFD O.L. Config: 100% Bypass O.L. Config: VFD U.V. Config: Enable (time) System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 488 221 Vac Vac C-A: C-A: C: C: 488 221 Vac Vac

/ Data X n/a n/a n/a X X n/a X 34 Hz

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 487 221 Vac Vac B-C: B-C: B: B: Vdc

Display 219 Vac Display 27 Amps 656 0 661 Vdc Hz

12.4 Amps 27.5 Amps 660

12.5 Amps 28 Amps

12.5 Amps 28 Amps 1.4 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: 7.72 24.33 Vdc Vdc DC Level: DC Level: DC Level: 666 10 24.6 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: <1 1 3.2 126 1 9.7 Vac mVac mVac Vac mVac mVac